RFP2027_01 _ 2027 HVAC City of Duluth_Exh 1.pdf
PDF 2 MB Posted
- Attached to
- RFP2027-01 - HVAC City of Duluth
- Solicitation number
- PE-66750-NONST-2027-000000030
- Issued by
- Gwinnett County, Georgia
About this file
This is a Request for Proposal (RFP) document from the City of Duluth, Georgia, for HVAC mechanical controls installation and system upgrades at 3167 Main Street, Duluth, GA 30096. The project involves replacing the existing Carrier CNN (Carrier Control Network) building automation system with a new open-source Building Automation System (BAS), and providing updated controls for all HVAC equipment including rooftop units (RTU-1 through RTU-4), an air handling unit (AHU-1) in the basement, terminal air units (T-B-1 through T-B-7, T-1-1 through T-1-15, T-2-1 through T-2-21, and T-3-1 through T-3-14), a condensing unit (CU-1), and an exhaust fan (EF-1) distributed across basement, three floors, and roof levels. The project is located in Gwinnett County, Georgia, with design conditions specified for the region, and all equipment must conform to 2024 International Building, Mechanical, Fire, and Fuel Gas Codes as well as the 2015 International Energy Conservation Code. The contractor must analyze existing system sequences of operation and submit a complete list prior to demolition work to ensure new controls replicate existing functionality.
The scope requires the contractor to provide a complete DDC (Direct Digital Controls) system with full BACnet communication protocol, web-based access with password protection, and integration of all equipment with updated control interfaces and start/stop controls. The system must support multiple operator access methods including desktop workstations, portable terminals, wireless connections, and remote web access. All new thermostats shall be provided in existing locations unless specifically noted for relocation, with at least one thermostat (serving unit T-1-9) requiring relocation from room 11.24 to 11.30 as coordinated with the owner. The contractor must supply DDC system manufacturer and provider qualifications, provide comprehensive operations and maintenance manuals, and include a two-year warranty on all components (three years for gateway equipment) from substantial completion. A commissioning process managed by an independent commissioning authority (CXA) is required, including construction checklists, functional performance testing, system verification checklists, and owner training, with the contractor responsible for all permits, inspections, and compliance with local jurisdictional requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
aX-001A
2 DIGIT SEQUENTIAL # (01-99)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - VARIES
7 - VARIES
8 - SPECIFICATIONS
9 - 3D VIEWS
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND LETTER
IS REPLACED WITH A DASH
"-" AS A PLACEHOLDER)**
OPTIONAL: 1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR ONLY
USED WHEN PLANS ARE
SUBDIVIDED INTO AREAS.)OPTIONAL : 1 DIGIT
BUILDING / SITE
DESIGNATOR (USE NUMBER
FOR LESS THAN 9)
MECHANICAL GENERAL NOTES:
1. COORDINATE INSTALLATION OF HVAC WORK MUST WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. PLANS ARE
DIAGRAMMATIC IN NATURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS WITH OTHER TRADES AND BUILDING ELEMENTS. EQUIPMENT, PIPING, OR DUCTWORK INTERFERING WITH OTHER TRADES MUST BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER. DO NOT SCALE THE DRAWINGS.
2. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
3. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK THAT MUST BE ACCOMPLISHED AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE SYSTEMS OPERATE AS INDICATED WITHIN THESE
DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
4. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
5. THE MECHANICAL EQUIPMENT AND INSTALLATION MUST CONFORM TO THE CODE REFERENCES TABLE SHOWN HEREIN.
6. AT THE START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE TO BE SUPPLIED THAT ARE ALSO REQUIRING ELECTRICAL WORK AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.
7. WRITTEN DIMENSIONS ON DRAWINGS HAVE PRECEDENCE OVER SCALED DIMENSIONS.
8. INSTALL CONTROL WIRING IN CONDUIT. SEE DIVISION 26 FOR REQUIREMENTS.
9. COORDINATE MECHANICAL AND ELECTRICAL WORK SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT
LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
10. VARIABLE FREQUENCY DRIVES FOR 3 PHASE MOTORS MUST BE 3 POLE TYPE.
11. CONTROL WIRING (I.E. 120 VOLT AND BELOW) INCLUDING 120 VOLT CONTROL POWER TO MOTOR OPERATED DAMPERS, VALVES, AND VARIABLE VOLUME BOXES MUST BE PROVIDED UNDER THIS DIVISION. POWER WIRING (120V) TO CONTROL PANELS MUST BE PROVIDED . POWER (120V) AND CONTROL (24V) WIRING TO APPLICATION-SPECIFIC CONTROLLERS AND OTHER CONTROL SYSTEM COMPONENTS MUST ORIGINATE AT CONTROL PANELS AND BE PROVIDED UNDER THIS DIVISION.
12. COORDINATE LOCATIONS OF WALL, FLOOR, AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.
13. CAULK WITH SILICONE ALL UNUSED PENETRATION GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS, AND HVAC EQUIPMENT PENETRATIONS MUST MATCH EXISTING OR AS SHOWN ON MECHANICAL DETAILS. PATCH LARGE GAPS BEFORE
CAULKING IS APPLIED.
14. EXACT LOCATIONS OF THERMOSTATS, SENSORS, AND HVAC CONTROL APPURTENANCES MUST BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL, FIRE PROTECTION, AND ELECTRICAL EQUIPMENT. MOUNT
THERMOSTATS AND SENSORS MINIMUM 4'-0" ABOVE FINISHED FLOOR.
15. ACCESS FOR INSPECTION MUST BE PROVIDED CLOSE TO EACH INSTANCE OF THE FOLLOWING: MOTOR OPERATED DAMPERS.
IF FEASIBLE, LOCATE DUCT ACCESS DOOR ON THE UNDERSIDE OF THE DUCT RATHER THAN THE SIDE. MINIMUM DUCT
ACCESS DOOR SIZE MUST BE BASED ON DUCT SIZE AS FOLLOWS:
DUCT SIZE ACCESS DOOR SIZE
12" AND SMALLER 12" LONG FLANGED & GASKETED REMOVABLE DUCT SECTION
13" TO 17" 12" X 12"
18" TO 24" 16" X 18"
25" AND LARGER 24" X 16"
16. EQUIPMENT
A. INSTALLATION OF EQUIPMENT MUST PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT
NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
M-001
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
GENERAL NOTES
AND DESIGN
CRITERIA
DULUTH
HVAC DESIGN CRITERIA
PROJECT LOCATION: GWINNETT COUNTY AP, GA,
USA (WMO: 797808)
LATITUDE: 33.98 N
LONGITUDE: 83.963 W
ELEVATION: 323 FT.
STANDARD DESIGN CONDITIONS
WINTER DESIGN DRY BULB (99.0%): 25.7 °F
SUMMER DESIGN DRY BULB (1.0%): 91.6 °F
SUMMER DESIGN WET BULB (1.0%): 74.4 °F
DEHUMIDIFICATION DESIGN CONDITIONS
DEWPOINT (1.0%): 75.1 °F
HUMIDITY RATIO (1.0%): 137.2
MEAN COINCIDENT DRY BULB (1.0%): 74.4 °F
CODE REFERENCES
CODE REFERENCE EDITION
INTERNATIONAL BUILDING CODE 2024
INTERNATIONAL ENERGY CONSERVATION CODE 2015
INTERNATIONAL FIRE CODE 2024
INTERNATIONAL FUEL GAS CODE 2024
INTERNATIONAL MECHANICAL CODE 2024
THE CONTRACTOR WILL BE RESPONSIBLE FOR PROVIDING A NEW OPEN SOURCE BAS (BUILDING
AUTOMATION SYSTEM) REPLACING THE EXISTING CARRIER CNN (CARRIER CONTROL NETWORK)
SYSTEM.
