RFB946300-01 - Project Manual.pdf

PDF 27 MB Posted

Attached to
Woodward Resource Center Birches Window Replacement
Solicitation number
RFB946300-01
Issued by
Dallas County, Iowa

About this file

Project Manual for RFB946300-01: Woodward Resource Center Birches Window Replacement

This project manual is a technical specification document prepared by Genesis Architectural Design for the Iowa Department of Administrative Services (IDAS) regarding the Birches building window replacement project at the Woodward Resource Center in Woodward, Iowa. The project involves comprehensive window replacement services including removal of existing windows, installation of new aluminum and aluminum clad wood windows, thermal insulation, moisture protection, interior finish carpentry, painting, and related construction activities. The scope encompasses approximately 195 windows across the facility with associated structural work including sheathing, thermal insulation, joint sealants, and interior finishes. Bids must be submitted electronically through the IMPACS Electronic Procurement System by 2:00 PM on July 24, 2025, with bid opening scheduled for 3:00 PM the same day via Google Meet teleconference. An optional pre-bid meeting is scheduled for 10:00 AM on July 8, 2025, at the Story Construction trailer on-site. Construction is anticipated to commence on August 25, 2025, and reach substantial completion by September 30, 2026. Questions regarding the project must be submitted by 10:00 AM on July 14, 2025, and substitute product requests must be received by the same deadline. Bidding documents are available from Rapids Reproductions beginning June 19, 2025.

The bid must be accompanied by a bid security in the amount of 5% of the total bid amount, submitted as a bid bond, cashier's check, or certified check. The project is exempt from Iowa Sales Tax and is not subject to Davis Bacon Wage requirements. A Hazardous Building Materials Survey completed in December 2024 identified asbestos-containing materials requiring proper handling and disposal, including thermal system insulation pipe (45% chrysotile), window glazing caulk (5-10% chrysotile), and window sill caulk (6% chrysotile). Lead-based paint was identified on various surfaces including radiators and plaster, with lead concentrations ranging from 0.013% to 0.64% by weight. Contractors must comply with all applicable OSHA, EPA, and State of Iowa regulations regarding asbestos and lead remediation. The procurement emphasizes opportunities for Targeted Small Businesses in accordance with Chapter 73 of the Code of Iowa. Contact Michael Bradbury, Issuing Officer, at (515) 823-9327 or construction.procurement@iowa.gov for additional information.

View the file

Other files

File Type Posted
RFB946300-01 - Bid Form.pdf PDF
RFB946300-01 - Drawings.pdf PDF
1323910-event.pdf PDF
RFB946300-01 - Notice to Bidders.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THIS PAGE

INTENTIONALLY

LEFT BLANK

IOWA DEPT. OF ADMINISTRATIVE SERVICES DAS # 9463.00

HHS WRC BIRCHES WINDOW REPLACEMENTS GENESIS PROJ: 2501

CERTIFICATION PAGE 00 0107 - 1

SECTION 00 0107 – CERTIFICATION PAGE

I hereby certify that the portion of this technical submission described below was prepared by me or under my supervision and responsible charge. I am a duly registered architect under the laws of the state of Iowa.

GENESIS Architectural Design Edward L. Matt, AIA

Signature

Pages or sheets covered in part or whole by this seal:

Specifications Div.1 thru 9.

Date Issued: ______June 19, 2025_______________

PROJECT 9463.00 TABLE OF CONTENTS 00 0110 - 1

B. 06 1600 Sheathing C. 06 2023 Interior Finish Carpentry

1.05 DIVISION 07 – THERMAL AND MOISTURE PROTECTION

A. 07 2100 Thermal Insulation B. 07 4213 Insulated Metal Window Panels

C. 07 9200 Joint Sealants

1.06 DIVISION 08 – OPENINGS

A. 08 5113 Aluminum Windows

B. 08 5200 Aluminum Clad Wood Windows

1.07 DIVISION 09 – FINISHES

A. 09 2400 Cement Plastering B. 09 9000 Painting

1.08 APPENDIX A - REFERENCE PHOTOS

END OF SECTION

PROJECT 9463.00 NOTICE TO BIDDERS 00 1113 - 1

SECTION 00 1113

NOTICE TO BIDDERS

RFB #946300-01

The Iowa Department of Administrative Services will be receiving bids for replacing the windows at the

Birches building at Woodward Resource Center, Woodward, Iowa 50276.

The Iowa Department of Administrative Services anticipates construction to begin on August 25, 2025 and end on September 30, 2026.

Bids must be received no later than 02:00 pm, Thursday, July 24th, 2025. Late bids will not be considered.

Bids shall be submitted on IMPACS Electronic Procurement System. The Bid shall be accompanied by a Bid Security as set forth in the Instructions to Bidders in the amount of 5% of the total bid amount. Each bid shall be accompanied by a bid bond, cashier’s check or a certified check drawn upon a solvent bank chartered under the laws of the United States of America.

Bid Opening The time and place of bid opening will be held at meet.google.com/kob-kzfi-aqy and teleconference number 415-634-7009 Pin: 983 599 354# at 03:00 pm on July 24th, 2025.

The Iowa Department of Administrative Services reserves the right to reject any and all bids, and to waive irregularities and to accept a bid that is deemed in the best interest of the State of Iowa.

Bidders must comply with all affirmative action/equal employment opportunity provisions of the State of Iowa and the Federal Government.

This project is exempt from Iowa Sales Tax. Davis Bacon Wages will not apply to this project.

Questions must be submitted by 10:00 am, July 14, 2025, to the Issuing Officer.

