RFB950400-02 - Drawings.pdf
PDF 4 MB Posted
- Attached to
- WRC Food Service Elevator Replacement
- Solicitation number
- RFB950400-02
- Issued by
- Dallas County, Iowa
About this file
This is a technical drawings document prepared by OPN Architects for the State of Iowa related to RFB950400-02, a food service elevator replacement project at the Woodward Resource Center located at 1251 334th Street, Woodward, Iowa 50276. The project involves the complete replacement of an existing hydraulic elevator system serving two levels (basement and first floor) of the facility. The scope of work includes demolition of existing elevator machinery, hoistway doors, and related equipment; installation of new elevator equipment including the cab, doors, controllers, and hydraulic systems; and associated mechanical, electrical, and fire safety modifications. The existing elevator shaft, rails, and sump pit will be retained and reused. The project drawings indicate coordination requirements among multiple consultants including Story Construction (general contractor), KCL Engineering (mechanical and electrical engineers), and Lerch Bates (elevator consultant and construction manager). The bid set is dated June 16, 2026.
The project must comply with the 2024 International Building Code as adopted by Iowa, the 2024 International Fire Code, the 2026 Iowa State Elevator Code, State Mechanical Code, State Plumbing Code, State Electrical Code, and the 2010 Americans with Disabilities Act. The work is limited in scope with minimal new construction; existing building use and occupancy classifications remain unchanged. The facility must maintain operational access throughout construction, with contractor parking limited to four vehicles and coordination required with facility operations. The building is not fully sprinklered, and the existing elevator machine room and shaft will remain non-sprinklered per project intent. All fire-rated penetrations must be sealed appropriately, and existing interior finishes must be matched or protected in place during construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB950400-02 - Project Manual.pdf | ||
| RFB950400-02 - Bid Form.pdf | ||
| RFB950400-02 - Notice to Bidders.pdf | ||
| RFB950400-02 - Addendum #1.pdf | ||
| 1431402-event.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IBC Chapter 2 - Use and Occupancy Classification
Primary Occupancy:
The use and occupancy classification of the existing building are unchanged.
IBC Chapter 5 - General Building Heights and Areas
Existing building use and size to remain unchanged.
IBC Chapter 6 - Types of Construction The type of construction for the existing building is unchanged.
IBC Chaper 7 - Fire and Smoke Protection Features
New construction is limited and existing construction is not being modified.
For construction purposes, shaft is considered to be 2 HR construction.
IBC Chapter 8 - Interior Finishes
New construction is limited and matches existing interior finishes.
IBC Chapter 10 - Means of Egress
All means of egress are being maintained in the existing building.
IBC Chapter 30 - Elevators and Conveying Systems
Fire resistance rated construction is provided at the elevator machine room.
Smoke protection at hoistway openings is not required per IBC 3006.2.
IBE Chapter 34 Existing Structures:
The updates to the existing building conform to the requirements of the code for new construction and are to be made with the same materials of which the original building is constructed. The existing building is in compliance with the mandatory fire safety requirements, the mandatory means of egress requirements, and the general safety requirements of this chapter.
Iowa Administrative Code, Chapter 16, Division VII - Accessibility Requirements For Facilities Used by the General Public:
Accessibility within the building will be maintained.
Iowa Administrative Code, Chapter 72 - Conveyances Installed on or After January 1, 1975 Elevator pit sump pump currently exists, and will be maintained.
NFPA-13 Chapter 8 - Section 8.15.5
Building is NOT fully sprinklered. The existing machine room and elevator shaft are not sprinklered and intent of project would be to maintain that condition.
APPLICABLE CODE INFORMATION
THE PROJECT SHALL COMPLY WITH THE FOLLOWING CODES
2024 INTERNATIONAL BUILDING CODE AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 481-280 AND 481-301
2010 AMERICANS WITH DISABILITIES ACT AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTER 481-301
STATE MECHANICAL CODE AS ADOPTED BY THE DEPARTMENT OF PUBLIC HEALTH IOWA ADMINISTRATIVE RULE CHAPTER 481-426
STATE PLUMBING CODE AS ADOPTED BY THE DEPARTMENT OF PUBLIC HEALTH IOWA ADMINISTRATIVE RULE CHAPTER 481-425
2024 INTERNATIONAL FIRE CODE AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 481-280
STATE ELECTRICAL CODE AS ADOPTED BY THE STATE ELECTRICAL LICENSING BOARD IOWA ADMINISTRATIVE RULE CHAPTER 481-404
2024 INTERNATIONAL EXISTING BUILDING CODE AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 481-301
2026 IOWA STATE ELEVATOR CODE
100 Court Ave. Suite 100, Des Moines, IA 50309
P: 515-309-0722 F: 515-309-0725 www.opnarchitects.com
ARCHITECT
OPN ARCHITECTS
100 COURT AVENUE
DES MOINES, IA 50309
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
ELEVATOR CONSULTANTMECHANICAL ENGINEER
KCL ENGINEERING
300 4th STREET
WEST DES MOINES, IA 50317
ELECTRICAL ENGINEER
KCL ENGINEERING
300 4th STREET
WEST DES MOINES, IA 50317
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE, SUITE T
EDEN PRAIRIE, MN 55344
STATE OF IOWA - 9504.00 - WRC FOOD SERVICE
ELEVATOR REPLACEMENT
1251 334TH STREET, WOODWARD, IA 50276
A G
B
ID
S
E T
/1
/2
PROJECT LOCATION MAP
SHEET INDEX
AG001
AG002
AD100
AD200
AD201
AG100
COVER SHEET
SITE LOGISTICS PLAN
DEMO FLOOR PLANS
EXISTING CONDITIONS
EXISTING CONDITIONS
OVERALL FLOOR PLANS
ME000 ELECTRICAL GENERAL NOTES & SYMBOLS
ME101 MECHANICAL-ELECTRICAL PLAN
ENLARGED LOCATION MAP
MAIN ENTRY TO WOODWARD
RESOURCE CENTER
FACILITY MAIN ENTRY
PROJECT ELEVATOR
CONTRACTOR PARKING
(LIMITED TO 4 VEHICLES AT THIS LOCATION)
ADDITIONAL CONTRACTOR PARKING
A101 ENLARGED FLOOR PLANS
ME401 ELECTRICAL ONE-LINE DIAGRAM & SCHEDULES
ARCHITECTURAL
OPN Architects, Inc.
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly Licensed Architect under the laws of the State of Iowa.
Joe Feldmann, AIA
Signature
Registration expires June 30, 2026 Iowa Reg No. 5219
Pages or sheets covered by this seal: all Architectural Sheets listed in 00 0115 List of Drawing Sheets.
Divisions: all Architectural Sections listed in the specifications document
ELECTRICAL
KCL Engineering responsible charge. I am a duly Licensed Engineer under the laws of the
Erick Heynen, P.E.
Registration expires December 31, 2027 Iowa Reg No. P24706
Pages or sheets covered by this seal: all Electrical Sheets listed in 00 0115 List of Drawing Sheets.
Divisions: all Electrical Sections listed in the specifications document.
MECHANICAL / PLUMBING
KCL Engineering responsible charge. I am a duly Licensed Engineer under the laws of the
Chad D. Bass, P.E.
Registration expires December 31, 2027 Iowa Reg No. 21397
Pages or sheets covered by this seal: all Mechanical & Plumbing
Sheets listed in 00 0115 List of Drawing Sheets.
Divisions: all Mechanical & Plumbing Sections listed in the specifications document.
Chad D. Bass, P.E.
A
19181716151413121110987654
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:3
:2
A M
AG002
SITE LOGISTICS PLAN
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
FACILITY MAIN ENTRY
PROJECT ELEVATOR
CONTRACTOR PARKING (LIMITED TO 4 VEHICLES)
S1
LOADING DOCK / PROJECT ENTRY
DUMPSTER STAGING
S1
Revision Description Date
COORDINATE CONNEX STAGING IN THIS
AREA WITH CONSTRUCTION MANAGER
THE LOADING DOCK CAN BE USED FOR
PROJECT DELIVERY USE AS NEEDED DURING
CONSTRUCTION. USE MUST BE COORDINATED
WITH THE FACILITY AND ACCESS FOR FACILITY
PROVIDED AT ALL TIMES.
FACILITY MAIN ENTRY.
COORDINATE EXHAUST AT EXISTING WINDOW,
THIS SIDE.
