RFB950000-01 - Drawings.pdf
PDF 5 MB Posted
- Solicitation number
- RFB950000-01
- Issued by
- Harrison County, Iowa
About this file
This is a set of engineering drawings and specifications for the Iowa Department of Corrections' diesel tank replacement and spill containment project at Mount Pleasant Correctional Facility in Mount Pleasant, Iowa. The project involves demolition of four existing diesel tanks and installation of one new 20,000-gallon double-wall, UL 142-listed aboveground horizontal cylindrical diesel storage tank designed to serve as backup fuel for the central steam plant. The design specifications include comprehensive structural, civil, mechanical, and electrical components prepared by KCL Engineering LLC and Shoemaker Haaland engineering firms. The project includes site preparation, grading, erosion control measures, concrete foundations with reinforced piers, spill containment infrastructure, piping systems with interstitial leak detection, electrical connections, and control panel installation. The drawings are dated April 27-29, 2026, and represent 100% construction documents with multiple sheets covering demolition plans, foundation details, mechanical schematics, tank specifications, and electrical diagrams.
The diesel tank is specified as having a nominal capacity of 20,000 gallons (10-foot diameter by 34-foot length), constructed of carbon steel with ASTM A36 or A516 material for the inner tank and an integral double-wall secondary containment shell with continuous interstitial leak detection and alarm systems. Design criteria include compliance with NFPA 30, UL 142 listing requirements, API 650 alignment where applicable, and ASCE 7 wind and seismic design standards for Mount Pleasant, Iowa. The tank shall include a 24-inch diameter top-center manway with integral ladder and platform, lockable fill connection with spill containment, 90 percent high-level alarm with remote capability, 95 percent automatic shutoff device, properly sized normal and emergency vents, and supply/return outlets rated for 120 gallons per minute. Foundation design is based on a geotechnical investigation by Terracon with a net allowable bearing pressure of 1,000 PSF and frost protection depth of 3 feet 6 inches below grade. Electrical work includes bonding the tank to an equipment ground, grounding lugs, 120-volt control panel installation with disconnect switch, and conduit installation meeting NEC Class 1 Division 2 requirements with seal-offs. The project requires contractor provision of 2,000 gallons of diesel fuel for plant use at the end of testing and compliance with all Iowa Statewide Urban Design and Specifications manuals, the 2024 International Building Code, and OSHA regulations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
P lo t D a te
T im e
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
/2
/2
:2 :5
P
M
MC
02/18/2026
26027
D O
C M
P C
F D
IE
S
E L
T A
N K
S R
E P
L A
C E
M E
N T
S
P
IL
L C
O N
T A
IN
M
E N
T M
T
P L E
A S
A N
T C
O R
R E
C T
IO
N
A L
F A
C
IL
IT
Y
COVER SHEET
DOC
MT. PLEASANT CORRECTIONAL FACILITY
MPCF DIESEL TANKS REPLACEMENT & SPILL CONTAINMENT
Sheet Index
Sheet Number Sheet Name
C100 CIVIL GRADING AND SWPPP PLAN
S000 GENERAL NOTES
S100 DEMO PLAN, FOUNDATION PLAN, AND DETAILS
S101 TANK ACCESS PLAN AND DETAILS
M000 MECHANICAL GENERAL NOTES & SYMBOLS
M100 MECHANICAL PLAN
M300 MECHANICAL SCHEMATIC
M500 MECHANICAL SCHEDULES TANK BID DOCUMENTS
E000 ELECTRICAL PLAN
SITE PLAN PLANT BASEMENT ROOF AND DIESEL TANKSSTATE LOCATION MAP
1200 E Washington St, Mt. Pleasant, IA 52641
DAS PROJECT #9500.00
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that i am a duly licensed Professional Engineer under the laws of the State of Iowa
(signature)
License Number :
Pages or sheets covered by this seal:
(date)
My license renewal date is December 31, E N
G N
E E
R I
AOFESSION
S E
D
PR
AI O W
L
IC
E N
L
ERIC HEYNEN, P.E.
ERIC
HEYNEN
E. Sheets
P24706P24706
# Revision Date
100% CD 04/27/2026
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Iowa.
Ryan E. Kuntz Reg. No. 19703 Date
My license renewal date is December 31, 2027.
Pages or sheets covered by the seal:
04/27/2026
S000, S100
WELCH
MICHAEL J.
19636
LIC
EN
SE
D
PROFESS IONAL
ENG
INEER
AWOI
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Iowa.
Michael J. Welch Reg. No. 19636 Date
My license renewal date is December 31, 2026.
Pages or sheets covered by the seal:
04/27/2026
C100
04/27/2026
04/27/2026
M. SHEETS
Date: 04/29/26
# Revision Date
0 100%CD 04/29/26
04/29/2026
04/29/2026
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Iowa.
Ryan E. Kuntz Reg. No. 19703 Date
My license renewal date is December 31, 2027.
Pages or sheets covered by the seal:
04/29/2026
S Sheets
WELCH
MICHAEL J.
19636
LIC
EN
SE
D
PROFESS IONAL
ENG
INEER
AWOI
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Iowa.
Michael J. Welch Reg. No. 19636 Date
My license renewal date is December 31, 2026.
Pages or sheets covered by the seal:
04/29/2026
C Sheets
X X
X X
X X
X
X X X X X X X X
X X
X X
X X
X X
X X
XXX
X
X X
XX
X
X X
714.16 Ex.
706.66 Ex.
1 71
712.50
712.50 712.50
712.50
Drawing #:
Date: 04/29/26
Project No: 26027
# Revision Date
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Pl ot
D at e
Ti m e:
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
25457SHPE PROJECT NO.
Shoemaker Haaland www.shoemaker-haaland.com
0 100%CD 04/29/26
FEET
0 5 10 2015
C100
STORM MANHOLE
RIM = 703.79
FL (N) 12"-15" RCP = 693.19
FL (E) 12"-15" RCP = 700.69
FL (NE) 6" PVC = 700.81
UTILITY MANHOLE
RIM = 711.76
BOTTOM = 707.66
SANITARY MANHOLE
UNABLE TO OPEN
STORM MANHOLE
UNABLE TO POP GRATE
STANDING WATER PRESENT
SANITARY MANHOLE
UNABLE TO OPEN
STORM MANHOLE
FL (W) 12"-15" RCP = 706.27
FL (E) 12"-15" RCP = 706.77
FUEL TANK FOUNDATIONS
-TO BE REMOVED WITH
THIS CONSTRUCTION
SEE STRUCTURAL FOR
ASSUMED SIZES
CIVIL GRADING
AND SWPPP PLAN
IO
W
A D
EP
AR
TM
EN
T O
F C
O R
R
EC
TI
O
N S
M T
PL
EA
SA
N
T C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
M
PC
F D
IE
SE
L
TA
N
KS
R
EP
LA
C
EM
EN
T
SP
IL
L C
O N
TA
IN
M
EN
T
GENERAL PROJECT NOTES
1. THE IOWA DEPARTMENT OF CORRECTIONS IS THE APPROVING AUTHORITY FOR THIS PROJECT.
2. THE USE OF THE TERM "ENGINEER" REFERS TO SHOEMAKER AND HAALAND.
3. THE USE OF THE TERM "CONTRACTOR" REFERS TO THE GENERAL CONTRACTOR AND ANY SUBCONTRACTORS WORKING ON THE PROJECT.
4. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE IOWA STATEWIDE URBAN DESIGN AND SPECIFICATIONS MANUALS (SUDAS).
5. THE LOCATION OF UNDERGROUND UTILITIES SHOWN ON THESE PLANS IS BASED ON MAPPING AND FIELD LOCATES. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ONECALL
UTILITY LOCATES (CALL 811) PRIOR TO PERFORMING ANY WORK.
6. THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES BETWEEN THE PLAN AND FIELD LOCATES.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE NOTICE TO UTILITY COMPANIES, THE LOCAL MUNICIPALITY, AND/OR COUNTY ROADS DEPARTMENT/DOT (IF
APPLICABLE) PRIOR TO PERFORMING WORK.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS (LOCAL, STATE, AND FEDERAL) UNLESS EXPLICITLY STATED OTHERWISE IN THE CONTRACT
DOCUMENTS.
9. THE CONTRACTOR SHALL CONFINE WORK TO THE AREAS INDICATED ON THE PLANS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL PROPERTY MONUMENTS WITHIN AND ADJACENT TO THE PROJECT AREA. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH RESETTING PROPERTY MONUMENTS THAT ARE REMOVED BY CONSTRUCTION ACTIVITY. ALL PROPERTY MONUMENTS SHALL BE
SET BY A LAND SURVEYOR REGISTERED TO PRACTICE IN THE STATE OF IOWA.
SITE PREPARATION NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROTECT TREES AND OTHER DESIRABLE VEGETATION FROM DAMAGES FROM CONSTRUCTION ACTIVITY. THE CONTRACTOR SHALL
DESIGNATE A LOCATION FOR ON SITE PARKING, LOCATION FOR EQUIPMENT STORAGE, AND LOCATION(S) FOR MATERIAL LAYDOWN AND STORAGE.
