RFP Attachment J01b Lower Brule Pharm USP - Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 75H70124R00043
About this file
This document is a Request for Proposals (RFP) for the renovation of the Lower Brule Indian Health Center (IHC) pharmacy in Lower Brule, South Dakota. The purpose of the project is to renovate the pharmacy to meet the compounding requirements of USP 795, 797, and 800. The contract will be a single Firm Fixed Price award, with a period of performance of 180 calendar days. The project is anticipated to be between $500,000 and $1,000,000 in value and is set aside for small businesses under NAICS code 236220 with a $45 million size standard. The solicitation will be posted on SAM.gov, and a site visit is required. Contractors must be registered in SAM to be considered for award. This is a 100% set-aside for small businesses.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER ARCHITECT
DSGW Architects
2 West First St. Suite 201
Duluth, MN 55802
Phone: 218-727-2626
Contact: Ryan Turner, AIA, ACHA, EDAC Email: rturner@dsgw.com
Great Plains Indian Health Services
Office of Environmental Health and Engineering
115 4th Ave. SE, Room 309 Aberdeen, SD 57401
Phone: 605-226-7581
Contact: Kurt Petersen
Email: kurt.petersen@ihs.gov
MECH/ELECT. ENGINEER
EDI-Dolejs Consulting Engineers
1112 North 5th Street
Minneapolis, MN 55411
Phone: 612-343-5965
Contact: Jay Hruby, PE Email: jhruby@edi-dolejs.com
Project Team
EARTH
COMPACT FILL/SAND
POROUS FILL/GRAVEL
FACE BRICK
MORTAR/PLASTER
CMU
CONCRETE
RIGID INSULATION
BATT INSULATION
STUD WALL/METAL
PLYWOOD
GYPSUM BOARD
FINISHED WOOD
CONT. ROUGH WOOD
WOOD BLOCKING
BITUMINOUS
Materials
Symbols
DETAIL
NUMBER
SHEET
NUMBER
AREA TO BE
DETAILED OR
ENLARGED
ACTUAL NORTH
(IF DIFFERENT)
REVISION TYPE
SHEET NUMBER
SECTION NUMBER
A8.1
MATCH LINE
SHEET
NUMBER
ELEVATION
NUMBER
A7.2
NORTH ARROW
DETAIL REFERENCESECTION REFERENCE
REVISION IDENTIFICATIONTITLE MARKER
ROOM IDENTIFICATION
ROOM NAME
ROOM NUMBER
DOOR TAG
BREAKLINE
ELEVATION REFERENCE
WALL TAGWINDOW TAG
ELEVATION LABEL MATCHLINE IDENTIFICATION NOTE IDENTIFICATION
(LEADER
OPTIONAL)
A7.1
A5.1
TOILET
ROOM
T.O. STL.
100'-0"
VIEW TITLE
VIEW SCALE
W205
1A S
I
5A
SEQUENTIAL
INDICATOR
APPROXIMATE
THICKNESS IN INCHES
N
(WHEN REQ'D)
REPRESENTS NEW
DOOR
REPRESENTS
EXISTING DOOR
TO REMAIN
REPRESENTS
EXISTING DOOR
TO BE REMOVED.
WALLS WITH
HATCH
INDICATE NEW
CONSTRUCTION
WALLS SHADED
GRAY INDICATE
EXISTING TO
REMAIN
DASHED LINES
INDICATE WALLS
& ITEMS TO BE
REMOVED.
PLAN NORTH
REVISION NUMBER
5A 48"
PARTIAL
WALL; HT
IN INCHES
PHASE 1 PHARMACY
PHASE 2 PHARMACY MAIN
ENTRY
Phase 1
• DEMO EXISTING OFFICE
• BUILD OUT TEMPORARY PHARMACY
• MOVE SHELVING AND EQUIPMENT FROM EXISTING PHARMACY TO TEMPORARY
PHARMACY.
Phasing Notes
Phase 2
• DEMO EXISTING PHARMACY AND MEDICAL RECORDS SPACES
• BUILD OUT NEW PHARMACY
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
023016.03
BC
RT
04/29/24
Lower Brule Pharmacy
USP
Compliance
G0.1
Title Sheet
601 Gall Street Lower Brule, SD 57548
Sheet Index 0-General Sheets
G0.1 Title Sheet
4-Architectural
A1.2 Demo Plan
A2.1 Floor Plans and Interior Elevations
A3.1 Reflected Ceiling Plan
A4.1 Schedules and Types
5-Mechanical
M0.1 Mechanical Title Sheet
M1.1 Partial Floor Plan - Phase 1 & 2 - Fire Protection
M2.0 Partial Underfloor Plan - Phase 1 - Plumbing
M2.1 Partial Underfloor Plan - Phase 2 - Plumbing
M2.2 Partial Floor Plan - Phase 1 - Plumbing
M2.3 Partial Floor Plan - Phase 2 - Plumbing
M3.1 Partial Floor Plan - Phase 1 - Piping
M3.2 Partial Floor Plan - Phase 2 - Piping
M4.1 Partial Floor Plan - Phase 1 - HVAC
M4.2 Partial Basement Floor Plan - Phase 2 - HVAC
M4.3 Partial Floor Plan - Phase 2 - HVAC
M5.1 Mechanical Schedules
M6.1 Mechanical Details
6-Electrical
E0.1 Electrical Title Sheet
E1.0 Basement - Electrical Demolition
E1.1 Partial Floor Plans - Demolition
E2.1 Partial Floor Plans - Lighting
E3.0 Basement - Power
E3.1 Partial Floor Plans - Power
E4.1 Partial Floor Plans - Systems
E6.1 Schedules - Electrical
E6.2 Scedules - Electrical
E7.1 Details - Electrical
Key Plan
Abbreviations
Project Number:
Lower Brule Pharmacy USP Compliance 601 Gall Street
Lower Brule, SD 57548
023016.03
Architectural General Notes
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECT
B.O. BOTTOM OF
B.SPLASH BACKSPLASH
BLDG BUILDING
BLKG BLOCKING
BRG BEARING
C-TOP COUNTERTOP
CG CORNER GUARD
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINOUS
CPT CARPET
CT CERAMIC TILE
D DEEP
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DS DOWNSPOUT
DW DISHWASHER
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EPDM ETHYLENE PROPYLENE DIENE TERPOLYMER
ROOFING
EQ EQUAL
EQUIP / EQPT. EQUIPMENT
EXST / EX. / EXIST. EXISTING
F.T. FIRE TREATED
F.V. FIELD VERIFY
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFGB FIBERGLASS FACED GYPSUM BOARD
FLR FLOOR
FRP FIBERGLASS REINFORCED PANEL
FTG FOOTING
FUR FURRING
GALV GALVANIZED
GB GRAB BAR
GLAZ GLAZING
GYP. BD. / G.BD / GBD GYPSUM BOARD
HC HANDICAPPED
HM HOLLOW METAL
HT HEIGHT
ICF INSULATED (OR INSULATING) CONCRETE FORM
INSUL INSULATION
JST JOIST
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.