MAINTAIN ACCESS AND DRIVE FOR USE BY
FACILITY AT ALL TIMES. COORDINATE ANY
DELIVERIES THROUGH CONSTRUCTION
MANAGER.
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
GENERAL NOTES
1. DIMENSIONS ARE MEASURED FACE-
OF-FINISH TO FACE-OF-FINISH OR
ROUGH MASONRY OPENING UNLESS
NOTED OTHERWISE - TYPICAL FOR ALL
DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS AND
EXISTING CONDITIONS - TYPICAL FOR
ALL DRAWINGS.
3. IN THE EVENT OF A DISCREPANCY
BETWEEN ARCHITECTURAL AND
CONSULTANT DRAWINGS, NOTIFY
ARCHITECT IMMEDIATELY PRIOR TO
COMMENCING WORK - TYPICAL FOR
ALL DRAWINGS.
4. ALL PENETRATIONS IN FIRE RATED
FLOORS AND WALLS MUST BE SEALED
WITH APPROPRIATE FIRESTOPPING
SYSTEM.
5. PATCH AND REPAIR EXISTING FLOOR
SLABS AND WALL SURFACES
DAMAGED FROM DEMOLITION.
A101
F13
AD100
F13
A101
F1
AD100
F1
A
19181716151413121110987654
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:4
:4
A M
AG100
OVERALL FLOOR PLANS
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
N
1/8" = 1'-0" A1
OVERALL FLOOR PLAN - BASEMENT
N
1/8" = 1'-0" K1
FIRST FLOOR PLAN - OVERALL
Revision Description Date
SEE ELEVATOR SPECIFICATIONS FOR
DEMO ITEMS AND FOR EXISTING
ELEVATOR ITEMS TO REMAIN.
DEMO EXISTING DOORS AND OPENERS -
SEE ELEVATOR SPEC.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
EXISTING FIXTURES TO BE REMOVED
AND REPLACED. NEW FIXTURES TO
COVER EXISTING OPENINGS
COMPLETELY.
(ABOVE)
22, 23
(ABOVE)
11,12
SEE ELEVATOR SPEC FOR DEMO
ITEMS AND FOR EXISTING
ELEVATOR ITEMS TO REMAIN.
DEMO DISCONNECT - SEE ELECTRICAL
PATCH ALL HOLES FROM REMOVED
EQUIPMENT AND PREP ROOM FOR
NEW PAINT ON ALL SURFACES.
EXISTING SHEET METAL ENCLOSURE
TO REMOVED AND REPLACED.
REMOVE TO PROVIDE ACCESS TO
MODIFICATIONS CALLED OUT
ELSEWHERE IN THESE PLANS AND
REPLACE TO MATCH EXISTING
CONFIGURATION TO MAINTAIN
PROPER SEPARATION FROM
ELEVATOR MACHINE ROOM.
EXIST ELEV. CAB DIMS:
W: 3'-4 1/2" (CLEAR)
D: 5'-1" (CLEAR)
CLG: 7'-0"
3'-4"W x 7'-1" BI-PARTING
VERTICAL DOOR.
SEE ELEVATOR SPECIFICATIONS FOR
DEMO ITEMS AND FOR EXISTING
ELEVATOR ITEMS TO REMAIN.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
EXISTING FIXTURES TO BE REMOVED
AND REPLACED. NEW FIXTURES TO
COVER EXISTING OPENINGS
COMPLETELY.
DEMO EXISTING DOORS AND OPENERS -
SEE ELEVATOR SPEC.
DEMO EXISTING DOORS AND OPENERS -
SEE ELEVATOR SPEC.
1 3
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
EXISTING FIXTURES TO BE REMOVED
AND REPLACED. NEW FIXTURES TO
COVER EXISTING OPENINGS
COMPLETELY.
GENERAL NOTES
1. DIMENSIONS ARE MEASURED FACE-
OF-FINISH TO FACE-OF-FINISH OR
ROUGH MASONRY OPENING UNLESS
NOTED OTHERWISE - TYPICAL FOR ALL
DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS AND
EXISTING CONDITIONS - TYPICAL FOR
ALL DRAWINGS.
3. IN THE EVENT OF A DISCREPANCY
BETWEEN ARCHITECTURAL AND
CONSULTANT DRAWINGS, NOTIFY
ARCHITECT IMMEDIATELY PRIOR TO
COMMENCING WORK - TYPICAL FOR
ALL DRAWINGS.
4. ALL PENETRATIONS IN FIRE RATED
FLOORS AND WALLS MUST BE SEALED
WITH APPROPRIATE FIRESTOPPING
SYSTEM.
5. PATCH AND REPAIR EXISTING FLOOR
SLABS AND WALL SURFACES
DAMAGED FROM DEMOLITION.
A
19181716151413121110987654
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:4
:4
A M
AD100
DEMO FLOOR PLANS
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
N
1/2" = 1'-0" F13
DEMO FLOOR PLAN - BASEMENTN
1/2" = 1'-0" F1
DEMO FLOOR PLAN - FIRST FLOOR
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:3
:2
A M
AD200
EXISTING CONDITIONS
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
IMAGE 3
IMAGE 2
IMAGE 1
IMAGE 4
IMAGE 5
IMAGE 6
IMAGE 7
IMAGE 8
IMAGE 9
IMAGE 10
IMAGE 11
IMAGE 12
EXISTING CEILING STRUCTURE TO
REMAIN - REMOVE ACCESS PANEL AND
DRYWALL COMPLETE. PROVIDE
ADDITIONAL FRAMING AS REQUIRED AT
REMOVED ACCESS PANEL AND PROVIDE
NEW DRYWALL AT ENTIRE CEILING. TAPE /
MUD JOINTS ONLY.
REMOVE AND REPLACE EXISTING
DISCONNECT COMPLETE - SEE
ELECTRICAL.
EXISTING DOOR AND FRAME TO REMAIN.
PROTECT IN PLACE DURING
CONSTRUCTION.
REMOVE AND REPLACE EXISTING ELEVATOR
MACHINERY COMPLETE - SEE ELEVATOR
SPEC FOR SPECIFIC REQUIREMENTS.
EXISTING SHEET METAL ENCLOSURE TO
REMOVED AND REPLACED. REMOVE TO
PROVIDE ACCESS TO MODIFICATIONS
CALLED OUT ELSEWHERE IN THESE
PLANS AND REPLACE TO MATCH
EXISTING CONFIGURATION TO MAINTAIN
PROPER SEPARATION FROM ELEVATOR
MACHINE ROOM.
REMOVE FIRE EXTINGUISHER DURING
CONSTRUCTION AND RE-INSTALL AT END OF
PROJECT. RELOCATE AS REQUIRED TO
COORDINATE WITH NEW ELEVATOR
EQUIPMENT.
REMOVE UNUSED EQUIPMENT AND NON-
ELEVATOR RELATED EQUIPMENT - SEE
ELECTRICAL.
EXISTING WALLS TO BE
CLEANED OF DEBRIS, PATCH
ANY HOLES CREATED BY THIS
PROJECT, REMAINDER TO
REMAIN AS IS - NO PAINT.
Revision Description Date
REPLACE ALL CAULKING AT CEILING
AFTER ALL NEW WORK HAS BEEN
COMPLETED.
EXISTING CEILING STRUCTURE TO
REMAIN - REMOVE ACCESS PANEL AND
DRYWALL COMPLETE. PROVIDE
ADDITIONAL FRAMING AS REQUIRED AT
REMOVED ACCESS PANEL AND PROVIDE
NEW DRYWALL AT ENTIRE CEILING. TAPE /
MUD JOINTS ONLY.
EXISTING DOOR AND FRAME TO REMAIN.
PROTECT IN PLACE DURING CONSTRUCTION.
EXISTING ROOM AND SHAFT ARE NOT FIRE
RATED PER REVIEW OF EXISTING
CONDITIONS. AREA ONLY CONNECTS 2
LEVELS AND NO FIRE RATING PRESENT.
REMOVE AND REPLACE EXISTING ELEVATOR
MACHINERY - SEE ELEVATOR SPEC FOR
SPECIFIC REQUIREMENTS.