EACH PIECE OF EQUIPMENT SPECIFIED SHALL BE PROVIDED WITH UPDATED CONTROLS. THIS
INCLUDES ALL RTU'S (ROOFTOP UNITS) WITH BACNET AND UPC INTERFACE, NEW BACNET CONTROL
INTERFACE FOR AHU-1 (AIR HANDLING UNIT) IN THE BASEMENT, AND NEW BACNET AND UPC
INTERFACE FOR ALL TERMINAL AIR UNITS, AND START/STOP CONTROLS ON THE ROOF EXHAUST FAN.
THE NEW FRONT END MUST CONTAIN THE SAME INFORMATION AND FUNCTIONALITY AS THE EXISTING EQUIPMENT INCLUDING BUT NOT LIMITED TO: EQUIPMENT STATUS, MODE OF OPERATION, SETPOINTS, AIRFLOW, TEMPERATURES, OCCUPANCY, AND ALARMS.
THE ORIGINAL SEQUENCE OF OPERATION, INCLUDING INTERLOCKS, IS NOT AVAILABLE. THE
CONTRACTOR MUST ANALYZE THE EXISTING SYSTEMS AND EACH ITEM'S CURRENT SEQUENCE OF
OPERATION. PRIOR TO ANY DEMOLITION WORK, THE CONTRACTOR MUST SUBMIT A COMPLETE LIST OF ALL ITEMS AND THEIR SEQUENCES OF OPERATION. THIS APPROVED SUBMITTAL MUST BE USED DURING CONSTRUCTION AND INSTALLATION OF THE NEW CONTROL SYSTEM TO ENSURE ALL ITEMS
OPERATE THE SAME AS EXISTING.
EXISTING DRAWINGS INDICATE THE BASELINE HVAC EQUIPMENT LOCATIONS, TYPES, AND QUANTITIES
REQUIRING CONTROL UPGRADES. ALL OTHER GRAPHIC ELEMENTS, STRUCTURAL DETAILS, OR
ARCHITECTURAL INFORMATION ON THESE DRAWINGS ARE FOR BACKGROUND REFERENCE ONLY AND
ARE EXCLUDED FROM THIS SCOPE OF WORK.
NEW THERMOSTATS SHALL BE PROVIDED IN THE SAME LOCATION AS EXISTING UNLESS SPECIFICALLY
NOTED TO BE RELOCATED.
SCOPE OF WORK:
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
MECHANICAL ABBREVIATIONS:
@ AT
& AND
AFF ABOVE FINISHED FLOOR
A/C ABOVE CEILING
AC AIR CONDITIONER
ADJ ADJUSTABLE
AFMS AIRFLOW MEASURING STATION
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AHRI AIR CONDITIONING, HEATING, AND REFRIGERATION
INSTITUTE
AHU AIR HANDLING UNIT
AMB AMBIENT
AMCA AIR MOVEMENT AND CONTROL ASSOCIATION
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR CONDITIONING
ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AUX AUXILIARY
AWS AMERICAN WELDING SOCIETY
AWG AMERICAN WIRE GAUGE
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BD BACKDRAFT DAMPER
BLDG BUILDING
BOD BOTTOM OF DUCT
B/F BELOW FLOOR
B/S BELOW SLAB
BT BUFFER TANK
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CA COMBUSTION AIR INTAKE
CAV CONSTANT AIR VOLUME
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CRAC COMPUTER ROOM AIR CONDITIONER
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DDC DIRECT DIGITAL CONTROLS
DEG. F, (°F) DEGREES FAHRENHEIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DOAS DEDICATED OUTSIDE AIR SYSTEM
DP DIFFERENTIAL PRESSURE
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DSS DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
ESP EXTERNAL STATIC PRESSURE
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXST, (E) EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT, FACE VELOCITY
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
H HEIGHT
HGRH HOT GAS REHEAT
HP HORSEPOWER, HEAT PUMP
HR HOUR
HSPF HEATING SEASONAL PERFORMANCE FACTOR
HTG HEATING
HUH HYDRONIC UNIT HEATER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HVLS HIGH-VOLUME LOW-SPEED
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MERV MINIMUM EFFICIENCY REPORTING VALUE
MECH MECHANICAL
MFR, MFG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOD MOTOR OPERATED DAMPER
MSS MANUFACTURER'S STANDARDIZATION SOCIETY
MTD MOUNTED
MUW MAKE-UP WATER (POTABLE/ DOMESTIC)
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NO. NUMBER
N.O. NORMALLY OPEN
NPLV NET PART LOAD VALUE
NTS NOT TO SCALE
OA OUTSIDE AIR
O.C. ON CENTER
PD PRESSURE DROP
PH PHASE
PIU POWERED-INDUCTION UNIT
PLBG PLUMBING
PPM PARTS PER MILLION
PRV PRESSURE REDUCING VALVE
PSI(G) POUNDS-FORCE PER SQUARE INCH (GAUGE)
QTY QUANTITY
RA RETURN AIR
RH RELATIVE HUMIDITY, ROOF HOOD
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RLA RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SKD SMOKE DETECTOR
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
SS STAINLESS STEEL
TA TRANSFER AIR
TEMP TEMPERATURE
TG TRANSFER GRILLE
TP TEMPERATURE/ PRESSURE TEST PORT
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VELO VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S), WIDTH
W/ WITH
W/O WITHOUT
WB, Twb WET BULB (TEMPERATURE)
WD WIDE
WMS WIRE MESH SCREEN
AIR DISTRIBUTION DEVICE TAGS:
DIFFUSER TYPE
A
400 AIRFLOW (CFM), "PLENUM", OR "TRANSFER"
A1
M-501
DRAWING REFERENCE KEY:
REFER TO
DETAIL NUMBER
SHEET NUMBER OF DETAIL
RE:A1/M-501
SP
F
CO CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
STATIC PRESSURE SENSOR
ROUND
FIRESTAT
TEMPERATURE SENSOR
MISCELLANEOUS LEGEND:
T
VARIABLE FREQUENCY DRIVEVFD
PIPING LEGEND:
EXPANSION JOINT (EJ)
CLEANOUT
WATER METER
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE PORT WITH
GAUGE COCK
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER (WITH BLOWDOWN
VALVE, CAP, AND CHAIN)
METERED BALANCING VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
DIRECTION OF SLOPE DOWN
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA)X
UNION
TEE OUTLET UP
CONDENSATE DRAIN
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
M
M
FIRE DAMPER
H
DUCT MOUNTED HUMIDIFIER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
FLARED SPIN-IN WITH DAMPER AND
FLEX DUCT (DIFFUSER CONNECTION)
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
FLOW ARROW
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø
DUCTWORK LEGEND:
RETURN AIR DEVICE
ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (LEFT SIDE IS HIGHER)
FD
SD
P - PNEUMATIC-ACTUATED DAMPER
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
SUPPLY AIR DEVICE
FSD
COMBINATION
FIRE/SMOKE DAMPER
EXHAUST AIR DEVICE
FC FAN CONTROLLER
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START / STOP SWITCH
TH THERMOSTAT / HUMIDISTAT
HUMIDITY SENSORH
REFRIGERANT HOT GAS
REFRIGERANT LIQUIDRL
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
REFRIGERANT SUCTIONRS
RHG
CD
CHILLED WATER RETURNCHWR
CHILLED WATER SUPPLYCHWS
CONDENSER WATER RETURNCWR
CONDENSER WATER SUPPLYCWS
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (RIGHT SIDE IS HIGHER)
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,
FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (LEFT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (LEFT SIDE IS HIGHER)
CONNECTION SIZE
(X"xX" INDICATES RECTANGULAR, X"/X"
INDICATES OVAL, X"Ø INDICATES ROUND)
X"xX"
TYP. OF #
TYPICAL OF QUANTITY INDICATED
DP DIFFERENTIAL PRESSURE SENSOR
FLEXIBLE PIPE
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
SKD
DUCT MOUNTED SMOKE DETECTOR
PLAN NORTH
TRUE NORTH
NORTH ARROW:
3-WAY 2-WAY 1-WAY
ALL CEILING SUPPLY DIFFUSERS MUST BE 4-WAY FLOW
PATTERN, UNLESS NOTED OTHERWISE BY FILLED REGION.