2. REMOVAL AND DISPOSAL OF EXISTING TREES AND VEGETATION WITHIN THE CONSTRUCTION LIMITS SHALL BE INCIDENTAL TO THE GRADING ACTIVITIES, UNLESS STATED
OTHERWISE IN THE CONTRACT DOCUMENTS. TREES AND WOODY VEGETATION MAY BE CHIPPED AND USED TO SUPPLEMENT EROSION CONTROL MEASURES. NO BURNING SHALL
BE ALLOWED.
3. PAVEMENT REMOVAL OPERATIONS ADJACENT TO PAVEMENT THAT WILL REMAIN SHALL USE FULL-DEPTH SAW CUTS TO PREVENT DAMAGE TO ADJACENT PAVING.
4. PAVEMENT, CURB AND GUTTER, AND/OR SIDEWALKS SHALL BE REMOVED TO THE NEAREST JOINT. REMOVAL SHALL EXTEND A MINIMUM OF TWO FEET BEYOND EXCAVATION AND
TRENCH LIMITS TO PREVENT UNDERMINING OF PAVING SLABS.
5. UTILITY LINES AND STRUCTURES, BUILDING FOUNDATIONS (IF APPLICABLE), AND PAVEMENTS (STREETS, CURBS, SIDEWALKS) NOTED FOR REMOVAL SHALL BE REMOVED IN THEIR
ENTIRETY, UNLESS NOTED OTHERWISE.
6. CONTRACTOR SHALL REPLACE CURB AND GUTTER AND SIDEWALKS AT CONSTRUCTION EXITS UPON REMOVAL OF THE CONSTRUCTION EXIT.
7. CONCRETE, BUILDING MATERIALS, AND OTHER WASTE MATERIALS SHALL BE HAULED OFFSITE AND DISPOSED OF PROPERLY. THE CONTRACTOR SHALL PROVIDE APPROPRIATE
SORTING AND WASTE STORAGE AREAS ON SITE FOR WASTE MATERIALS PRIOR TO HAUL OFF. DISPOSAL SITES SHALL BE APPROVED BY THE ENGINEER AND OFF-SITE DISPOSAL
SHALL BE IN ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS.
GENERAL GRADING NOTES
1. SEDIMENT AND EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO COMMENCING GRADING OPERATIONS.
THE COMPACTION REQUIREMENTS LISTED BELOW ARE BASED ON STANDARD PROCTOR DRY DENSITIES AS DETERMINED BY ASTM D698. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING MATERIAL SAMPLES TO THE TESTING AGENCY AND PROVIDE SUFFICIENT NOTICE FOR TESTING. VALUES BELOW ARE PROVIDED IN LIEU OF A SITE-SPECIFIC GEOTECHNICAL REPORT. IF A GEOTECHNICAL EVALUATION AND REPORT ARE AVAILABLE, THE DATA IN THE REPORT SHALL SUPERSEDE THESE VALUES.
RELATIVE MOISTURE VARIANCE
LOCATION OF FILL MATERIALS COMPACTION FROM OPTIMUM
LESS THAN 12" BELOW FLOOR 98% -3% to +3% SANDS SLABS AND FOUNDATIONS* -1% to 3% CLAYEY SOILS
MORE THAN 12" BELOW FLOOR 95% -3% to +3% SANDS SLABS AND FOUNDATIONS -1% to 3% CLAYEY SOILS
BELOW EXTERIOR PAVEMENTS 95% -3% to +3% SANDS -1% to 3% CLAYEY SOILS
BELOW LANDSCAPED SURFACES 90% -3% to +3% ALL SOILS
CONTRACTOR TO PROTECT
EXISTING PIV
DURING CONSTRUCTION
GRADING LIMITS
170 LF OF 8" FILTER SOCK
TOP OF FOOTING = 709.50
TOP OF PIER = 713.00
FG = 712.50
GENERAL EROSION CONTROL NOTES
1. SEDIMENT SHALL BE REMOVED FROM BEHIND SILT SOCKS BEFORE ACCUMULATED SEDIMENT HAS REACHED HALF THE TOTAL HEIGHT OF THE BARRIER.
2. TEMPORARY SEED OR OTHER APPROPRIATE STABILIZATION MEASURE SHALL BE APPLIED TO DISTURBED AREAS THAT WILL REMAIN INACTIVE FOR MORE THAN FOURTEEN (14) DAYS.
3. PERMANENT SEEDING MIX SHALL BE TYPE 1-PERMANENT LAWN MIXTURE PER SUDAS SPECIFICATIONS SECTION 9010.
APPROXIMATE LOCATION OF UNDERGROUND TUNNEL.
DO NOT WORK OVER AREA. CONTRACTOR TO VERIFY
LOCATION & INCLUDE SIGNAGE AS NECESSARY
Date: 04/29/26
# Revision Date
0 100%CD 04/29/26
STRUCTURAL DESIGN INFORMATION
1. SNOW LOAD
GROUND SNOW LOAD, P g = 20 PSF FLAT-ROOF SNOW LOAD, P f = 20 PSF SNOW EXPOSURE FACTOR, C e = 1.0 SNOW IMPORTANCE FACTOR, I s = 1.0 THERMAL FACTOR, Ct = 1.2
2. WIND DESIGN DATA
ULTIMATE DESIGN WIND SPEED, Vult = 109 MPH NOMINAL DESIGN WIND SPEED, Vasd = 90 MPH
RISK CATEGORY II
WIND EXPOSURE CATEGORY C
TOPOGRAPHIC FACTOR, Kzt = 1.0 Gcpi = ± 0.18
3. DESIGN LIVE LOADS
EXTERIOR WALKWAYS - 50 PSF
EQUIPMENT LOADS AS PROVIDED ON FINAL SHOP DRAWINGS
4. SEISMIC DESIGN DATA
SITE CLASS D
RISK CATEGORY II
SEISMIC DESIGN CATEGORY B
SEISMIC IMPORTANCE FACTOR, Ie = 1.0 MAPPED SPECTRAL RESPONSE ACCEL. (SHORT PERIOD), S s = 0.089
MAPPED SPECTRAL RESPONSE ACCEL. (1 SEC PERIOD), S 1 = 0.067
DESIGN SPECTRAL RESPONSE ACCEL. (SHORT PERIOD), S ds = 0.095 DESIGN SPECTRAL RESPONSE ACCEL. (1 SEC PERIOD), S d1 = 0.108
CODES, STANDARDS, AND SPECIFICATIONS
1. DESIGN AND CONSTRUCTION OF THIS PROJECT SHALL CONFORM TO THE REQUIREMENTS OF THE 2024 EDITION OF THE INTERNATIONAL BUILDING CODE (IBC) AND ANY APPLICABLE AMENDMENTS, AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION
2. DESIGN REQUIREMENTS FOR THE MATERIALS OF CONSTRUCTION BASED ON THE REFERENCED STANDARDS IN CHAPTER 35 OF THE IBC
3. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) 29 CFR 1910 - STANDARDS FOR GENERAL INDUSTRY AND CFR 1926 - SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION HAVE BEEN REFERENCED FOR REQUIREMENTS RELATED TO WORKPLACE SAFETY
CAST-IN-PLACE CONCRETE
1. MATERIALS:
CONCRETE - MINIMUM 28 DAY COMPRESSIVE STRENGTH
4,500 PSI (5% - 7% AIR) = CONCRETE EXPOSED TO FREEZE THAW CYCLES
4,000 PSI = ALL OTHER CONCRETE
CEMENT - ASTM C150 OR ASTM C595 TYPE IL
AGGREGATE - ASTM C33
STEEL REINFORCING BARS - ASTM A615 GR. 60
STEEL REINFORCING WELDABLE - ASTM A706 GR. 60
WELDED WIRE FABRIC - ASTM A185
GROUT - ASTM C827
ANCHOR BOLTS - ASTM F1554 GR. 55
2. CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI 318 AND ACI 301 AND ALL LOCAL BUILDING CODES. REFER TO THE FOLLOWING CODE
SECTIONS FOR SPECIFIC REQUIREMENTS:
MIX PROPORTIONS - ACI 211.1
HOT WEATHER CONCRETE - ACI 305R
COLD WEATHER CONCRETE - ACI 306.1
CONCRETE CURING - ACI 308
CONCRETE CONSOLIDATION - ACI 309
REBAR DETAILING AND PLACEMENT - ACI 315
ENVIRONMENTAL STRUCTURES - ACI 350
3. CLEAR COVER FROM FACE OF CONCRETE TO OUTERMOST REINFORCING, UNLESS NOTED OTHERWISE:
WALLS, PIERS - 2"
COLUMNS (EDGE TIES) - 1-1/2"
FOOTINGS - 3"
SLABS EXPOSED TO EARTH AND WEATHER - 1-1/2"
SLABS NOT EXPOSED TO EARTH AND WEATHER - 3/4"
GRADE BEAMS - (EDGE OF STIRRUPS) - 1-1/2" TOP, 3" BOT., 3" SIDES
4. WATER REDUCING ADMIXTURES MAY BE INCORPORATED IN THE MIX DESIGN WITH THE APPROVAL OF THE ENGINEER. ADMIXTURE SHALL CONFORM TO ASTM C494 AND USED PER MANUFACTURER'S RECOMMENDATIONS. CHLORIDE CONTAINING ADMIXTURES SHALL NOT BE USED