EXISTING SHEET METAL ENCLOSURE TO
REMOVED AND REPLACED. REMOVE TO
PROVIDE ACCESS TO MODIFICATIONS
CALLED OUT ELSEWHERE IN THESE
PLANS AND REPLACE TO MATCH
EXISTING CONFIGURATION TO MAINTAIN
PROPER SEPARATION FROM ELEVATOR
MACHINE ROOM.
REPLACE ALL CAULKING AT CEILING
AFTER ALL NEW WORK HAS BEEN
COMPLETED.
CLEAN FLOOR AND REPAINT - SEE
ELEVATOR SPECIFICATIONS.
EXISTING DOOR AND FRAME TO REMAIN.
PROTECT IN PLACE DURING
CONSTRUCTION.
REMOVE AND REPLACE EXISTING ELEVATOR
MACHINERY - SEE ELEVATOR SPEC FOR
SPECIFIC REQUIREMENTS.
CLEAN FLOOR AND REPAINT - SEE
ELEVATOR SPECIFICATIONS.
REMOVE AND REPLACE LIGHTING - SEE
ELECTRICAL. PATCH ALL HOLES AS
REQUIRED
EXISTING SHEET METAL ENCLOSURE TO
REMOVED AND REPLACED. REMOVE TO
PROVIDE ACCESS TO MODIFICATIONS
CALLED OUT ELSEWHERE IN THESE
PLANS AND REPLACE TO MATCH
EXISTING CONFIGURATION TO MAINTAIN
PROPER SEPARATION FROM ELEVATOR
MACHINE ROOM.
EXISTING WALLS TO BE
CLEANED OF DEBRIS, PATCH
ANY HOLES CREATED BY THIS
PROJECT, REMAINDER TO
REMAIN AS IS - NO PAINT.
CLEAN FLOOR AND REPAINT - SEE
ELEVATOR SPECIFICATIONS.
EXISTING SHEET METAL ENCLOSURE TO
REMOVED AND REPLACED. REMOVE TO
PROVIDE ACCESS TO MODIFICATIONS
CALLED OUT ELSEWHERE IN THESE
PLANS AND REPLACE TO MATCH
EXISTING CONFIGURATION TO MAINTAIN
PROPER SEPARATION FROM ELEVATOR
MACHINE ROOM.
EXISTING WALLS TO BE
CLEANED OF DEBRIS, PATCH
ANY HOLES CREATED BY THIS
PROJECT, REMAINDER TO
REMAIN AS IS - NO PAINT.
EXISTING SHAFT AND RAILS TO REMAIN -
SEE ELEVATOR SPEC FOR ELEVATOR
REQUIREMENTS.
DETECTION REQUIRED AT TOP OF SHAFT -
SEE ELECTRICAL.
NEW SHAFT LIGHTING REQUIRED - SEE
ELECTRICAL.
CLEAN ALL SURFACES WITHIN SHAFT -
SEE ELEVATOR SPEC.
EXISTING SHAFT AND RAILS TO REMAIN -
SEE ELEVATOR SPEC FOR ELEVATOR
REQUIREMENTS.
REMOVE AND PROVIDE NEW ELEVATOR
DOORS - SEE ELEVATOR SPEC.
REMOVE AND REPLACE EXISTING ELEVATOR
MACHINERY - SEE ELEVATOR SPEC FOR
SPECIFIC REQUIREMENTS.
EXISTING SUMP AND DISCHARGE TO REMAIN.
PROVIDE NEW SUMP PUMP ON DEDICATED
CIRCUIT WITH WATER AND OIL DETECTION -
SEE MECHANICAL / ELECTRICAL.
EXISTING SHAFT AND RAILS TO REMAIN -
SEE ELEVATOR SPEC FOR ELEVATOR
REQUIREMENTS.
NEW PIT AND SHAFT LIGHTING REQUIRED -
SEE ELECTRICAL.
EXISTING JACK TO REMAIN - SEE ELEVATOR
SPEC FOR REQUIREMENTS.
PIT FLOOR TO BE CLEANED AND PREPPED
FOR NEW PAINT FINISH - SEE ELEVATOR
SPEC.
EXISTING PIT LADDER CAN REMAIN -
ELEVATOR PROVIDER TO CONFIRM
COMPLIANCE WITH ALL ELEVATOR CODES.
SEE ELEVATOR SPEC FOR SPECIFIC
REQUIREMENTS ON PLATFORM AND CAB
REQUIREMENTS.
EXISTING SHAFT AND RAILS TO REMAIN -
SEE ELEVATOR SPEC FOR ELEVATOR
REQUIREMENTS.
NEW SHAFT LIGHTING REQUIRED - SEE
ELECTRICAL.
EXISTING JACK TO REMAIN - SEE ELEVATOR
SPEC FOR REQUIREMENTS.
REMOVE AND PROVIDE NEW ELEVATOR
DOORS - SEE ELEVATOR SPEC.
EXISTING SILL TO REMAIN, CLEAN AND
POLISH - SEE ELEVATOR SPEC.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
REMOVE AND REPLACE EXISTING ELEVATOR
FINISHES - SEE ELEVATOR SPEC AND
DRAWINGS FOR SPECIFIC REQUIREMENTS.
REMOVE AND PROVIDE NEW ELEVATOR
DOORS - SEE ELEVATOR SPEC.
REMOVE AND REPLACE EXISTING ELEVATOR
FINISHES - SEE ELEVATOR SPEC AND
DRAWINGS FOR SPECIFIC REQUIREMENTS.
EXISTING CEILING CAN REMAIN - REPAINT.
PROVIDE NEW RECESS LIGHTING - SEE
ELEVATOR SPEC.
REMOVE AND PROVIDE NEW ELEVATOR
DOORS - SEE ELEVATOR SPEC.
REMOVE AND REPLACE EXISTING ELEVATOR
FINISHES - SEE ELEVATOR SPEC AND
DRAWINGS FOR SPECIFIC REQUIREMENTS.
EXISTING CEILING CAN REMAIN - REPAINT.
PROVIDE NEW RECESS LIGHTING - SEE
ELEVATOR SPEC.
PROVIDE ALL NEW CONTROLS AND CODE
COMPLIANT SIGNAGE. SEE ELEVATOR SPEC
AND DRAWINGS FOR SPECIFIC
REQUIREMENTS.
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:3
:2
A M
AD201
EXISTING CONDITIONS
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
IMAGE 13
IMAGE 14
IMAGE 15
IMAGE 16
IMAGE 17
IMAGE 18
IMAGE 19
IMAGE 20
IMAGE 21
IMAGE 22
IMAGE 23
PATCH ABANDONED HOLE TO MACHINE
ROOM AND PAINT TO MATCH ADJACENT
SURFACES.
COORDINATE ROUTING OF ANY NON-
ELEVATOR WIRING TO AVOID PASSAGE
WITHIN ELEVATOR MACHINE ROOM - SEE
ELECTRICAL.
EXISTING PIPING TO REMAIN. SHOWN FOR
COORDINATION OF EQUIPMENT IN ROOM BELOW.
PIPING TO BE REMEDIATED BY OWNER - NO
WORK. CONFIRM IF PIPING IS REQUIRED.
Revision Description Date
PROVIDE NEW FIXTURES - SURFACE
MOUNTED FIXTURES ARE ACCEPTABLE.
FIXTURES SHOULD COMPLETELY COVER
EXISTING OPENINGS AND MAINTAIN THE
EXISTING FINISHES. INCORPORATE ALL
CODE REQUIRED SIGNAGE INTO
ELEVATOR FIXTURE.
PROTECT ALL EXISTING HALLWAY
FINISHES DURING CONSTRUCTION.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
PROVIDE NEW PREFINISHED ELEVATOR
DOORS AND OPENERS - SEE ELEVATOR
SPEC. FINISH TO MATCH EXISTING.
EXISTING DOOR AND FRAME TO REMAIN.
PROTECT IN PLACE DURING CONSTRUCTION.
EXISTING ROOM AND SHAFT ARE NOT FIRE
RATED PER REVIEW OF EXISTING
CONDITIONS. AREA ONLY CONNECTS 2
LEVELS AND NO FIRE RATED PRESENT.
PROVIDE CODE REQUIRED SIGNAGE AT
ELEVATOR MACHINE ROOM.
PROVIDE NEW FIXTURES - SURFACE
MOUNTED FIXTURES ARE ACCEPTABLE.
FIXTURES SHOULD COMPLETELY COVER
EXISTING OPENINGS AND MAINTAIN THE
EXISTING FINISHES. INCORPORATE ALL
CODE REQUIRED SIGNAGE INTO
ELEVATOR FIXTURE.