2-WAY
PIPE CONTINUATION
PIPE BELOW SLAB OR BELOW GRADE
X DUCT PRESSURE CLASS (IN WG)
LINEAR SLOT AIR DEVICE
GLOBE VALVE
FLEXIBLE PIPE CONNECTOR
PT
EB BOILER EMERGENCY SHUTDOWN SWITCH
VALVE (GENERIC)
SIDEWALL AIR DEVICE
REFER TO
DETAIL NUMBER
SHEET NUMBER OF DETAIL
REF: A1/ M-5011
KEYNOTE NUMBER; REFER TO
KEYNOTE LEGEND ON SHEET
ES EMERGENCY HVAC SHUTDOWN SWITCH
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
M-002
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
ABBREVIATIONS
AND LEGENDS
DULUTH
M A
R K
D E
S C
R
IP
T
IO
N D
A
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
SHEET NOTES
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
MH101
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
FLOOR PLAN -
BASEMENT
DULUTH
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. THE FLOOR PLAN IS A DISPLAY OF THE OWNERS COPY OF THE
RECORD DRAWINGS CREATED 10/16/06 AND ARE FOR
REFERENCE ONLY.
NOT TO SCALEA1
MECHANICAL FLOOR PLAN - BASEMENT
LIST OF EQUIPMENT IS AS FOLLOWS FOR THE BASEMENT LEVEL:
T-B-1 T-B-2 T-B-3 T-B-4 T-B-5 T-B-6 T-B-7
AHU-1
T-B-1
T-B-2
T-B-3
T-B-4
T-B-5
T-B-6
T-B-7
AHU-1
M A
R K
D E
S C
R
IP
T
IO
N D
A
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
SHEET NOTES
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
MH102
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
FLOOR PLAN -
LEVEL 1
DULUTH
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. THE FLOOR PLAN IS A DISPLAY OF THE OWNERS COPY OF THE
RECORD DRAWINGS CREATED 10/16/06 AND ARE FOR
REFERENCE ONLY.
4. CONTRACTOR TO RELOCATE THE THERMOSTAT SERVING UNIT
T-1-9 FROM ROOM 11.24 TO 11.30. COORDINATE WITH OWNER
FOR EXACT LOCATION.
NOT TO SCALEA1
MECHANICAL FLOOR PLAN - LEVEL 1
LIST OF EQUIPMENT IS AS FOLLOWS FOR THE FIRST FLOOR:
T-1-1 T-1-2 T-1-3 T-1-4 T-1-5 T-1-6 T-1-7 T-1-8 T-1-9 T-1-10 T-1-11 T-1-12 T-1-13 T-1-14 T-1-15
T
T-1-1
T-1-2
T-1-3
T-1-4
T-1-5
T-1-6
T-1-7
T-1-8
T-1-9T-1-10 T-1-11T-1-12
T-1-13
T-1-14 T-1-15
THERMOSTAT IS NOT
ACCURATE TO ACTUAL
LOCATION. SEE MARKUP.
T
CONTRACTOR TO
RELOCATE
THERMOSTAT TO THE
INDICATED AREA.
M A
R K
D E
S C
R
IP
T
IO
N D
A
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
SHEET NOTES
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
MH103
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
FLOOR PLAN -
LEVEL 2
DULUTH
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. THE FLOOR PLAN IS A DISPLAY OF THE OWNERS COPY OF THE
RECORD DRAWINGS CREATED 10/16/06 AND ARE FOR
REFERENCE ONLY.
4. THE LOCATIONS OF T-2-11 AND T-2-20 ARE BOTH NOT
ACCURATE TO THE DRAWINGS. SEE MARKUPS FOR
CORRECTED LOCATIONS. RELOCATION OF THESE
THERMOSTATS ARE NOT NECESSARY AND ARE BEING NOTED
FOR CLARITY ONLY.
SCALE: 1/8" = 1'-0"A1
MECHANICAL FLOOR PLAN - LEVEL 2
LIST OF EQUIPMENT IS AS FOLLOWS FOR THE SECOND FLOOR:
T-2-1 T-2-2 T-2-3 T-2-4 T-2-5 T-2-6 T-2-7 T-2-8 T-2-9 T-2-10 T-2-11 T-2-12 T-2-13 T-2-14 T-2-15 T-2-16 T-2-17 T-2-18 T-2-19 T-2-20 T-2-21
T
T
THE ACTUAL LOCATIONS FOR THE
THERMOSTATS IN THESE LOCATIONS ARE AS
PICTURED. RELOCATION IS NOT NECESSARY.
T-2-1 T-2-2 T-2-3T-2-4 T-2-5 T-2-6
T-2-7
T-2-8
T-2-9
T-2-10 T-2-11
T-2-12
T-2-13
T-2-14
T-2-15
T-2-16T-2-17T-2-18T-2-19
T-2-20
T-2-21
M A
R K
D E
S C
R
IP
T
IO
N D
A
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
SHEET NOTES
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
MH104
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
FLOOR PLAN -
LEVEL 3
DULUTH
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. THE FLOOR PLAN IS A DISPLAY OF THE OWNERS COPY OF THE
RECORD DRAWINGS CREATED 10/16/06 AND ARE FOR
REFERENCE ONLY.
NOT TO SCALEA1
MECHANICAL FLOOR PLAN - LEVEL 3
T-3-1
LIST OF EQUIPMENT IS AS FOLLOWS FOR THE THIRD FLOOR:
T-3-1 T-3-2 T-3-3 T-3-4 T-3-5 T-3-6 T-3-7 T-3-8 T-3-9 T-3-10 T-3-11 T-3-12 T-3-13 T-3-14
CU-1
RTU-2
T-3-2
T-3-3
T-3-4
T-3-5
T-3-6
T-3-7
T-3-8
T-3-9
T-3-10T-3-11
T-3-12
T-3-13
T-3-14
CU-1
RTU-2
M A
R K
D E
S C
R
IP
T
IO
N D
A
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
SHEET NOTES
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
MH105
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
FLOOR PLAN -
ROOF
DULUTH
1. REFER TO M-001 FOR MECHANICAL GENERAL NOTES AND
DESIGN CRITERIA.
2. REFER TO M-002 FOR MECHANICAL ABBREVIATIONS AND
LEGENDS.
3. THE FLOOR PLAN IS A DISPLAY OF THE OWNERS COPY OF THE
RECORD DRAWINGS CREATED 10/16/06 AND ARE FOR
REFERENCE ONLY.
NOT TO SCALEA1
MECHANICAL FLOOR PLAN - ROOF
LIST OF EQUIPMENT IS AS FOLLOWS FOR THE ROOF:
RTU-1
RTU-2
RTU-3
RTU-4
CU-1
EF-1
RTU-1
RTU-2
RTU-3
RTU-4
CU-1
EF-1
M A
R K
D E
S C
R
IP
T
IO
N D
A
23 00 00 - HVAC GENERAL
QUALITY ASSURANCE:
A. THE MECHANICAL EQUIPMENT AND INSTALLATION MUST
CONFORM TO THE FOLLOWING CODES:
1. THE INTERNATIONAL BUILDING CODE 2024 EDITION.
2. THE INTERNATIONAL MECHANICAL CODE 2024 EDITION.
3. THE INTERNATIONAL PLUMBING CODE, 2024 EDITION.
4. THE INTERNATIONAL FUEL GAS CODE, 2024 EDITION.
5. THE INTERNATIONAL FIRE CODE, 2024 EDITION.
6. THE INTERNATIONAL ENERGY CONSERVATION CODE, 2015
EDITION.