Bidding documents may stipulate a specific product. Substitute product will be considered if a written request is received by 10:00 am, July 14, 2025, prior to bid opening. Substitution requests will be considered for all products per Section 01 2500 Substitution Procedures, even if the specification does not include a statement such as “or equal,” “equal to,” “equivalent to,” or “basis of design,” unless otherwise noted.

An optional Pre-Bid meeting will be held on Tuesday, July 8, 2025 at 10:00 am at Story Construction trailer at the Woodward Resource Center at 1251 334th Street, Woodward, Iowa 50276. This meeting is not mandatory but is highly recommended.

Bidding Documents, including drawing sheets bearing the project name WRC Birches Window

Replacement, Dated 06/19/2025 and the Project Manual prepared by Genesis Architectural Design dated 06/19/2025, may be obtained from Rapids Reproductions by visiting www.rapidsrepro.com or by calling

(515) 251-3222 on Monday through Friday 8:00 am to 5:00 pm.

For further information regarding this project contact:

Michael Bradbury – Issuing Officer Phone: (515) 823-9327 E-Mail: construction.procurement@iowa.gov

JHerman Text Box 109 SE 13th Street Des Moines, IA 50319

JHerman Cloud

JHerman Text Box amount varies based on paragraph 10.2.2 of the ConsensusDocs 802 contract jkleene Typewritten Text Project 9463.00 jkleene

DRAFT

(Number varies by project)

PROJECT 9463.00 PRELIMINARY SCHEDULE 00 3113 - 1

SECTION 00 3113

PRELIMINARY SCHEDULE

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. Preliminary Construction Schedule B. Schedule Durations

1.02 PRELIMINARY SCHEDULE

A. A preliminary schedule has been identified by the Owner for the implementation of the Project.

Refer to the schedule following this Section for references to anticipated milestones and construction duration.

B. Each step of the Preliminary Schedule is subject to receipt of acceptable bids, Owner’s decision process and date of commencement.

C. A proposed construction schedule shall be submitted by all Trade Contractors to the Construction Manager no later than 48 hours prior to the pre-construction meeting. A revised Construction Schedule will be submitted by the Construction Manager once all preliminary schedules are reviewed and approved by the Owner.

D. The final construction schedule will be established post award of bids with the cooperation of all contractors.

1.03 SCHEDULE DURATIONS

A. Anticipated Notice of Intent to Award – 07/25/25

B. Anticipated Date of Commencement – 08/25/25

C. Substantial Completion by – 09/30/26

PART 2 - PRODUCTS – NOT USED

PART 3 - EXECUTION – NOT USED

Task Aug-25 Sep-25 Oct-25 Nov-25 Dec-25 Jan-26 Feb-26 Mar-26 Apr-26 May-26 Jun-26 Jul-26 Aug-26 Sep-26 Oct-26 Nov-26 Dec-26

Contracts

Abatement

Temporary Infills

Window Install

Interior Finishes

Weather Contingency

Closeout

4503 East 50th Street, Suite 800, Des Moines, Iowa 50317

515.981.4528 | oneatlas.com

H A Z A R D O U S B U I L D I N G M A T E R I A L S S U R V E Y

PREPARED FOR:

Iowa Department of Administrative Services 109 SE 13th Street

Des Moines, Iowa 50319

PROJECT LOCATION:

Woodward Resource Center - Phase 4 Decentralization Project #9279 Birches Building 1251 334th Street Woodward, Iowa

Project Date: September 25 and November 20, 2024

Report Date: December 16, 2024

Atlas Project ID: 204BS07475

PREPARED BY:

Atlas Technical Consultants LLC 4503 East 50th Street, Suite 800

Des Moines, IA 50317 i

December 16, 2024

Ms. Jennifer Kleene Iowa Department of Administrative Services 109 SE 13th Street Des Moines, IA 50319

Re: Hazardous Building Materials Survey Report – Birches Building Woodward Resource Center – Phase 4 Decentralization Project #9279

1251 334th Street

Atlas Project Number: 204BS07475

Atlas is pleased to submit the attached Hazardous Building Materials Survey Report for the above-referenced site. This report includes procedures, methodologies and analytical laboratory results.

Atlas appreciates the opportunity to perform these services for the Iowa Department of Administrative Services (IDAS), and we look forward to working with you in the future. If you need any assistance with the implementation of the recommendations contained in this report, please feel free to give us a call at (515) 981-4528 and we will respond promptly to your needs.

Sincerely, ATLAS TECHNICAL CONSULTANTS LLC

Eric Brown Steve Hudson, MS, CIH Iowa Inspector Senior Project Manager

(515) 981-4528 (402) 670-3842

T A B L E O F C O N T E N T S

LETTER OF TRANSMITTAL ............................................................................................... i

1.0 SCOPE OF SERVICES

2.0 GENERAL SITE CONDITIONS

3.0 ASBESTOS SURVEY

3.1 Regulation Review

3.2 Homogeneous Areas

3.3 Sampling Strategy

3.4 Laboratory Analytical Results

3.5 Suspect Asbestos-Containing Materials

4.0 LEAD PAINT CHIP TESTING

4.1 Inspection

4.2 Lead Paint Testing

5.0 HAZARDOUS MATERIALS ASSESSMENT

6.0 CONCLUSIONS

6.1 Asbestos

6.2 Lead

6.3 Hazardous Building Materials

7.0 ASSUMPTIONS AND LIMITATIONS

APPENDICES

APPENDIX A: Asbestos Analytical Report and Chain of Custody

APPENDIX B: Lead Analytical Report and Chain of Custody

APPENDIX C: Drawings with Sample Locations

APPENDIX D: Asbestos and Lead Paint Photo Logs

APPENDIX E: Inspector Accreditations

Hazardous Building Materials Survey Report – Birches Building

Woodward Rescource Center Phase 4 Decentralization Project #9279

December 16, 2024 Project No. 204BS07475

H A Z A R D O U S B U I L D I N G M A T E R I A L S

S U R V E Y R E P O R T

Woodward Resource Center – Birches Building Phase 4 Decentralization Project #9279

1251 334th Street

Atlas Project Number: 204BS07475

1.0 SCOPE OF SERVICES

The purpose of this project was to perform a survey to identify hazardous building materials at the above-referenced property.