7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.
8. Immediately notify Architect of any long lead items that will affect the completion date
9. All wood in contact with concrete or concrete block to be pressure treated - typical.
10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code. Fireproof any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherwise noted
13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls
LAM LAMINATE
LVT LUXURY VINYL TILE
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OPCI OWNER PROVIDED CONTRACTOR INSTALLED
P.T. PRESSURE TREATED
PC PRECAST
PLAM / P.LAM. PLASTIC LAMINATE
PLYWD PLYWOOD
PNT PAINT
PTD PAPER TOWEL DISPENSER
QT QUARRY TILE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RPF STRIP REINFORCED PERIMETER FASTENING STRIP
RTU ROOF TOP UNIT (MECH.)
RWL RAIN WATER LEADER
S.SPLASH SIDESPLASH
SACT SUSPENDED ACOUSTICAL CEILING TILE
SCHED SCHEDULE
SD SOAP DISPENSER
SEAL SEALANT
SF SQUARE FOOT (FEET)
SIM SIMILAR
SIP STRUCTURAL INSULATED (OR INSULATING)
PANEL
SND SANITARY NAPKIN DISPOSAL
SPEC SPECIFICATION
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
STL STEEL
STRUCT STRUCTURAL CONSULTANT
T.O. TOP OF
TBB TILE BACKER BOARD
TP TOILET PAPER
TRTD TREATED
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WD WOOD
WRB WEATHER RESISTIVE BARRIER
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
RYAN
TURNER
U.C.
Refr.
A1
A1
C1
OFFICE
C1
D1
D5
D1 D1
D2 C1 D3
D4
Z7
C1
Z2
G1
A1
A1
A1
A1
A1
A1
A1
DISPENSING
F1 Z8
Z9
Z9
Z9
Z10
Z2
Z2
MEDICAL RECORDS
NARCOTICS
F2
PHARMACY
F2 F1
Z3
C2
Z4
DISPENSING
PHARMACY
NARCOTICS
MEDICAL RECORDS
CORRIDOR
CORRIDOR
WAITING
Z11
Z11
Z13
Z12
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
023016.03
BC
RT
04/29/24
Lower Brule Pharmacy
USP
Compliance
A1.2
Demo Plan
601 Gall Street Lower Brule, SD 57548
1/4" = 1'-0"
DEMO PLAN - PHASE 1
Demo Plan Notes
A1 FURNITURE AND EQUIPMENT TO BE REMOVED BY OWNER
C1 DEMO & REMOVE EXISTING CASEWORK INCLUDING ANY UPPER OR LOWER CABINETS AND SHELVES, COUNTER, PLUMBING FIXTURES AND WALL MOUNTED ACCESSORIES
C2 REMOVE TALL OPEN STORAGE CABINET, RELOCATE TO PHASE 1 TEMP PHARMACY
D1 DEMO INTERIOR DOOR, FRAME & HARDWARE
D2 DEMO SECURITY MESH GATE, FRAME AND HARDWARE
D3 DEMO COILING SHUTTER
D4 DEMO PASSTHRU DOOR
D5 DEMO INTERIOR DOOR, FRAME & HARDWARE, SALVAGE FOR RELOCATION IN PHASE 2
F1 DEMO SHEET VINYL FLOOR, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE
F2 DEMO CORK FLOOR, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE
G1 DEMO EXTERIOR WINDOW, PREPARE FOR WALL INFILL TO MATCH EXISTING
Z2 REMOVE & SALVAGE EXISTING WALL MOUNTED ITEMS AND EQUIPMENT SUCH AS WHITEBOARDS FOR RELOCATION
Z3 REMOVE & SALVAGE EXISTING METAL SHELVING UNIT, RELOCATE TO PHASE 1 TEMP PHARMACY
Z4 CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR RELOCATION AND CALIBRATING EQUIPMENT TO PHASE 1
TEMP PHARMACY
Z7 REMOVE MOBILE HD SHELVING UNIT
Z8 REMOVE TV AND MOUNTING BRACKET, SALVAGE FOR RELOCATION IN PHASE 2
Z9 DEMO HAND RAIL
Z10 REMOVE AED CABINET, SALVAGE FOR RELOCATION
Z11 REMOVE AND RELOCATE UNDER COUNTER REFRIGERATOR TO PHASE 1 TEMP PHARMACY
Z12 REMOVE AND RELOCATE FILLMASTER DISP. AND FILTRATION SYSTEM TO PHASE 1 TEMP PHARMACY
Z13 REMOVE AND SALVAGE FOR RELOCATION EXISTING AIPHONE MASTER STATION AND DOOR STATION
Demo General Notes
1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.
2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.
3. Demolition notes without leaders indicate that the note applies to the entire room.
4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.
5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.
6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).
7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.
8. Prep floors as needed for new finishes.
9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.
10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.
11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.
12. Verify any items to be retained for owners use prior to removal.
13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.
1/4" = 1'-0"
DEMO PLAN - PHASE 2
1/4" = 1'-0"
DEMO PLAN - PHASE 1B
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
U .C
R e fr
U
.C
R e fr
A2.112
A2.1 11
WAITING
CONSULT
101NARCOTICS
PHARMACY
RECEIVING HZD
STORAGE
OFFICE
OFFICE
7'-9 7/8" 9'-8"
11'-6"
/8
A2.1 8
A2.19
TA
-W
107B
107A
B 101A
1B
7B
5C7B
7A
7B
7A
5B
5C
5C
8'-6"
CORRIDOR
100B
CORRIDOR
100C
CORRIDOR
100A
CORRIDOR
100D
TA-W1
100B
1'-10"
/8
1'-7"
/8
5C
7B
A2.1
A2.1
A2.14 3
A2.1
1A
3A
3A
7B
13 14
A2.1
8'-6"
5C 48"
INFILL WINODW OPENING, MATCH EXISTING WALL CONSTRUCTION.
USE FULL SHEET OF T1-11 SIDING FOR WINDOW INFILL.