B. THE MECHANICAL EQUIPMENT AND INSTALLATION MUST
CONFORM TO THE FOLLOWING STANDARDS:
1. ASSOCIATE AIR BALANCE COUNCIL (AABC): NATIONAL
STANDARD FOR TOTAL SYSTEM BALANCE.
2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA):
STANDARD 90A: INSTALLATION OF AIR CONDITIONING AND
VENTILATING SYSTEMS.
STANDARD 70: NATIONAL ELECTRICAL CODE (NEC)
C. PUBLICATION DATES: WHERE THE DATE OF ISSUE OF A
REFERENCE STANDARD IS NOT SPECIFIED, COMPLY WITH THE
STANDARD THAT IS EFFECTIVE AS OF THE DATE OF CONTRACT
DOCUMENT.
D. PERMITS
1. OBTAIN ALL PERMITS AND INSPECTIONS FOR THE
INSTALLATION OF THIS WORK AND PAY ALL CHARGES
INCIDENT THERETO. DELIVER TO THE OWNER ALL
CERTIFICATES OF SAID INSPECTION ISSUED BY
AUTHORITIES HAVING JURISDICTION.
E. WORKMANSHIP AND MATERIALS COVERED BY THESE
SPECIFICATIONS MUST CONFORM TO ALL ORDINANCES AND
REGULATIONS OF THE CITY, COUNTY, AND/OR OTHER
AUTHORITIES HAVING JURISDICTION.
F. OPERATIONS AND MAINTENANCE MANUALS FOR ALL
SCHEDULED EQUIPMENT MUST BE PROVIDED TO THE OWNER
AS PART OF FINAL ACCEPTANCE.
GUARANTEE:
A. COMPONENTS OF THE MECHANICAL SYSTEM FURNISHED
UNDER THIS DIVISION OF THE SPECIFICATIONS MUST BE
GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF
ACCEPTANCE THEREOF, EITHER FOR BENEFICIAL USE OR
FINAL ACCEPTANCE, WHICHEVER IS EARLIER, AGAINST
DEFECTIVE MATERIAL, DESIGN, AND WORKMANSHIP.
ELECTRICAL WORK:
A. ALL ELECTRICAL EQUIPMENT FURNISHED UNDER THIS DIVISION
OF THESE SPECIFICATIONS MUST COMPLY THE ELECTRICAL
SYSTEM CHARACTERISTICS INDICATED ON THE ELECTRICAL
DRAWINGS.
B. MOTOR CONTROL COMPONENTS FURNISHED AS AN INTEGRAL
PART OF MECHANICAL EQUIPMENT MUST CONFORM TO
REQUIREMENTS OF ELECTRICAL DRAWINGS.
C. POWER WIRING MUST BE PROVIDED BY ELECTRICAL.
D. WIRING AND CONDUIT BETWEEN VFD AND MOTOR MUST BE
UNDER THIS DIVISION UNLESS IT IS INDICATED ON THE
ELECTRICAL DRAWINGS. WIRING AND CONDUIT MUST BE PER
NEC AND ELECTRICAL SPECIFICATIONS.
PAINTING:
A. FACTORY PAINTED EQUIPMENT THAT HAS BEEN SCRATCHED
OR MARRED MUST BE REPAINTED TO MATCH ORIGINAL COLOR.
B. STEEL EQUIPMENT HANGERS, SUPPORTS, AND UNINSULATED
BLACK STEEL PIPE EXPOSED TO SIGHT INSIDE THE BUILDING
WHICH ARE NOT PROVIDED WITH A FACTORY APPLIED PRIME
COAT MUST BE CLEANED OF RUST, GREASE, AND SCALE.
AFTER CLEANING HANGERS, SUPPORTS, AND PIPE, PROVIDE A
FILED-APPLIED PRIME COAT. IN ADDITION, SUCH ITEMS IN
FINISHED SPACES MUST BE PROVIDED WITH TWO COATS OF
FINISH PAINT IN A COLOR TO MATCH THE ADJACENT SURFACE.
CLEANING AND ADJUSTING:
A. ALL EQUIPMENT, PIPE, VALVES, AND FITTINGS MUST BE
CLEANED OF GREASE, OIL, PAINT SPOTS, METAL CUTTINGS,
SLUDGE, AND CONSTRUCTION DEBRIS.
B. DUCTS, PLENUMS, AND CASINGS MUST BE CLEANED OF ALL
DEBRIS AND BLOWN FREE OF ALL PARTICLES OF RUBBISH AND
DUST BEFORE INSTALLING OUTLET FACES.
C. BEARINGS MUST BE LUBRICATED AS RECOMMENDED BY THE
EQUIPMENT MANUFACTURER.
D. TEMPORARY FILTERS MUST BE PROVIDED FOR FANS THAT ARE
USED DURING CONSTRUCTION. AT THE TIME OF STARTING THE
TEST AND BALANCE PROCEDURES OF THE AIR DISTRIBUTION
SYSTEM, NEW FILTERS MUST BE INSTALLED.
23 05 93.01 - HVAC SYSTEMS COMMISSIONING
GENERAL:
A. THE PURPOSE OF THE COMMISSIONING PROCESS IS TO
PROVIDE THE OWNER/OPERATOR WITH ASSURANCE THAT THE
SYSTEMS HAVE BEEN INSTALLED ACCORDING TO THE
CONTRACT DOCUMENTS, AND OPERATE WITHIN THE
PERFORMANCE GUIDELINES SET OUT IN THE BASIS OF DESIGN
(BOD) AND THESE SPECIFICATIONS. THE INDEPENDENT
COMMISSIONING AUTHORITY (CXA) WILL PROVIDE THE OWNER
WITH AN UNBIASED, OBJECTIVE VIEW OF THE SYSTEM’S
INSTALLATION, OPERATION, AND PERFORMANCE. THE
COMMISSIONING PROCESS DOES NOT TAKE AWAY OR REDUCE
THE RESPONSIBILITY OF THE INSTALLING CONTRACTORS TO
PROVIDE A FINISHED PROJECT, INSTALLED, AND FULLY
FUNCTIONAL IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
B. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, AND
SUB-CONTRACTORS MUST BE RESPONSIBLE FOR
COOPERATING, AND COORDINATING THEIR WORK WITH THE
CXA. EACH PARTY MUST ALSO BE RESPONSIBLE FOR
CARRYING OUT ALL THE PHYSICAL ACTIVITIES REQUIRED FOR
INSTALLATION OF COMPONENTS AND SYSTEMS, AND
OPERATING THEM DURING THE COMMISSIONING PROCESS AS
REQUIRED IN THIS SECTION.
C. DEFINITIONS:
1. BOD: BASIS OF DESIGN. A DOCUMENT, PREPARED BY
ARCHITECT/ENGINEER, THAT RECORDS CONCEPTS,
CALCULATIONS, DECISIONS, AND PRODUCT SELECTIONS
USED TO MEET THE OWNER'S PROJECT REQUIREMENTS
(OPR) AND TO SATISFY APPLICABLE REGULATORY
REQUIREMENTS, STANDARDS, AND GUIDELINES. THE
DOCUMENT INCLUDES BOTH NARRATIVE DESCRIPTIONS
AND LISTS OF INDIVIDUAL ITEMS THAT SUPPORT THE
DESIGN PROCESS.
2. COMMISSIONING PLAN: A DOCUMENT, PREPARED BY THE
CXA, THAT OUTLINES THE ORGANIZATION, SCHEDULE,
ALLOCATION OF RESOURCES, AND DOCUMENTATION
REQUIREMENTS OF THE COMMISSIONING PROCESS.
