RFP Attachment J01b Lower Brule Pharm USP - Drawings.pdf

PDF 9 MB Posted

Attached to
Lower Brule Indian Health Center Pharmacy Renovation
Solicitation number
75H70124R00043
Issued by

About this file

This document is a Request for Proposals (RFP) for the renovation of the Lower Brule Indian Health Center (IHC) pharmacy in Lower Brule, South Dakota. The purpose of the project is to renovate the pharmacy to meet the compounding requirements of USP 795, 797, and 800. The contract will be a single Firm Fixed Price award, with a period of performance of 180 calendar days. The project is anticipated to be between $500,000 and $1,000,000 in value and is set aside for small businesses under NAICS code 236220 with a $45 million size standard. The solicitation will be posted on SAM.gov, and a site visit is required. Contractors must be registered in SAM to be considered for award. This is a 100% set-aside for small businesses.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER ARCHITECT

DSGW Architects

2 West First St. Suite 201

Duluth, MN 55802

Phone: 218-727-2626

Contact: Ryan Turner, AIA, ACHA, EDAC Email: rturner@dsgw.com

Great Plains Indian Health Services

Office of Environmental Health and Engineering

115 4th Ave. SE, Room 309 Aberdeen, SD 57401

Phone: 605-226-7581

Contact: Kurt Petersen

Email: kurt.petersen@ihs.gov

MECH/ELECT. ENGINEER

EDI-Dolejs Consulting Engineers

1112 North 5th Street

Minneapolis, MN 55411

Phone: 612-343-5965

Contact: Jay Hruby, PE Email: jhruby@edi-dolejs.com

Project Team

EARTH

COMPACT FILL/SAND

POROUS FILL/GRAVEL

FACE BRICK

MORTAR/PLASTER

CMU

CONCRETE

RIGID INSULATION

BATT INSULATION

STUD WALL/METAL

PLYWOOD

GYPSUM BOARD

FINISHED WOOD

CONT. ROUGH WOOD

WOOD BLOCKING

BITUMINOUS

Materials

Symbols

DETAIL

NUMBER

SHEET

NUMBER

AREA TO BE

DETAILED OR

ENLARGED

ACTUAL NORTH

(IF DIFFERENT)

REVISION TYPE

SHEET NUMBER

SECTION NUMBER

A8.1

MATCH LINE

SHEET

NUMBER

ELEVATION

NUMBER

A7.2

NORTH ARROW

DETAIL REFERENCESECTION REFERENCE

REVISION IDENTIFICATIONTITLE MARKER

ROOM IDENTIFICATION

ROOM NAME

ROOM NUMBER

DOOR TAG

BREAKLINE

ELEVATION REFERENCE

WALL TAGWINDOW TAG

ELEVATION LABEL MATCHLINE IDENTIFICATION NOTE IDENTIFICATION

(LEADER

OPTIONAL)

A7.1

A5.1

TOILET

ROOM

T.O. STL.

100'-0"

VIEW TITLE

VIEW SCALE

W205

1A S

I

5A

SEQUENTIAL

INDICATOR

APPROXIMATE

THICKNESS IN INCHES

N

(WHEN REQ'D)

REPRESENTS NEW

DOOR

REPRESENTS

EXISTING DOOR

TO REMAIN

REPRESENTS

EXISTING DOOR

TO BE REMOVED.

WALLS WITH

HATCH

INDICATE NEW

CONSTRUCTION

WALLS SHADED

GRAY INDICATE

EXISTING TO

REMAIN

DASHED LINES

INDICATE WALLS

& ITEMS TO BE

REMOVED.

PLAN NORTH

REVISION NUMBER

5A 48"

PARTIAL

WALL; HT

IN INCHES

PHASE 1 PHARMACY

PHASE 2 PHARMACY MAIN

ENTRY

Phase 1

• DEMO EXISTING OFFICE

• BUILD OUT TEMPORARY PHARMACY

• MOVE SHELVING AND EQUIPMENT FROM EXISTING PHARMACY TO TEMPORARY

PHARMACY.

Phasing Notes

Phase 2

• DEMO EXISTING PHARMACY AND MEDICAL RECORDS SPACES

• BUILD OUT NEW PHARMACY

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

023016.03

BC

RT

04/29/24

Lower Brule Pharmacy

USP

Compliance

G0.1

Title Sheet

601 Gall Street Lower Brule, SD 57548

Sheet Index 0-General Sheets

G0.1 Title Sheet

4-Architectural

A1.2 Demo Plan

A2.1 Floor Plans and Interior Elevations

A3.1 Reflected Ceiling Plan

A4.1 Schedules and Types

5-Mechanical

M0.1 Mechanical Title Sheet

M1.1 Partial Floor Plan - Phase 1 & 2 - Fire Protection

M2.0 Partial Underfloor Plan - Phase 1 - Plumbing

M2.1 Partial Underfloor Plan - Phase 2 - Plumbing

M2.2 Partial Floor Plan - Phase 1 - Plumbing

M2.3 Partial Floor Plan - Phase 2 - Plumbing

M3.1 Partial Floor Plan - Phase 1 - Piping

M3.2 Partial Floor Plan - Phase 2 - Piping

M4.1 Partial Floor Plan - Phase 1 - HVAC

M4.2 Partial Basement Floor Plan - Phase 2 - HVAC

M4.3 Partial Floor Plan - Phase 2 - HVAC

M5.1 Mechanical Schedules

M6.1 Mechanical Details

6-Electrical

E0.1 Electrical Title Sheet

E1.0 Basement - Electrical Demolition

E1.1 Partial Floor Plans - Demolition

E2.1 Partial Floor Plans - Lighting

E3.0 Basement - Power

E3.1 Partial Floor Plans - Power

E4.1 Partial Floor Plans - Systems

E6.1 Schedules - Electrical

E6.2 Scedules - Electrical

E7.1 Details - Electrical

Key Plan

Abbreviations

Project Number:

Lower Brule Pharmacy USP Compliance 601 Gall Street

Lower Brule, SD 57548

023016.03

Architectural General Notes

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECT

B.O. BOTTOM OF

B.SPLASH BACKSPLASH

BLDG BUILDING

BLKG BLOCKING

BRG BEARING

C-TOP COUNTERTOP

CG CORNER GUARD

CJ CONTROL JOINT

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONT CONTINOUS

CPT CARPET

CT CERAMIC TILE

D DEEP

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DN DOWN

DS DOWNSPOUT

DW DISHWASHER

EA EACH

EIFS EXTERIOR INSULATION & FINISH SYSTEM

EJ EXPANSION JOINT

ELEC ELECTRICAL

EPDM ETHYLENE PROPYLENE DIENE TERPOLYMER

ROOFING

EQ EQUAL

EQUIP / EQPT. EQUIPMENT

EXST / EX. / EXIST. EXISTING

F.T. FIRE TREATED

F.V. FIELD VERIFY

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FFGB FIBERGLASS FACED GYPSUM BOARD

FLR FLOOR

FRP FIBERGLASS REINFORCED PANEL

FTG FOOTING

FUR FURRING

GALV GALVANIZED

GB GRAB BAR

GLAZ GLAZING

GYP. BD. / G.BD / GBD GYPSUM BOARD

HC HANDICAPPED

HM HOLLOW METAL

HT HEIGHT

ICF INSULATED (OR INSULATING) CONCRETE FORM

INSUL INSULATION

JST JOIST

1. General Notes apply to all drawing sheets.

2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.