PROTECT ALL EXISTING HALLWAY
FINISHES DURING CONSTRUCTION.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
PROVIDE NEW PREFINISHED ELEVATOR
DOORS AND OPENERS - SEE ELEVATOR
SPEC. FINISH TO MATCH EXISTING.
PROVIDE NEW FIXTURES - SURFACE
MOUNTED FIXTURES ARE ACCEPTABLE.
FIXTURES SHOULD COMPLETELY COVER
EXISTING OPENINGS AND MAINTAIN THE
EXISTING FINISHES. INCORPORATE ALL
CODE REQUIRED SIGNAGE INTO
ELEVATOR FIXTURE.
PROTECT ALL EXISTING HALLWAY
FINISHES DURING CONSTRUCTION.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
PROVIDE NEW PREFINISHED ELEVATOR
DOORS AND OPENERS - SEE ELEVATOR
SPEC. FINISH TO MATCH EXISTING.
PROVIDE NEW FIXTURES - SURFACE
MOUNTED FIXTURES ARE ACCEPTABLE.
FIXTURES SHOULD COMPLETELY COVER
EXISTING OPENINGS AND MAINTAIN THE
EXISTING FINISHES. INCORPORATE ALL
CODE REQUIRED SIGNAGE INTO
ELEVATOR FIXTURE.
PROTECT ALL EXISTING HALLWAY
FINISHES DURING CONSTRUCTION.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
PROVIDE NEW PREFINISHED ELEVATOR
DOORS AND OPENERS - SEE ELEVATOR
SPEC. FINISH TO MATCH EXISTING.
IF ANY ELEVATOR FIXTURES ARE NOT TO
BE REUSED, THEN CAULK AND PROVIDE
BLANK PLATE COVER.
CAULK AND SEAL ABANDONED CONDUITS
AT FLOOR ABOVE ELEVATOR MACHINE
ROOM TO PREVENT WATER INTRUSION
TO ROOM BELOW.
PROVIDE NEW FIXTURES - SURFACE
MOUNTED FIXTURES ARE ACCEPTABLE.
FIXTURES SHOULD COMPLETELY COVER
EXISTING OPENINGS AND MAINTAIN THE
EXISTING FINISHES. INCORPORATE ALL
CODE REQUIRED SIGNAGE INTO
ELEVATOR FIXTURE.
PROTECT ALL EXISTING HALLWAY
FINISHES DURING CONSTRUCTION.
EXISTING PAINTED FRAMES TO REMAIN -
PROTECT IN PLACE. CLEAN, PATCH / FILL
ANY DAMAGE TO FRAME AND REPAINT.
EXISTING BELL SYSTEM TO REMAIN.
PROTECT IN PLACE.
EXISTING OWNER SIGNAGE TO REMAIN.
REMOVE ALL MISC. LOOSE ITEMS AT
CEILING SPACE.
PATCH ABANDONED HOLE TO MACHINE
ROOM AND PAINT TO MATCH ADJACENT
SURFACES.
EXISTING PIPING / DUCTWORK TO REMAIN.
SHOWN FOR COORDINATION OF EQUIPMENT
IN ROOM BELOW.
PIPING TO BE REMEDIATED BY OWNER - NO
WORK. CONFIRM IF PIPING IS REQUIRED.
EXISTING CEILING STRUCTURE TO REMAIN -
REMOVE ACCESS PANEL AND DRYWALL
COMPLETE. PROVIDE ADDITIONAL FRAMING
AS REQUIRED AT REMOVED ACCESS PANEL
AND PROVIDE NEW DRYWALL AT ENTIRE
CEILING. TAPE / MUD JOINTS ONLY.
IF ANY ELEVATOR FIXTURES ARE NOT TO
BE REUSED, THEN CAULK AND PROVIDE
BLANK PLATE COVER.
PROVIDE NEW ELEVATOR DOORS AND
OPENERS - SEE ELEVATOR SPEC.
SEE ELEVATOR SPEC FOR FULL
SCOPE OF WORK.
PROTECT IN PLACE ALL EXISTING BUILDING
FINISHES DURING CONSTRUCTION.
PROVIDE TEMPORARY ENCLOSURES AS
REQUIRED DURING CONSTRUCTION TO
PROTECT WORK AND HOISTWAYS.
PROVIDE TEMPORARY WOOD SHEATHING
PARTITION WALL WITH DOOR. ENCLOSURES
TO BE COORDINATED WITH FACILITY AND
LIMITED TO ONLY WHEN WORK OCCURRING
THIS SIDE. COORDINATE TIMING WITH
FACILITY AND CONSTRUCTION MANAGER.
PREP CLEAN, PATCH / FILL AND DAMAGE TO
FRAME AND REPAINT.
CLEAN AND POLISH ALL SILLS TO
REMAIN - TYPICAL.
PROVIDE NEW ELEVATOR FINISHES -
SEE ELEVATIONS.
EXISTING SHEET METAL ENCLOSURE TO
REMOVED AND REPLACED. REMOVE TO
PROVIDE ACCESS TO MODIFICATIONS CALLED
OUT ELSEWHERE IN THESE PLANS AND
REPLACE TO MATCH EXISTING CONFIGURATION
TO MAINTAIN PROPER SEPARATION FROM
ELEVATOR MACHINE ROOM.
NEW ELEVATOR CONTROLLER - COORDINATE
FINAL LOCATION WITHIN ROOM WITH ALL
OTHER EQUIPMENT - SEE ELEVATOR
SPECIFICATIONS.
NEW ELEVATOR HYDRAULIC TANK -
COORDINATE FINAL LOCATION WITHIN ROOM
WITH ALL OTHER EQUIPMENT - SEE ELEVATOR
SPECIFICATIONS.
NEW ELECTRICAL DISCONNECT - SEE
ELECTRICAL. PROVIDE NEW UNISTRUT
SUPPORT FROM COLUMN TO WALL TO
PROVIDE MOUNTING SURFACE. COORDINATE
FINAL LOCATION WITH ELEVATOR EQUIPMENT.
APPROXIMATE ROUTING OF NEW
ELEVATOR MACHINE ROOM
VENTILATION - SEE MECHANICAL.
PROVIDE OPENINGS AS REQUIRED
AND FULLY SEAL AROUND ALL
PENETRATIONS TO BE WATER TIGHT.
NEW ROUTING OF SUMP DISCHARGE
RUNS TO WEST AND OUT BUILDING -
SEE MECHANICAL. PROVIDE
OPENINGS AS REQUIRED AND FULLY
SEAL AROUND ALL PENETRATIONS TO
BE WATER TIGHT.
PROVIDE NEW ELEVATOR DOORS AND
OPENERS - SEE ELEVATOR SPEC.
SEE ELEVATOR SPEC FOR FULL
SCOPE OF WORK.
PROTECT IN PLACE ALL EXISTING BUILDING
FINISHES DURING CONSTRUCTION.
PROVIDE TEMPORARY ENCLOSURES AS
REQUIRED DURING CONSTRUCTION TO
PROTECT WORK AND HOISTWAYS.
PROVIDE TEMPORARY SIGNAGE OR
BARRICADES AS REQUIRED WHEN WORK IS
BEING PERFORMED IN THIS AREA.
PREP CLEAN, PATCH / FILL AND DAMAGE TO
FRAME AND REPAINT.
CLEAN AND POLISH ALL SILLS TO
REMAIN - TYPICAL.
PROVIDE NEW ELEVATOR FINISHES -
SEE ELEVATIONS.
PROTECT IN PLACE ALL EXISTING BUILDING
FINISHES DURING CONSTRUCTION.
PROVIDE TEMPORARY ENCLOSURES AS
REQUIRED DURING CONSTRUCTION TO
PROTECT WORK AND HOISTWAYS.
PREP CLEAN, PATCH / FILL AND DAMAGE TO
FRAME AND REPAINT.
GENERAL NOTES
1. DIMENSIONS ARE MEASURED FACE-
OF-FINISH TO FACE-OF-FINISH OR
ROUGH MASONRY OPENING UNLESS
NOTED OTHERWISE - TYPICAL FOR ALL
DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS AND
EXISTING CONDITIONS - TYPICAL FOR
ALL DRAWINGS.