3. OPR: OWNER’S PROJECT REQUIREMENTS. A DOCUMENT,
PREPARED BY THE OWNER, THAT DETAILS THE
FUNCTIONAL REQUIREMENTS OF THE PROJECT AND
EXPECTATIONS OF HOW IT WILL BE USED AND OPERATED.
THIS DOCUMENT INCLUDES PROJECT GOALS, MEASURABLE
PERFORMANCE CRITERIA, COST CONSIDERATIONS,
BENCHMARKS, SUCCESS CRITERIA, AND SUPPORTING
INFORMATION.
D. COMMISSIONING TEAM:
1. MEMBERS APPOINTED BY CONTRACTOR(S):
a. INDIVIDUALS, EACH HAVING AUTHORITY TO ACT ON
BEHALF OF THE ENTITY HE OR SHE REPRESENTS,
EXPLICITLY ORGANIZED TO IMPLEMENT THE
COMMISSIONING PROCESS THROUGH COORDINATED
ACTIONS; THE COMMISSIONING TEAM MUST CONSIST
OF (BUT NOT BE LIMITED TO) REPRESENTATIVE OF
EACH CONTRACTOR, INCLUDING PROJECT
SUPERINTENDENT AND SUBCONTRACTORS
INSTALLERS, SUPPLIERS, AND SPECIALISTS DEEMED
APPROPRIATE BY THE CXA.
2. MEMBERS APPOINTED BY OWNER:
a. CXA: AN ENTITY IDENTIFIED BY THE OWNER THAT
LEADS, PLANS, SCHEDULES, AND COORDINATES THE
COMMISSIONING TEAM TO IMPLEMENT THE
COMMISSIONING PROCESS; OWNER WILL ENGAGE THE
CXA UNDER A SEPARATE CONTRACT
b. REPRESENTATIVES OF THE FACILITY USER AND
OPERATION AND MAINTENANCE PERSONNEL
c. ARCHITECT AND ENGINEERING DESIGN
PROFESSIONALS
RESPONSIBILITIES:
A. OWNER'S RESPONSIBILITIES:
1. PROVIDE THE OPR DOCUMENTATION TO THE CXA AND
EACH CONTRACTOR FOR INFORMATION AND USE.
2. ASSIGN OPERATION AND MAINTENANCE PERSONNEL AND
SCHEDULE THEM TO PARTICIPATE IN COMMISSIONING
TEAM ACTIVITIES.
3. PROVIDE THE BOD DOCUMENTS, PREPARED BY ARCHITECT
AND APPROVED BY OWNER, TO THE CXA AND EACH
CONTRACTOR FOR USE IN DEVELOPING THE
COMMISSIONING PLAN, SYSTEMS MANUAL, AND
OPERATION AND MAINTENANCE TRAINING PLAN.
B. CONTRACTORS RESPONSIBILITIES:
1. EACH CONTRACTOR AND THE ASSOCIATED
SUBCONTRACTORS MUST ASSIGN REPRESENTATIVES WITH
EXPERTISE AND AUTHORITY TO ACT ON THE PARTY'S
BEHALF AND SCHEDULE THEM TO PARTICIPATE IN AND
PERFORM COMMISSIONING PROCESS ACTIVITIES
INCLUDING (BUT NOT LIMITED TO) THE FOLLOWING:
a. EVALUATE PERFORMANCE DEFICIENCIES IDENTIFIED IN
TEST REPORTS AND, IN COLLABORATION WITH ENTITY
RESPONSIBLE FOR SYSTEM AND EQUIPMENT
INSTALLATION, RECOMMEND CORRECTIVE ACTION
b. COOPERATE WITH CXA FOR RESOLUTION OF ISSUES
RECORDED IN “ISSUES LOG"
c. ATTEND AND PARTICIPATE IN COMMISSIONING TEAM
MEETINGS
d. INTEGRATE AND COORDINATE COMMISSIONING
PROCESS ACTIVITIES WITH CONSTRUCTION SCHEDULE
e. REVIEW AND ACCEPT CONSTRUCTION CHECKLISTS
PROVIDED BY THE COMMISSIONING AUTHORITY
f. COMPLETE CONSTRUCTION CHECKLISTS AS WORK IS
COMPLETED AND PROVIDE TO THE COMMISSIONING
AUTHORITY
g. REVIEW AND ACCEPT COMMISSIONING PROCESS TEST
PROCEDURES PROVIDED BY THE COMMISSIONING
AUTHORITY
h. ACCOMPLISH COMMISSIONING PROCESS TEST
PROCEDURES
C. CXA RESPONSIBILITIES:
1. REVIEW THE DESIGN DOCUMENTS TO VERIFY THE OPR HAS
BEEN ADDRESSED AND THAT ADEQUATE TESTING CAN BE
PERFORMED IN ORDER TO DOCUMENT THAT THE SYSTEMS,
EQUIPMENT, AND COMPONENTS WILL COMPLY WITH THE
OPR AND BOD.
2. REVIEW THE DESIGN DOCUMENTS FOR EQUIPMENT
ACCESSIBILITY FOR TESTING, SERVICE, AND
MAINTENANCE.
3. REVIEW EQUIPMENT SUBMITTALS FOR USE IN DEVELOPING
TESTING PROCEDURES USED IN THE COMMISSIONING
PLAN.
4. ORGANIZE AND LEAD THE COMMISSIONING TEAM.
5. PROVIDE COMMISSIONING PLAN.
6. CONVENE COMMISSIONING TEAM MEETINGS.
7. PROVIDE PROJECT-SPECIFIC CONSTRUCTION CHECKLISTS
AND COMMISSIONING PROCESS TEST PROCEDURES.
8. DEVELOP DETAILED AND SPECIFIC FUNCTIONAL TESTING
PROCEDURES FOR EQUIPMENT AND SYSTEMS TO BE
COMMISSIONED.
9. PERFORM SITE INSPECTIONS AND VERIFY CONTRACTOR
READINESS FOR THE FUNCTIONAL TESTING PROCESS.
DOCUMENT DEFICIENCIES FOR FUTURE RESOLUTION.
10. WITNESS CONTRACTOR PERFORMED FUNCTIONAL
TESTING PROCESS AS APPROPRIATE TO VERIFY
CONTRACTOR COMPLIANCE WITH THE FUNCTIONAL
TESTING PROCEDURES. DOCUMENT DEFICIENCIES FOR
FUTURE RESOLUTION
11. PREPARE AND MAINTAIN ISSUES LOG.
12. PREPARE AND MAINTAIN COMPLETED CONSTRUCTION
CHECKLIST LOG.
13. WITNESS SYSTEMS, ASSEMBLIES, EQUIPMENT, AND
COMPONENT START UP.
14. COMPILE TEST DATA, INSPECTION REPORTS, AND
CERTIFICATES, AND INCLUDE THEM IN THE SYSTEMS
MANUAL AND COMMISSIONING REPORT.