5. AIR-ENTRAINING AGENTS SHALL CONFORM TO ASTM C260 WITH AMOUNTS IN ACCORDANCE WITH ACI 318. ENTRAINED AIR SHALL BE
MEASURED IN THE FIELD AT THE DISCHARGE FROM THE TRUCK
6. ALL EXPOSED CONCRETE EDGES TO HAVE 3/4" CHAMFER, U.N.O.
7. BAR LAP SPLICES SHALL BE BASED UPON THE REQUIREMENTS OF ACI 318 OR CRSI UNLESS NOTED OTHERWISE. LAP WELD WIRE FABRIC
SHEETS 8 INCHES MINIMUM. LAP SPLICES SHALL BE STAGGERED
8. REINFORCING STEEL SHALL BE PLACED AS NOTED ON THE DRAWINGS AND DETAILED IN ACCORDANCE WITH ACI 315. BARS SHALL BE HELD IN PLACE WITH BOLSTERS, CHAIRS, AND SPACERS AS REQUIRED TO ENSURE POSITIONS AND CONCRETE COVER AS INDICATED ON THE
DRAWINGS
9. PLACE TWO #4 X 5' - 0" LONG BARS, CENTERED IN SLAB & WALL, AT EACH CORNER OF ALL OPENINGS
GENERAL NOTES:
FOUNDATIONS
1. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL INVESTIGATION PREPARED BY TERRACON, PROJECT NO. 06265018-01 DATED APRIL 9, 2026
2.NET ALLOWABLE DESIGN SOIL BEARING PRESSURE = 1000 PSF
3. MINIMUM FROST PROTECTION DEPTH FOR THE BASE OF FOUNDATIONS SHALL BE 3' - 6" BELOW GRADE ELEVATION
4. FOUNDATIONS SHALL BE CARRIED TO LOWER ELEVATIONS THAN THOSE SHOWN ON THE DRAWINGS IF FIELD CONDITIONS OBSERVED BY THE GEOTECHNICAL ENGINEER OR TESTING LAB REVEAL SOILS NOT CAPABLE OF PROVIDING THE DESIGN ALLOWABLE SOIL BEARING PRESSURE. IF THIS CONDITION OCCURS, CONSULT WITH ENGINEER FOR CHANGES TO DESIGNED FOUNDATIONS
5. ALL SUBGRADE SHALL BE PREPARED AND COMPACTED ACCORDING TO THE RECOMMENDATIONS IN THE GEOTECHNICAL REPORT. IF ADDITIONAL PROBING OR TESTING IS REQUIRED, THE TESTING SHALL BE CONDUCTED BY THE GEOTECHNICAL ENGINEER DURING CONSTRUCTION TO VERIFY THAT SOIL CONDITIONS CONFORM WITH THE ASSUMPTIONS USED WHEN ESTABLISHING THE ALLOWABLE BEARING
PRESSURES
GENERAL STRUCTURAL NOTES
1. ALL WORK SHALL CONFORM TO ALL APPLICABLE BUILDING CODES, ORDINANCES, AND REGULATIONS AS ADOPTED BY LOCAL AUTHORITIES
HAVING JURISDICTIONS
2. ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR: CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF
ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS
3. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS, DIMENSIONS, AND ELEVATIONS AT THE SITE. IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN ON CONTRACT DOCUMENTS, CONSTRUCTION OF ANY AFFECTED ELEMENTS SHALL NOT COMMENCE WITHOUT APPROVAL OF
DESIGN ENGINEER
4. THE LOCATION OF ANY EXISTING UTILITIES SHOWN ON THE DRAWINGS ARE TAKEN FROM EXISTING RECORDS. ADDITIONAL UTILITIES MAY BE ENCOUNTERED DURING CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UTILITIES WHICH COME IN
CONFLICT WITH THE PROPOSED CONSTRUCTION
5. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST TO THE DESIGN ENGINEER FOR APPROVAL BEFORE PROCEEDING WITH ANY
CHANGES, MODIFICATIONS OR SUBSTITUTIONS DIFFERING FROM CONTRACT DOCUMENTS
6. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SHORING AND BRACING FOR ALL STRUCTURAL ELEMENTS UNTIL THE ENTIRE
STRUCTURAL SYSTEM IS PLUMB AND SECURED
7. THE CONTRACTOR SHALL VERIFY THE POSITION, ELEVATION, AND ORIENTATION OF PROCESS EQUIPMENT PRIOR TO FABRICATION. THIS INCLUDES ANCHOR BOLT SIZES AND LOCATIONS, FLOOR PENETRATIONS, AND REQUIRED CLEARANCES TO ADJACENT WALLS, FRAMING, AND
OTHER OBSTRUCTIONS
8. WHERE NEW CONSTRUCTION INTERFACES WITH EXISTING, FIELD VERIFY EXISTING DIMENSIONS, MEMBER SIZES, AND ELEVATIONS SHOWN ON THE DRAWINGS PRIOR TO STARTING CONSTRUCTION. ALL DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE
DESIGN ENGINEER.
9. DO NOT SCALE DIMENSIONS FROM DRAWINGS. INTERPRETATION OF PLANS, DETAILS, DIMENSIONS, OR OTHER ITEMS PROVIDED IN THE
CONTRACT DOCUMENTS ARE TO BE COMPLETED BY THE DESIGN ENGINEER
10. DETAILED SHOP DRAWINGS SHALL BE SUBMITTED FOR APPROVAL, BY THE OWNER AND DESIGN ENGINEER, PRIOR TO FABRICATION FOR ALL STRUCTURAL ITEMS INCLUDING: CONCRETE AND MASONRY REINFORCEMENT, EMBEDDED STEEL ITEMS, STRUCTURAL STEEL, STEEL
STACKS, STEEL JOISTS, STEEL DECKING, METAL GRATING, GUARDRAILS AND STAIRS
11. ALL OPEN EXCAVATIONS SHALL CONFORM TO OSHA STANDARDS FOR THE CONSTRUCTION INDUSTRY
12. WHERE APPLICATION IS MADE TO THE BUILDING OFFICIAL FOR CONSTRUCTION, THE OWNER SHALL EMPLOY A SPECIAL INSPECTOR TO PROVIDE INSPECTIONS AND TESTS PER THE REQUIREMENTS OF CHAPTER 17 OF THE IBC UNLESS WAIVED BY THE BUILDING OFFICIAL
13. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF DETERMINING IF WORK IS PROCEEDING IN ACCORDANCE WITH STRUCTURAL CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OF WORK, BUT RATHER AS PERIODIC IN AN EFFORT TO REVIEW THE PROGRESS OF THE
CONTRACTOR
10. PROVIDE CORNER BARS AT INTERSECTIONS OF ALL WALLS AND CURBS FOR CONTINUITY OF HORIZONTAL REINFORCING. CORNER BAR SIZE SHALL MATCH THE HORIZONTAL BARS AND LAP THE MAIN BARS BY AT LEAST 30 BAR DIAMETERS
11. ROUGHEN ALL CONSTRUCTION JOINTS TO AN AMPLITUDE OF AT LEAST 1/4" AND APPLY A BONDING AGENT SUBMITTED TO AND APPROVED
BY DESIGN ENGINEER
12. CONTRACTOR SHALL PROVIDE NECESSARY CONSTRUCTION JOINTS IN MONOLITHIC CONCRETE POURS SO THAT THE QUALITY OF PLACEMENT AND FINISH MEETS THE REQUIREMENTS OF PLANS AND SPECIFICATIONS. CONTROL JOINTS IN CONCRETE FOUNDATION WALLS SHALL BE SPACED AT 20' - 0" ON CENTER MAX. CONSTRUCTION JOINTS SHALL BE PLACED AT 100' - 0" ON CENTER MAX.
13. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS
14. ALL VERTICAL CONSTRUCTION JOINTS IN SLABS AND BEAMS SHALL BE MADE WITH BULKHEADS. ADDITIONAL REINFORCING AT CONSTRUCTION JOINTS SHALL BE AS SPECIFIED BY THE STRUCTURAL ENGINEER. REFER TO TYPICAL CONSTRUCTION JOINT DETAILS IN
CONTRACT DOCUMENTS
15. SLAB ON GRADE SHALL BE SUPPORTED ON CONTROLLED BACKFILL MATERIAL. WHERE FILL IS REQUIRED IT SHALL BE PLACED IN 9" LOOSE LIFTS AND COMPACTED TO AT LEAST 95% OF THE MATERIALS MAXIMUM STANDARD PROCTOR DRY DENSITY (ASTM D698). THE TOP 6"
OF MATERIAL BELOW SLABS SHALL BE COMPACTED GRANULAR BACKFILL
16. SAW CUT CONTROL JOINTS IN ALL SLABS-ON-GRADE. JOINTS SHALL BE LOCATED ALONG COLUMN LINES WITH INTERMEDIATE JOINTS SPACED AT A MAXIMUM OF 30 TIMES THE SLAB THICKNESS, LIMITED TO 15 FEET MAXIMUM, U.N.O. JOINTS SHALL BE CONTINUOUS, NOT STAGGERED OR OFFSET. SLAB PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5 TO 1. PROVIDE ADDITIONAL JOINTS AT ALL
RE-ENTRANT CORNERS FORMED IN THE SLAB
17. SAW CUT JOINTS WITHOUT TEARING THE AGGREGATE FROM THE SLAB SURFACE. SAW CUT WITHIN 4 TO 12 HOURS BUT NO LATER THAN 12 HOURS AFTER CONCRETE PLACEMENT. SAW CUT DEPTH TO BE 1/4 THE THICKNESS OF THE SLAB BUT NOT LESS THAN 1 INCH, U.N.O.
18. CONTINUOUS TOP AND BOTTOM HORIZONTAL BARS IN WALLS AND GRADE BEAMS SHALL BE SPLICED AS FOLLOWS:
TOP BARS - AT MIDSPAN
BOTTOM BARS - OVER SUPPORTS
GRADE BEAM SIDE BARS - OVER SUPPORTS
WALL AND BEAM SIDE BARS - AT MIDSPAN
19. FOUNDATION FOR FLAT BOTTOM STORAGE TANKS SHALL MEET THE FOLLOWING TOLERANCES PER AMERICAN PETROLEUM INSTITUTE
STANDARD 650:
A. WHERE A CONCRETE RINGWALL IS PROVIDED UNDER THE TANK SHELL, THE TOP OF THE
RINGWALL SHALL BE LEVEL WITHIN 1/8" IN ANY 30 FT OF THE CIRCUMFERENCE AND WITHIN
1/4" IN THE TOTAL CIRCUMFERENCE MEASURED FROM THE AVERAGE ELEVATION
B. WHERE A CONCRETE SLAB FOUNDATION IS PROVIDED, THE FIRST 1 FT OF THE FOUNDATION, MEASURED FROM THE OUTSIDE OF THE TANK RADIALLY TOWARDS THE CENTER, SHALL
COMPLY WITH THE CONCRETE RINGWALL REQUIREMENT. THE REMAINDER OF THE
FOUNDATION SHALL BE WITHIN 1/2" OF THE DESIGN SHAPE
20. WATERSTOP SHALL BE 4" THERMOPLASTIC ELASTOMERIC WESTEC ENVIROSTOP PROFILE #618, OR APPROVED EQUAL. PROVIDE
FACTORY FABRICATED CORNER PIECES.
21. ALL AREAS SUBJECT TO HYDROSTATIC PRESSURE EITHER FROM CONTAINED WATER AND/OR FROM GROUND WATER SHALL BE CONSTRUCTED WITH A CONCRETE MIX CONTAINING XYPEX CRYSTALLINE TECHNOLOGY ADMIX PER MANUFACTURERS RECOMMENDATIONS.
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Pl ot
D at e
Ti m e:
Drawing Name:
info@kclengineering.com
2180 Norcor Ave, Suites 208/209 Coralville, IA 52241 319-774-3852
SHPE PROJECT NO.
Shoemaker Haaland www.shoemaker-haaland.com
4/
/2
2:
:5
PM
S000
04/29/26
26027
GENERAL NOTES
D O
C
M T
PL
EA
SA
N
T C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
25457
M
PC
F D
IE
SE
L
TA
N
KS
R
EP
LA
C
EM
EN
T
SP
IL
L C
O N
TA
IN
M
EN
T
# Revision Date
0 100% CD 04/29/26
Date: 04/29/26
109' - 7"
PARKING BLOCK (E)
EL. 715' - 9 1/2"
T/ SLAB (E)BUILDING (E)
DUMPSTER (E)
TANK (E)
TANK (E)
TANK (E)
TANK (E)
3 7 /8"
1 1 /2"
4'
- 6
DEMO SUPPORT PIER (E) AND ANY
FOUNDATIONS BELOW GRADE (TYP.)
44' - 1" 10' - 7 3/4" 10' - 5 7/8"
DEMO EXISTING
DIESEL TANK
DEMO EXISTING
DIESEL TANK
DEMO EXISTING
DIESEL TANK
DEMO EXISTING
DIESEL TANK
FOOTINGS ARE ASSUMED TO BE 1' - 6" THICK
w/ T/ FOOTING 3' - 6" BELOW GRADE
5' - 0" 5' - 0"
12' - 0"
26' - 2"
5' - 0" 5' - 0" 5' - 0"
NOTE: ACTUAL FOOTING SIZE, THICKNESS, AND ELEVATION IS UNKNOWN.
DIMENSIONS SHOWN ARE BASED ON ASSUMED WEIGHT & SOIL BEARING PRESSURE
38' - 4"
PARKING BLOCK (E)
EL. 715' - 9 1/2"
T/ SLAB (E)
BUILDING (E)
DUMPSTER (E)
CL PIER
C L
TA
NK
P
IE
R
10' - 0" 10' - 0" 35' - 7"
0"
S100
3(3 LOC.)
CL PIERCL PIER
EL. 709' - 6"
T/ FOOTING
4' - 0" SQ. X 6" THICK PAD w/ #4 @ 12" O.C.
EACH WAY CENTERED IN SLAB; LOCATION
& ELEVATION TO BE FIELD VERIFIED
T/ PIER
EL. 713' - 0"
3/4" CHAMFERED
EDGE, TYP.
GRADE SEE
CIVIL DRAWINGS
ANCHOR RODS, SEE PLAN
2" GROUT, TYP.
T/ FOOTING
EL. 709' - 6"
S100
1'
- 6
3" C
LR
3" CLR.
1' - 0" 12' - 0" 1' - 0"
14' - 0"
2" C
LR
TANK
TIES AND VERT. BARS
SEE PIER PLAN FOR SIZE
#7 @ 1' - 0" O.C.
EACH WAY T+B
3'
- 6
" M
IN
(2)
2- 1/2
1'
- 0
" T
YP
COMPACTED GRANULAR FILL
PER GEOTECHNICAL REPORT
1'
- 6
EM
BE
DM
EN
T
6"
TH
RE
AD
ED
PR
OJ
EC
TIO
N
NUT
ASTM F1554 HOT
ROLLED BAR, SEE
LAYOUT FOR DIAMETER
T/ CONCRETE
TACK
T/ PIER
EL. 713' - 0"
T/ FOOTING
EL. 709' - 6"
(2)
1/2
1'
- 0 " T
YP
2' - 0" 2' - 0" 2' - 0"
6' - 0" 3"
C
LR
2"
C
LR
1'
- 6
COMPACTED GRANULAR FILL
PER GEOTECHNICAL REPORT
GRADE SEE
CIVIL DRAWINGS
ANCHOR RODS, SEE PLAN
2" GROUT, TYP.4
S100
3/4" CHAMFERED EDGE, TYP.
TIES AND VERT. BARS
SEE PIER PLAN FOR SIZE
#7 @ 1' - 0" O.C.
EACH WAY T+B 3" CLR.
3'
- 6
" M
IN
S100
S100
1'
- 0
6'
- 0
6'
- 0
1'
- 0
EL. 713' - 0"
T/ PIER (TYP.)
6' - 0"
7'
- 0
7'
- 0
EL. 709' - 6"
T/ FOOTING (TYP.)
(3 LOC.)
(3 LOC.)
(4) 1" Ø ANCHORS SEE
DETAIL
#4 TIES
#7 VERT. @ 1' - 0" O.C.
AROUND PERIMETER
3' - 0" 3' - 0"
2' - 0" 1' - 0" 1' - 0" 2' - 0"
CL PIER
0" C L
PI
ER
/6 S100
L6X4X5/16 X 0' - 3"
(1) 5/8"Ø ADHESIVE
ANCHOR & WASHER
LADDER PROVIDED w/ TANK;
INSIDE FACE OF LADDER RAIL
BASE CONNECTION AT CONCRETE
CONCRETE SLAB
1 1 /2"
1/2
1"
1 1 /2"
1 1 /2"
3/4" Ø BOLT IN 3" LONG SLOT;
FIELD DRILL HOLE IN LADDER
NOTE: TANK FOUNDATION SPACING & ANCHOR ROD REQUIREMENTS TO
BE VERIFIED BY EOR w/ FINAL TANK DRAWING PRIOR TO CONSTRUCTIO N
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Pl ot
D at e
Ti m e:
Drawing Name:
info@kclengineering.com
2180 Norcor Ave, Suites 208/209 Coralville, IA 52241 319-774-3852
SHPE PROJECT NO.