3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.

4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.

5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.

6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.

7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.

8. Immediately notify Architect of any long lead items that will affect the completion date

9. All wood in contact with concrete or concrete block to be pressure treated - typical.

10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.

11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code. Fireproof any new penetrations required by the work. Refer to code summary for ratings.

12. All exposed metal to receive paint unless otherwise noted

13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls

LAM LAMINATE

LVT LUXURY VINYL TILE

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

MISC MISCELLANEOUS

MTL METAL

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OPCI OWNER PROVIDED CONTRACTOR INSTALLED

P.T. PRESSURE TREATED

PC PRECAST

PLAM / P.LAM. PLASTIC LAMINATE

PLYWD PLYWOOD

PNT PAINT

PTD PAPER TOWEL DISPENSER

QT QUARRY TILE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIGERATOR

REINF REINFORCED

REQD REQUIRED

RPF STRIP REINFORCED PERIMETER FASTENING STRIP

RTU ROOF TOP UNIT (MECH.)

RWL RAIN WATER LEADER

S.SPLASH SIDESPLASH

SACT SUSPENDED ACOUSTICAL CEILING TILE

SCHED SCHEDULE

SD SOAP DISPENSER

SEAL SEALANT

SF SQUARE FOOT (FEET)

SIM SIMILAR

SIP STRUCTURAL INSULATED (OR INSULATING)

PANEL

SND SANITARY NAPKIN DISPOSAL

SPEC SPECIFICATION

SS STAINLESS STEEL

SSM SOLID SURFACE MATERIAL

STL STEEL

STRUCT STRUCTURAL CONSULTANT

T.O. TOP OF

TBB TILE BACKER BOARD

TP TOILET PAPER

TRTD TREATED

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VIF VERIFY IN FIELD

VWC VINYL WALL COVERING

W/ WITH

W/O WITHOUT

WD WOOD

WRB WEATHER RESISTIVE BARRIER

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

RYAN

TURNER

U.C.

Refr.

A1

A1

C1

OFFICE

C1

D1

D5

D1 D1

D2 C1 D3

D4

Z7

C1

Z2

G1

A1

A1

A1

A1

A1

A1

A1

DISPENSING

F1 Z8

Z9

Z9

Z9

Z10

Z2

Z2

MEDICAL RECORDS

NARCOTICS

F2

PHARMACY

F2 F1

Z3

C2

Z4

DISPENSING

PHARMACY

NARCOTICS

MEDICAL RECORDS

CORRIDOR

CORRIDOR

WAITING

Z11

Z11

Z13

Z12

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

023016.03

BC

RT

04/29/24

Lower Brule Pharmacy

USP

Compliance

A1.2

Demo Plan

601 Gall Street Lower Brule, SD 57548

1/4" = 1'-0"

DEMO PLAN - PHASE 1

Demo Plan Notes

A1 FURNITURE AND EQUIPMENT TO BE REMOVED BY OWNER

C1 DEMO & REMOVE EXISTING CASEWORK INCLUDING ANY UPPER OR LOWER CABINETS AND SHELVES, COUNTER, PLUMBING FIXTURES AND WALL MOUNTED ACCESSORIES

C2 REMOVE TALL OPEN STORAGE CABINET, RELOCATE TO PHASE 1 TEMP PHARMACY

D1 DEMO INTERIOR DOOR, FRAME & HARDWARE

D2 DEMO SECURITY MESH GATE, FRAME AND HARDWARE

D3 DEMO COILING SHUTTER

D4 DEMO PASSTHRU DOOR

D5 DEMO INTERIOR DOOR, FRAME & HARDWARE, SALVAGE FOR RELOCATION IN PHASE 2

F1 DEMO SHEET VINYL FLOOR, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE

F2 DEMO CORK FLOOR, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE

G1 DEMO EXTERIOR WINDOW, PREPARE FOR WALL INFILL TO MATCH EXISTING

Z2 REMOVE & SALVAGE EXISTING WALL MOUNTED ITEMS AND EQUIPMENT SUCH AS WHITEBOARDS FOR RELOCATION

Z3 REMOVE & SALVAGE EXISTING METAL SHELVING UNIT, RELOCATE TO PHASE 1 TEMP PHARMACY

Z4 CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR RELOCATION AND CALIBRATING EQUIPMENT TO PHASE 1

TEMP PHARMACY

Z7 REMOVE MOBILE HD SHELVING UNIT

Z8 REMOVE TV AND MOUNTING BRACKET, SALVAGE FOR RELOCATION IN PHASE 2

Z9 DEMO HAND RAIL

Z10 REMOVE AED CABINET, SALVAGE FOR RELOCATION

Z11 REMOVE AND RELOCATE UNDER COUNTER REFRIGERATOR TO PHASE 1 TEMP PHARMACY

Z12 REMOVE AND RELOCATE FILLMASTER DISP. AND FILTRATION SYSTEM TO PHASE 1 TEMP PHARMACY

Z13 REMOVE AND SALVAGE FOR RELOCATION EXISTING AIPHONE MASTER STATION AND DOOR STATION

Demo General Notes

1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.

2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.

3. Demolition notes without leaders indicate that the note applies to the entire room.

4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.

5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.

6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).

7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.

8. Prep floors as needed for new finishes.

9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.

10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.

11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.

12. Verify any items to be retained for owners use prior to removal.

13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.

1/4" = 1'-0"

DEMO PLAN - PHASE 2

1/4" = 1'-0"

DEMO PLAN - PHASE 1B

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

U .C

R e fr

U

.C

R e fr

A2.112

A2.1 11

WAITING

CONSULT

101NARCOTICS

PHARMACY

RECEIVING HZD

STORAGE

OFFICE

OFFICE

7'-9 7/8" 9'-8"

11'-6"

/8

A2.1 8

A2.19

TA

-W

107B

107A

B 101A

1B

7B

5C7B

7A

7B

7A

5B

5C

5C

8'-6"

CORRIDOR

100B

CORRIDOR

100C

CORRIDOR

100A

CORRIDOR

100D

TA-W1

100B

1'-10"

/8

1'-7"

/8

5C

7B

A2.1

A2.1

A2.14 3

A2.1

1A

3A

3A

7B

13 14

A2.1

8'-6"

5C 48"

INFILL WINODW OPENING, MATCH EXISTING WALL CONSTRUCTION.

USE FULL SHEET OF T1-11 SIDING FOR WINDOW INFILL.

/8

3'-0"

6'-2"

A2.1

RELOCATED

U/C REFR.