/8
3'-0"
6'-2"
A2.1
RELOCATED
U/C REFR.
2'-0" 2'-0" 2'-0" 10"
STEEL PACKAGE
RECIEVER
TA-W1
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
WALL MOUNTED
PHONE
3'-0" 3'-3" 2'-6" 9"
FILLER PANEL
WALL PORT W/
2" ID
GROMMET IN
COUNTERTOP
EXIST DF TO
REMAIN
RELOCATED TV AND
MOUNTING BRACKET,
PROVIDE BLOCKING
TA-W1
12" C-TOP SEE
SECTION 12 00 50
RELOCATED
LITERATURE RACK
FUTURE WALL
MOUNTED
MONITOR,
PROVIDE
BLOCKNING
STEEL PACKAGE
RECEIVER
CENTER UNDER WINDOW
4'-0" 5'-4"
1'-0" 3'-0" 5'-9"
2"
WALL PORT
W/ 2" ID
GROMMET IN
COUNTERTOP
Wall Types
5A
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE
5B
OMIT BATT INSULATION, GYP BD
TO EXTEND 6" ABOVE CEILING
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
5C
3 5/8" 16 GAUGE METAL
STUD @ 16" O.C.
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/ SECURITY
BARRIER MESH
3 5/8" 16 GUAGE METAL
STUD CHANNEL
3 5/8" 16 GAUGE METAL
STUD DEFLECTION TRACK
BASE - SEE SCHEDULE
ROOF OR FLOOR
STRUCTURE
5/8" GYP.BD.
1A
SECURITY BARRIER
MESH
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
EXISTING WALL
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE RCP
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
ACOUSTIC SEALANT
EA. SIDE
NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED
7/8" 4 7/8" 5 1/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER MESH
1B
BULLET RESISTANT
PANEL
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
EXISTING WALL
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE RCP
1 1/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
7A
6" METAL STUD @
16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE
6" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
ACOUSTIC SEALANT
EA. SIDE
7 1/4"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
7B
6" 16 GAUGE METAL
STUD @ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/ SECURITY
BARRIER MESH
6" 16 GAUGE METAL
STUD CHANNEL
3 5/8" 16 GAUGE METAL
STUD DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
ACOUSTIC SEALANT
EA. SIDE
7 1/2"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER MESH
3A
2 1/2" METAL
STUD @ 16" O.C.
5/8" GYP.BD.
METAL STUD WALL TO
STRUCTURE
2 1/2" METAL STUD
CHANNEL
2 1/2" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
COUNTERTOP,
SEE SECTION
12 00 50
RELOCATED
UNDERCTR
REFR.
2'-6"
RELOCATED
SHELVING UNITS
"4
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
WALL CABINET,
SEE SECTION
12 00 50
NARCOTICS SAFE
(NIC)
SIT-STAND
DESK (NIC)
RELOCATED
FILLMASTER
SD (OPCI)
PTH (OPCI)
FILLMASTER
FILTRATION
SYSTEM MOUNTED
IN CABINET,
RELOCATE FROM
EXIST PHARMACY
V E
R
IF
Y W
S
TA
FF
3'-9" 5'-0" 1" 2'-6" 3'-0" 1" 1'-0"
1" 3'-0" 5'-8"1"2'-0"2'-0"2'-2"2'-0"1'-6"
1"3'-0"3'-0"
3'-0"
TA-W1
FILLMASTER
RELOCATE FROM
TEMP PHARMACY
SD (OPCI)
PTH (OPCI)
FILLMASTER
FILTRATION SYSTEM
MOUNTED IN CABINET,
RELOCATE FROM TEMP
PHARMACY
BASE CABINET
AND COUNTERTOP,
SEE SECTION
12 00 50
BASE CABINETS
AND CNTRTOP,
SEE SECTION
12 00 50
WALL CABINETS,
SEE SECTION
12 00 50
W
S
TA
FF
V E
R
IF
Y
NEW REFR. (NIC)
PULL OUT
PRINTER SHELF
SUPPORT PANEL
TALL STORAGE
CABINET, SEE
SECTION 12 00 50
3'-0" 3'-0"
6'-0" 1'-6"
6"
WALL CABINET,
SEE SECTION
12 00 50
3'-6"
COUNTERTOP,
SEE SECTION
12 00 50
EXHAUST
GRILLES, SEE
MECH 3
" SINK W/
EYEWASH
SEE MECH
PTH (OPCI)
SD (OPCI)
O P
E R
A B
LE
P
A R
TS
TO
FRP WAINSCOT
1'-6"
6" 6" 6" 3'-6"
METAL LOCKERS
SEE SECTION
12 00 50
(4) ROBE HOOKS
2'-6" 2'-6" 2'-11"
(2) 2'-0" LONG
WILLCALL RODS
WALL MOUNTED
MONITOR MOUNTING
BRACKET, PROVIDE
BLOCKING
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
2'-6" 2'-6"
WALL CABINETS
SEE SECTION
12 00 50
2'-6"
COUNTERTOP,
SEE SECTION
12 00 50
MICROWAVE
(NIC)
RELOCATED
UNDER CTR.
REFR.
1"3'-0"3'-0"1"
BASE CABINETS
AND COUNTERTOP
SEE SECTION 12 00 50
(5) 4'-0" LONG
WILLCALL RODS
ON BRACKETS AND
STANDARDS, SEE
SECTION 10 28 00
2'-3" 4'-0"
2'-0" 6"
(2) 2'-0" L.