Shoemaker Haaland www.shoemaker-haaland.com
4/
/2
2:
:5
PM
S100
04/29/26
26027
DEMO PLAN,
FOUNDATION PLAN
AND DETAILS
D O
C
M T
PL
EA
SA
N
T C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
25457
M
PC
F D
IE
SE
L
TA
N
KS
R
EP
LA
C
EM
EN
T
SP
IL
L C
O N
TA
IN
M
EN
T
1/8" = 1'-0"1 EXISTING TANK DEMO PLAN
1/8" = 1'-0"2 FOUNDATION PLAN
1/2" = 1'-0"4 TANK PIER ELEVATION
1 1/2" = 1'-0"6 TYPICAL ANCHOR ROD DETAIL
N
1/2" = 1'-0"5 TANK PIER SECTION
1/2" = 1'-0"3 ENLARGED TANK PIER PLAN
N
# Revision Date
0 100% CD 04/29/26
1" = 1'-0"7 LADDER BASE CONNECTION
Date: 04/29/26
NEW CONNECTION POINT
POINT OF DISCONNECT
EQUIPMENT IDENTIFICATION TAG
SHEET REFERENCE
SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
EXISTING = HALFTONE LINEWORK
NEW = DARK LINEWORK
DEMO = DASHED DARK LINEWORK
KEYNOTE
GENERAL SYMBOLS
SHEET REFERENCE
DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
A101
SIM
INTERIOR ELEVATION DRAWING REFERENCE TAG
BELOW GRADE = LONG DASHED DARK LINEWORK
A101 1
R e f
XXX
X
A101
SIM
1. MECHANICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN
PREPARED BASED ON NON-DESTRUCTIVE FIELD OBSERVATION AND AS-BUILT DRAWINGS
PROVIDED BY THE OWNER. FIELD VERIFY EXISTING SYSTEMS BEFORE BEGINNING WORK.
NOTIFY ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE MATERIALLY DIFFERENT THAN
THOSE SHOWN ON THE PLANS.
2. BE FAMILIAR WITH EXISTING MECHANICAL SYSTEMS THAT WILL BE AFFECTED BY THE
DEMOLITION WORK. OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE TO SHUT
OFF SERVICES OR SYSTEMS THAT AFFECT AREAS BEYOND THE LIMITS OF THE IMMEDIATE
DEMOLITION AREA. INFORM THE OWNER’S REPRESENTATIVE OF THE REASON FOR AND
DURATION OF THE SHUTDOWN. MINIMIZE IMPACT TO OTHER AREAS. PROCEED WITH THE
SHUT-DOWN AFTER PERMISSION FROM THE OWNER IS GRANTED.
3. REMOVE PIPING, HANGERS, DUCTWORK, GRILLES, REGISTERS, DIFFUSERS, ETC. THAT ARE
INDICATED TO BE REMOVED IN A TIMELY MANNER IN ACCORDANCE WITH THE GENERAL
DEMOLITION SPECIFICATIONS. COORDINATE WITH THE OWNER AND OTHER CONTRACTORS.
4. UNLESS EQUIPMENT TO BE REMOVED IS NOTED AS OWNER’S SALVAGE, DISPOSE OF
EQUIPMENT AND/OR MATERIALS INDICATED TO BE REMOVED PROMPTLY.
5. REMOVE ALL ABANDONED PIPING AND DUCTWORK THAT IS EXPOSED OR ACCESSIBLE
WITHOUT WALL OR CEILING DEMOLITION. REFER TO ARCH PLANS FOR CEILINGS TO BE
REMOVED.
6. REPAIR OR REPLACE TELECOMMUNICATIONS FACILITIES OR EQUIPMENT FOUND TO BE
DAMAGED OR NON-FUNCTIONAL AFTER SUBSTANTIAL COMPLETION.
MECHANICAL – DEMOLITION NOTES
ABSOR
ACU
AD
AFF
AFG
AHU
AV
BOT
BTU
BTUH
BV
CA
CB
CENT
CFM
CI
CL
COND
CO
CONC
CONTR
CP
CU
CUH
CWP
DDC
DN
DR
DS
EA
EAT
EC
EDBT
EEW
EF
EJ
EQUIP
ESE
EST
EWBT
EWC
EWT
EX
EXH
EXP
FAI
FCU
FD
FDC
FLEX
FLR
FPM
FPS
FS
FSEC
FT
FTG
GA
GAL
GALV
GC
GW
GPH
GPM
HR
HTG
HB
ISP
JR
LAV
LDBT
LWT
LWBT
MB
MBH
MC
MECH
MH
NTS
OA
OD
PC
PSI
PRV
PRV
PV
PVC
RA
RD
RH
RTU
RV
RVT
SK
SA
SH
SO
ST
TCC
TYP
UH
UR
UV
VA
VTR
WB
WC
WHA
WH
ABSORPTION
AIR CONDITIONING UNIT
ACCESS DOOR OR AREA DRAIN
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AIR VENT
BOTTOM
BRITISH THERMAL UNIT
BTU PER HOUR
BALL VALVE
COMPRESSED AIR
CATCH BASIN
CENTRIFUGAL
CUBIC FEET PER MINUTE
CAST IRON
CENTER LINE
CONDENSATE
CLEAN OUT
CONCRETE
CONTRACTOR
CONDENSATE PUMP/CIRC. PUMP
COPPER
CABINET UNIT HEATER
CIRCULATING WATER PUMP
DIRECT DIGITAL CONTROLS
DOWN
DRAIN
DOWNSPOUT
EXHAUST AIR
EXHAUST AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING DRY BULB
TEMPERATURE
EMERGENCY EYE WASH
EXHAUST FAN
EXPANSION JOINT
EQUIPMENT
EMERGENCY SHOWER/EYEWASH
EXTERNAL STATIC PRESSURE
ENTERING WET BULB
TEMPERATURE
ELECTRIC WATER COOLER
ENTERING WATER
TEMPERATURE
EXISTING
EXHAUST
EXPANSION
FRESH AIR INTAKE
FAN COIL UNIT
FLOOR DRAIN
FIRE DEPARTMENT CONNECTION
FLEXIBLE
FLOOR
FEET PER MINUTE
FEET PER SECOND
FLOOR SINK
FOOD SERVICE EQUIPMENT CONSULTANT
FINTUBE
FOOTING
GAGE
GALLON
GALVANIZED
GENERAL CONTRACTOR
GREASE WASTE
GALLONS PER HOUR
GALLONS PER MINUTE
HOUR
HEATING
HOSE BIBB
INTERNAL STATIC PRESSURE
JANITOR RECEPTOR
LAVATORY
LEAVING DRY BULB
TEMPERATURE
LEAVING WATER
TEMPERATURE
LEAVING WET BULB
TEMPERATURE
MOP BASIN
1000 BTUH
MECHANICAL CONTRACTOR
MECHANICAL
MANHOLE
NOT TO SCALE
OUTSIDE AIR
OVERFLOW ROOF DRAIN
PLUMBING CONTRACTOR
POUNDS PER SQUARE INCH
POWER ROOF VENTILATOR
PRESSURE REDUCING VALVE
PRESSURE VENT
POLYVINYL CHLORIDE
RETURN AIR
ROOF DRAIN
RELATIVE HUMIDITY
ROOF TOP UNIT
RELIEF VALVE
ROOF VENT TERMINATION
SINK
SUPPLY AIR
SHOWER
STORM OVERFLOW
STORM
TEMPERATURE CONTROL
CONTRACTOR
TYPICAL
UNIT HEATER
URINAL
UNIT VENTILATOR
VENTILATION AIR
VENT THROUGH ROOF
WALL BOX – CONDENSATE
WATER CLOSET
WATER HAMMER ARRESTOR
WATER HEATER
MECHANICAL ABBREVIATIONS
45° ELBOW
ELBOW
PIPE FITTINGS
SINGLE LINE DOUBLE LINE
ELBOW - DOUBLE BRANCH
ELBOW - OUTLET DOWN
ELBOW - OUTLET UP
ELBOW - LONG RADIUS
ELBOW - SHORT RADIUS
TEE - VENT
TEE - SANITARY
TEE - OUTLET DOWN
TEE - OUTLET UP
TEE - SIDE OUTLET DOWN
TEE - SIDE OUTLET UP
CROSS - VENT
CROSS - SANITARY
LATERAL
TEE - SINGLE SWEEP
"COMBO WYE"
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
CAPPED CONNECTION
FLANGED CONNECTION
45° ELBOW
ELBOW
ELBOW - DOUBLE BRANCH
ELBOW - OUTLET DOWN
ELBOW - OUTLET UP
ELBOW - LONG RADIUS
ELBOW - SHORT RADIUS
TEE - VENT
TEE - SANITARY
TEE - OUTLET DOWN
TEE - OUTLET UP
TEE - SIDE OUTLET DOWN
TEE - SIDE OUTLET UP
CROSS - VENT
CROSS - SANITARY
LATERAL
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
CAPPED CONNECTION
FLANGED CONNECTION
TEE - SINGLE SWEEP
"COMBO WYE"
ACID VENT
ACID WASTE
COMPRESSED AIR
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC SOFT WATER
GREASE WASTE
NATURAL GAS
NON-POTABLE COLD WATER
NON-POTABLE HOT WATER
NON-POTABLE SOFT WATER
OIL / SAND WASTE
PUMPED DISCHARGE
RECIRCULATING HOT WATER
SANITARY
STORM
STORM OVERFLOW
VENT
PROCESSED AIR
TRAP PRIMER
NATURAL GAS VENT
PROPANE
AV
AW
CA
CW
HW
DSW
GW
G
NPCW
NPHW
NPSW
OSW
PD
RHW
SAN
ST
SO
V
PA
P
GV
LP
PIPING LEGEND - PLUMBING
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIN
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
HIGH PRESSURE STEAM
HOT/CHILLED WATER RETURN
HOT/CHILLED WATER SUPPLY
HYDRONIC RETURN
HYDRONIC SUPPLY
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
REFRIGERANT GAS
REFRIGERANT LIQUID
PUMPED CONDENSATE
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL VENT
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT HOT GAS
BOILER BLOWDOWN
BOILER FEED
LOW PRESSURE STEAM CONDENSATE
MEDIUM PRESSURE STEAM CONDENSATE
HIGH PRESSURE STEAM CONDENSATE
CWR
CWS
CD
HPWR
HPWS
HPS
HCR
HCS
HWR
HWS
LPS
MPS
RS
RL
PC
FOR
FOS
FOV
CR
CS
RHG
BD
BF
LPC
MPC
HPC
PIPING LEGEND - MECHANICAL
LOOP WATER RETURN
LOOP WATER SUPPLY
LWR
LWS
EXHAUST PIPE - PVCEA
1. COORDINATE MECHANICAL AND ELECTRICAL WORK WITH ALL OTHER TRADES. BEGIN
INSTALLATION AND ROUGH-IN AFTER COORDINATION WITH ALL TRADES ASSOCIATED WITH
THE INSTALLATION IS COMPLETE. COORDINATE BUILDING STRUCTURE, ARCHITECTURAL
ASSEMBLIES, SHEET METAL, ALL PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE
TRAYS, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR REWORK
ASSOCIATED WITH FAILURE TO COORDINATE.