3. IN THE EVENT OF A DISCREPANCY
BETWEEN ARCHITECTURAL AND
CONSULTANT DRAWINGS, NOTIFY
ARCHITECT IMMEDIATELY PRIOR TO
COMMENCING WORK - TYPICAL FOR
ALL DRAWINGS.
4. ALL PENETRATIONS IN FIRE RATED
FLOORS AND WALLS MUST BE SEALED
WITH APPROPRIATE FIRESTOPPING
SYSTEM.
5. PATCH AND REPAIR EXISTING FLOOR
SLABS AND WALL SURFACES
DAMAGED FROM DEMOLITION.
WALL PANEL TYPE A - ST. STL. BRUSHED
METAL WITH 5WL TEXTURE. PANEL TO BE
SET TIGHT CAB SHELL TO MAINTAIN
MAXIMUM CLEARANCE IN CAB. INSTALL WITH
COUNTERSUNK STAINLESS STEEL SCREWS.
ANODIZED ST. STL. BUMPER - SET FLAT
TO WALL PANEL (NO STAND OFFS)
PROVIDE VENTS AT BASE OF CAB
SIDE WALLS
EXISTING EXPANDED WIRE
MESH TO REMAIN - PAINT
FLAT WHITE - SEE RCP
FRONT / BACK WALL
RESILIENT FLOORING -
SEE SPECIFICATIONS
ELEVATOR CONTROL PANEL
(ANOD ST.STL.)
RESILIENT FLOORING - SEE SPECIFICATIONS
PREFINISHED EXPANDED MESH
INTERIOR BI-PARTING DOOR.
NEW LINEAR LIGHT FIXTURE
RECESSED INTO THE EXISTING
EXPANDED WIRE MESH CEILING.
EXISTING CAB EXTERIOR
EXISTING EXPANDED WIRE MESH TO
REMAIN - PAINT FLAT WHITE - SEE RCP
1/2" = 1'-0" A1
ELEVATOR ELEVATIONS
1/2" = 1'-0"
A13
ELEVATOR REFLECTED CEILING
A
19181716151413121110987654
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/1
/2
:4
:4
A M
A101
ENLARGED FLOOR PLANS
25832000
BID SET 06/16/2026
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
1251 334TH STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
N
1/2" = 1'-0" F13
ENLARGED FLOOR PLAN - BASEMENTN
1/2" = 1'-0" F1
ENLARGED FLOOR PLAN - FIRST FLOOR
EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE
DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
INTERIOR ELEVATION DRAWING REFERENCE TAG
GENERAL SYMBOLS
A101
SIM
A101 1
R e f
KEYNOTE#
XXX
X
SHEET REFERENCE
SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
SHEET REFERENCE
JUNCTION BOX, CEILING OR FLOOR MOUNTED.
JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.
J
J
A101
SIM
1 DRAWINGS REVISION. REFER TO TITLEBLOCK FOR REVISION NAME AND DATE
RECESSED LIGHT FIXTURE, LETTER INDICATES SWITCH LEG (TYPICAL), SHADING
INDICATES EMERGENCY LIGHT (TYPICAL)
SURFACE MOUNTED STRIP FIXTURE
LINEAR PENDANT MOUNTED FIXTURE
INDUSTRIAL STRIP LIGHT FIXTURE
WALL MOUNTED STRIP LIGHT FIXTURE.
EMERGENCY LIGHT FIXTURE, WALL MOUNT, +96" OR AS NOTED
EMERGENCY LIGHT FIXTURE, CEILING MOUNT
EXIT SIGN, WALL MOUNT +96", SHADED AREAS INDICATE NUMBER OF
FACES, ARROWS INDICATE SIGN ARROWS
EXIT SIGN, CEILING MOUNT, SHADED AREAS INDICATE NUMBER OF FACES,
ARROWS INDICATE SIGN ARROWS
SINGLE POLE SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
THREE WAY SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
LIGHTING SYMBOLS
a a b
ROUND LIGHT FIXTURE - SURFACE MOUNTED
SQUARE LIGHT FIXTURE - SURFACE MOUNTED
PENDANT MOUNTED LIGHT FIXTURE
POWER SYMBOLS
DUPLEX RECEPTACLE, WALL MOUNTED, TAMPER-RESISTANT
DUPLEX GFCI RECEPTACLE, TAMPER-RESISTANT, WALL MOUNT,
"G" INDICATES PROTECTION INCLUDED IN DEVICE. SHADING INDICATES DEVICE
PROTECTED BY EITHER UPSTREAM GFCI DEVICE OR CIRCUIT BREAKER
EQUIPMENT CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
EQUIPMENT CONNECTION, WALL MOUNT,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
DUPLEX RECEPTACLE, CEILING MOUNTED
SINGLE RECEPTACLE, WALL MOUNTED
G
SR
DUPLEX RECEPTACLE, WALL MOUNTED, SURFACE RACEWAY
SAFETY DISCONNECT SWITCH
PANELBOARD - SURFACE MOUNTED
PANELBOARD - RECESSED IN WALL
DISTRIBUTION PANELBOARD/SWITCHBOARD - SURFACE MOUNTED AS NOTED.
MOTOR CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
M
DUPLEX RECEPTACLE, HALF SWITCHED, WALL MOUNTED, TAMPER-RESISTANT
LOWERCASE LETTER INDICATES SWITCH LEG.
a
ELECTRICAL ABBREVIATIONS
A DEVICE MOUNTED +8" ABOVE
COUNTER TOP (VERIFY LOCATION)
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
C CEILING
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
E EXISTING ITEM TO REMAIN
EC ELECTRICAL CONTRACTOR
EM EMERGENCY LIGHT FIXTURE
ER NEW LOCATION OF EXISTING ITEM
F ROUGH IN FOR FUTURE DEVICE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
G GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
KVA KILO-VOLT-AMPERES
KW KILOWATTS
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
N NEW DEVICE IN EXISTING LOCATION
NIC NOT IN CONTRACT
NM NONMETALLIC
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
R EXISTING ITEM TO BE REMOVED
RR EXISTING ITEM TO BE REMOVED AND
RELOCATED
RN EXISTING ITEM TO BE REMOVED AND
REPLACED WITH NEW
SCCR SHORT CIRCUIT CURRENT RATING
T TAMPER PROOF DEVICE
TCC TEMPERATURE CONTROL CONTRACTOR
TV TELEVISION
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
WG WIREGUARD COVER
WP WEATHERPROOF DEVICE
WR WEATHER RESISTANT DEVICE
XFR TRANSFORMER
+24" INDICATES MOUNTING HEIGHT CENTER
LINE OF DEVICE TO FINISHED FLOOR
1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL STATE CODES.
2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE
ELECTRICAL INSTALLATION. VERIFY WITH LOCAL OFFICIALS WHEN PERMITS ARE OBTAINED.
NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR
DRAWINGS AND THE GOVERNING CODE.
3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH
DISABILITIES ACT.
4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE
CODES.
5. PER NEC EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO
ITS CLEAR, EVIDENT AND SPECIFIC PURPOSE OR USE. CONTRACTOR TO PROVIDE FINAL
CIRCUIT IDENTIFICATION FOR ALL NEW AND MODIFIED CIRCUITS AT PROJECT COMPLETION.
CODE NOTES - ELECTRICAL
1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.
2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.
3. PROVIDE GFCI TYPE RECEPTACLES AT ALL LOCATIONS REQUIRED BY THE NEC.
4. INSTALL WALL MOUNTED RECEPTACLES AT +18" ABOVE FINISHED FLOOR UNLESS OTHERWISE
NOTED.
5. INSTALL WALL MOUNTED LIGHT SWITCHES AT +46” ABOVE FINISHED FLOOR UNLESS
OTHERWISE NOTED. EXCEPTION; INSTALL DEVICES ABOVE AN OBSTRUCTED HIGH FORWARD
REACH OBSTACLE GREATER THEN 20 INCHES IN DEPTH AT +42”.
6. INSTALL ABOVE COUNTERTOP RECEPTACLES +8” ABOVE COUNTERTOP OR AS OTHERWISE
INDICATED.
7. AT A COMMON COUNTERTOP, INSTALL ALL RECEPTACLES AND SWITCHES AT THE SAME
HEIGHT UNLESS OTHERWISE SPECIFICALLY INDICATED.
DEVICE INSTALLATION AND MATERIALS - ELECTRICAL
1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL
OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY
COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.