Atlas provided a representative asbestos survey in accordance with the referenced agreement and as outlined below:

1. Review any existing hazardous building material survey reports relating to the site, if available.

2. Identify suspect asbestos-containing materials (ACM), surface coatings potentially containing lead paint, and hazardous building materials throughout the interior and exterior of the building, not including the roof.

3. Collect and analyze bulk samples of suspect asbestos containing materials and collect paint chip samples from representative surface coatings potentially containing lead-based or lead-containing paint.

4. Provide laboratory analysis of collected samples.

5. Provide a report of findings with copies and interpretation of analytical results and identifying the locations of asbestos-containing materials, lead paint, and hazardous building materials.

2.0 GENERAL SITE CONDITIONS

The survey was conducted at the Woodward Resource Center – Birches Building located at 1251 334th Street in Woodward, Iowa. The survey was limited to accessible surfaces on the interior and exterior of the building, not including the roof.

3.0 ASBESTOS SURVEY

On September 25 and November 20, 2024, the Birches Building was inspected for ACMs by inspector Eric Brown of Atlas. Mr. Brown has completed the requisite training for asbestos accreditation as inspectors at a state approved training provider under TSCA Title II. Mr. Brown’s State of Iowa Inspector number is 24-11418.

Accessible areas were visually inspected for the presence of suspect ACMs. Materials that were hidden, not accessible, or when sampled would damage the integrity of the structure, were not sampled as part of this survey. Materials visibly identified as non-asbestos (fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos survey consisted of three basic steps: 1) a visual inspection of the proposed work areas; 2) a determination of homogeneous areas with suspect surfacing, thermal system insulation, and miscellaneous materials; and 3) sampling accessible, friable and non-friable, suspect materials.

3.1 Regulation Review

The United States Environmental Protection Agency (USEPA) qualifies ACM as materials with an asbestos content greater than 1%. The following definitions are taken from Section 61.141 of Subpart M, Part 61 of Title 40: Protection of Environment of the Code of Federal Regulations

(CFR).

• “Category I non-friable ACM” is defined as asbestos-containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1% asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy (PLM).

• “Category II non-friable ACM” is defined as any material, excluding Category I non-friable ACM, containing more than 1% asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

• “Friable asbestos material” is defined as any material containing more than 1% asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, PLM that when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. If the asbestos content is less than 10% as determined by a method other than point counting by PLM, verify the asbestos content by point counting using PLM.

3.2 Homogeneous Areas

Prior to sampling, homogeneous areas were identified in order to facilitate a sampling strategy. A homogeneous sampling area can be described as one or more areas with suspect material similar in appearance and texture that have the same installation date and function. The actual number of samples collected from each homogeneous sampling area may vary, dependent upon material type and the professional judgment of the inspector.

3.3 Sampling Strategy

The sampling strategy incorporated Asbestos Hazard Emergency Response Acts (AHERA) requirements, quantities of suspect material, and the inspector’s judgment to aid in the identification of suspect asbestos-containing materials. If the analytical results indicated that all the samples collected per homogeneous area did not contain asbestos, then the homogeneous area (material) was considered non-asbestos-containing. However, if the analytical results of one or more of the samples collected per homogeneous area indicated that asbestos was present in quantities greater than one percent asbestos (as defined by EPA), all of the homogeneous area (material) was treated as an asbestos-containing material regardless of any other analytical results. Materials which were visually determined to be non-asbestos (i.e. fibrous glass, foam rubber, etc.) by the accredited inspector were not required to be sampled. Actual collection of a bulk asbestos sample involves physically removing approximately one square inch (1 in2) of material and placing it in an airtight sample container. Sample containers were marked with a unique identification number, which was documented in the field notes.

3.4 Laboratory Analytical Results

A total of 52 samples were collected from building materials suspected of containing asbestos. The samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) located at 200 Route 130 North in Cinnaminson, New Jersey, for analysis by polarized light microscopy (PLM) with dispersion staining techniques per the USEPA Method for the Determination of Asbestos in Bulk Building Materials (600/R-93-116). The percentage of asbestos, if applicable, was established by microscopic visual estimation. EMSL is an accredited laboratory by the National Voluntary Laboratory Accreditation Plan (NVLAP) No. 101048-0. Any material that contains greater than one percent (>1%) asbestos is considered an ACM and must be handled according to Occupational Safety and Health Administration (OSHA), USEPA, and all applicable state and local regulations.

Laboratory test results are provided in Appendix A.