2. INCORPORATE MECHANICAL SPECIFICATIONS, DRAWINGS, STATE AND LOCAL CODES, AND
OWNER STANDARDS INTO WORK.
3. WARNING - CALL 48 HOURS BEFORE YOU DIG: LAW REQUIRES ANYONE DOING ANY
EXCAVATION, FENCING, PLANTING OR DRILLING TO CALL 48 HOURS IN ADVANCE. HAND DIG
WITHIN 18 INCHES OF ANY LOCATE MARK OR FLAG. ONE CALL 811.
4. REFER TO ARCHITECTURAL SPECIFICATIONS FOR THROUGH-PENETRATION FIRESTOPPING
AND TO ARCHITECTURAL CODE PLAN FOR FIRE RATED WALLS, FLOORS, AND CEILINGS. EACH
TRADE IS RESPONSIBLE TO FIRESTOP PENETRATIONS THROUGH RATED ASSEMBLIES.
5. EACH TRADE IS RESPONSIBLE FOR MAKING PENETRATIONS WHERE REQUIRED IN EXISTING
WALLS, FLOORS, CEILINGS, AND ROOFS. MAKE PENETRATIONS NEAT. PATCH, CONCEAL, OR
CAULK OVERCUT.
6. COVER EXPOSED WALL PENETRATIONS WITH ESCUTCHEONS OR SHEET METAL AS
APPROPRIATE.
7. CAULK ALL CONCEALED AND EXPOSED PIPING AND DUCT WALL PENETRATIONS TO PREVENT
NOISE TRANSFER BETWEEN SPACES.
8. CREATE OPENINGS IN THE BUILDING THAT ARE REQUIRED TO REMOVE EXISTING ITEMS AND
TO BRING IN NEW EQUIPMENT. PATCH ALL OPENINGS CREATED AND FINISHED WITH
MATERIALS TO MATCH EXISTING CONDITIONS. INCLUDE THIS WORK IN BID.
9. ON COMPLETION OF THE INSTALLATION, COOPERATE WITH THE OWNER TO PROVIDE
TESTING, ADJUSTING, AND BALANCING TO OBTAIN PROPER OPERATION OF ALL EQUIPMENT
AND SYSTEMS. PROVIDE ALL FACILITIES AND EQUIPMENT AND COMPLETE ALL TESTS
REQUIRED FOR ADJUSTMENTS AND BALANCING TO ESTABLISH THE PROPER PERFORMANCE
OF EQUIPMENT. CONTRACTOR IS REQUIRED TO PROVIDE TESTING REQUIREMENTS AND
INCLUDE 2,000 GALLONS OF DIESEL FOR PLANT USE AT END OF TESTING.
10. PROVIDE WARRANTIES FOR ALL EQUIPMENT AND INSTALLATION PER THE CONTRACT
DOCUMENTS. CONDITIONING REFRIGERATION SYSTEMS SHALL BE WARRANTED FOR A
MINIMUM OF 5 YEARS, PARTS ONLY, NON-PRORATED, FROM THE DATE OF OCCUPANCY OR
SUBSTANTIAL COMPLETION, OR WHICHEVER OCCURS FIRST. THE WARRANTY SHALL COVER
COMPRESSORS, EVAPORATORS, CONDENSER COILS, HIGH AND LOW SIDE PIPING, AND
PIPING SPECIALTIES INCLUDING EXPANSION AND SOLENOID VALVES, RELIEF VALVES, FILTER-
DRYER, AND SIGHT GLASSES. PRESSURE GAUGES AND PRESSURE SWITCHES ARE NOT
UNDER THE EXTENDED WARRANTY EXCEPT FOR LOSS OF REFRIGERANT AND
CONSEQUENTIAL DAMAGE TO THE SYSTEM WHICH WILL BE AN EXTENDED WARRANTY
OBLIGATION. ALL DEFECTS THAT BECOME APPARENT WITHIN THE WARRANTY PERIOD SHALL
BE REPAIRED BY THE MECHANICAL CONTRACTOR AS DIRECTED BY THE ENGINEER THROUGH
THE OWNER’S REPRESENTATIVE. WARRANTY DOES NOT OBLIGATE THE MECHANICAL
CONTRACTOR TO REPAIR DAMAGE RESULTING FROM THE OWNER’S ACCIDENT, IMPROPER
OPERATION, OR FAILURE TO PROVIDE MAINTENANCE. WARRANTY COVERS DEFECTIVE
MATERIAL AND INSTALLATION. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS AND
OTHER WARRANTY INFORMATION.
MECHANICAL - GENERAL NOTES
GENERAL NOTE:
UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES HAVE BEEN SHOWN BASED UPON
INFORMATION OBTAINED FROM FIELD LOCATIONS BY UTILITY COMPANIES, AVAILABLE SURVEYS
AND RECORDS. THEIR LOCATIONS MUST BE CONSIDERED APPROXIMATE ONLY. IT IS ALSO
POSSIBLE THAT THERE MAY BE OTHER UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES IN
EXISTENCE THAT ARE NOT SHOWN. IT IS THE RESPONSIBILITY OF EACH INDIVIDUAL PARTY
REFERENCING THIS PLAN TO DETERMINE THE EXACT LOCATION AND TYPE OF UNDERGROUND
FACILITIES ON THE SITE. HAND EXCAVATE AT CRITICAL POINTS AS NECESSARY TO VERIFY
LOCATIONS, SIZES, ELEVATIONS, FLOW LINES, ETC. IF A PROBLEM OR INTERFERENCE EXISTS, NOTIFY ARCHITECT/ENGINEER BEFORE PROCEEDING.
IOWA
ONE CALL
1-800-292-8989
CALL - BEFORE - YOU - DIG
**NOTE: ALL SYMBOLS MAY NOT APPLY TO THIS PROJECT**
CLEAN OUT
HOSE BIBB
FLOOR CLEAN OUT
HB
CO
FCO
ROOF HYDRANTRH
BACKFLOW PREVENTER
PLUMBING ACCESSORY LEGEND
VALVE - BALL / SHUT-OFF
LEVEL TRANSMITTERLT
LEVEL SWITCH HIGHLSH
LEVEL SWITCH HIGH-HIGHLSHH
LEVEL DETECTION ALARMLDA
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
P lo t D a te
T im e
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
/2
/2
:2 :5
P
M
M000
02/20/2026
26027
D O
C M
P C
F D
IE
S
E L
T A
N K
S R
E P
L A
C E
M E
N T
S
P
IL
L C
O N
T A
IN
M
E N
T M
T
P L E
A S
A N
T C
O R
R E
C T
IO
N
A L
F A
C
IL
IT
Y
MECHANICAL
GENERAL NOTES &
SYMBOLS
# Revision Date
100% CD 04/27/2026
Date: 04/29/26
DEMO EXISTING DIESEL TANKS 1 THRU 4
AND PIPING, ASSOCIATED CONCRETE
STANDS AND FOUNDATIONS. REFER
STRUCTURAL SET FOR ADDITIONAL
DETAILS.