2'-0" 2'-0" 2'-0" 10"

STEEL PACKAGE

RECIEVER

TA-W1

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL MOUNTED

PHONE

3'-0" 3'-3" 2'-6" 9"

FILLER PANEL

WALL PORT W/

2" ID

GROMMET IN

COUNTERTOP

EXIST DF TO

REMAIN

RELOCATED TV AND

MOUNTING BRACKET,

PROVIDE BLOCKING

TA-W1

12" C-TOP SEE

SECTION 12 00 50

RELOCATED

LITERATURE RACK

FUTURE WALL

MOUNTED

MONITOR,

PROVIDE

BLOCKNING

STEEL PACKAGE

RECEIVER

CENTER UNDER WINDOW

4'-0" 5'-4"

1'-0" 3'-0" 5'-9"

2"

WALL PORT

W/ 2" ID

GROMMET IN

COUNTERTOP

Wall Types

5A

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

5B

OMIT BATT INSULATION, GYP BD

TO EXTEND 6" ABOVE CEILING

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

5C

3 5/8" 16 GAUGE METAL

STUD @ 16" O.C.

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/ SECURITY

BARRIER MESH

3 5/8" 16 GUAGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE SCHEDULE

ROOF OR FLOOR

STRUCTURE

5/8" GYP.BD.

1A

SECURITY BARRIER

MESH

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

EXISTING WALL

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE RCP

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

ACOUSTIC SEALANT

EA. SIDE

NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED

7/8" 4 7/8" 5 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER MESH

1B

BULLET RESISTANT

PANEL

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

EXISTING WALL

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE RCP

1 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

7A

6" METAL STUD @

16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

6" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

ACOUSTIC SEALANT

EA. SIDE

7 1/4"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

7B

6" 16 GAUGE METAL

STUD @ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/ SECURITY

BARRIER MESH

6" 16 GAUGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

ACOUSTIC SEALANT

EA. SIDE

7 1/2"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER MESH

3A

2 1/2" METAL

STUD @ 16" O.C.

5/8" GYP.BD.

METAL STUD WALL TO

STRUCTURE

2 1/2" METAL STUD

CHANNEL

2 1/2" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

COUNTERTOP,

SEE SECTION

12 00 50

RELOCATED

UNDERCTR

REFR.

2'-6"

RELOCATED

SHELVING UNITS

"4

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINET,

SEE SECTION

12 00 50

NARCOTICS SAFE

(NIC)

SIT-STAND

DESK (NIC)

RELOCATED

FILLMASTER

SD (OPCI)

PTH (OPCI)

FILLMASTER

FILTRATION

SYSTEM MOUNTED

IN CABINET,

RELOCATE FROM

EXIST PHARMACY

V E

R

IF

Y W

S

TA

FF

3'-9" 5'-0" 1" 2'-6" 3'-0" 1" 1'-0"

1" 3'-0" 5'-8"1"2'-0"2'-0"2'-2"2'-0"1'-6"

1"3'-0"3'-0"

3'-0"

TA-W1

FILLMASTER

RELOCATE FROM

TEMP PHARMACY

SD (OPCI)

PTH (OPCI)

FILLMASTER

FILTRATION SYSTEM

MOUNTED IN CABINET,

RELOCATE FROM TEMP

PHARMACY

BASE CABINET

AND COUNTERTOP,

SEE SECTION

12 00 50

BASE CABINETS

AND CNTRTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

W

S

TA

FF

V E

R

IF

Y

NEW REFR. (NIC)

PULL OUT

PRINTER SHELF

SUPPORT PANEL

TALL STORAGE

CABINET, SEE

SECTION 12 00 50

3'-0" 3'-0"

6'-0" 1'-6"

6"

WALL CABINET,

SEE SECTION

12 00 50

3'-6"

COUNTERTOP,

SEE SECTION

12 00 50

EXHAUST

GRILLES, SEE

MECH 3

" SINK W/

EYEWASH

SEE MECH

PTH (OPCI)

SD (OPCI)

O P

E R

A B

LE

P

A R

TS

TO

FRP WAINSCOT

1'-6"

6" 6" 6" 3'-6"

METAL LOCKERS

SEE SECTION

12 00 50

(4) ROBE HOOKS

2'-6" 2'-6" 2'-11"

(2) 2'-0" LONG

WILLCALL RODS

WALL MOUNTED

MONITOR MOUNTING

BRACKET, PROVIDE

BLOCKING

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

2'-6" 2'-6"

WALL CABINETS

SEE SECTION

12 00 50

2'-6"

COUNTERTOP,

SEE SECTION

12 00 50

MICROWAVE

(NIC)

RELOCATED

UNDER CTR.

REFR.

1"3'-0"3'-0"1"

BASE CABINETS

AND COUNTERTOP

SEE SECTION 12 00 50

(5) 4'-0" LONG

WILLCALL RODS

ON BRACKETS AND

STANDARDS, SEE

SECTION 10 28 00

2'-3" 4'-0"

2'-0" 6"

(2) 2'-0" L.

WILLCALL RODS

ON BRACKETS

AND STANDARDS

SEE SECTION

10 28 00

WIRE MESH PARTITION

AND DOOR, SEE

SECTION 10 22 13

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

023016.03

BC

RT

04/29/24

Lower Brule Pharmacy

USP

Compliance

A2.1

Floor Plans and Interior Elevations

601 Gall Street Lower Brule, SD 57548

1/4" = 1'-0"

FLOOR PLAN - PHASE 1

Floor Plan Notes

2 RELOCATED FILLMASTER AND FILTRATION SYSTEM FROM PHASE 1B DEMO

4 RELOCATED METAL SHELVING UNITS FROM PHASE 1B DEMO

5 RELOCATED TALL OPEN STORAGE CABIENTS FROM PHASE 1B DEMO

6 RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND

CALIBRATING EQUIPMENT

7 TV AND MOUNTING BRACKET, RELOCATED FROM PHASE 2 DEMO

8 LITERATURE RACK, RELOCATED FROM PHASE 2 DEMO

9 RELOCATED U/C REFRIGERATORS FROM PHASE 1A DEMO, 2nd REFR. SET ON TOP OF COUNTER

TOP

10 PROVIDE BLOCKING FOR FUTURE WALL MOUNTED MONITOR

11 (2) 2'-0" LONG WILL CALL RACKS, SEE SECTION 10 28 00

12 EXISTING RELOCATED AED, CABINET AND SIGN

13 AIPHONE DOOR STATION, SEE ELEC

14 AIPHONE MASTER STATION, SEE ELEC

15 WIRE MESH PARTITION AND DOOR, SEE SECTION 10 22 13

16 (5) 4'-0" LONG WILL CALL RACKS, SEE SECTION 10 28 00

17 STEEL PACKAGE RECIEVER

18 CONSULT DESK, SEE SECTION 12 00 50

19 (2) ROBE HOOKS MOUNTED 5'-0" AFF

20 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50

21 NARCOTICS SAFE RELOCATED FROM TEMP PHARMACY

22 NEW 30"X48" SIT-STAND DESK (NIC)

23 EXISTING RELOCATED MEDSAFE MEDICATION DISPOSAL BOX

24 NEW NARCOTICS SAFE (NIC)

25 NEW REFRIGERATOR (NIC)

26 EXISTING 30"X48" SIT-STAND DESK RELOCATED FROM TEMP PHARMACY

Floor Plan General Notes A Interior dimensions are to finished face of stud wall, face of masonry walls, to centerline of columns or to other grid points unless otherwise noted. Dimensions labeled as CLEAR or CLR indicate minimum distance to finished face of walls. Dimensions are to finished face of existing walls if applicable.