COORDINATE WITH BUILDING STRUCTURE, ARCHITECTURE, MECHANICAL SHEET METAL, ALL
PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT
ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL
DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR
REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.
2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND
CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE
SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;
ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN
REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.
GENERAL NOTES - ELECTRICAL
1. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO
CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.
2. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL
AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER
OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF
INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.
3. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.
MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND
OPERATIONAL SYSTEM.
4. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO
NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.
5. DO NOT INSTALL BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE SAME WALL.
MAINTAIN MINIMUM OF 8” DISTANCE BETWEEN BOXES WHEREVER APPLICABLE.
6. BALANCE PANEL LOADS DURING INSTALLATION. CIRCUIT NUMBERING SHOWN ON PLANS
MAY BE ADJUSTED TO ACCOMMODATE.
7. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND
EXISTING PANELS WITH CIRCUITS MODIFIED DURING PROJECT. USE OWNER’S CURRENT
ROOM NUMBERS AND EQUIPMENT NAMES. PROVIDE UNIQUE CIRCUIT IDENTIFICATION
PER NEC 408.4(A)
8. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND
ROOFS THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL
PENETRATIONS IN ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY.
REFER TO ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.
INSTALLATION NOTES - ELECTRICAL
SECURITY - ACCESS CONTROL:
SECURITY MANAGEMENT SYSTEM - HEAD END COMPONENTS
SECURITY MANAGEMENT SYSTEM - FIELD DEVICES
SECURITY MANAGEMENT SYSTEM - ELECTRIFIED DOOR HARDWARE
ROUGH-IN, PATHWAYS AND SLEEVES
ROUGH-IN, PATHWAYS AND SLEEVES
SECURITY - VIDEO SURVEILLANCE:
CAMERA(S)
HEAD END EQUIPMENT AND COMPONENTS
SECURITY MANAGEMENT SYSTEM - ALL CABLING
OFOI
OFCI
CFCI
OWNER FURNISHED & OWNER INSTALLED
OWNER FURNISHED & CONTRACTOR INSTALLED
CONTRACTOR FURNISHED & CONTRACTOR INSTALLED
GENERAL NOTE:
A. MATRIX IS NOT INTENDED TO BE EXHAUSTIVE TO COVER ALL MATERIALS NECESSARY FOR
SCOPE AND SHOULD ONLY BE USED TO QUICKLY IDENTIFY SYSTEMS AND RELATED
INFRASTRUCTURE INSIDE AND OUTSIDE THE BID OF THIS PROJECT. ANY ITEMS FURNISHED OR
INSTALLED BY THE BIDDING CONTRACTOR SHALL COVER ALL REQUIRED APPERTUNANCES
NECESSARY FOR A COMPLETE SYSTEM. THIS SHALL INCLUDE BUT NOT BE LIMITED TO,
EQUIPMENT, ACCESSORIES, TERMINATIONS, TERMINATION COMPONENTS, ALL FINAL
CORDAGE CONNECTIVITY, SOFTWARE, PROGRAMMING, AND THE LABOR TO INSTALL.
SAFETY - FIRE DETECTION AND ALARM:
ROUGH-IN, PATHWAYS AND SLEEVES
INITIATING FIELD DEVICES (SMOKE, MANUAL PULL, MONITOR MODULES)
NOTIFICATION APPLIANCES (HORNS, STROBES, SPEAKERS)
MISCELLANEOUS DEVICES (RELAYS, TEST STATION, ANNUNCIATOR)
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
OFOI OFCI CFCI
TECHNOLOGY RESPONSIBILITY MATRIX
PROVISION RESPONSIBILITIES DEFINED
RACKS, FRAMES AND ENCLOSURES
COPPER HORIZONTAL CABLING
DATA COMMUNICATIONS SWITCHES AND HUBS
ROUGH-IN, PATHWAYS AND SLEEVES
COMMUNICATIONS - TELECOM SYSTEMS:
REUSE EXISTING
REUSE EXISTING
1. MECHANICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN
PREPARED BASED ON NON-DESTRUCTIVE FIELD OBSERVATION AND AS-BUILT DRAWINGS
PROVIDED BY THE OWNER. FIELD VERIFY EXISTING SYSTEMS BEFORE BEGINNING WORK.
NOTIFY ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE MATERIALLY DIFFERENT THAN
THOSE SHOWN ON THE PLANS.
2. BE FAMILIAR WITH EXISTING MECHANICAL SYSTEMS THAT WILL BE AFFECTED BY THE
DEMOLITION WORK. OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE TO SHUT
OFF SERVICES OR SYSTEMS THAT AFFECT AREAS BEYOND THE LIMITS OF THE IMMEDIATE
DEMOLITION AREA. INFORM THE OWNER’S REPRESENTATIVE OF THE REASON FOR AND
DURATION OF THE SHUTDOWN. MINIMIZE IMPACT TO OTHER AREAS. PROCEED WITH THE
SHUT-DOWN AFTER PERMISSION FROM THE OWNER IS GRANTED.
3. REMOVE PIPING, HANGERS, DUCTWORK, GRILLES, REGISTERS, DIFFUSERS, ETC. THAT ARE
INDICATED TO BE REMOVED IN A TIMELY MANNER IN ACCORDANCE WITH THE GENERAL
DEMOLITION SPECIFICATIONS. COORDINATE WITH THE OWNER AND OTHER CONTRACTORS.
MECHANICAL – DEMOLITION NOTES
1. COORDINATE MECHANICAL AND ELECTRICAL WORK WITH ALL OTHER TRADES. BEGIN
INSTALLATION AND ROUGH-IN AFTER COORDINATION WITH ALL TRADES ASSOCIATED WITH
THE INSTALLATION IS COMPLETE. COORDINATE BUILDING STRUCTURE, ARCHITECTURAL
ASSEMBLIES, SHEET METAL, ALL PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE
TRAYS, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR REWORK
ASSOCIATED WITH FAILURE TO COORDINATE.
2. INCORPORATE MECHANICAL SPECIFICATIONS, DRAWINGS, STATE CODES, AND OWNER
STANDARDS INTO WORK.
3. EACH TRADE IS RESPONSIBLE FOR MAKING PENETRATIONS WHERE REQUIRED IN EXISTING
WALLS, FLOORS, CEILINGS, AND ROOFS. MAKE PENETRATIONS NEAT. PATCH, CONCEAL, OR
CAULK OVERCUT.
4. COVER EXPOSED WALL PENETRATIONS WITH ESCUTCHEONS OR SHEET METAL AS
APPROPRIATE.
5. CAULK ALL CONCEALED AND EXPOSED PIPING AND DUCT WALL PENETRATIONS TO PREVENT
NOISE TRANSFER BETWEEN SPACES.
6. ON COMPLETION OF THE INSTALLATION, COOPERATE WITH THE OWNER TO PROVIDE
TESTING, ADJUSTING, AND BALANCING TO OBTAIN PROPER OPERATION OF ALL EQUIPMENT
AND SYSTEMS. PROVIDE ALL FACILITIES AND EQUIPMENT AND COMPLETE ALL TESTS
REQUIRED FOR ADJUSTMENTS AND BALANCING TO ESTABLISH THE PROPER PERFORMANCE
OF EQUIPMENT.
MECHANICAL - GENERAL NOTES
FIRE DETECTION & ALARM NOTES
1. INSTALL HEAT DETECTORS IN WORK AREAS DURING CONSTRUCTION TO MINIMIZE
FALSE TRIPS. INSTALL PERMANENT DETECTORS IN LOCATIONS SHOWN UPON
CONSTRUCTION COMPLETION.
2. INSTALL MODULES AT ELEVATOR EQUIPMENT TO PROVIDE PRIMARY RECALL,
SECONDARY RECALL, FIRE HAT AND SHUNT TRIP. PROVIDE PROGRAMMING AS
NECESSARY FOR FUNCTION SYSTEM.
3. FIRE ALARM ITEMS AND DEVICES ARE SHOWN IN SUGGESTED LOCATIONS. FINAL
LAYOUTS, LOCATIONS, AND QUANTITIES SHALL BE IN ACCORDANCE WITH APPLICABLE
CODES, MANUFACTURER’S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.
COORDINATE LOCATIONS WITH LIGHTING AND AIR HANDLING SYSTEMS.