WILLCALL RODS
ON BRACKETS
AND STANDARDS
SEE SECTION
10 28 00
WIRE MESH PARTITION
AND DOOR, SEE
SECTION 10 22 13
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
023016.03
BC
RT
04/29/24
Lower Brule Pharmacy
USP
Compliance
A2.1
Floor Plans and Interior Elevations
601 Gall Street Lower Brule, SD 57548
1/4" = 1'-0"
FLOOR PLAN - PHASE 1
Floor Plan Notes
2 RELOCATED FILLMASTER AND FILTRATION SYSTEM FROM PHASE 1B DEMO
4 RELOCATED METAL SHELVING UNITS FROM PHASE 1B DEMO
5 RELOCATED TALL OPEN STORAGE CABIENTS FROM PHASE 1B DEMO
6 RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND
CALIBRATING EQUIPMENT
7 TV AND MOUNTING BRACKET, RELOCATED FROM PHASE 2 DEMO
8 LITERATURE RACK, RELOCATED FROM PHASE 2 DEMO
9 RELOCATED U/C REFRIGERATORS FROM PHASE 1A DEMO, 2nd REFR. SET ON TOP OF COUNTER
TOP
10 PROVIDE BLOCKING FOR FUTURE WALL MOUNTED MONITOR
11 (2) 2'-0" LONG WILL CALL RACKS, SEE SECTION 10 28 00
12 EXISTING RELOCATED AED, CABINET AND SIGN
13 AIPHONE DOOR STATION, SEE ELEC
14 AIPHONE MASTER STATION, SEE ELEC
15 WIRE MESH PARTITION AND DOOR, SEE SECTION 10 22 13
16 (5) 4'-0" LONG WILL CALL RACKS, SEE SECTION 10 28 00
17 STEEL PACKAGE RECIEVER
18 CONSULT DESK, SEE SECTION 12 00 50
19 (2) ROBE HOOKS MOUNTED 5'-0" AFF
20 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50
21 NARCOTICS SAFE RELOCATED FROM TEMP PHARMACY
22 NEW 30"X48" SIT-STAND DESK (NIC)
23 EXISTING RELOCATED MEDSAFE MEDICATION DISPOSAL BOX
24 NEW NARCOTICS SAFE (NIC)
25 NEW REFRIGERATOR (NIC)
26 EXISTING 30"X48" SIT-STAND DESK RELOCATED FROM TEMP PHARMACY
Floor Plan General Notes A Interior dimensions are to finished face of stud wall, face of masonry walls, to centerline of columns or to other grid points unless otherwise noted. Dimensions labeled as CLEAR or CLR indicate minimum distance to finished face of walls. Dimensions are to finished face of existing walls if applicable.
B All interior door frames to be 4" from adjacent wall or centered between walls unless otherwise noted.
C Furniture & equipment shown is for reference only and is not included in the contract.
D Coordinate size and location of all duct and shaft openings in walls and floors with MEP consultant.
E Fire ratings are indicated on the Life Safety Plan.
1/4" = 1'-0"
FLOOR PLAN - PHASE 2
1/4" = 1'-0"
ELEV PHARMACY - EAST
1/4" = 1'-0"
ELEV WAITING - WEST
1/4" = 1'-0"
TEMP PHARMACY - EAST
1/4" = 1'-0"
ELEV TEMP PHARMACY - WEST
1/4" = 1'-0"
ELEV PHARMACY - NORTH
1/4" = 1'-0"
ELEV PHARMACY - SOUTH
1/4" = 1'-0"
RECEIVING/ HZRD STOR. - EAST
1/4" = 1'-0"
RECEIVING/ HZD STOR - WEST
1/4" = 1'-0"
ELEV PHARMACY HALLWAY
1/4" = 1'-0"
ELEV NARCOTICS - WEST
1/4" = 1'-0"
ELEV OFFICE - SOUTH
1/4" = 1'-0"
PHARMACY - NORTH
1/4" = 1'-0"
PHARMACY - SOUTH
1/4" = 1'-0"
ELEV NARCOTICS - NORTH
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
OFFICE
RECEIVING HZD
STORAGE
OFFICE
PHARMACY
NARCOTICS
CONSULT
WAITING
7'-6"
8'-0" 8'-0"
PATCH TO MATCH
ACT CEILING WERE
REMODELING
OCCURS
7'-0"
GYP BD AND
SECURITY BARRIER
MESH CEILING, SEE
DETAIL 2/A3.1
A3.1
A3.1
8'-0"
8'-0"
7'-0"
CORRIDOR
100B
8'-0"
A3.1
STRUCTURE/FRAMING ABOVE
3 5/8" 16 GAUGE METAL
STUD FRAMING
5/8" GYP. BD.
SECURITY BARRIER MESH
METAL CORNER BEAD
V E
R
IF
Y W
R
C P
SACT CEILING
3-5/8" MTL. STUD W/
5/8" GYP. BD.
NOTE: SEE RCP FOR BULKHEAD HEIGHTS
NOTE: SEE RCP FOR SOFFIT HEIGHTS
METAL CORNER BEAD
5/8" GYP. BOARD
3 5/8" MTL. STUDS @ 16"
O.C.
CEILING AS SCHEDULED
NOTE:
PROVIDE SECERITY BARRIER
MESH AT NARCOTICS ROOM 108
NOTE: SEE RCP FOR SOFFIT HEIGHTS
METAL CORNER BEAD
5/8" GYP. BOARD
3 5/8" 16 GAUGE MTL.
STUDS @ 16" O.C.
3 5/8" 16 GAUGE METAL
STUD FRAMING
5/8" GYP. BD.
SECURITY BARRIER
MESH
SECURITY BARRIER
MESH
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
023016.03
BC
RT
04/29/24
Lower Brule Pharmacy
USP
Compliance
A3.1
Reflected Ceiling Plan
601 Gall Street Lower Brule, SD 57548
1/4" = 1'-0"
REFLECTED CEILING PLAN - PHASE 2
RCP General Notes
1. Coordinate final locations of ceiling mounted equipment w/ owner and architect.
2. See M&E drawings for lighting, grills, and diffuser locations.
3. Suspended acoustical ceiling tile grid is to be centered in rectangular room or centered between the longest walls of irregularly shaped rooms unless otherwise noted.
4. Verify gypsum board control joint locations with architect prior to installation.
5. Ceiling heights indicated are from finished floor of current level shown.
1" = 1'-0"
Gyp. Bd. Ceiling Detail
1" = 1'-0"
Bulkhead Detail
1" = 1'-0"
Gyp. Bd. Soffit
1" = 1'-0"
Gyp. Bd. Soffit at Narcotics êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
Door Types
WD-D1
Solid Core
Wood Flush
WD-D2
Solid Core Wood w/Quarter Lite
8" 8"
WD-D3
Solid Core Wood w/Half Lite
8" 8"
1/4" TEMPERED
GLASS
1/4" TEMPERED
GLASS
Frame Types
HM-F1
Hollow Metal
FRAME WIDTH IS 2" UNLESS OTHERWISE DIMENSIONED. FRAME DEPTH TO MATCH WALL THICKNESS
PER INDUSTRY STANDARDS UNLESS OTHERWISE NOTED. SEE DETAILS.