B All interior door frames to be 4" from adjacent wall or centered between walls unless otherwise noted.

C Furniture & equipment shown is for reference only and is not included in the contract.

D Coordinate size and location of all duct and shaft openings in walls and floors with MEP consultant.

E Fire ratings are indicated on the Life Safety Plan.

1/4" = 1'-0"

FLOOR PLAN - PHASE 2

1/4" = 1'-0"

ELEV PHARMACY - EAST

1/4" = 1'-0"

ELEV WAITING - WEST

1/4" = 1'-0"

TEMP PHARMACY - EAST

1/4" = 1'-0"

ELEV TEMP PHARMACY - WEST

1/4" = 1'-0"

ELEV PHARMACY - NORTH

1/4" = 1'-0"

ELEV PHARMACY - SOUTH

1/4" = 1'-0"

RECEIVING/ HZRD STOR. - EAST

1/4" = 1'-0"

RECEIVING/ HZD STOR - WEST

1/4" = 1'-0"

ELEV PHARMACY HALLWAY

1/4" = 1'-0"

ELEV NARCOTICS - WEST

1/4" = 1'-0"

ELEV OFFICE - SOUTH

1/4" = 1'-0"

PHARMACY - NORTH

1/4" = 1'-0"

PHARMACY - SOUTH

1/4" = 1'-0"

ELEV NARCOTICS - NORTH

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

OFFICE

RECEIVING HZD

STORAGE

OFFICE

PHARMACY

NARCOTICS

CONSULT

WAITING

7'-6"

8'-0" 8'-0"

PATCH TO MATCH

ACT CEILING WERE

REMODELING

OCCURS

7'-0"

GYP BD AND

SECURITY BARRIER

MESH CEILING, SEE

DETAIL 2/A3.1

A3.1

A3.1

8'-0"

8'-0"

7'-0"

CORRIDOR

100B

8'-0"

A3.1

STRUCTURE/FRAMING ABOVE

3 5/8" 16 GAUGE METAL

STUD FRAMING

5/8" GYP. BD.

SECURITY BARRIER MESH

METAL CORNER BEAD

V E

R

IF

Y W

R

C P

SACT CEILING

3-5/8" MTL. STUD W/

5/8" GYP. BD.

NOTE: SEE RCP FOR BULKHEAD HEIGHTS

NOTE: SEE RCP FOR SOFFIT HEIGHTS

METAL CORNER BEAD

5/8" GYP. BOARD

3 5/8" MTL. STUDS @ 16"

O.C.

CEILING AS SCHEDULED

NOTE:

PROVIDE SECERITY BARRIER

MESH AT NARCOTICS ROOM 108

NOTE: SEE RCP FOR SOFFIT HEIGHTS

METAL CORNER BEAD

5/8" GYP. BOARD

3 5/8" 16 GAUGE MTL.

STUDS @ 16" O.C.

3 5/8" 16 GAUGE METAL

STUD FRAMING

5/8" GYP. BD.

SECURITY BARRIER

MESH

SECURITY BARRIER

MESH

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

023016.03

BC

RT

04/29/24

Lower Brule Pharmacy

USP

Compliance

A3.1

Reflected Ceiling Plan

601 Gall Street Lower Brule, SD 57548

1/4" = 1'-0"

REFLECTED CEILING PLAN - PHASE 2

RCP General Notes

1. Coordinate final locations of ceiling mounted equipment w/ owner and architect.

2. See M&E drawings for lighting, grills, and diffuser locations.

3. Suspended acoustical ceiling tile grid is to be centered in rectangular room or centered between the longest walls of irregularly shaped rooms unless otherwise noted.

4. Verify gypsum board control joint locations with architect prior to installation.

5. Ceiling heights indicated are from finished floor of current level shown.

1" = 1'-0"

Gyp. Bd. Ceiling Detail

1" = 1'-0"

Bulkhead Detail

1" = 1'-0"

Gyp. Bd. Soffit

1" = 1'-0"

Gyp. Bd. Soffit at Narcotics êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

Door Types

WD-D1

Solid Core

Wood Flush

WD-D2

Solid Core Wood w/Quarter Lite

8" 8"

WD-D3

Solid Core Wood w/Half Lite

8" 8"

1/4" TEMPERED

GLASS

1/4" TEMPERED

GLASS

Frame Types

HM-F1

Hollow Metal

FRAME WIDTH IS 2" UNLESS OTHERWISE DIMENSIONED. FRAME DEPTH TO MATCH WALL THICKNESS

PER INDUSTRY STANDARDS UNLESS OTHERWISE NOTED. SEE DETAILS.

SEE SCHED

S E

E S

C H

E D

U

LE

TA-W1

QUICKSERV

SPEAK AROUND

36X36

3'-0"

INTERCOM

SYSTEM

LEVEL 3 BULLET

RESISTANT

GLAZING

5/8" GYP. BD. EA. SIDE

MTL. STUD @ 16" O.C. FILL

W/ BATT INSUL. SEE WALL

TYPES

CONT. SEALANT

BOTH SIDES

H.M. FRAME

DOOR PANEL; SEE TYPES

MTL. STUD CHANNEL - SEE

STRUCT. FOR LINTEL

CONT. SEALANT BOTH SIDES

H.M. FRAME

DOOR PANEL; SEE TYPES

METAL STUDS @ 16" O.C.

FILL W/BATT INSUL; SEE

WALL TYPES

STL. ANCHORS (3 PER JAMB,

FLOOR CLIP EA. JAMB)

METAL STUDS (2)

5/8" GYP. BD. BOTH SIDES

WAITING

CONSULT

NARCOTICS

PHARMACY

RECEIVING HZD

STORAGE

OFFICE

OFFICE

need location for aed cabinet

CG-1

HR-1

HR-1

HR-1

PAINT TO MATCH EXISTING

P N

T-

PNT-5

P N

T-

CORRIDOR

100D

PNT-5

P N

T-

FRP/

EPOXY PNT

FRP/

EPOXY PNT

FRP/

EPOXY PNT

Finish Abbreviations

ACT ACOUSTICAL CEILING TILE

CT PORCELAIN/CERAMIC TILE

EXIST. EXISTING

GYP. BD. GYPSUM BOARD

LVT LUXURY VINYL TILE

T.B.B. TILE BACKER BOARD

VCT VINYL COMPOSITION TILE

QT QUARRY TILE

EP EPOXY

PNT PAINT

CPT CARPET

VWC VYNL WALLCOVERING

WB WOOD BASE

WS WINDOW SHADE

WD WOOD

FRP FIBER REFORCED PANEL

CG CORNER GUARD

VB VINYL BASE

1. SEE FINISH PLAN FOR CLARIFICATION OF FLOOR AND WALL FINISH LOCATIONS.

2. ALL WALLS TO RECIEVE PNT-1 UNLESS OTHERWISE NOTED

3. ALL CEILING TO RECEIVE PNT-4 UNLESS OTHERWISE NOTED

4. ALL HM FRAMES AND DOORS TO RECEIVE PNT-3 UNLESS OTHERWISE NOTED

5. ALL FLOORS TO RECEIVE RB-1 UNLESS OTHERWISE NOTED IN FINISH SCHEDULE

6. FRP WAINSCOT TO 4'-0" ABOVE BASE. SEAL TOP, BOTTOM AND ALL JOINTS W/

CHEMLINK M-1 CR SEALANT.