REMOVE EXISTING CATWALK PLATFORM
AND STAIRS COMPLETELY.
PLANT BASEMENT ROOF
(BUNKER BUILDING)
TANK 1
TANK 2
TANK 3
TANK 4
NEW DIESEL TANK 1
PLANT BASEMENT ROOF
(BUNKER BUILDING)
FILL CONTROL PANEL
DIESEL TANK FILL LINE
SUPPLY AND
RETURN PIPING
CONNECT TO EXISTING
PLANT HEADER PIPING
27' - 7"
M A
IN
T
A
IN
M
IN
IU
M
O F
F R
O M
B U
N K
E R
B U
IL
D
IN
G
36' - 0"
B U
IL
D
IN
G
S
O U
T H
B U
IL
D
IN
G
N O
T S
H O
W N
M A
IN
T
A
IN
M
IN
U M
N O
F
F
R O
M S
O U
T H
MANHOLE
LADDER PLATFORM ABOVE TANK
PROVIDE PIPE SUPPORTS
FOR PIPING ABOVE GRADE.
REFER TO DETAIL: 3/M100
38' - 0"
TEMP
TANK
(5000
GALLONS)
A. REFER TO M000 FOR GENERAL NOTES & SYMBOLS.
B. REFER TO M500 FOR PIPING SCHEDULES.
C. BRANCH PIPING SHALL BE TAKEN OFF THE TOP OF MAIN PIPING.
GENERAL NOTES:
(M
IN
GRADE
3/4" BOLT (TYP OF 4)
12" ⌀ CONCRETE
6"x6"x2" GROUT PAD
6"x6"x2" GROUT PAD
2"x2"x1/4" CS STRUCTURAL TUBING
U-BOLT PIPE
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
P lo t D a te
T im e
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
/2
/2
:2 :5
P
M
M100
09/02/21
26027
D O
C M
P C
F D
IE
S
E L
T A
N K
S R
E P
L A
C E
M E
N T
S
P
IL
L C
O N
T A
IN
M
E N
T M
T
P L E
A S
A N
T C
O R
R E
C T
IO
N
A L
F A
C
IL
IT
Y
MECHANICAL PLAN
1/8" = 1'-0"
MECHANICAL PIPING DEMO
1/8" = 1'-0"
MECHANICAL PIPING PLAN
# Revision Date
100% CD 04/27/2026
NTS
PIPE SUPPORT DETAIL
Date: 04/29/26
TANK 1 TANK 2 TANK 3 TANK 4
PLANT HEADER
PLANT HEADER WALL
NEW DIESEL
TANK 1
LDA
LSH
LSHH
90%
95%
INTERSTITIAL
LEAK DETECTION
LT
FILL CONNECTION
VTAVTA
NORMAL VENT
EMERGENCY VENT
AUTOMATIC SHUTOFF VALVE
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
P lo t D a te
T im e
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
/2
/2
:2 :5
P
M
M300
09/02/21
26027
D O
C M
P C
F D
IE
S
E L
T A
N K
S R
E P
L A
C E
M E
N T
S
P
IL
L C
O N
T A
IN
M
E N
T M
T
P L E
A S
A N
T C
O R
R E
C T
IO
N
A L
F A
C
IL
IT
Y
MECHANICAL
SCHEMATIC
N.T.S.
DEMO SCHEMATIC
N.T.S.
NEW PIPING SCHEMATIC
# Revision Date
100% CD 04/27/2026
Date: 04/29/26
Drawing #:
Date:
Project No:
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
P lo t D a te
T im e
Drawing Name:
info@kclengineering.com
300 4th St West Des Moines, IA 50265 515-724-7938
/2
/2
:1 :2
P
M
M500
09/02/21
26027
D O
C M
P C
F D
IE
S
E L
T A
N K
S R
E P
L A
C E
M E
N T
S
P
IL
L C
O N
T A
IN
M
E N
T M
T
P L E
A S
A N
T C
O R
R E
C T
IO
N
A L
F A
C
IL
IT
Y
MECHANICAL
SCHEDULES TANK BID
DOCUMENTS
NOTES:
1. ALL THREADED PIPE SHALL BE SEAMLESS (TYPE S)
2. BRONZE BODY VALVES MAY BE USED FOR PIPE SIZES 1/4" - 2" IN LIEU OF SOCKET WELDED VALVES.
3. NO BACKING RING
VALVE SELECTION
BONNEY FORGE OR
EQUIVALENT
APOLLO OR EQUIVALENT JAMESBURY OR EQUAL
CONSTRUCTION
BODY: A106B
API TRIM 8
BALL VALVE
CONNECTION AND RATING
CLASS 800 SOCKETWELDED ENDS CLASS 150 FLANGED ENDS
PIPE SIZE (NPS) 2" AND SMALLER 2 1/2" AND LARGER
NG1
CARBON STEEL SEE RATING BELOW ASME B31.1 ASME B16.34
VALVE SPECIFICATION: SPECIFICATION MATERIAL:
PRESSURE CLASS: DESIGN CODE:
CARBON STEEL ASME B16.34 ASME B31.1 1 9/23/2025
PIPE MATERIAL: DESIGN/CONSTRUCTION CODE: REVISION: DATE REVISED:
THERMOWELLS: MATERIAL INSERTION THERMOWELLS - ASTM A105 - 3000 PSIG PRESSURE CLASS - SEAL WELDED WELLS
MATERIAL FLEXITALLIC STYLE CGI - TYPE 304 STAINLESS - FLEXICARB FILLER
GASKETS:
CONSTRUCTION SPIRAL WOUND - SUITABLE FOR RAISED-FACE OR FLAT-FACE FLANGES
WASHER: CONSTRUCTION F436
FLANGE NUTS: CONSTRUCTION HEAVY HEX - A194 GRADE 2H
FLANGE BOLTS:
CONSTRUCTION
ALLOY STEEL, AISI 4140/4142 QUENCHED AND TEMPERED, A193 GRADE B7, STUD - FULL LENGTH
MATERIAL FORGED CARBON STEEL - ASTM A105
WALL THICKNESS SAME AS ADJOINING PIPEFLANGES:
CONSTRUCTION CLASS 150 - WELD NECK - ASME B16.5
MATERIAL FORGED CARBON STEEL - ASTM A105 --
WALL THICKNESS SAME AS ADJOINING PIPE --
UNIONS:
CONSTRUCTION
CLASS 3000 - B16.11 - FLAT FACE WITH SPIRAL WOUND GASKET
DESIGN NOT PERMITTED
OTHER WHERE FLANGE REQUIRED WHERE FLANGE REQUIRED
PIPING JOINTS:
TYPE SOCKET WELDED (5) BUTTWELD - END PREP PER B16.25
MATERIAL SOCKET WELDED FITTING - ASTM A105 - SEAMLESS BUTTWELD FITTING - ASTM A234 GRADE B -...