SEE SCHED
S E
E S
C H
E D
U
LE
TA-W1
QUICKSERV
SPEAK AROUND
36X36
3'-0"
INTERCOM
SYSTEM
LEVEL 3 BULLET
RESISTANT
GLAZING
5/8" GYP. BD. EA. SIDE
MTL. STUD @ 16" O.C. FILL
W/ BATT INSUL. SEE WALL
TYPES
CONT. SEALANT
BOTH SIDES
H.M. FRAME
DOOR PANEL; SEE TYPES
MTL. STUD CHANNEL - SEE
STRUCT. FOR LINTEL
CONT. SEALANT BOTH SIDES
H.M. FRAME
DOOR PANEL; SEE TYPES
METAL STUDS @ 16" O.C.
FILL W/BATT INSUL; SEE
WALL TYPES
STL. ANCHORS (3 PER JAMB,
FLOOR CLIP EA. JAMB)
METAL STUDS (2)
5/8" GYP. BD. BOTH SIDES
WAITING
CONSULT
NARCOTICS
PHARMACY
RECEIVING HZD
STORAGE
OFFICE
OFFICE
need location for aed cabinet
CG-1
HR-1
HR-1
HR-1
PAINT TO MATCH EXISTING
P N
T-
PNT-5
P N
T-
CORRIDOR
100D
PNT-5
P N
T-
FRP/
EPOXY PNT
FRP/
EPOXY PNT
FRP/
EPOXY PNT
Finish Abbreviations
ACT ACOUSTICAL CEILING TILE
CT PORCELAIN/CERAMIC TILE
EXIST. EXISTING
GYP. BD. GYPSUM BOARD
LVT LUXURY VINYL TILE
T.B.B. TILE BACKER BOARD
VCT VINYL COMPOSITION TILE
QT QUARRY TILE
EP EPOXY
PNT PAINT
CPT CARPET
VWC VYNL WALLCOVERING
WB WOOD BASE
WS WINDOW SHADE
WD WOOD
FRP FIBER REFORCED PANEL
CG CORNER GUARD
VB VINYL BASE
1. SEE FINISH PLAN FOR CLARIFICATION OF FLOOR AND WALL FINISH LOCATIONS.
2. ALL WALLS TO RECIEVE PNT-1 UNLESS OTHERWISE NOTED
3. ALL CEILING TO RECEIVE PNT-4 UNLESS OTHERWISE NOTED
4. ALL HM FRAMES AND DOORS TO RECEIVE PNT-3 UNLESS OTHERWISE NOTED
5. ALL FLOORS TO RECEIVE RB-1 UNLESS OTHERWISE NOTED IN FINISH SCHEDULE
6. FRP WAINSCOT TO 4'-0" ABOVE BASE. SEAL TOP, BOTTOM AND ALL JOINTS W/
CHEMLINK M-1 CR SEALANT.
Finish Notes
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
023016.03
BC
RT
04/29/24
Lower Brule Pharmacy
USP
Compliance
A4.1
Schedules and Types
601 Gall Street Lower Brule, SD 57548
1 1/2" = 1'-0"
HM Door Head @ Metal Stud Wall 1 1/2" = 1'-0"
HM Door Jamb @ Metal Stud Wall
ROOM FINISH SCHEDULE
NO. NAME
FLOOR WALL FINISH
NOTESFINISH BASE NORTH EAST SOUTH WEST
100 WAITING EXIST MATCH EXIST EXIST EXIST PNT-5 PNT-5
100A CORRIDOR SEE NOTES PNT PNT PATCH TO MATCH EXISTING WERE REMODELING OCCURS
100B CORRIDOR SEE NOTES EXIST PNT PNT EXIST PATCH TO MATCH EXISTING WERE REMODELING OCCURS
100C CORRIDOR SEE NOTES PNT PATCH TO MATCH EXISTING WERE REMODELING OCCURS
100D CORRIDOR PNT-5
101 CONSULT LVT-1 RB PNT PNT PNT PNT-2
105 PHARMACY SV-1 RB PNT PNT PNT-2 PNT
106 OFFICE LVT-1 RB PNT PNT PNT-2 PNT
107 RECEIVING HZD STORAGE SV-2 RB FRP/ EPOXY PNT EPOXY PNT FRP/ EPOXY PNT RFP/ EPOXY PNT
108 NARCOTICS SV-1 RB PNT PNT PNT PNT
114 OFFICE LVT-1 RB PNT PNT PNT-2 PNT
DOOR AND FRAME SCHEDULE
DOOR FRAME
FIRE LABEL
HDW.
NO. NOTESNO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
100B 3'-0" 7'-0" EXISTING
DOOR, FRAME
AND
HARDWARE
RELOCATED
101A 3'-0" 7'-0" WD-D1 HM-F1 -- 03
101B 3'-0" 7'-0" WD-D2 HM-F1 1/A4.1 2/A4.1 -- 02
106 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 -- 01
107A 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 -- 02
107B 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 02
114 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 -- 01
1/4" = 1'-0"
FINISH PLAN - PHASE 2
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
PLUMBING AND PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
TYPE (SEE SCHEDULE)
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE)
ACTIVE SLOT LENGTH /
NUMBER OF SLOTS
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
Ø ROUND
ABV ABOVE
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING UNIT
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CF CABINET FAN
CF CHEMICAL FEEDER
CFP CHEMICAL FEEDER PUMP
CH CHILLER
CRU CONDENSATE RETURN UNIT
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
CWP CONDESATE WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
H HUMIDIFIER
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HPU HEAT PUMP UNIT
HRU HEAT RECOVERY UNIT
PF PROPELLER FAN
PRV POWER ROOF VENTILATOR
PWF POWER WALL FAN
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SA SHOCK ABSORBER
SAT SOUND ATTENUATOR
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
US UTILITY SET
UV UNIT VENTILATOR
WFMS WATER FLOW MEASURING STATION
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
TYPE (SEE SCHEDULE)
BOTTOM OF EQUIPMENT
ELEVATION
HEATING
COIL
FLOW OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY
DRAIN TAGS
"P" - INDICATES
PRIMER CONNECTION
FIXTURE UNITS
ROOF AREA
SERVED BY DRAIN
PIPE ACCESSORY TAGS
DATA DEVICE TAGS
DAMPER TAGS
EQUIPMENT ID
SYMBOL
FIXTURE UNITS
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
TYPE (SEE SCHEDULE)
EXISTING RELOCATED
EQUIPMENT
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
MECHANICAL SHEET INDEX