15. DEVELOP A COMMISSIONING SCHEDULE TO PARALLEL THE
CONSTRUCTION SCHEDULE. THIS SCHEDULE MUST
INCLUDE (BUT IS NOT LIMITED TO) THE FOLLOWING:
a. ALL COMMISSIONING MEETINGS
b. CONSTRUCTION REVIEW AND STATIC TESTING
c. PRE-START AND START UP CHECK LIST PROCEDURES
d. SYSTEM OPERATIONAL VERIFICATIONS
e. FUNCTIONAL PERFORMANCE AND ACCEPTANCE
TESTING
f. OWNER TRAINING
g. SPECIAL TESTING
h. OFF-SEASON TESTING
16. DEVELOP A RESOLUTION TRACKING FORM (RTF) FORMAT
TO DOCUMENT EACH ISSUE, NON-COMPLIANCE ITEM, OR
DEFICIENCY ENCOUNTERED DURING THE COMMISSIONING
PROCESS. THE RTF WILL BE REVIEWED AT EACH
COMMISSIONING MEETING TO ASSURE ISSUES ARE ON
TRACK AND COMPLETED IN A TIMELY MANNER. THE RTF
FORMAT WILL INCLUDE:
a. A SPECIFIC AND INDIVIDUAL NUMBER FOR EACH ISSUE
b. A DESCRIPTION OF THE ISSUE
c. THE DATE THE ISSUE WAS DISCOVERED
d. THE PARTY RESPONSIBLE FOR RESOLVING THE ISSUE
e. THE DATE THE ISSUE WAS CORRECTED BY THE
RESPONSIBLE PARTY
f. THE DATE OF THE FINAL VERIFICATION BY THE CXA AS
COMPLETE
17. PERFORM CONSTRUCTION REVIEWS FROM TIME TO TIME.
THE RESULTS OF THE REVIEWS AND TESTS WILL BE
INCLUDED IN THE FINAL COMMISSIONING REPORT. ALL
ISSUES ENCOUNTERED WILL BE INCLUDED ON THE ISSUE
RESOLUTION TRACKING FORM. THE AGENT MUST
OBSERVE:
a. THE GENERAL INSTALLATION
b. THE INSTALLATION PRIOR TO BURIAL OR
CONCEALMENT
c. TO WITNESS STATIC TESTING (DUCT, HYDRONIC, ETC.)
18. DEVELOP SYSTEM VERIFICATION CHECKLISTS (SVC) FOR
EACH PIECE OF EQUIPMENT TO BE STARTED UP.
19. SCHEDULE THE CONTRACTORS AND VENDORS FOR ALL
OPERATION & MAINTENANCE (O&M) TRAINING.
COMMISSIONING REQUIREMENTS:
A. SYSTEMS TO BE COMMISSIONED:
1. ALL EQUIPMENT SHOWN ON THE SCHEDULE SHEETS
B. COMMISSIONING REPORT:
1. THE COMMISSIONING REPORT WILL INCLUDE A NARRATIVE
DESCRIPTION OF ALL SYSTEMS, EQUIPMENT, AND
COMPONENTS FOR EACH DIVISION OF THE
SPECIFICATIONS COMMISSIONED. IN ADDITION, THE
COMMISSIONING REPORT MUST INCLUDE (BUT IS NOT
LIMITED TO) THE FOLLOWING:
a. EXECUTIVE SUMMARY
b. MEETING MINUTES
c. OWNER’S PROJECT REQUIREMENTS REVIEWS
d. DESIGN REVIEWS
e. SUBMITTAL REVIEWS
f. CONSTRUCTION CHECKLIST
g. RESOLUTION TRACKING FORMS (RTF)
h. SYSTEM VERIFICATION CHECKLIST (SVC)
i. START-UP, POINT-TO-POINT/SEQUENCE VERIFICATION
AND TAB REPORTS.
j. FUNCTION PERFORMANCE TESTING (FPT)
k. O&M DATA
l. TRAINING AUDIO/VISUAL DOCUMENTATION
m. SYSTEMS MANUAL
n. OFF-SEASON MODE TESTS/TRAINING REPORTS
o. NEAR END OF WARRANTY REVIEW REPORT
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
M-301
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
SPECIFICATIONS
DULUTH
M A
R K
D E
S C
R
IP
T
IO
N D
A
23 09 23 - DDC CONTROLS
GENERAL REQUIREMENTS:
A. PROVIDE AND INSTALL A WHOLE AND FULLY COMPLETE DIRECT
DIGITAL CONTROLS (DDC) SYSTEM. PROVIDE PRODUCT DATA
SUBMITTAL FOR ALL EQUIPMENT AND SOFTWARE ASSOCIATED
WITH THE CONTROL SYSTEM. PROVIDE SUBMITTAL WITH
DESCRIPTION AND EXAMPLES OF GRAPHICAL INTERFACE.
PROVIDE FULL DESCRIPTION OF SYSTEM ARCHITECTURE.
COMMUNICATIONS PROTOCOL MUST BE FULLY BACNET.
PROVIDE SCHEDULE FOR ALL CONTROL DAMPERS AND ALL
CONTROL VALVES. PROVIDE OPERATION AND MAINTENANCE
MANUALS FOR EACH DEVICE AND THE SYSTEM AS A WHOLE.
B. DDC SYSTEM MANUFACTURER QUALIFICATIONS:
1. NATIONALLY RECOGNIZED MANUFACTURER OF DDC
SYSTEMS AND PRODUCTS.
2. DDC SYSTEMS AND PRODUCTS THAT HAVE BEEN
SUCCESSFULLY TESTED AND IN USE ON AT LEAST FIVE
PREVIOUS PROJECTS.
3. HAVING COMPLETE PUBLISHED CATALOG LITERATURE,
INSTALLATION, OPERATION AND MAINTENANCE MANUALS
FOR ALL PRODUCTS INTENDED FOR USE.
4. HAVING FULL-TIME IN-HOUSE EMPLOYEES FOR THE
FOLLOWING:
a. PRODUCT RESEARCH AND DEVELOPMENT.
b. PRODUCT AND APPLICATION ENGINEERING.
c. PRODUCT MANUFACTURING, TESTING AND QUALITY
CONTROL.
d. TECHNICAL SUPPORT FOR DDC SYSTEM INSTALLATION
TRAINING, COMMISSIONING, AND TROUBLESHOOTING
OF INSTALLATIONS.
e. OWNER OPERATOR TRAINING.
C. DDC SYSTEM PROVIDER QUALIFICATIONS:
1. AUTHORIZED REPRESENTATIVE OF, AND TRAINED BY, DDC
SYSTEM MANUFACTURER.
2. DEMONSTRATED PAST EXPERIENCE WITH INSTALLATION OF
DDC SYSTEM PRODUCTS BEING INSTALLED FOR PERIOD
WITHIN FIVE CONSECUTIVE YEARS BEFORE TIME OF BID.
3. DEMONSTRATED PAST EXPERIENCE ON FIVE PROJECTS OF
SIMILAR COMPLEXITY, SCOPE, AND VALUE.
4. EACH PERSON ASSIGNED TO PROJECT MUST HAVE
DEMONSTRATED PAST EXPERIENCE.
5. STAFFING RESOURCES OF COMPETENT AND EXPERIENCED
FULL-TIME EMPLOYEES THAT ARE ASSIGNED TO EXECUTE
WORK ACCORDING TO SCHEDULE.
6. SERVICE AND MAINTENANCE STAFF ASSIGNED TO
SUPPORT PROJECT DURING WARRANTY PERIOD.
7. DDC SYSTEM MANUFACTURER'S BACKING MUST TAKE
OVER EXECUTION OF WORK IF NECESSARY, TO COMPLY
WITH REQUIREMENTS INDICATED. INCLUDE PROJECT-
SPECIFIC WRITTEN LETTER, SIGNED BY MANUFACTURER'S
CORPORATE OFFICER, IF REQUESTED.
D. MANUFACTURER'S WARRANTY: MANUFACTURER AND
INSTALLER AGREE TO REPAIR OR REPLACE PRODUCTS THAT
FAIL IN MATERIALS OR WORKMANSHIP WITHIN SPECIFIED
WARRANTY PERIOD.
1. FAILURES MUST BE ADJUSTED, REPAIRED, OR REPLACED
AT NO ADDITIONAL COST OR REDUCTION IN SERVICE TO
OWNER.
2. INCLUDE UPDATES OR UPGRADES TO SOFTWARE AND
FIRMWARE IF NECESSARY, TO RESOLVE DEFICIENCIES.
a. INSTALL UPDATES ONLY AFTER RECEIVING OWNER'S
WRITTEN AUTHORIZATION.