Finish Notes

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

023016.03

BC

RT

04/29/24

Lower Brule Pharmacy

USP

Compliance

A4.1

Schedules and Types

601 Gall Street Lower Brule, SD 57548

1 1/2" = 1'-0"

HM Door Head @ Metal Stud Wall 1 1/2" = 1'-0"

HM Door Jamb @ Metal Stud Wall

ROOM FINISH SCHEDULE

NO. NAME

FLOOR WALL FINISH

NOTESFINISH BASE NORTH EAST SOUTH WEST

100 WAITING EXIST MATCH EXIST EXIST EXIST PNT-5 PNT-5

100A CORRIDOR SEE NOTES PNT PNT PATCH TO MATCH EXISTING WERE REMODELING OCCURS

100B CORRIDOR SEE NOTES EXIST PNT PNT EXIST PATCH TO MATCH EXISTING WERE REMODELING OCCURS

100C CORRIDOR SEE NOTES PNT PATCH TO MATCH EXISTING WERE REMODELING OCCURS

100D CORRIDOR PNT-5

101 CONSULT LVT-1 RB PNT PNT PNT PNT-2

105 PHARMACY SV-1 RB PNT PNT PNT-2 PNT

106 OFFICE LVT-1 RB PNT PNT PNT-2 PNT

107 RECEIVING HZD STORAGE SV-2 RB FRP/ EPOXY PNT EPOXY PNT FRP/ EPOXY PNT RFP/ EPOXY PNT

108 NARCOTICS SV-1 RB PNT PNT PNT PNT

114 OFFICE LVT-1 RB PNT PNT PNT-2 PNT

DOOR AND FRAME SCHEDULE

DOOR FRAME

FIRE LABEL

HDW.

NO. NOTESNO. WIDTH HEIGHT TYPE TYPE

DETAIL

HEAD JAMB SILL

100B 3'-0" 7'-0" EXISTING

DOOR, FRAME

AND

HARDWARE

RELOCATED

101A 3'-0" 7'-0" WD-D1 HM-F1 -- 03

101B 3'-0" 7'-0" WD-D2 HM-F1 1/A4.1 2/A4.1 -- 02

106 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 -- 01

107A 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 -- 02

107B 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 02

114 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 -- 01

1/4" = 1'-0"

FINISH PLAN - PHASE 2

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

PLUMBING AND PIPING SYMBOLS

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

DRAIN SIZE

PIPE RISE

PIPE DROP

PIPE TEE REDUCING 45

DEGREE TEE

45 DEGREE TEE

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

TYPE (SEE SCHEDULE)

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

LINEAR DIFFUSER TAG

CFM

TYPE (SEE SCHEDULE)

ACTIVE SLOT LENGTH /

NUMBER OF SLOTS

DUCT BEING DEMOLISHED

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

EQUIPMENT BY OTHERS

(REFER TO OTHER DISCIPLINE

FOR ADDITIONAL INFORMATION)

EXISTING EQUIPMENT

TO REMAIN

Ø ROUND

ABV ABOVE

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CW COLD WATER

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FL FLOOR

ABBREVIATIONS

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AFMS AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CF CABINET FAN

CF CHEMICAL FEEDER

CFP CHEMICAL FEEDER PUMP

CH CHILLER

CRU CONDENSATE RETURN UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

CHWP CHILLED WATER PUMP

CWP CONDESATE WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

H HUMIDIFIER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

PF PROPELLER FAN

PRV POWER ROOF VENTILATOR

PWF POWER WALL FAN

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SA SHOCK ABSORBER

SAT SOUND ATTENUATOR

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

US UTILITY SET

UV UNIT VENTILATOR

WFMS WATER FLOW MEASURING STATION

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

TYPE (SEE SCHEDULE)

BOTTOM OF EQUIPMENT

ELEVATION

HEATING

COIL

FLOW OPERATING WEIGHT

NOT INCLUDING CURB

FUEL INPUT

GAS PIPE FLOW

NOMINAL COOLING

CAPACITY

DRAIN TAGS

"P" - INDICATES

PRIMER CONNECTION

FIXTURE UNITS

ROOF AREA

SERVED BY DRAIN

PIPE ACCESSORY TAGS

DATA DEVICE TAGS

DAMPER TAGS

EQUIPMENT ID

SYMBOL

FIXTURE UNITS

PIPE ACCESORY

TAG

PLUMBING FIXTURE TAGS

TYPE (SEE SCHEDULE)

EXISTING RELOCATED

EQUIPMENT

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

MECHANICAL SHEET INDEX

CD-XXX

CFM

TYPE (SEE SCHEDULE)

CG-XXX

24x24 SIZE (NOTED IF DIFFERENT

THAN 24x12)

CFM

TYPE (SEE SCHEDULE)

CD-XXX

CFMSR-XXX

24x24 SIZE

TYPE (SEE SCHEDULE)

CFMRR-XXX

24x24 SIZE

TYPE (SEE SCHEDULE)

LSD-XXX

48" x (2) 3/4" SLOTS

VAV-XX

RTU-XX

SENSOR

MANUAL SWITCH

THERMOSTAT

TEMPERATURE SENSOR

TEMPERATURE & HUMIDITY SENSOR

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

HUMIDISTAT

LINEAR SLOT

DIFFUSER

ROUND DIFFUSER

WITH ADJUSTABLE

PATTERNS

SUPPLY

REGISTER/GRILLE

CEILING DIFFUSER

RETURN/EXHAUST

REGISTER/GRILLE

CEILING RETURN

GRILLE

4000 SF

6" SD-1

4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN

4" FS-4FLOOR SINK

4" SD-29 DECK DRAIN4" FD-3PFLOOR DRAIN

8 WFU

4" FD-13

HUB DRAIN

FLOW CONTROL

DRAIN

4" SD-12

COMBINATION

DRAINS

STORM DRAIN4" SD-15

WATER CLOSET -

WALL HUNG - ADA WC-1

U-1

1 WFU

LAV-1

1.5 CWFU

1.5 HWFU

LAV-1

WC-1A

VAV-XX

10' - 0"

(E)VAV-XX

VAV-XX

590 lb

RTU-XX

4.0 ton

RTU-XX

115000 Btu/h

115 CFH

RTU-XX

Htg: 3.7 GPM

VAV-XX

VAV BOX

ROOFTOP UNIT

(R)VAV-XX

16/8

16/8

(E)