3.5 Suspect Asbestos-Containing Materials

The following table contains a list of suspect asbestos containing materials sampled:

T A B L E 1 : S U S P E C T A S B E S T O S M A T E R I A L S

Material Location Sample Number

Plaster & Skim Coat Room 305 B-1

Plaster & Skim Coat Room 300 B-2

Plaster & Skim Coat Room 304 B-3

Terrazzo Flooring Room 303 B-4

Popcorn Ceiling Texture Room 305 B-5

TSI Pipe Insulation Room 305 B-6

Fiberglass Insulation Room 305 B-7

Terrazzo Flooring Room 215 B-8

Popcorn Ceiling Texture Room 217 B-9

Cove Base Room 217 B-10

Cove Base Mastic Brown Room 217 B-11

White Window Sill/Trim Caulk Room 217A B-12

Drywall Mud Room 217A B-13

Drywall Tape Room 217A B-14

Drywall Room 217A B-15

Brick Mortar Room 216 B-16

2’ x 2’ Ceiling Tile Room 213B B-17

Drywall Room 213B B-18

Drywall Mud Room 213B B-19

Popcorn Ceiling Texture Room 213B B-20

Wall Texture Room 213B B-21

Cove Base Black Room 213B B-22

T A B L E 1 : S U S P E C T A S B E S T O S M A T E R I A L S

Material Location Sample Number

Cove Base Mastic Tan Room 213B B-23

Cove Base Beige Room 213A B-24

Cove Base Mastic Tan Room 213A B-25

Cove Base White Room 213G B-26

Cove Base Mastic Tan Room 213G B-27

HVAC Sealant Room 210 B-28

Plaster & Skim Coat Room 231 B-29

TSI Pipe Insulation Room 212 B-30

Drywall Mud Room 222A B-31

Popcorn Ceiling Texture Room 201 B-32

Drywall Mud Room 222A B-33

Window Glazing Room 201A B-34

Terrazzo Flooring Room 206A B-35

Plaster & Skim Coat Room 208 B-36

Plaster & Skim Coat Room 119 B-37

Terrazzo Flooring Room 119 B-38

Brick Mortar Room 119 B-39

CMU Mortar Room 124 B-40

Plaster & Skim Coat Room 124B B-41

Plaster & Skim Coat Room 108A B-42

Particle Board Room 105 B-43

Plaster & Skim Coat Room B17 B-44

TSI Pipe Sealant Room B12 B-45

Plaster & Skim Coat Room B29 B-46

Drywall Room B29 B-47

Plaster & Skim Coat Room B01 B-48

Terrazzo Flooring Room B01 B-49

Caulk White Room B01 B-50

Window Glazing Exterior NE Window B-51

Caulk Gray Exterior NE Window B-52

The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:

T A B L E 2 : A S B E S T O S - C O N T A I N I N G M A T E R I A L S

Sample Number

Material Location Approx.

Quantity

Asbestos Content

B-6 TSI Pipe Insulation Room 305

(may be insulated within wall from 2nd to ground floor)

2 LF

45%

Chrysotile

B-12 White Window Sill Caulk Room 217A 60 LF 6%

Chrysotile

4.0 LEAD PAINT CHIP TESTING

Atlas collected paint chip samples from representative surface coatings that may be impacted by renovation activities.

Surface coatings that were collected were considered to be representative of materials in a homogeneous area if:

1. They exhibited similar physical characteristics (suspect materials alike in appearance, substrate, color, and time of application were tested as homogenous areas)

2. The application of the tested surface could be associated to an application of an unsampled surface.

Atlas collected and submitted a total of 14 paint chip samples from surface coatings. The samples were submitted to EMSL of Cinnaminson, New Jersey, under proper chain of custody for analysis by Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B). EMSL is accredited under the American Industrial Hygiene Association-Laboratory Accreditation Program (AIHA-LAP, LLC) (AIHA-LAP; lab code 100194). A copy of the analytical results and chain of custody can be found in Appendix B.

The USEPA has defined LBP as “paint or other surface coatings that contain lead in excess of 0.5 percent by weight (>0.5%)”. Results less than 0.5% by weight indicate that lead is not present at or above the USEPA regulatory level; however, lead may be present in lower concentrations above the laboratory detection limit in other surfaces tested and these are classified as lead-containing paint (LCP). Negative results do not mean that lead is not present.

4.1 Inspection

The disturbance and disposal of materials with surface coatings that contain lead paint are regulated by the USEPA, OSHA and the State of Iowa. The Resource Conservation and Recovery Act (RCRA) provides the USEPA with the authority to regulate the waste status of renovation debris, including lead-containing materials. Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes.

Construction work covered by 29 CFR 1926.62 includes any repair, renovation or other activities that disturb in-place, lead-containing materials, but does not include routine cleaning and

T A B L E 2 : A S B E S T O S - C O N T A I N I N G M A T E R I A L S

Sample Number

Material Location Approx.

Quantity

Asbestos Content

B-51 Window Glazing Exterior, Windows

Windows 5%

Chrysotile

B-52 Window Caulk (gray) Exterior, Windows

Windows 10%

Chrysotile

SF = Square Feet, LF = Linear Feet repainting where there is insignificant damage, wear or corrosion of existing lead-containing coatings or substrates. Unless adequately protected, employee exposures to lead must not exceed airborne concentrations >50 micrograms per cubic meter (g/m3) averaged over an 8-hour period.

Occupational exposure to lead occurring in the course of construction work, including maintenance activities, painting, alteration and repairs is subject to the OSHA Lead standard (29 CFR 1926.62). The lead standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon the method of removal and other workplace conditions.