3. WARRANTY SERVICE MUST OCCUR DURING NORMAL
BUSINESS HOURS AND COMMENCE WITHIN 24 HOURS OF
OWNER'S WARRANTY SERVICE REQUEST.
4. WARRANTY PERIOD: TWO YEAR(S) FROM DATE OF
SUBSTANTIAL COMPLETION.
a. FOR GATEWAY: THREE YEAR PARTS AND LABOR
WARRANTY FOR EACH.
E. DDC SYSTEM MUST BE MICROPROCESSOR-BASED
MONITORING AND CONTROL INCLUDING ANALOG/DIGITAL
CONVERSION AND PROGRAM LOGIC. A CONTROL LOOP OR
SUBSYSTEM IN WHICH DIGITAL AND ANALOG INFORMATION IS
RECEIVED AND PROCESSED BY A MICROPROCESSOR, AND
DIGITAL CONTROL SIGNALS ARE GENERATED BASED ON
CONTROL ALGORITHMS AND TRANSMITTED TO FIELD DEVICES
TO ACHIEVE A SET OF PREDEFINED CONDITIONS. DDC SYSTEM
MUST CONSIST OF A PEER-TO-PEER NETWORK OF
DISTRIBUTED DDC CONTROLLERS, OTHER NETWORK DEVICES,
OPERATOR INTERFACES, AND SOFTWARE.
F. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES:
LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED
TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND
APPLICATION.
G. DDC SYSTEM MUST BE WEB BASED:
1. WEB-BASED ACCESS TO DDC SYSTEM:
a. DDC SYSTEM SOFTWARE MUST BE BASED ON SERVER
THIN-CLIENT ARCHITECTURE, DESIGNED AROUND OPEN
STANDARDS OF WEB TECHNOLOGY. DDC SYSTEM
SERVER MUST BE ACCESSED USING A WEB BROWSER
OVER DDC SYSTEM NETWORK, USING LOCAL AREA
NETWORK (LAN) INSTALLED BY CONTROLS VENDOR,
AND REMOTELY OVER INTERNET
b. INTENT OF THIN-CLIENT ARCHITECTURE IS TO PROVIDE
OPERATORS COMPLETE ACCESS TO DDC SYSTEM VIA A
WEB BROWSER. NO SPECIAL SOFTWARE OTHER THAN A
WEB BROWSER MUST BE REQUIRED TO ACCESS
GRAPHICS, POINT DISPLAYS, AND TRENDS; TO
CONFIGURE TRENDS, POINTS, AND CONTROLLERS; AND
TO EDIT PROGRAMMING.
c. WEB ACCESS MUST BE PASSWORD PROTECTED.
2. WEB-COMPATIBLE ACCESS TO DDC SYSTEM:
a. WORKSTATION AND SERVER MUST PERFORM OVERALL
SYSTEM SUPERVISION AND CONFIGURATION,
GRAPHICAL USER INTERFACE, MANAGEMENT REPORT
GENERATION, AND ALARM ANNUNCIATION.
b. DDC SYSTEM MUST SUPPORT WEB BROWSER ACCESS
TO BUILDING DATA. OPERATOR USING A STANDARD
WEB BROWSER MUST BE ABLE TO ACCESS CONTROL
GRAPHICS AND CHANGE ADJUSTABLE SET POINTS.
c. WEB ACCESS MUST BE PASSWORD PROTECTED.
C. ENGAGE A QUALIFIED PROFESSIONAL TO DESIGN DDC SYSTEM
TO SATISFY REQUIREMENTS INDICATED.
1. DDC SYSTEM TO MANAGE HVAC SYSTEMS.
2. DDC SYSTEM CONTROL MUST OPERATE HVAC SYSTEMS TO
ACHIEVE OPTIMUM OPERATING COSTS WHILE USING LEAST
POSSIBLE ENERGY AND MAINTAINING SPECIFIED
PERFORMANCE.
3. DDC SYSTEM MUST RESPOND TO POWER FAILURES, HVAC
EQUIPMENT FAILURES, AND ADVERSE AND EMERGENCY
CONDITIONS ENCOUNTERED THROUGH CONNECTED
INPUT/OUTPUT (I/O) POINTS.
4. DDC SYSTEM MUST OPERATE WHILE UNATTENDED BY AN
OPERATOR AND THROUGH OPERATOR INTERACTION.
5. DDC SYSTEM MUST RECORD TRENDS AND TRANSACTION
OF EVENTS AND PRODUCE REPORT INFORMATION SUCH AS
PERFORMANCE, ENERGY, OCCUPANCIES, AND EQUIPMENT
OPERATION.
D. CONTINUITY OF OPERATION AFTER ELECTRIC POWER
INTERRUPTION:
1. EQUIPMENT AND ASSOCIATED FACTORY-INSTALLED
CONTROLS, FIELD-INSTALLED CONTROLS, ELECTRICAL
EQUIPMENT, AND POWER SUPPLY CONNECTED TO
BUILDING NORMAL AND BACKUP POWER SYSTEMS MUST
AUTOMATICALLY RETURN EQUIPMENT AND ASSOCIATED
CONTROLS TO OPERATING STATE OCCURRING
IMMEDIATELY BEFORE LOSS OF NORMAL POWER, WITHOUT
NEED FOR MANUAL INTERVENTION BY OPERATOR WHEN
POWER IS RESTORED EITHER THROUGH BACKUP POWER
SOURCE OR THROUGH NORMAL POWER IF RESTORED
BEFORE BACKUP POWER IS BROUGHT ONLINE.
E. DDC SYSTEM MUST CONSIST OF DEDICATED AND SEPARATED
LANS THAT ARE NOT SHARED WITH OTHER BUILDING SYSTEMS
AND TENANT DATA AND COMMUNICATION NETWORKS.
F. SYSTEM ARCHITECTURE MUST PERFORM MODIFICATIONS
WITHOUT HAVING TO REMOVE AND REPLACE EXISTING
NETWORK EQUIPMENT.
G. SYSTEM DESIGN MUST ELIMINATE DEPENDENCE ON ANY
SINGLE DEVICE FOR SYSTEM ALARM REPORTING AND
CONTROL EXECUTION. EACH CONTROLLER MUST OPERATE
INDEPENDENTLY BY PERFORMING ITS' OWN CONTROL, ALARM
MANAGEMENT AND HISTORICAL DATA COLLECTION.
H. OPERATOR MEANS OF SYSTEM ACCESS: OPERATOR MUST BE
ABLE TO ACCESS ENTIRE DDC SYSTEM THROUGH ANY OF
MULTIPLE MEANS, INCLUDING (BUT NOT LIMITED TO) THE
FOLLOWING:
1. DESKTOP AND PORTABLE WORKSTATION WITH HARDWIRED
CONNECTION THROUGH LAN PORT.
2. PORTABLE OPERATOR TERMINAL WITH HARDWIRED
CONNECTION THROUGH LAN PORT.
3. PORTABLE OPERATOR WORKSTATION WITH WIRELESS
CONNECTION THROUGH LAN ROUTER.
4. MOBILE DEVICE AND APPLICATION WITH SECURED
WIRELESS CONNECTION THROUGH LAN ROUTER OR
CELLULAR DATA SERVICE.
5. REMOTE CONNECTION THROUGH WEB ACCESS.
I. NETWORK PORTS: FOR HARDWIRED CONNECTION OF
DESKTOP OR PORTABLE WORKSTATION. NETWORK PORT TO
BE EASILY ACCESSIBLE, PROPERLY PROTECTED, CLEARLY
LABELED, AND INSTALLED AT THE FOLLOWING LOCATIONS:
1. EACH MECHANICAL EQUIPMENT ROOM.
2. EACH DIFFERENT ROOF LEVEL WITH ROOF-MOUNTED AIR-
HANDLING UNITS OR ROOFTOP UNITS.