4. ALL FIRE ALARM CIRCUITRY IN EXPOSED CEILING SPACES SHALL BE IN ¾” CONDUIT PER
SPECIFICATIONS. EXPOSED CABLING SHALL NOT BE ACCEPTED.
5. ALL CONCEALED, ACCESSIBLE CEILING TILE LOCATIONS SHALL BE ALLOWED TO HAVE
OPEN AIR CABLING INSTALLED. PROVIDE J-HOOKS, BRIDLE RINGS AND ASSOCIATED
CABLE SUPPORTS TO KEEP INFRASTRUCTURE MANAGED AND OFF OF THE CEILING TILE.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRESTOPPING AT ALL PENETRATIONS PER
SPECIFICATION.
COMMUNICATION NOTES
1. REUSE EXISTING POTS LINE IN THE ELEVATOR EQUIPMENT ROOM FOR THE ELEVATOR
TELEPHONE. REVISE LOCATION AND EXTEND AS NECESSARY FOR NEW EQUIPMENT
LOCATIONS.
2. INSTALL NEW DATA CABLING FROM IDF LOCATIONS SHOWN ON PLANS TO EACH
ELEVATOR EQUIPMENT ROOM FOR NEW 2-WAY COMMUNICATION SYSTEM.
ELEVATOR PIT
BOTTOM FLOOR CEILING
TOP FLOOR
TOP FLOOR CEILING
KEY NOTES:
FUSED, LOCKABLE MAIN DISCONNECT SWITCH AND DEDICATED
CAT6 DATA TERMINATION TO SERVE ELEVATOR MAIN POWER.
PROVIDED WITH NO/NC LOW VOLTAGE CONTACTS.
FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH TO SERVE
ELEVATOR AUXILLIARY LIGHTING/VENTILATION,
DEDICATED CIRCUIT 120V DUPLEX GFCI MAINTENANCE
RECEPTACLE WITHIN MACHINE ROOM SPACE ADJACENT TO
DISCONNECTS.
FIRE ALARM SYSTEM HAT FLASH, PRIMARY RECALL, AND
SECONDARY RECALL RELAYS.
S
SMOKE DETECTORS INSTALLED AT TOP OF HOISTWAY.
ELEVATOR HOISTWAY LIGHTING. TYP.
PROVIDE HOISTWAY LIGHTING CONTROLS THREE WAY SWITCHES AT
BOTTOM AND TOP FLOOR HOISTWAY ENTRIES. WHERE MULTIPLE CARS
SHARE A COMMON HOISTWAY, PROVIDE 4 WAY SWITCHES AND PROVIDE
SWITCH AT EACH CARS BOTTOM AND TOP FLOORS. SWITCH SHALL
CONTROLS ALL LIGHTING IN HOISTWAY AND PIT
S
LOBBY, TOP FLOOR
TOP OF HOISTWAY2
HOISTWAY LIGHTING SWITCH
S
ELEVATOR LOBBY SMOKE DECTOR.
<21' FROM CENTERLINE OF ELEVATOR
DOOR. TYP FOR EVERY LOBBY.
ELEVATOR LOBBY SMOKE DECTOR.
<21' FROM CENTERLINE OF ELEVATOR
DOOR. TYP FOR EVERY LOBBY.
LOBBY, BOTTOM FLOOR S
SMOKE DETECTOR WITHIN ELEVATOR
MACHINE ROOM
MACHINE ROOM
HOISTWAY LIGHTING SWITCH
120V DEDICATED CIRCUIT PIT SUMP
PUMP SIMPLEX RECEPTACLE
120V DEDICATED CIRCUIT PIT
MAINTENANCE GFCI DUPLEX RECEPTACLE
BOTTOM FLOOR
TYPICAL ELEVATOR HOISTWAY ELEVATION TYPICAL ELEVATOR MACHINE ROOM
ELEVATOR
MAIN POWER
DISCONNECT
ELEVATOR
CONTROL
PANEL
ELEVATOR MACHINE
ROOM LIGHTING.
DEDICATED CIRCUIT. TYP.
AOM
FIRE ALARM
SYSTEM RELAYS
MACHINE ROOM
LIGHTING SWITCH
ELEVATOR
AUX POWER
DISCONNECT
ELEVATOR CAB
RESCUE ASSISTANCE
SYSTEM DISCONNECT
FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH AND
DEDICATED CAT6 DATA TERMINATION TO SERVE ELEVATOR CAB
INTERNAL RESCUE ASSISTANCE SYSTEM.
MAINTENANCE
RECEPTACLE
ELEVATOR HOISTWAY LIGHTING POWERED BY DEDICATED
CIRCUIT. FOR EACH CAR, PROVIDE LIGHT FIXTURE AT TOP OF
HOISTWAY, PIT, AND AT EACH FLOOR. FIXTURES ABOVE PIT
LOCATED TO ILLUMINATE TOP OF CAR AT EACH STOP, TYPICAL 10'
ABOVE EACH LEVEL.
208V/3PH ELEVATOR MAIN
DISCONNECT SWITCH
FUSED/LOCKABLE
NO/NC LV CONTACTS
208V/3PH
LV
ELEVATOR
CONTROLLER
120V/1PH 120V/1PHELEVATOR AUXILARY
DISCONNECT SWITCH
FUSED/LOCKABLE
20A/1P DEDICATED CIRCUIT
DEDICATED CIRCUIT
SHUNT TRIP BREAKER
120V/1PH 120V/1PHELEVATOR INTERNAL
RESCUE ASSISTANCE
DISCONNECT SWITCH
FUSED/LOCKABLE
20A/1P DEDICATED CIRCUIT
LV/CAT6POTS LINE FROM
BUILDING MDF
1LV/CAT6
SHUNT TRIP COIL
LVFIRE ALARM
CONTROL PANEL
LV
LV/CAT6CAT6 FROM
BUILDING MDF
1LV/CAT6
AOM
HAT FLASH, PRIMARY,
SECONDARY RECALL
HOISTWAY LIGHTINGDEDICATED 20A/1P CIRCUIT
PIT GFCI DUPLEXDEDICATED 20A/1P CIRCUIT
MACHINE ROOM GFCI DUPLEXDEDICATED 20A/1P CIRCUIT
PIT SUMP PUMP SIMPLEXDEDICATED 20A/1P CIRCUIT
MACHINE ROOM LIGHTINGDEDICATED 20A/1P CIRCUIT
MACHINE ROOM HVAC20A/1P CIRCUIT
120V/1PH
120V/1PH
120V/1PH
120V/1PH
120V/1PH
120V/1PH
TYPICAL ELEVATOR SYSTEMS WIRING DIAGRAM
FUTURE
MANUAL FIRE ALARM PULL STATION
FIRE DETECTION AND ALARM SYMBOLS
SMOKE DETECTOR
SMOKE DETECTOR WITH 520Hz SOUNDER BASE
DUCT SMOKE DETECTOR
HEAT DETECTOR
COMBINATION HORN WITH STROBE
COMBINATION SPEAKER WITH STROBE
STROBE
ADDRESSABLE INPUT MODULE; FS - SPRINKLER WATER FLOW SWITCH,
TS - TAMPER SWITCH, PIV - POST INDICATOR VALVE
FIRE ALARM CONTROL PANEL + EMERGENCY COMMUNICATIONS PANEL
COMBINATION FIRE/SMOKE DAMPER
SMOKE DAMPER
S
S
AIM
ADDRESSABLE OUTPUT MODULE; SD - FAN SHUT DOWN RELAYAOM
S
SB
H HORN
SD
FSD
S
F
FACP
XX
XX
ROUND DUCT (DIAMETER / SYSTEM)
RECTANGULAR DUCT (WIDTH / HEIGHT / SYSTEM)
FIRE/SMOKE DAMPERFSD
R
FLAT OVAL DUCT (WIDTH / HEIGHT / SYSTEM)
ELEVATION CHANGE (RISE OR DROP)
HIGH EFF. TAKE OFF FITTING w/ VOLUME DAMPER
FLEXIBLE DUCTWORK
SUPPLY (SA), OUTSIDE (OA), VENTILATION (VA) AIR DUCT (UP / DOWN /
SECTION)
DUCT END CAP
DUCT ACCESS DOOR
RETURN (RA) AIR DUCT (UP / DOWN / SECTION)
EXHAUST (EA) AIR DUCT (UP / DOWN / SECTION)
SUPPLY DIFFUSER
LINEAR SLOT DIFFUSER
SUPPLY REGISTER OR GRILLE
SIDE WALL DIFFUSER
EXHAUST REGISTER OR GRILLE
ROUND DIFFUSER
EXTERIOR LOUVER
RETURN REGISTER OR GRILLE
MOTORIZED ACTUATOR
THERMOSTAT
X-#
#x#/CFM
FIXTURE IDENTIFICATION TAG
NECK SIZE / CFM
VAV TERMINAL UNIT
RECT. RND. OVAL
TURNING VANES
H.V.A.C. / DUCTWORK SYMBOLS
10/6 SA
10 Ø SA
10/6 Ø SA
AD
M
T
A
19181716151413121110987654
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
P R
IN
T
E D
R
S
T
U
20 21 22 23 24 25
Sheet Name
Key Plan
19181716151413121110987654 20 21 22 23 24 25321
Sheet Number
Sheet Issue Date
OPN Project No.