F

FS

M

B

D

FS

16Ø

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE

DAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

Room

CHWS

CWV

CA

CD

CDR

CWR

CWS

CW

F-CW

H-CW

S-CW

HW

HW 140°

HW-R

HW-R 140°

GV

GW

HWR

HWS

G

OV

OW

PD

V

SS

SHWR

SHWS

STM

SD

OSD

(E)

CHWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

COMBINATION WASTE & VENT

COMPRESSED AIR

CONDENSATE DRAINAGE

CONDENSATE RETURN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

DOMESTIC COLD WATER

FILTERED COLD WATER

HARD COLD WATER

SOFT COLD WATER

HOT WATER

HOT WATER 140°

HOT WATER RECIRCULATION

HOT WATER RECIRCULATION 140°

GREASE VENT

GREASE WASTE

HEATING WATER RETURN

HEATING WATER SUPPLY

NATURAL GAS

OIL VENT

OIL WASTE

PUMP DISCHARGE

SANITARY VENT

SANITARY SEWER

SOLAR HOT WATER RETURN

SOLAR HOT WATER SUPPLY

STEAM

STORM DRAINAGE

OVERFLOW STORM DRAINAGE

REF-L

REF-S

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

2"

4"

4"

REF-HG REFRIGERANT-HOT GAS

PG PROPANE GAS

INVERT: -105' - 1"

1/8" / 12" SLOPE

RO REVERSE OSMOSIS WATER

IW INDIRECT WASTE

2" DOM. WM

DOMESTIC WATER METER

BALANCING VALVE

1/4 TURN BALL VALVE

CHECK VALVE

3-WAY MIXING VALVE

MOTORIZED CONTROL VALVE

3 WAY MOTORIZED CONTROL VALVE

PRESSURE REDUCING VALVE

REFRIGERANT SOLENOID VALVE

BUTTERFLY VALVE

2" BALANCING

2" SHUTOFF

2" CHECK

2" TMV

2" M-CNTRL

2" 3-WAY CNTRL

2" PRV

3/8" SOLENOID

2" BUTTERFLY

4" WCO 4" WCO

CAP

PLUG

GWR

GWS

GEOTHERMAL WATER RETURN

GEOTHERMAL WATER SUPPLY

CO2

CO

H

HS

NO2

S

TH

TS

T

MS

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

MECHANICAL DRAWINGS

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

Lower Brule Pharmacy UPS Compliance 601 Gall St.

Lower Brule, SD 57548

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M0.1

Mechanical

Title Sheet

M0.1 Mechanical Title Sheet

M1.1 Partial Floor Plan - Phase 1 & 2 - Fire Protection

M2.1 Partial Underfloor Plan - Phase 1 - Plumbing

M2.2 Partial Underfloor Plan - Phase 2 - Plumbing

M2.3 Partial Floor Plan - Phase 1 - Plumbing

M2.4 Partial Floor Plan - Phase 2 - Plumbing

M3.1 Partial Floor Plan - Phase 1 - Piping

M3.2 Partial Floor Plan - Phase 2 - Piping

M4.1 Partial Floor Plan - Phase 1 - HVAC

M4.2 Partial Basement Floor Plan - Phase 2 - HVAC

M4.3 Partial First Floor Plan - Phase 2 - HVAC

M5.1 Mechanical Schedules

M6.1 Mechanical Details êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

PLAN NOTES

GENERAL NOTES

A. THIS DRAWING IS A BID DOCUMENT AND IS NOT A DESIGN DRAWING.

CONFIRMATION OF FINAL DESIGN VIA SHOP DRAWINGS, HYDRAULIC

CALCULATIONS, PRODUCT SUBMITTALS, ETC. IS THE SOLE

RESPONSIBILITY OF THE FIRE PROTECTION DESIGN/BUILD

CONTRACTOR.

B. REFER TO ARCHITECTURAL PLANS FOR COMPLETE

CEILING/FLOOR/ROOM PLAN INFORMATION.

C. ALL AREAS SHALL BE DESIGNED AS LIGHT HAZARD OCCUPANCY

UNLESS INDICATED OTHERWISE OR AS REQUIRED BY AUTHORITIES

HAVING JURISDICTION.

D. PROVIDE PROTECTION ABOVE AND BELOW OBSTRUCTIONS AS

REQUIRED, WHETHER INDICATED OR NOT.

E. ALL SPRINKLERS LOCATED IN FINISHED AREAS SHALL BE

SYMMETRICAL IN PATTERN FOR THE AREA SERVED.

F. HIGH TEMPERATURE SPRINKLERS SHALL BE PROVIDED NEAR ALL

HEAT PRODUCING EQUIPMENT IN ACCORDANCE WITH NFPA 13.

G. DRY TYPE PENDANT AND SIDEWALL SPRINKLER HEADS SHALL

FOLLOW THE MANUFACTURER'S REQUIREMENTS FOR THE MINIMUM

BARREL LENGTH IN THE HEATED AREA.

H. PROVIDE AUXILIARY DRAINS WITH PIPING TO APPROVED LOCATIONS

FOR ALL TRAPPED PIPING. DRAIN PIPING SHALL BE SIZED PER NFPA

13 REQUIREMENTS.

I. ALL WALL AND FLOOR PENETRATIONS WITH FIRE PROTECTION

PIPING SHALL BE FULLY SLEEVED AND SEALED.

J. APPROVED THROUGH PENETRATION FIRE STOP SYSTEMS SHALL BE

USED FOR ALL RATED WALLS AND FLOORS TO MAINTAIN RATING.

K. NO STORAGE IS PERMITTED IN MECHANICAL OR ELECTRICAL ROOMS.

L. EXTENDED COVERAGE SPRINKLERS SHALL NOT BE INSTALLED IN

MECHANICAL ROOMS.

M. DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS

ALLOWED BY NFPA 13 SHALL NOT APPLY TO AREAS WITH CLOUD

CEILINGS.

N. ALL MATERIALS USED IN THE INSTALLATION OF THE FIRE

PROTECTION SYSTEMS SHALL BE NEW AND OF CURRENT ISSUE,

APPROVED BY U.L. AND/OR F.M. AND THE AUTHORITIES HAVING

JURISDICTION.

O. ALL FIRE PROTECTION WET AND DRY TYPE SYSTEM PIPING SHALL BE

STEEL. DRY TYPE SYSTEM PIPING SHALL BE SCHEDULE 40.

P. WHERE NEW SPRINKLER HEADS ARE INSTALLED IN AREAS WITH

CEILINGS THEY SHALL BE CENTERED IN THE CEILING TILES.

Q. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR

CONFIRMING FINAL SPRINKLER TYPES. LOCATIONS AND FINISHES IN

ALL AREAS WITH ARCHITECT.

R. TAMPER SWITCHES AND FLOW SWITCHES SHALL BE FURNISHED AND

INSTALLED BY FIRE PROTECTION CONTRACTOR. WIRING OF SUCH

DEVICES IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR.

COORDINATE ALL FIRE PROTECTION WORK WITH FIRE ALARM

CONTRACTOR.