CD-XXX
CFM
TYPE (SEE SCHEDULE)
CG-XXX
24x24 SIZE (NOTED IF DIFFERENT
THAN 24x12)
CFM
TYPE (SEE SCHEDULE)
CD-XXX
CFMSR-XXX
24x24 SIZE
TYPE (SEE SCHEDULE)
CFMRR-XXX
24x24 SIZE
TYPE (SEE SCHEDULE)
LSD-XXX
48" x (2) 3/4" SLOTS
VAV-XX
RTU-XX
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
LINEAR SLOT
DIFFUSER
ROUND DIFFUSER
WITH ADJUSTABLE
PATTERNS
SUPPLY
REGISTER/GRILLE
CEILING DIFFUSER
RETURN/EXHAUST
REGISTER/GRILLE
CEILING RETURN
GRILLE
4000 SF
6" SD-1
4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN
4" FS-4FLOOR SINK
4" SD-29 DECK DRAIN4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13
HUB DRAIN
FLOW CONTROL
DRAIN
4" SD-12
COMBINATION
DRAINS
STORM DRAIN4" SD-15
WATER CLOSET -
WALL HUNG - ADA WC-1
U-1
1 WFU
LAV-1
1.5 CWFU
1.5 HWFU
LAV-1
WC-1A
VAV-XX
10' - 0"
(E)VAV-XX
VAV-XX
590 lb
RTU-XX
4.0 ton
RTU-XX
115000 Btu/h
115 CFH
RTU-XX
Htg: 3.7 GPM
VAV-XX
VAV BOX
ROOFTOP UNIT
(R)VAV-XX
16/8
16/8
(E)
F
FS
M
B
D
FS
16Ø
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
Room
CHWS
CWV
CA
CD
CDR
CWR
CWS
CW
F-CW
H-CW
S-CW
HW
HW 140°
HW-R
HW-R 140°
GV
GW
HWR
HWS
G
OV
OW
PD
V
SS
SHWR
SHWS
STM
SD
OSD
(E)
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRCULATION
HOT WATER RECIRCULATION 140°
GREASE VENT
GREASE WASTE
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
STEAM
STORM DRAINAGE
OVERFLOW STORM DRAINAGE
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
REF-HG REFRIGERANT-HOT GAS
PG PROPANE GAS
INVERT: -105' - 1"
1/8" / 12" SLOPE
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
2" DOM. WM
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
4" WCO 4" WCO
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
MECHANICAL DRAWINGS
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
Lower Brule Pharmacy UPS Compliance 601 Gall St.
Lower Brule, SD 57548
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M0.1
Mechanical
Title Sheet
M0.1 Mechanical Title Sheet
M1.1 Partial Floor Plan - Phase 1 & 2 - Fire Protection
M2.1 Partial Underfloor Plan - Phase 1 - Plumbing
M2.2 Partial Underfloor Plan - Phase 2 - Plumbing
M2.3 Partial Floor Plan - Phase 1 - Plumbing
M2.4 Partial Floor Plan - Phase 2 - Plumbing
M3.1 Partial Floor Plan - Phase 1 - Piping
M3.2 Partial Floor Plan - Phase 2 - Piping
M4.1 Partial Floor Plan - Phase 1 - HVAC
M4.2 Partial Basement Floor Plan - Phase 2 - HVAC
M4.3 Partial First Floor Plan - Phase 2 - HVAC
M5.1 Mechanical Schedules
M6.1 Mechanical Details êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
PLAN NOTES
GENERAL NOTES
A. THIS DRAWING IS A BID DOCUMENT AND IS NOT A DESIGN DRAWING.
CONFIRMATION OF FINAL DESIGN VIA SHOP DRAWINGS, HYDRAULIC
CALCULATIONS, PRODUCT SUBMITTALS, ETC. IS THE SOLE
RESPONSIBILITY OF THE FIRE PROTECTION DESIGN/BUILD
CONTRACTOR.
B. REFER TO ARCHITECTURAL PLANS FOR COMPLETE
CEILING/FLOOR/ROOM PLAN INFORMATION.
C. ALL AREAS SHALL BE DESIGNED AS LIGHT HAZARD OCCUPANCY
UNLESS INDICATED OTHERWISE OR AS REQUIRED BY AUTHORITIES
HAVING JURISDICTION.
D. PROVIDE PROTECTION ABOVE AND BELOW OBSTRUCTIONS AS
REQUIRED, WHETHER INDICATED OR NOT.
E. ALL SPRINKLERS LOCATED IN FINISHED AREAS SHALL BE
SYMMETRICAL IN PATTERN FOR THE AREA SERVED.
F. HIGH TEMPERATURE SPRINKLERS SHALL BE PROVIDED NEAR ALL
HEAT PRODUCING EQUIPMENT IN ACCORDANCE WITH NFPA 13.
G. DRY TYPE PENDANT AND SIDEWALL SPRINKLER HEADS SHALL
FOLLOW THE MANUFACTURER'S REQUIREMENTS FOR THE MINIMUM
BARREL LENGTH IN THE HEATED AREA.
H. PROVIDE AUXILIARY DRAINS WITH PIPING TO APPROVED LOCATIONS
FOR ALL TRAPPED PIPING. DRAIN PIPING SHALL BE SIZED PER NFPA
13 REQUIREMENTS.
I. ALL WALL AND FLOOR PENETRATIONS WITH FIRE PROTECTION
PIPING SHALL BE FULLY SLEEVED AND SEALED.
J. APPROVED THROUGH PENETRATION FIRE STOP SYSTEMS SHALL BE
USED FOR ALL RATED WALLS AND FLOORS TO MAINTAIN RATING.
K. NO STORAGE IS PERMITTED IN MECHANICAL OR ELECTRICAL ROOMS.
L. EXTENDED COVERAGE SPRINKLERS SHALL NOT BE INSTALLED IN
MECHANICAL ROOMS.
M. DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS
ALLOWED BY NFPA 13 SHALL NOT APPLY TO AREAS WITH CLOUD
CEILINGS.
N. ALL MATERIALS USED IN THE INSTALLATION OF THE FIRE
PROTECTION SYSTEMS SHALL BE NEW AND OF CURRENT ISSUE,
APPROVED BY U.L. AND/OR F.M. AND THE AUTHORITIES HAVING
JURISDICTION.
O. ALL FIRE PROTECTION WET AND DRY TYPE SYSTEM PIPING SHALL BE
STEEL. DRY TYPE SYSTEM PIPING SHALL BE SCHEDULE 40.
P. WHERE NEW SPRINKLER HEADS ARE INSTALLED IN AREAS WITH
CEILINGS THEY SHALL BE CENTERED IN THE CEILING TILES.
Q. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
CONFIRMING FINAL SPRINKLER TYPES. LOCATIONS AND FINISHES IN
ALL AREAS WITH ARCHITECT.