The disposal of lead-based paint waste, as well as paint waste containing other heavy metals, is regulated by the USEPA and State of Iowa. Wastes generated by industrial businesses, commercial businesses, and government institutions are subject to regulation. Commercial business owners and removal contractors are required to determine if paint waste generated from nonresidential structures (such as public and commercial buildings, warehouses, bridges, water towers, and transmission towers) contains heavy metals that would cause the debris to be considered a hazardous waste. Disposal options and applicable management requirements for collected debris will be based upon whether the waste stream is considered a hazardous waste and the amount of debris generated. Removal contractors and building owners need to include these factors when preparing and responding to bid specifications. Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes. Lead-containing wastes are considered hazardous waste under RCRA if Toxicity Characteristic Leachate Procedure (TCLP) results exceed 5 milligrams per liter (mg/L). The USEPA has made exceptions for the handling and disposal of lead wastes generated from residential housing.

Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes. Lead-containing wastes are considered hazardous waste under RCRA if Toxicity Characteristic Leachate Procedure (TCLP) results exceed 5 milligrams per liter (mg/L). The USEPA has made exceptions for the handling and disposal of lead wastes generated from residential housing.

The above overview is not intended to be inclusive of all potentially pertinent regulatory information. The relevant USEPA, OSHA and State of Iowa regulations should be consulted prior to undertaking activities involving the demolition, renovation or maintenance of surface coatings that contain lead.

4.2 Lead Paint Testing

The following surface coatings were collected as part of the lead paint testing:

T A B L E 3 : L E A D P A I N T S U M M A R Y

Sample Number

Sample Location

Representative Material Paint Color

Lead Concentration (% by weight)

PCB-1 Room 301 Radiator Metal Teal 0.42 bolded = lead-based paint

This evaluation report can help the Owner develop a plan for renovating the building by having concentrations of lead in the paint identified. It is our understanding that the information in this report will be provided to the contractors so that appropriate precautions can be made to minimize worker exposure to lead. If surface coatings with lead containing paint are handled improperly, exposure could occur to workers and future occupants of the facility.

5.0 HAZARDOUS MATERIALS ASSESSMENT

Atlas completed a visual inspection of rooms / areas throughout the intended work areas in an attempt to identify hazardous wastes or universal wastes that may be impacted by planned renovation activities. The survey included a visual inspection of: light fixtures and other equipment for the presence of Polychlorinated Biphenyls (PCBs); light bulbs, thermostats, switches, and other equipment for the presence of mercury; refrigerants, batteries, and devices with potential radioactive materials.

T A B L E 4 : H A Z A R D O U S B U I L D I N G M A T E R I A L S

Category Material Estimated Quantity

Batteries Lead Acid NA

T A B L E 3 : L E A D P A I N T S U M M A R Y

Sample Number

Sample Location

Representative Material Paint Color

Lead Concentration (% by weight)

PCB-2 Room 304 Radiator Metal Yellow 0.49

PCB-3 Room 300 Plaster Yellow 0.14

PCB-4 Room 303 Plaster Green 0.46

PCB-5 Room 305 Plaster Blue-Green 0.64

PCB-6 Room 217 Plaster Cream-Tan 0.013

PCB-7 Room 213D Plaster White 0.046

PCB-8 Room 216 Drain Pipe Metal White 0.26

PCB-9 Room 213E Metal White <0.008

PCB-10 Room 201A Plaster Blue <0.008

PCB-11 Room 115 Plaster Lt Blue 0.26

PCB-12 Room 117 Plaster Yellow 0.29

PCB-13 Room 112 Plaster Lt Purple 0.043

PCB-14 Room 108 Door Frame Metal Silver 0.026

PCB-15

Exterior, Window Lintels and

Mullions Metal White 10

T A B L E 4 : H A Z A R D O U S B U I L D I N G M A T E R I A L S

Category Material Estimated Quantity

Nickel Cadmium 16 (exit signs)

Lithium-Ion NA

Mercury

Thermostats NA

Fluorescent Light Tubes 336

High Intensity Discharge Bulbs NA

Strobes NA

Poly-Chlorinated Biphenyl (PCBs) Light Ballasts NA

Transformers NA

Low Level Radioactive Sources (LLR) Tritium Exit Signs NA

Smoke Detectors 137

Chlorofluorocarbons (CFCs) or Hydro Chlorofluorocarbons (HCFCs)

Refrigerator/Cooler NA

Freezer NA

Water Fountain NA

6.0 CONCLUSIONS

6.1 Asbestos

The NESHAP and OSHA regulations govern the removal of ACM. Atlas recommends that a State of Iowa certified abatement contractor be retained to properly abate and dispose of ACM identified in Table 1 above and in accordance with local, state, and federal regulations.

The owner and/or operator are responsible for NESHAP regulatory compliance regarding the proper removal, handling, and disposal of ACM containing >1% asbestos prior to renovation or demolition. Also, per state regulations, please be aware that the owner and/or operator must submit a notification to the Iowa Department of Natural Resources (IDNR) 10-buisness days prior to asbestos abatement at certain quantity thresholds and prior to renovation/demolition activities.

6.2 Lead

Lead was identified above the laboratory detection limit in 12 of the 15 surface coatings tested.

Contractors should use caution during construction-related activities as concealed surface coatings containing lead paints that were not previously tested may be encountered. If materials not sampled during this investigation are later identified to contain regulated quantities of lead concentrations, then they should be removed, controlled and/or disposed in accordance with federal, state and local regulations, prior to disturbance. OSHA considers any detectable level of lead as LCP and disturbance of these surface coatings is subject to the training and work practices in OSHA 29 CFR 1926.62 “Lead in Construction”.