1. DISCONNECT AND REMOVE EXISTING SPRINKLER HEADS, FITTINGS,

ESCUTCHEONS AND RELATED PIPING AS REQUIRED TO

ACCOMMODATE NEW CONSTRUCTION. PROVIDE NEW SPRINKLER

HEADS, FITTINGS, ESCUTCHEONS AND PIPING TO COORDINATE

WITH CEILINGS, WALLS, RELATED MECHANICAL AND ELECTRICAL

SYSTEMS AND CEILING DEVICES. SPRINKLER DESIGN AND

INSTALLATION SHALL COMPLY WITH NFPA 13, OWNER INSURANCE

REQUIREMENTS AND AUTHORITIES HAVING JURISDICTION. NEW

SPRINKLER HEADS SHALL MATCH EXISTING HEADS IN

APPEARANCE AND FUNCTION.

2. MINIMUM OCCUPANCY CLASSIFICATION FOR BIDDING PURPOSES:

ORDINARY HAZARD GROUP 1.

Space

RECEIVING HZD

STORAGE

OFFICE

OFFICE

PHARMACY

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M1.1

Partial Floor

Plan - Phase 1 &

2 - Fire

Protection

NORTH

0 4' 8'2' 1/4" = 1'-0"M1.1

1 Partial Floor Plan - Phase 1 - Fire Protection

0 4' 8'2' 1/4" = 1'-0"M1.1

2 Partial Floor Plan - Phase 2 - Fire Protection

NORTH

êÉîáëáçå=L

2" SS UP TO SK-1

CONNECT TO

NEAREST EXISTING

2" SS OR LARGER.

CONNECT TO

NEAREST EXISTING

1/2" CW OR LARGER

AND 1/2" HW OR

LARGER.

A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING

WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,

PIPING AND EQUIPMENT TO BE REMOVED.

B. NOTIFY ENGINEER OF ANY DISCREPANCIES.

C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR

CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL

MATCH SURROUNDINGS SURFACES.

D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE

EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A

NON-ACCESSIBLE TRAP, TYPICAL.

E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE

EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.

TYPICAL.

F. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND

THROUGH FLOOR SHALL BE 2" MINIMUM.

G. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M6.1

INDICATING INSTALLATION REQUIREMENTS, TYPICAL.

H. REFER TO PIPE PENETRATION DETAIL ON SHEET M6.1 FOR PIPE

PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.

I. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC

WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,

VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET

M5.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.

TYPICAL.

J. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING

THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.

REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET

M6.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY

EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.

K. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER

BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH

VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION

SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.

1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE

IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL

CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,

DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-

IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M2.1

Partial

Underfloor

Plan - Phase 1 -

Plumbing

NORTHNORTH

1/4" = 1'-0"M2.1

1 Partial Underfloor Plan - Phase 1 - Plumbing 1/4" = 1'-0"M2.1

2 Partial Underfloor Plan - Phase 1 - Plumbing

SHUT OFF VALVE,

TYPICAL UNLESS

OTHERWISE NOTED. êÉîáëáçå=L

1/2" CW, 1/2" HW, AND

2" SS LOCATED IN

BASEMENT UP TO SK-1.

1/2" CW, 1/2" HW AND

2" SS LOCATED IN

BASEMENT CEILING

SPACE UP TO SK-3

3/4" CW AND 3/4" HW UP

TO EEW-1 AND ETMV-1

EXTEND ABOVE FLOOR

WASTE AS REQUIRED TO

CONNECT TO EXISTING

WASTE AND CONNECT

NEW 2" WASTE TO

EXISTING. PROVIDE NEW

SANITARY WYE FITTING.

FIELD VERIFY EXACT

LOCATION OF EXISTING

WASTE.

EXTEND HOT AND COLD WATER AS

REQUIRED TO CONNECT TO EXISTING

HOT AND COLD WATER AND CONNECT

NEW 3/4" HOT AND 3/4" COLD WATER TO

EXISTING. PROVIDE NEW TEE FITTINGS.

FIELD VERIFY EXACT LOCATION OF

EXISTING HOT AND COLD WATER.

3/4" HW

3/4" CW

1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE

IDENTIFICATION. PROVIDE ROUGH-IN AND FINAL CONNECTIONS.

REFER TO DIVISION 22 SPECIFICATION FOR MODEL, DESCRIPTION

AND ADDITIONAL INFORMATION. TYPICAL.

2. SHUT OFF VALVE, TYPICAL UNLESS OTHERWISE NOTED.

A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING

WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK, PIPING

AND EQUIPMENT TO BE REMOVED.

B. NOTIFY ENGINEER OF ANY DISCREPANCIES.

C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR

CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL

MATCH SURROUNDINGS SURFACES.

D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE

EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A

NON-ACCESSIBLE TRAP, TYPICAL.

E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE

EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS. TYPICAL.

F. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET MX.X

INDICATING INSTALLATION REQUIREMENTS, TYPICAL.

G. REFER TO PIPE PENETRATION DETAIL ON SHEET MX.X FOR PIPE

PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.

H. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC

WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,

VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET

MX.X FOR PLUMBING ROUGH-IN SCHEDULE, TYPICAL.

I. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING

THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.

REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET

MX.X FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY

EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.

J. PROVIDE A MINIMUM OF 2-INCH (R-10) RIGID POLYSTYRENE

INSULATION BOARD ON ALL BELOW GRADE SANITARY SEWER AND

STORM DRAIN PIPING LOCATED OUTSIDE THE BUILDING

FOUNDATION WALL, IF THE PIPING HAS LESS THAN 5'-0" COVER

OVER THE TOP OF THE PIPE. INSULATION SHALL ALSO BE LOCATED

ALONG EACH SIDE OF THE PIPE AT 30 DEGREE ANGLE FROM

VERTICAL.

K. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING ROUGH-

IN SIZES AND ADDITIONAL INFORMATION, TYPICAL.

L. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

M. PROVIDE A WALL CLEANOUT AS REQUIRED TO SERVE EACH

PLUMBING FIXTURE THAT HAS A NON-ACCESSIBLE TRAP, TYPICAL.

DISCONNECT AND REMOVE EXISTING

1/2" CW, 1/2" HW AND 2" SS PIPING UP

TO EXISTING SINK. CAP AT MAINS.

SK-1

1 1/2" V

CO

SK-3

1 1/2" V

2" SS

CO

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M2.2

Partial

Underfloor

Plan - Phase 2 -

Plumbing

NORTH

0 4' 8'2' 1/4" = 1'-0"M2.2

1 Partial Underfloor Plan - Phase 2 - Plumbing

0 4' 8'2' 1/4" = 1'-0"M2.2

2 Partial Underfloor Plan - Phase 2 - Plumbing Demolition

NORTH

NOT TO SCALEM2.2

3 Plumbing Riser - Waste and Vent - 105 Pharmacy

NOT TO SCALEM2.2

4 Plumbing Riser - Waste and Vent - 107 Receiving/HZD Storage

PHARMACY

RECEIVING / HZD

STORAGE

R e fr

U

.C

R e fr

PLAN NOTES

GENERAL NOTES

Space

SK-1

CONNECT NEW 1-1/2" V TO

NEAREST EXISTING 1-1/2" V

OR LARGER.