R. TAMPER SWITCHES AND FLOW SWITCHES SHALL BE FURNISHED AND
INSTALLED BY FIRE PROTECTION CONTRACTOR. WIRING OF SUCH
DEVICES IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR.
COORDINATE ALL FIRE PROTECTION WORK WITH FIRE ALARM
CONTRACTOR.
1. DISCONNECT AND REMOVE EXISTING SPRINKLER HEADS, FITTINGS,
ESCUTCHEONS AND RELATED PIPING AS REQUIRED TO
ACCOMMODATE NEW CONSTRUCTION. PROVIDE NEW SPRINKLER
HEADS, FITTINGS, ESCUTCHEONS AND PIPING TO COORDINATE
WITH CEILINGS, WALLS, RELATED MECHANICAL AND ELECTRICAL
SYSTEMS AND CEILING DEVICES. SPRINKLER DESIGN AND
INSTALLATION SHALL COMPLY WITH NFPA 13, OWNER INSURANCE
REQUIREMENTS AND AUTHORITIES HAVING JURISDICTION. NEW
SPRINKLER HEADS SHALL MATCH EXISTING HEADS IN
APPEARANCE AND FUNCTION.
2. MINIMUM OCCUPANCY CLASSIFICATION FOR BIDDING PURPOSES:
ORDINARY HAZARD GROUP 1.
Space
RECEIVING HZD
STORAGE
OFFICE
OFFICE
PHARMACY
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M1.1
Partial Floor
Plan - Phase 1 &
2 - Fire
Protection
NORTH
0 4' 8'2' 1/4" = 1'-0"M1.1
1 Partial Floor Plan - Phase 1 - Fire Protection
0 4' 8'2' 1/4" = 1'-0"M1.1
2 Partial Floor Plan - Phase 2 - Fire Protection
NORTH
êÉîáëáçå=L
2" SS UP TO SK-1
CONNECT TO
NEAREST EXISTING
2" SS OR LARGER.
CONNECT TO
NEAREST EXISTING
1/2" CW OR LARGER
AND 1/2" HW OR
LARGER.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,
PIPING AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDINGS SURFACES.
D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.
TYPICAL.
F. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND
THROUGH FLOOR SHALL BE 2" MINIMUM.
G. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M6.1
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
H. REFER TO PIPE PENETRATION DETAIL ON SHEET M6.1 FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
I. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
M5.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.
TYPICAL.
J. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
M6.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
K. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH
VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION
SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.
1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE
IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL
CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,
DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-
IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M2.1
Partial
Underfloor
Plan - Phase 1 -
Plumbing
NORTHNORTH
1/4" = 1'-0"M2.1
1 Partial Underfloor Plan - Phase 1 - Plumbing 1/4" = 1'-0"M2.1
2 Partial Underfloor Plan - Phase 1 - Plumbing
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED. êÉîáëáçå=L
1/2" CW, 1/2" HW, AND
2" SS LOCATED IN
BASEMENT UP TO SK-1.
1/2" CW, 1/2" HW AND
2" SS LOCATED IN
BASEMENT CEILING
SPACE UP TO SK-3
3/4" CW AND 3/4" HW UP
TO EEW-1 AND ETMV-1
EXTEND ABOVE FLOOR
WASTE AS REQUIRED TO
CONNECT TO EXISTING
WASTE AND CONNECT
NEW 2" WASTE TO
EXISTING. PROVIDE NEW
SANITARY WYE FITTING.
FIELD VERIFY EXACT
LOCATION OF EXISTING
WASTE.
EXTEND HOT AND COLD WATER AS
REQUIRED TO CONNECT TO EXISTING
HOT AND COLD WATER AND CONNECT
NEW 3/4" HOT AND 3/4" COLD WATER TO
EXISTING. PROVIDE NEW TEE FITTINGS.
FIELD VERIFY EXACT LOCATION OF
EXISTING HOT AND COLD WATER.
3/4" HW
3/4" CW
1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE
IDENTIFICATION. PROVIDE ROUGH-IN AND FINAL CONNECTIONS.
REFER TO DIVISION 22 SPECIFICATION FOR MODEL, DESCRIPTION
AND ADDITIONAL INFORMATION. TYPICAL.
2. SHUT OFF VALVE, TYPICAL UNLESS OTHERWISE NOTED.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK, PIPING
AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDINGS SURFACES.
D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS. TYPICAL.
F. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET MX.X
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
G. REFER TO PIPE PENETRATION DETAIL ON SHEET MX.X FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
H. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
MX.X FOR PLUMBING ROUGH-IN SCHEDULE, TYPICAL.
I. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
MX.X FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
J. PROVIDE A MINIMUM OF 2-INCH (R-10) RIGID POLYSTYRENE
INSULATION BOARD ON ALL BELOW GRADE SANITARY SEWER AND
STORM DRAIN PIPING LOCATED OUTSIDE THE BUILDING
FOUNDATION WALL, IF THE PIPING HAS LESS THAN 5'-0" COVER
OVER THE TOP OF THE PIPE. INSULATION SHALL ALSO BE LOCATED
ALONG EACH SIDE OF THE PIPE AT 30 DEGREE ANGLE FROM
VERTICAL.
K. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING ROUGH-
IN SIZES AND ADDITIONAL INFORMATION, TYPICAL.
L. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
M. PROVIDE A WALL CLEANOUT AS REQUIRED TO SERVE EACH
PLUMBING FIXTURE THAT HAS A NON-ACCESSIBLE TRAP, TYPICAL.
DISCONNECT AND REMOVE EXISTING
1/2" CW, 1/2" HW AND 2" SS PIPING UP
TO EXISTING SINK. CAP AT MAINS.
SK-1
1 1/2" V
CO
SK-3
1 1/2" V
2" SS
CO
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M2.2
Partial
Underfloor
Plan - Phase 2 -
Plumbing
NORTH
0 4' 8'2' 1/4" = 1'-0"M2.2
1 Partial Underfloor Plan - Phase 2 - Plumbing
0 4' 8'2' 1/4" = 1'-0"M2.2
2 Partial Underfloor Plan - Phase 2 - Plumbing Demolition
NORTH
NOT TO SCALEM2.2
3 Plumbing Riser - Waste and Vent - 105 Pharmacy
NOT TO SCALEM2.2
4 Plumbing Riser - Waste and Vent - 107 Receiving/HZD Storage
PHARMACY
RECEIVING / HZD
STORAGE
R e fr
U
.C
R e fr
PLAN NOTES
GENERAL NOTES
Space
SK-1
CONNECT NEW 1-1/2" V TO
NEAREST EXISTING 1-1/2" V
OR LARGER.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,
PIPING AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDINGS SURFACES.