6.3 Hazardous Building Materials

Hazardous materials or universal wastes identified in Table 4 that will be impacted by renovation activities shall be removed as part of the renovation contractor’s scope of work and disposed of according to USEPA Toxic Substances Control Act (TSCA) and the State of Iowa regulations.

7.0 ASSUMPTIONS AND LIMITATIONS

The results, findings, conclusions, and recommendations expressed in this report are based solely on conditions noted during the September 25 and November 20, 2024, Atlas hazardous building materials survey of the Woodward Resource Center – Birches Building in Woodward, Iowa.

Atlas did not perform destructive sampling -- it was not within Atlas’s scope of work to remove surface materials to investigate portions of the structure or materials that may lay beneath the surface -- thus, any materials that could not be visually identified on the surface were not inspected and would not be noted in this report. Atlas’s selection of sample locations and frequency of sampling was based on the inspector’s assumption that like materials in the same area are homogeneous in content.

The report is designed to aid the building owner, architect, construction manager, general contractor, and potential abatement contractor in locating hazardous building materials. Under no circumstances is the report to be utilized as a bidding document or as a project specification document since it does not have all the components required to serve as a Project Design document or an Abatement Work plan.

Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against future operations or conditions, nor does it warrant against operations or conditions present of a type or at a location not investigated.

This report is intended for the sole use of IDAS. The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.

Atlas recommendations are based in part on federal, state, local regulations, and guidelines. Atlas does not undertake responsibility for reporting to any local, state, or federal public agencies of conditions at the site that may present a potential danger to public health or safety. Atlas recommends that the Client comply with regulations and response actions in accordance with federal, state, and local regulations.

APPENDIX A

ASBESTOS ANALYTICAL RESULTS AND CHAIN OF CUSTODY

EMSL Analytical, Inc.

200 Route 130 North Cinnaminson, NJ 08077

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042420594EMSL Order:

Customer ID: ATC55

Customer PO:

Project ID:

Attention: Phone:Eric Brown (402) 697-9747

Fax:Atlas Technical (402) 597-8532

Received Date:11117 Mockingbird Drive 10/03/2024 11:40 AM

Analysis Date:Omaha, NE 68137 10/07/2024 - 10/08/2024

Collected Date: 09/23/2024

Project: 204BS07475 / Birches / Tunnel Survey Woodward

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

B-1-Plaster

042420594-0001

None DetectedNon-fibrous (Other)97%Cellulose3%Gray

Fibrous

Homogeneous

3rd Floor - Rm 305 -

Plaster

B-1-Skim Coat

042420594-0001A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

3rd Floor - Rm 305 -

Skim Coat

B-2-Plaster

042420594-0002

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

3rd Floor - Rm 300 -

Plaster

B-2-Skim Coat

042420594-0002A

None DetectedNon-fibrous (Other)100%White/Pink

Non-Fibrous

Homogeneous

3rd Floor - Rm 300 -

Skim Coat

B-3-Plaster

042420594-0003

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

3rd Floor - Rm 304 -

Plaster

B-3-Skim Coat

042420594-0003A

None DetectedNon-fibrous (Other)100%White/Beige

Non-Fibrous

Homogeneous

3rd Floor - Rm 304 -

Skim Coat

B-4

042420594-0004

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

3rd Floor - Rm 303 -

Terrazzo Floor

B-5

042420594-0005

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

3rd Floor - Rm 305 -

Popcorn Ceiling

B-6

042420594-0006

45% ChrysotileNon-fibrous (Other)55%White

Fibrous

Homogeneous

3rd Floor - Rm 305 -

Pipe Insulation

B-7

042420594-0007

None DetectedNon-fibrous (Other)5%Glass95%Yellow/Orange

Fibrous

Homogeneous

3rd Floor - Rm 305 -

Fiberglass Insulation

B-8

042420594-0008

None DetectedNon-fibrous (Other)100%Gray/Red

Non-Fibrous

Homogeneous

2nd Floor - Rm 215 -

Terrazzo Floor

B-9

042420594-0009

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 217 -

Popcorn Ceiling

B-10

042420594-0010

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

2nd Floor - Rm 217 -

Cove Base

B-11

042420594-0011

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

2nd Floor - Rm 217 -

Brown Mastic

B-12

042420594-0012

6% ChrysotileNon-fibrous (Other)94%Tan/White

Non-Fibrous

Homogeneous

2nd Floor - Rm 217A -

White Caulk

B-13

042420594-0013

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 217A -

Drywall Mud

Initial report from: 10/08/2024 09:14:51

Page 1 of 4ASB_PLM_0008_0002 - 2.31 Printed: 10/8/2024 9:14 AM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042420594EMSL Order:

Customer ID: ATC55

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

B-14

042420594-0014

None DetectedNon-fibrous (Other)5%Cellulose95%Tan

Fibrous

Homogeneous

2nd Floor - Rm 217A -

Drywall Tape

B-15

042420594-0015

None DetectedNon-fibrous (Other)82%Cellulose

Glass

15%

3%

Brown/White

Fibrous

Homogeneous

2nd Floor - Rm 217A -

Drywall

B-16

042420594-0016

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

2nd Floor - Rm 216 -

Brick Mortar

B-17

042420594-0017

None DetectedPerlite

Non-fibrous (Other)