WALL THICKNESS SAME AS ADJOINING PIPE SAME AS ADJOINING PIPEFITTINGS:
CONSTRUCTION CLASS 3000 - SOCKETWELD - B16.11 BUTTWELD - ASME B16.9 (3)
PIPE PIPE SIZE (NPS) 2" AND SMALLER 2 1/2" AND LARGER
ASME B36.10M MATERIAL ASTM A53 GRADE B, SEAMLESS
PIPE: WEIGHT/SCHEDULE XS SCH 40
PIPE SIZE (NPS) 2" AND SMALLER 2 1/2" AND LARGER
NG1 NATURAL GAS (150PSIG OR LESS) 150 PSIG AT 150°F
PIPING SPECIFICATION PROCESS: DESIGN CONDITIONS:
Location Outdoor installation
Installation Code NFPA 30 and adopted IFC
Listing UL 142 listed and labeled
Construction Double-wall steel
Capacity (Nominal) 20,000 gallons (Inside diameter of tank @ 10' dia x 34' long)
Tank Type Aboveground, Horizontal, Cylindrical
Application Backup fuel for central steam plant
Qty 1
Service No. 2 Diesel Fuel (Class II Combustible)
Item Specification / Requirement
General Information
Anchorage Provide anchor bolt reactions and recommendations
Foundation Loads Vendor to provide empty and full weights
Wind/Seismic Design ASCE 7 (Mt. Pleasant, Iowa)
Outer Tank Material Carbon steel secondary containment shell
Inner Tank Material ASTM A36 or ASTM A516 carbon steel
Corrosion Allowance Minimum 1/16 inch
Specific Gravity 0.85 (diesel typical)
Design Temperature -20°F to 120°F
Design Pressure Atmospheric
Item Specification / Requirement
Design Criteria
Grounding Lugs 2 required
Ladder and Platform See specification for requirements for integral ladder and platform
Painting and Coating Painting and Coating shall be to manufacturer's standard
Interstitial Leak Detection Continuous monitoring with alarm
High-High Shutdown 95% automatic fill shutdown device
High Level Alarm 90% capacity (local + remote alarm)
Level Transmitter 4–20 mA or Modbus output to DCS/BMS
Level Gauge Direct-reading, visible to delivery operator
Manway Minimum 24-inch diameter, top center of tank, provide a ladder into the tank
Drain Valved and capped; controlled discharge only
Return Inlet Sized per fuel demand (120 gpm); anti-siphon protection required
Supply Outlet Sized per fuel demand (120 gpm); anti-siphon protection required
Emergency Vent Sized per NFPA 30 and UL 142 listing
Normal Vent Sized per NFPA 30 and UL 142 listing
Fill Connection Lockable cap; size by vendor; spill containment provided
Item Specification / Requirement
Nozzles & Appurtenances
Labeling Diesel Fuel – Combustible; No Smoking signage
API 650 Alignment Vendor to state alignment with applicable API 650 provisions where not in conflict with UL 142
Secondary Containment Integral double wall; interstitial monitoring required
SPCC Applicability Evaluate per EPA 40 CFR 112
NEC Compliance Electrical classification per NFPA 70
NFPA 30 Compliance Overfill protection, venting, and installation per NFPA 30
UL Listing UL 142 certification required
Item Specification / Requirement
Codes & Regulatory Compliance
Inspection/Test Procedures Factory test documentation
Ladder and Platform Connection and Layout Details
Coating System Data Exterior coating and painting specifications
Foundation Load Data Empty and full tank weights
Overfill Protection Cut Sheet Alarm and shutoff documentation
Leak Detection Cut Sheet Manufacturer data and alarm details
Vent Sizing Documentation Normal and emergency vent basis
General Arrangement Drawing Dimensions, nozzle schedule, elevations
UL 142 Documentation Provide certificate and nameplate photo
Item Specification / Requirement
Required Vendor Submittals
DIESEL TANK SPECIFICATIONS
# Revision Date
100% CD 04/27/2026
Date: 04/29/26
W
EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE
DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
INTERIOR ELEVATION DRAWING REFERENCE TAG
GENERAL SYMBOLS
A101
SIM
A101 1
R e f
KEYNOTE#
XXX
X
SHEET REFERENCE
SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
SHEET REFERENCE
JUNCTION BOX, CEILING OR FLOOR MOUNTED.
JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.
J
J
A101
SIM
1 DRAWINGS REVISION. REFER TO TITLEBLOCK FOR REVISION NAME AND DATE
POWER SYMBOLS
DUPLEX GFCI RECEPTACLE, TAMPER-RESISTANT, WALL MOUNT,
"G" INDICATES PROTECTION INCLUDED IN DEVICE. SHADING INDICATES DEVICE
PROTECTED BY EITHER UPSTREAM GFCI DEVICE OR CIRCUIT BREAKER
DUPLEX GFCI WEATHER RESISTANT RECEPTACLE WITH WEATHER-PROOF
IN-USE COVER, TAMPER-RESISTANT, WALL MOUNT
EQUIPMENT CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
EQUIPMENT CONNECTION, WALL MOUNT,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
G
W
SAFETY DISCONNECT SWITCH
EMERGENCY PUSH BUTTON
PANELBOARD - SURFACE MOUNTED
PANELBOARD - RECESSED IN WALL
GENERATORGEN
MOTOR CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
M
ELECTRICAL ABBREVIATIONS
A DEVICE MOUNTED +8" ABOVE
COUNTER TOP (VERIFY LOCATION)
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
C CEILING
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
E EXISTING ITEM TO REMAIN
EC ELECTRICAL CONTRACTOR
EM EMERGENCY LIGHT FIXTURE
ER NEW LOCATION OF EXISTING ITEM
F ROUGH IN FOR FUTURE DEVICE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
G GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
KVA KILO-VOLT-AMPERES
KW KILOWATTS
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
N NEW DEVICE IN EXISTING LOCATION
NIC NOT IN CONTRACT
NM NONMETALLIC
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
R EXISTING ITEM TO BE REMOVED
RR EXISTING ITEM TO BE REMOVED AND
RELOCATED
RN EXISTING ITEM TO BE REMOVED AND
REPLACED WITH NEW
SCCR SHORT CIRCUIT CURRENT RATING
T TAMPER PROOF DEVICE
TCC TEMPERATURE CONTROL CONTRACTOR
TV TELEVISION
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
WG WIREGUARD COVER
WP WEATHERPROOF DEVICE
WR WEATHER RESISTANT DEVICE
XFR TRANSFORMER
+24" INDICATES MOUNTING HEIGHT CENTER
LINE OF DEVICE TO FINISHED FLOOR
1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL STATE CODES.
2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE
ELECTRICAL INSTALLATION. VERIFY WITH LOCAL OFFICIALS WHEN PERMITS ARE OBTAINED.
NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR
DRAWINGS AND THE GOVERNING CODE.
3. PER NEC EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO
ITS CLEAR, EVIDENT AND SPECIFIC PURPOSE OR USE. CONTRACTOR TO PROVIDE FINAL
CIRCUIT IDENTIFICATION FOR ALL NEW AND MODIFIED CIRCUITS AT PROJECT COMPLETION.
CODE NOTES - ELECTRICAL 1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.
2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.
DEVICE INSTALLATION AND MATERIALS - ELECTRICAL
1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL
OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY
COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.
COORDINATE WITH BUILDING STRUCTURE, ARCHITECTURE, MECHANICAL SHEET METAL, ALL
PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT
ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL
DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR
REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.
2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND
CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE
SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;
ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN
REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.
GENERAL NOTES - ELECTRICAL
1. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO
CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.
2. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL
AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER
OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF
INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.
3. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO
NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.
4. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND
EXISTING PANELS WITH CIRCUITS MODIFIED DURING PROJECT. USE OWNER’S CURRENT
ROOM NUMBERS AND EQUIPMENT NAMES. PROVIDE UNIQUE CIRCUIT IDENTIFICATION
PER NEC 408.4(A)
5. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND
ROOFS THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL
PENETRATIONS IN ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY.
REFER TO ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.
6. INSTALL NEW CONDUIT A MINIMUM OF 18" BELOW GRADE.
7. INSTALL CONDUIT AND PATHWAYS FROM CONTROL PANEL TO SENSORS AT TANKS.
COORDINATE INSTALLATION AND CONTROL LOCATIONS WITH MANUFACTURER AND
CONTRACTOR.
8. CONDUIT INSTALLATION TO TANK AREA TO BE INSTALLED TO MEET NEC CLASS 1
DIVISION 2 REQUIREMENTS. PROVIDE SEAL-OFFS AND INSTALL CONDUIT BELOW GRADE
TO MEET NEC REQUIREMENTS.
INSTALLATION NOTES - ELECTRICAL
NEW DIESEL TANK 1
PLANT BASEMENT ROOF
(BUNKER BUILDING)
FILL CONTROL PANEL
GENERATOR BUILDING
EXISTING PANEL PP-SG-1
UTILIZE (2) 120V 1P SPARE BREAKERS
IN SPACES 14 AND 16 IN PANEL.
EXISTING PANEL IS SQUARE D NQ.
INSTALL (1) 1" CONDUIT WITH #10
AWG CONDUCTORS USED FOR
BRANCH CIRCUITS TO FILL
CONTROL PANEL AND
RECEPTACLE CIRCUIT.
E000
INSTALL CONDUIT TO FLOOR AND CORE
THROUGH WALL. INSTALL "LB" ON EXTERIOR
TO TURN CONDUIT DOWN BELOW GRADE.
INSTALL IMC OR RMC CONDUIT ON EXPOSED
EXTERIOR TO MINIMIZE DAMAGE. AT CORE
INSTALL SILICONE CAULK ON BOTH SIDES
OF OPENING FOR PROPER SEAL.
INSTALL 10' X 5/8" ELECTRODE NEAR BASE
OF TANK. INSTALL #4 CU FROM TANK TO ELECTRODE.
CAD-WELD CONNECTIONS TO ELECTRODE.
INSTALL (1) 1" CONDUIT FROM CONTROL
PANEL TO TANK. CONDUIT USED FOR CONTROL
WIRING TO SENSORS ON TANK. INSTALL SEAL-OFFS
TO MEET CLASS 1 DIVISION 2 REQUIREMENTS.
COORDINATE LOCATIONS OF THE SENSORS
ON THE TANK WITH PROVIDER. INSTALL ALL CABLING
AND PATHWAYS NECESSARY FOR A FULLY
FUNCTIONAL SYSTEM.
1' - 0"
M A
X
SIDE ELEVATION FRONT ELEVATION
#3 ties @ 12" OC. TYP.
CONC. FOOTING. TYP
TAPE-WRAP 6" ABOVE GRADE
GALV 3" PIPE POST. TYP.
GRADE
1/2" HOT DIP
GALVANIZED THU
B…
This is the start of the file's text. The full file is on GovTribe.