Owner
All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by
OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc.
shall retain all common law, statutory and other reserved rights, including the copyright thereto.
© 2025 OPN Architects, Inc.
100 Court Ave., Suite 100
Des Moines, IA 50309
P: 515-309-0722 www.opnarchitects.com
STORY CONSTRUCTION
2810 WAKEFIELD CIRCLE
AMES, IA 50010
Project
CONSTRUCTION MANAGER
LERCH BATES
7625 GOLDEN TRIANGLE DRIVE,
SUITE T
EDEN PRAIRIE, MN 55344
ELEVATOR CONSULTANT
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Mechanical Engineer
KCL ENGINEERING
300 4TH STREET
WEST DES MOINES, IA 50317
Electrical Engineer
/2
/2
:5
:3
P M
ME000
ELECTRICAL GENERAL
NOTES & SYMBOLS
25832000
100% CD SET 06/16/26
WRC FOOD SERVICE ELEVATOR
REPLACEMENT
STATE OF IOWA - 9504.00
34 CEDAR STREET
WOODWARD, IA 50276
109 SE 13TH STREET
DES MOINES, IA 50319
MECHANICAL SCOPE: INSTALL LOCAL ALARM IN KITCHEN WHEN ELEVATOR
EQUIPMENT ROOM IS ABOVE 90 DEGREES. INSTALL THERMOSTAT AS
SHOWN ON PLANS TIED INTO LOCAL ALARM SYSTEM.
Revision Description Date
NOT TO SCALE
ELEVATOR SYSTEM DETAIL
NOT TO SCALE
2 ELEVATOR SYSTEM DETAIL
S
C
S
S
F
+46"
S F
A C
P F
A C
P F
A C
P
B L
HN
F
S
+46"
+46"
F A
C P
F A
C P
F A
C P
S
C
S
+46"
S
FSD
AOMAOM
T
F S
D
AOM
AOM
POWER GENERAL NOTES
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL
WORK WITH ALL OTHER TRADES. NO ASPECT OF A SYSTEM INSTALLATION
OR ITS ROUGH-IN SHALL COMMENCE UNTIL PROPER AND TIMELY
COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION HAS
TRANSPIRED. ITEMS TO BE COORDINATED SHALL INCLUDE BUT NOT BE
LIMITED TO: BUILDING STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT
FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,
MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR THIS
PROJECT.
B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS WITH
MECHANICAL CONTRACTOR AND FINAL MECHANICAL SHOP DRAWINGS.
C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS THROUGH
THE BUILDING. COORDINATE FIRE RATED WALL PENETRATIONS AND
PROVIDE CONDUIT SLEEVES AND FIRE STOPPING TO MAINTAIN RATING.
COMMUNICATION GENERAL NOTES
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE
UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES
ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS
TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:
BUILDING STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT
FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL
GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT.
B. PROVIDE PENETRATIONS REQUIRED FOR ROUTING CABLING
AND RACEWAYS THROUGH THE BUILDING. COORDINATE FIRE
RATED WALL PENETRATIONS AND PROVIDE CONDUIT SLEEVES
AND FIRE STOPPING TO MAINTAIN RATING.
C. PROVIDE J-HOOKS, BRIDLE RINGS AND OTHER ACCESSORIES
REQUIRED TO SUPPORT ALL TELECOMMUNICATIONS AND
SECURITY MANAGEMENT SYSTEM CABLING.
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE
UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES
ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS
TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:
BUILDING STRUCTURE, SHEET METAL, ALL PIPING SYSTEMS,
LIGHT FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL
GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT
B. UNLESS NOTED OTHERWISE, CONNECT ALL EMERGENCY
BATTERY FIXTURES WITH AN UN-SWITCHED LEG OF THE
LIGHTING CIRCUIT THAT SERVES THE FIXTURES SPACE.
MAINTAIN NORMAL SWITCHING SCHEME OF EMERGENCY
FIXTURES UNDER NORMAL OPERATION.
C. LIGHTING CONTROLS SENSORS SHOWN ON PLANS AT
SUGGESTED LOCATIONS. VERIFY FINAL LOCATIONS AND
QUANTITIES WITH MANUFACTURER GUIDELINES AND
INSTALLATION RECOMMENDATIONS. COORDINATE
RELOCATIONS WITH ARCHITECTS CEILING PLAN.
LIGHTING GENERAL NOTES
N
E
E
INSTALL ABOVE TOP OF ELEVATOR
RAIL ON WALL.
F1
E
6-26-2
F1
6-26-2
INSTALL NEW NOTIFICATION
HORN AT 7' AFF ON WALL FOR
SUMP PUMP ALERT.
+2'
+9'
F1 F1
E E E E
N
INSTALL NEW 400A
MAIN BREAKER IN
MDP. EXISTING PANEL
IS SQUARE D I-LINE
NEW PANEL 6.
400A PANEL FOR ELEVATOR
CIRCUITS.
NEW OVERHEAD FEEDER
TO PANEL 6
CORE THROUGH WALL AND INSTALL
FIRESTOPPING TO MEET 2 HOUR WALL
REQUIREMENTS
APPROXIMATE BRANCH CIRCUIT
CONDUIT PATH FROM PANEL 6 TO
ELEVATOR EQUIPMENT. COORDINATE
EXACT LOCATION IN THE FIELD
x E
A
WALL CAP BY FAN MFR.
LOCATE 12" ABOVE
GRADE
CORE DRILL/CUT EXISTING
CONCRETE WALL AS REQUIRED
ME101
INSTALL LOCAL ALARM
IN KITCHEN SPACE TO ALERT
STAFF WHEN TEMPERATURE IN
ELEVATOR MACHINE ROOM
IS ABOVE 90 DEGREES
INSTALL ELBOWS AND ACCESSORIES AS NECESSARY
TO INSTALL DUCT AS HIGH AS POSSIBLE IN STORAGE
SPACE.
2" PUMPED DISCHARGE.
INSTALL AS HIGH AS POSSIBLE
IN SPACE
DISCONNECT ELBOW AND PATCH AND
SEAL EXISTING SANITARY PIPING. EXTEND
EXISTING PUMPED DISCHARGE TO ABOVE
CEILING IN ELEVATOR EQUIPMENT ROOM.
DISCHARGE ABOVE
GRADE. INSTALL
ADJACENT TO GAS
ENTRANCE IN
GREEN SPACE.
6-19
6-17
6-26-2
EXISTING BELL TO
REMAIN INTACT
REMOVE EXISTING LIGHTING CIRCUIT FOR CORRIDOR
FROM ELEVATOR SHAFT. NEW LIGHTING FOR SHAFT WILL
BE ON A DEDICATED CIRCUIT.
EXISTING SUMP PIT AND
PIPING TO REMAIN.
REPLACE EXISTING SUMP
PUMP WITH NEW 1/2 HP
SUBMERSIBLE PUMP AND
ALERT SYSTEM.
RN
REPLACE WITH HEAT
DETECTOR DURING
CONSTRUCTION
RN
R
RN
E
EXISTING SIEMENS
DESIGO FIRE ALARM
PANEL
EXISTING DATA RACK.
REUSE FOR NEW 2-WAY
COMMUNICATION DEVICE
E E
E
EXISTING 3 PANELS
TO REMAIN INTACT.
DIETARY MDP
1200A MAIN
REMOVE EXISTING JUNCTION BOX IN SPACE.
EXTEND…