D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.
TYPICAL.
F. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE
WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH
CODE REQUIREMENTS. TYPICAL.
G. PROVIDE A FULL SIZE CLEANOUT AT THE BASE OF EACH SOIL,
WASTE, OR STORM DRAIN STACK. CLEAN OUT TO BE LOCATED AT
18'' A.F.F. PROVIDE A CLEANOUT COVER PLATE WHERE STACKS
ARE LOCATED IN WALLS.
H. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND
THROUGH FLOOR SHALL BE 2" MINIMUM.
I. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M8.1
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
J. REFER TO PIPE PENETRATION DETAIL ON SHEET M8.1 FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
K. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
M7.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.
TYPICAL.
L. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
M8.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
M. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH
VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION
SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.
N. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING
ROUGH-IN PIPE SIZES AND ADDTIONAL INFORMATION, TYPICAL.
O. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
P. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
SERVING FAUCETS AND ON QUICK CLOSING DEVICES. REFER TO
SPECIFICATION SECTION 22 1119 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS, TYPICAL.
1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE
IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL
CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,
DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-
IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M2.3
Partial Floor
Plan - Phase 1 -
Plumbing
NORTHNORTH
0 4' 8'2' 1/4" = 1'-0"M2.3
1 Partial Floor Plan - Phase 1 - Plumbing Demolition
0 4' 8'2' 1/4" = 1'-0"M2.3
2 Partial Floor Plan - Phase 1 - Plumbing
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK,
PIPING AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDINGS SURFACES.
D. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
E. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.
TYPICAL.
F. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE
WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH
CODE REQUIREMENTS. TYPICAL.
G. PROVIDE A FULL SIZE CLEANOUT AT THE BASE OF EACH SOIL,
WASTE, OR STORM DRAIN STACK. CLEAN OUT TO BE LOCATED AT
18'' A.F.F. PROVIDE A CLEANOUT COVER PLATE WHERE STACKS
ARE LOCATED IN WALLS.
H. WASTE AND VENT PIPING BELOW GROUND FLOOR SLAB AND
THROUGH FLOOR SHALL BE 2" MINIMUM.
I. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M8.1
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
J. REFER TO PIPE PENETRATION DETAIL ON SHEET M8.1 FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
K. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
M7.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.-IN SCHEDULE.
TYPICAL.
L. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
M8.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
M. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
BRANCH PIPING SERVING SENSORED ACTIVATED FAUCETS, FLUSH
VALVES, AND QUICK CLOSING DEVICES. REFER TO SPECIFICATION
SECTION 22 1119 FOR ADDITIONAL INFORMATION. TYPICAL.
N. REFER TO PLUMBING ROUGH-IN SCHEDULE FOR PLUMBING
ROUGH-IN PIPE SIZES AND ADDTIONAL INFORMATION, TYPICAL.
O. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
P. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
SERVING FAUCETS AND ON QUICK CLOSING DEVICES. REFER TO
SPECIFICATION SECTION 22 1119 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS, TYPICAL.
1. INDICATES PLUMBING FIXTURE OR PLUMBING SPECIALTY DEVICE
IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL
CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,
DESCRIPTION, ACCESSORIES, ETC., REFER TO PLUMBING ROUGH-
IN SCHEDULE FOR ROUGH-IN SIZES. TYPICAL.
DISCONNECT AND REMOVE EXISTING
SINK, AND ALL ASSOCIATED HOT,
COLD, WASTE AND VENT PIPING BACK
TO MAINS AND CAP.
EXISTING ELECTRIC
WATER COOLER TO
REMAIN.
RECEIVING HZD
STORAGE
OFFICE
OFFICE
PHARMACY
3/4" ETMV-1
EEW-1
SK-3
SK-1
1 1/2" V1/2" CW, 1/2" HW,
AND 2" SS DOWN.
3/4" CW AND 3/4" HW
DOWN.
1/2" CW, 1/2" HW, AND
2" SS DOWN.
EXISTING ELECTRIC
WATER COOLER TO
REMAIN.
1 1 1/2" V
NARCOTICS
CONSULT
SK-1
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
EEW-1
3/4" ETMV-1
3/4" HW
3/4" CW
SK-3
3/4" CW
3/4" HW
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M2.4
Partial Floor
Plan - Phase 2 -
Plumbing
NORTHNORTH
0 4' 8'2' 1/4" = 1'-0"M2.4
1 Partial Floor Plan - Phase 2 - Plumbing Demolition
0 4' 8'2' 1/4" = 1'-0"M2.4
2 Partial Floor Plan - Phase 2 - Plumbing
NOT TO SCALEM2.4
3 Plumbing Riser - Domestic Water - 105 Pharmacy
NOT TO SCALEM2.4
4 Plumbing Riser - Domestic Water - 107 Receiving/HZD Storage
PHARMACY
RECEIVING / HZD
STORAGE
R e fr
U
.C
R e fr
EXISTING PIPING CONDITIONS
TO REMAIN IN THIS AREA
Space
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
23016.03
04/29/2024
04/29/2024
EDI-DOLEJS #23-033
14204
Michael S. Dolejs
Lower
Brule
Pharmacy
UPS
Compliance 601 Gall St.
Lower Brule, SD 57548
AE, LNS
JSH
M3.1
Partial Floor
Plan - Phase 1 -
Piping
NORTHNORTH
0 4' 8'2' 1/4" = 1'-0"M3.1
1 Partial Floor Plan - Phase 1 - Piping Demolition
0 4' 8'2' 1/4" = 1'-0"M3.1
2 Partial Floor Plan - Phase 1 - Piping
S
S
S
H S
H S
TS
GENERAL NOTES
T
DISCONNECT AND REMOVE
EXISTING THERMOSTAT IN
ITS ENTIRETY
RECEIVING HZD
STORAGE
PHARMACY
OFFICE
TO HP-1
CORRIDOR
100C
OFFICE
NARCOTICS
CONSULT
WAITING
CORRIDOR
100ACORRIDOR
100B
NURSE STATION
ROOM 107 WALL MONITOR: DIFFERENTIAL PRESSURE OF ROOM TO
PHARMACY AND OF ROOM TO CORRIDOR, ROOM TEMPERATURE AND ROOM
HUMIDITY. REFER TO SPECIFICATION 230993 FOR SEQUENCE OF OPERATION
AND ROOM PRESSURE MONITOR AND…