J. CRITICAL ALARM REPORTING:
1. OPERATOR-SELECTED CRITICAL ALARMS MUST BE SENT BY
DDC SYSTEM TO NOTIFY OPERATOR OF CRITICAL ALARMS
THAT REQUIRE IMMEDIATE ATTENTION.
2. DDC SYSTEM MUST SEND ALARM NOTIFICATION TO
MULTIPLE RECIPIENTS THAT ARE ASSIGNED FOR EACH
ALARM.
3. DDC SYSTEM MUST NOTIFY RECIPIENTS BY ANY OR ALL
MEANS, INCLUDING E-MAIL, TEXT MESSAGE, AND
PRERECORDED PHONE MESSAGE TO MOBILE AND
LANDLINE PHONE NUMBERS.
K. INCLUDE BACNET COMMUNICATION PORTS, WHENEVER
AVAILABLE AS AN EQUIPMENT OEM STANDARD OPTION, FOR
INTEGRATION VIA A SINGLE COMMUNICATION CABLE. BACNET-
CONTROLLED PLANT EQUIPMENT INCLUDES, BUT IS NOT
LIMITED TO, BOILERS, CHILLERS, AND VARIABLE-SPEED
DRIVES.
L. INCLUDE GATEWAYS TO CONNECT BACNET TO LEGACY
SYSTEMS, EXISTING NON-BACNET DEVICES, AND EXISTING
NON-BACNET DDC-CONTROLLED EQUIPMENT, ONLY WHEN
SPECIFICALLY REQUESTED AND APPROVED BY OWNER.
CONTROLLER REQUIREMENTS:
A. DDC SYSTEM MUST CONSIST OF A COMBINATION OF NETWORK
CONTROLLERS, PROGRAMMABLE APPLICATION CONTROLLERS
AND APPLICATION-SPECIFIC CONTROLLERS TO SATISFY
PERFORMANCE REQUIREMENTS INDICATED.
B. DDC CONTROLLERS MUST PERFORM MONITORING, CONTROL,
ENERGY OPTIMIZATION, AND OTHER REQUIREMENTS
INDICATED.
C. DDC CONTROLLERS MUST USE A MULTITASKING, MULTIUSER,
REAL-TIME DIGITAL CONTROL MICROPROCESSOR WITH A
DISTRIBUTED NETWORK DATABASE AND INTELLIGENCE.
D. EACH DDC CONTROLLER MUST BE CAPABLE OF FULL AND
COMPLETE OPERATION AS A COMPLETELY INDEPENDENT UNIT
AND AS A PART OF A DDC SYSTEM-WIDE DISTRIBUTED
NETWORK.
E. NETWORK CONTROLLER REQUIREMENTS:
1. INCLUDE ADEQUATE NUMBER OF CONTROLLERS TO
ACHIEVE PERFORMANCE INDICATED.
2. SYSTEM MUST CONSIST OF ONE OR MORE INDEPENDENT,
STANDALONE, MICROPROCESSOR-BASED NETWORK
CONTROLLERS TO MANAGE GLOBAL STRATEGIES
INDICATED.
3. CONTROLLER MUST HAVE ENOUGH MEMORY TO SUPPORT
ITS OPERATING SYSTEM, DATABASE, AND PROGRAMMING
REQUIREMENTS.
4. DATA MUST BE SHARED BETWEEN NETWORKED
CONTROLLERS AND OTHER NETWORK DEVICES.
5. OPERATING SYSTEM OF CONTROLLER TO MANAGE INPUT
AND OUTPUT COMMUNICATION SIGNALS TO ALLOW
DISTRIBUTED CONTROLLERS MUST SHARE REAL AND
VIRTUAL OBJECT INFORMATION AND ALLOW FOR CENTRAL
MONITORING AND ALARMS.
6. CONTROLLERS MUST HAVE A REAL-TIME CLOCK.
7. CONTROLLER MUST CONTINUALLY CHECK STATUS OF ITS
PROCESSOR AND MEMORY CIRCUITS. IF AN ABNORMAL
OPERATION IS DETECTED, CONTROLLER MUST ASSUME A
PREDETERMINED FAILURE MODE AND GENERATE AN
ALARM NOTIFICATION.
8. CONTROLLERS MUST BE FULLY PROGRAMMABLE.
F. APPLICATION-SPECIFIC CONTROLLERS MUST BE
MICROPROCESSOR-BASED CONTROLLERS, WHICH THROUGH
HARDWARE OR FIRMWARE DESIGN ARE DEDICATED TO
CONTROL A SPECIFIC PIECE OF EQUIPMENT. CONTROLLERS
ARE NOT FULLY USER-PROGRAMMABLE BUT ARE
CONFIGURABLE AND CUSTOMIZABLE FOR OPERATION OF
EQUIPMENT THEY ARE DESIGNED TO CONTROL.
1. CAPABLE OF STANDALONE OPERATION AND MUST
CONTINUE TO INCLUDE CONTROL FUNCTIONS WITHOUT
BEING CONNECTED TO NETWORK.
2. DATA MUST BE SHARED BETWEEN NETWORKED
CONTROLLERS AND OTHER NETWORK DEVICES.
INSTALLATION REQUIREMENTS:
A. INSTALL PRODUCTS TO SATISFY MORE STRINGENT OF ALL
REQUIREMENTS INDICATED.
B. INSTALL PRODUCTS LEVEL, PLUMB, PARALLEL, AND
PERPENDICULAR WITH BUILDING CONSTRUCTION.
C. SUPPORT PRODUCTS, TUBING, PIPING, WIRING, AND
RACEWAYS. BRACE PRODUCTS TO PREVENT LATERAL
MOVEMENT AND SWAY OR A BREAK IN ATTACHMENT WHEN
SUBJECTED TO A FORCE.
D. FABRICATE OPENINGS AND INSTALL SLEEVES IN CEILINGS,
FLOORS, ROOF, AND WALLS REQUIRED BY INSTALLATION OF
PRODUCTS. BEFORE PROCEEDING WITH DRILLING, PUNCHING,
AND CUTTING, CHECK FOR CONCEALED WORK TO AVOID
DAMAGE. PATCH, FLASH, GROUT, SEAL, AND REFINISH
OPENINGS TO MATCH ADJACENT CONDITION.
E. IF PRODUCT LOCATIONS ARE NOT INDICATED, INSTALL
PRODUCTS IN LOCATIONS THAT ARE ACCESSIBLE AND THAT
WILL PERMIT SERVICE AND MAINTENANCE FROM FLOOR,
EQUIPMENT PLATFORMS, OR CATWALKS WITHOUT REMOVAL
OF PERMANENTLY INSTALLED FURNITURE AND EQUIPMENT.
F. CONTROL WIRE, CABLE, AND RACEWAYS INSTALLATION MUST
COMPLY WITH NECA 1.
G. ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE
WITH COMPLETE KNOWLEDGE OF PROJECT-SPECIFIC SYSTEM
INSTALLED TO TRAIN OWNER'S MAINTENANCE PERSONNEL TO
ADJUST, OPERATE, AND MAINTAIN DDC SYSTEM.
Copyright © 2026 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond & Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
PROJECT #:
/2
/2
:4
:5
P
M A u to d e sk
D o cs
/1
D u lu th M e ch a n ic a l C o n tr o ls /1
D u lu th M e ch
C o n tr o ls
M
E C
H v2
.r vt
95% DESIGN
M-302
TT
CMM
CMM
WWC
8/25/26
1260399
DULUTH
MECH
CONTROLS
3167 Main St, Duluth, GA 30096
MECHANICAL
SPECIFICATIONS
DULUTH
M A
R K
D E
S C
R
IP
T
IO
N D
A
File details come from the government source that posted it. Updated .