5%

15%

Cellulose

Min. Wool

50%

30%

Tan/White

Fibrous

Homogeneous

2nd Floor - Rm 213B

- 2x2 Ceiling Tile

B-18

042420594-0018

None DetectedNon-fibrous (Other)85%Cellulose15%Brown/White

Fibrous

Homogeneous

2nd Floor - Rm 213B

- Drywall

B-19

042420594-0019

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 213B

- Drywall Mud

B-20

042420594-0020

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 213B

- Popcorn Ceiling

B-21

042420594-0021

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 213B

- Wall Texture

B-22

042420594-0022

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

2nd Floor - Rm 213B

- Black Cove Base

B-23

042420594-0023

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 213B

- Tan Cove Base

Mastic

B-24

042420594-0024

None DetectedNon-fibrous (Other)100%Beige

Non-Fibrous

Homogeneous

2nd Floor - Rm 213A -

Beige Cove Base

B-25

042420594-0025

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 213A -

Tan Cove Base

Mastic

B-26

042420594-0026

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 213G

- White Cove Base

B-27

042420594-0027

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 213G

- Tan Cove Base

Mastic

B-28

042420594-0028

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

2nd Floor - Rm 210 -

HVAC Sealant

B-29-Plaster

042420594-0029

None DetectedNon-fibrous (Other)97%Cellulose3%Brown

Fibrous

Homogeneous

2nd Floor - Rm 231 -

Plaster

B-29-Skim Coat

042420594-0029A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 231 -

Skim Coat

B-30-Insulation

042420594-0030

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

2nd Floor - Rm 212 -

Pipe Insulation

B-30-Sealant

042420594-0030A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 212 -

Sealant

Page 2 of 4ASB_PLM_0008_0002 - 2.31 Printed: 10/8/2024 9:14 AM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042420594EMSL Order:

Customer ID: ATC55

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

B-31

042420594-0031

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 22A -

Drywall Mud

B-32

042420594-0032

None DetectedNon-fibrous (Other)100%Tan/White

Non-Fibrous

Homogeneous

2nd Floor - Rm 201 -

Popcorn Ceiling

B-33

042420594-0033

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

2nd Floor - Rm 201A -

Drywall Mud

B-34

042420594-0034

None DetectedNon-fibrous (Other)94%Fibrous (Other)6%Tan/White

Non-Fibrous

Homogeneous

2nd Floor - Rm 201A -

Window Glazing

B-35

042420594-0035

None DetectedNon-fibrous (Other)100%Gray/Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 206A -

Terrazzo Flooring

B-36-Plaster

042420594-0036

None DetectedNon-fibrous (Other)97%Cellulose3%Gray

Fibrous

Homogeneous

2nd Floor - Rm 208 -

Plaster

B-36-Skim Coat

042420594-0036A

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

2nd Floor - Rm 208 -

Skim Coat

B-37-Plaster

042420594-0037

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

1st Floor - Rm 119 -

Plaster

B-37-Skim Coat

042420594-0037A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

1st Floor - Rm 119 -

Skim Coat

B-38

042420594-0038

None DetectedNon-fibrous (Other)100%Brown/Gray

Non-Fibrous

Homogeneous

1st Floor - Rm 119 -

Terrazzo Flooring

B-39

042420594-0039

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

1st Floor - Rm 119 -

Brick Mortar

B-40

042420594-0040

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

1st Floor - Rm 124 -

CMU Mortar

B-41-Plaster

042420594-0041

None DetectedNon-fibrous (Other)97%Cellulose3%Brown

Fibrous

Homogeneous

1st Floor - Rm 124B -

Plaster

B-41-Skim Coat

042420594-0041A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

1st Floor - Rm 124B -

Skim Coat

B-42-Plaster

042420594-0042

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

1st Floor - Rm 108A -

Plaster

B-42-Skim Coat

042420594-0042A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

1st Floor - Rm 108A -

Skim Coat

B-43

042420594-0043

None DetectedNon-fibrous (Other)5%Cellulose95%Brown/Gray

Fibrous

Homogeneous

1st Floor - Rm 105 -

Particle Board

B-44-Plaster

042420594-0044

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B17 -

Plaster

B-44-Skim Coat

042420594-0044A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B17 -

Skim Coat

Page 3 of 4ASB_PLM_0008_0002 - 2.31 Printed: 10/8/2024 9:14 AM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042420594EMSL Order:

Customer ID: ATC55

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

B-45-Sealant

042420594-0045

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B12 -

Pipe Sealant

B-45-Insulation

042420594-0045A

None DetectedNon-fibrous (Other)5%Glass95%Yellow

Fibrous

Homogeneous

Basement - B12 -

Pipe Sealant

B-46-Plaster

042420594-0046

None DetectedNon-fibrous (Other)97%Cellulose3%Brown/Gray

Fibrous

Homogeneous

Basement - B29 -

Plaster

B-46-Skim Coat

042420594-0046A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B29 -

Skim Coat

B-47

042420594-0047

None DetectedNon-fibrous (Other)85%Cellulose15%Brown/White

Fibrous

Homogeneous

Basement - B29 -

Drywall

B-48-Plaster

042420594-0048

None DetectedNon-fibrous (Other)97%Cellulose3%Brown

Fibrous

Homogeneous

Basement - B01 -

Plaster

B-48-Skim Coat

042420594-0048A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B01 -

Skim Coat

B-49

042420594-0049

None DetectedNon-fibrous (Other)100%Brown/Gray

Non-Fibrous

Homogeneous

Basement - B01 -

Terrazzo Flooring

B-50

042420594-0050

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Basement - B01 -

White Caulk

B-51

042420594-0051

5% ChrysotileNon-fibrous (Other)95%White

Non-Fibrous

Homogeneous

Exterior - NE Window

- Window Glazing

B-52

042420594-0052

10% ChrysotileNon-fibrous (Other)90%Brown/Gray

Fibrous

Homogeneous

Exterior - NE Window

- Gray Caulk

Analyst(s)