A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING

WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,

PIPING AND EQUIPMENT TO BE REMOVED.

B. NOTIFY ENGINEER OF ANY DISCREPANCIES.

C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR

CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL

MATCH SURROUNDINGS SURFACES.

D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE

EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A

NON-ACCESSIBLE TRAP, TYPICAL.

E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE

EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.

TYPICAL.

F. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE

WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH

CODE REQUIREMENTS. TYPICAL.

G. PROVIDE A FULL SIZE CLEANOUT AT THE BASE OF EACH SOIL,

WASTE, OR STORM DRAIN STACK. CLEAN OUT TO BE LOCATED AT

18'' A.F.F. PROVIDE A CLEANOUT COVER PLATE WHERE STACKS

ARE LOCATED IN WALLS.

H. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND

THROUGH FLOOR SHALL BE 2" MINIMUM.

I. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M8.1

INDICATING INSTALLATION REQUIREMENTS, TYPICAL.

J. REFER TO PIPE PENETRATION DETAIL ON SHEET M8.1 FOR PIPE

PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.

K. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC

WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,

VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET

M7.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.

TYPICAL.

L. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING

THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.

REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET

M8.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY

EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.

M. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER

BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH

VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION

SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.

N. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING

ROUGH-IN PIPE SIZES AND ADDTIONAL INFORMATION, TYPICAL.

O. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

P. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER

SERVING FAUCETS AND ON QUICK CLOSING DEVICES. REFER TO

SPECIFICATION SECTION 22 1119 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS, TYPICAL.

1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE

IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL

CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,

DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-

IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M2.3

Partial Floor

Plan - Phase 1 -

Plumbing

NORTHNORTH

0 4' 8'2' 1/4" = 1'-0"M2.3

1 Partial Floor Plan - Phase 1 - Plumbing Demolition

0 4' 8'2' 1/4" = 1'-0"M2.3

2 Partial Floor Plan - Phase 1 - Plumbing

A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING

WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,

PIPING AND EQUIPMENT TO BE REMOVED.

B. NOTIFY ENGINEER OF ANY DISCREPANCIES.

C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR

CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL

MATCH SURROUNDINGS SURFACES.

D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE

EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A

NON-ACCESSIBLE TRAP, TYPICAL.

E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE

EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.

TYPICAL.

F. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE

WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH

CODE REQUIREMENTS. TYPICAL.

G. PROVIDE A FULL SIZE CLEANOUT AT THE BASE OF EACH SOIL,

WASTE, OR STORM DRAIN STACK. CLEAN OUT TO BE LOCATED AT

18'' A.F.F. PROVIDE A CLEANOUT COVER PLATE WHERE STACKS

ARE LOCATED IN WALLS.

H. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND

THROUGH FLOOR SHALL BE 2" MINIMUM.

I. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M8.1

INDICATING INSTALLATION REQUIREMENTS, TYPICAL.

J. REFER TO PIPE PENETRATION DETAIL ON SHEET M8.1 FOR PIPE

PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.

K. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC

WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,

VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET

M7.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.

TYPICAL.

L. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING

THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.

REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET

M8.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY

EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.

M. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER

BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH

VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION

SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.

N. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING

ROUGH-IN PIPE SIZES AND ADDTIONAL INFORMATION, TYPICAL.

O. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

P. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER

SERVING FAUCETS AND ON QUICK CLOSING DEVICES. REFER TO

SPECIFICATION SECTION 22 1119 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS, TYPICAL.

1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE

IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL

CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,

DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-

IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.

DISCONNECT AND REMOVE EXISTING

SINK, AND ALL ASSOCIATED HOT,

COLD, WASTE AND VENT PIPING BACK

TO MAINS AND CAP.

EXISTING ELECTRIC

WATER COOLER TO

REMAIN.

RECEIVING HZD

STORAGE

OFFICE

OFFICE

PHARMACY

3/4" ETMV-1

EEW-1

SK-3

SK-1

1 1/2" V1/2" CW, 1/2" HW,

AND 2" SS DOWN.

3/4" CW AND 3/4" HW

DOWN.

1/2" CW, 1/2" HW, AND

2" SS DOWN.

EXISTING ELECTRIC

WATER COOLER TO

REMAIN.

1 1 1/2" V

NARCOTICS

CONSULT

SK-1

SHUT OFF VALVE,

TYPICAL UNLESS

OTHERWISE NOTED.

EEW-1

3/4" ETMV-1

3/4" HW

3/4" CW

SK-3

3/4" CW

3/4" HW

SHUT OFF VALVE,

TYPICAL UNLESS

OTHERWISE NOTED.

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M2.4

Partial Floor

Plan - Phase 2 -

Plumbing

NORTHNORTH

0 4' 8'2' 1/4" = 1'-0"M2.4

1 Partial Floor Plan - Phase 2 - Plumbing Demolition

0 4' 8'2' 1/4" = 1'-0"M2.4

2 Partial Floor Plan - Phase 2 - Plumbing

NOT TO SCALEM2.4

3 Plumbing Riser - Domestic Water - 105 Pharmacy

NOT TO SCALEM2.4

4 Plumbing Riser - Domestic Water - 107 Receiving/HZD Storage

PHARMACY

RECEIVING / HZD

STORAGE

R e fr

U

.C

R e fr

EXISTING PIPING CONDITIONS

TO REMAIN IN THIS AREA

Space

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW

1112 North 5th Street Minneapolis, MN 55411

(612) 343-5965

1624 North Riverfront Drive Mankato, MN 56001

(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

23016.03

04/29/2024

04/29/2024

EDI-DOLEJS #23-033

14204

Michael S. Dolejs

Lower

Brule

Pharmacy

UPS

Compliance 601 Gall St.

Lower Brule, SD 57548

AE, LNS

JSH

M3.1

Partial Floor

Plan - Phase 1 -

Piping

NORTHNORTH

0 4' 8'2' 1/4" = 1'-0"M3.1

1 Partial Floor Plan - Phase 1 - Piping Demolition

0 4' 8'2' 1/4" = 1'-0"M3.1

2 Partial Floor Plan - Phase 1 - Piping

S

S

S

H S

H S

TS

GENERAL NOTES

T

DISCONNECT AND REMOVE

EXISTING THERMOSTAT IN

ITS ENTIRETY

RECEIVING HZD

STORAGE

PHARMACY

OFFICE

TO HP-1

CORRIDOR

100C

OFFICE

NARCOTICS

CONSULT

WAITING

CORRIDOR

100ACORRIDOR

100B

NURSE STATION

ROOM 107 WALL MONITOR: DIFFERENTIAL PRESSURE OF ROOM TO

PHARMACY AND OF ROOM TO CORRIDOR, ROOM TEMPERATURE AND ROOM

HUMIDITY. REFER TO SPECIFICATION 230993 FOR SEQUENCE OF OPERATION

AND ROOM PRESSURE MONITOR AND…