Hunter Kelly (57)

Amy Schulze (8)

Samantha Rundstrom, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA LAP, LLC-IHLAP Lab 100194, PA ID# 68-00367, LA #04127

Page 4 of 4ASB_PLM_0008_0002 - 2.31 Printed: 10/8/2024 9:14 AM

OrderID: 042420594

APPENDIX B

LEAD PAINT ANALYTICAL RESULTS AND CHAIN OF CUSTODY

Project Name:

Customer PO:

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 10/03/2024 10:00

10/04/2024 15:45

Anthony DeRosa

EMSL Order ID: 012432420

LIMS Reference ID: AC32420

EMSL Customer ID: ATC55

Woodward Tunnel Survey 204BS07475

Analytical Results

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g)

Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: PCB-1/Room 301 Radiator - Metal - Teal Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-01

5Lead D10/04/24 KD1 10/04/24 PMX0.42 % wt 0.037 % wt SW-846 3050B SW846-7000B0.2698

Sample Comments:

Client Sample ID: PCB-2/Room 304 Radiator - Metal - Yellow Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-02

5Lead D10/04/24 KD1 10/04/24 PMX0.49 % wt 0.035 % wt SW-846 3050B SW846-7000B0.2879

Sample Comments:

Client Sample ID: PCB-3/Room 300 - Plaster - Yellow Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-03

1Lead 10/04/24 KD1 10/04/24 PMX0.14 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2555

Sample Comments:

Client Sample ID: PCB-4/Room 303 - Plaster - Green Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-04

5Lead D10/04/24 KD1 10/04/24 PMX0.46 % wt 0.039 % wt SW-846 3050B SW846-7000B0.2537

Sample Comments:

Client Sample ID: PCB-5/Room 305 - Plaster - Blue-Green Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-05

5Lead D10/04/24 KD1 10/04/24 PMX0.64 % wt 0.038 % wt SW-846 3050B SW846-7000B0.2611

Sample Comments:

Client Sample ID: PCB-6/Room 217 - Plaster - Cream/Tan Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-06

1Lead 10/04/24 KD1 10/04/24 PMX0.013 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2933

Sample Comments:

Client Sample ID: PCB-7/Room 213D - Plaster - White Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-07

1Lead 10/04/24 KD1 10/04/24 PMX0.046 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2699

Sample Comments:

Client Sample ID: PCB-8/Room 216 Drain Pipe - Metal - White Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-08

1Lead 10/04/24 KD1 10/04/24 PMX0.26 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2734

Sample Comments:

Client Sample ID: PCB-9/Room 213E - Metal - White Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-09

1Lead 10/04/24 KD1 10/04/24 PMX<0.008 % wt 0.008 % wt SW-846 3050B SW846-7000B0.253

Sample Comments:

[TOC_1]Sample Results[TOC]

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 10/03/2024 10:00

10/04/2024 15:45

Anthony DeRosa

EMSL Order ID: 012432420

LIMS Reference ID: AC32420

EMSL Customer ID: ATC55

Woodward Tunnel Survey 204BS07475

Analytical Results

(Continued)

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g)

Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: PCB-10/Room 201A - Plaster - Blue Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-10

1Lead 10/04/24 KD1 10/04/24 PMX<0.008 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2587

Sample Comments:

Client Sample ID: PCB-11/Room 115 - Plaster - Lt. Blue Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-11

1Lead 10/04/24 KD1 10/04/24 PMX0.26 % wt 0.012 % wt SW-846 3050B SW846-7000B0.1655

Sample Comments:

Client Sample ID: PCB-12/Room 117 - Plaster - Yellow Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-12

1Lead 10/04/24 KD1 10/04/24 PMX0.29 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2747

Sample Comments:

Client Sample ID: PCB-13/Room 112 - Plaster - Lt. Purple Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-13

1Lead 10/04/24 KD1 10/04/24 PMX0.043 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2743

Sample Comments:

Client Sample ID: PCB-14/Room 108 Door Frame - Metal - Silver Date Sampled: 09/23/24

Matrix: Chips LIMS Reference ID: AC32420-14

1Lead 10/04/24 KD1 10/04/24 PMX0.026 % wt 0.008 % wt SW-846 3050B SW846-7000B0.2659

Sample Comments:

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 10/03/2024 10:00

10/04/2024 15:45

Anthony DeRosa

EMSL Order ID: 012432420

LIMS Reference ID: AC32420

EMSL Customer ID: ATC55

Woodward Tunnel Survey 204BS07475

CertificationsAnalyte

Certified Analyses included in this Report

SW846-7000B in Chips

AIHA LAPLead

[TOC_1]Certified

Analyses[TOC]

List of Certifications

Code Description Number Expires

NJDEP 03036New Jersey Department of Environmental Protection 06/30/2025

AIHA LAP 100194EMSL Analytical, Inc. Cinnaminson, NJ AIHA-LAP, LLC-ELLAP Accredited 01/01/2025

NYSDOH 10872New York State Department of Health 04/01/2025

California ELAP 1877California Water Boards 06/30/2025

A2LA 2845.01A2LA Environmental Certificate 07/31/2026

PADEP 68-00367Pennsylvania Department of Environmental Protection 11/30/2024

MADEP M-NJ337Massachusetts Department of Environmental Protection 06/30/2025

CTDPH PH-0270Connecticut Department of Public Health 06/23/2026

Please see the specific Field of Testing (FOT) on www.emsl.com <http://www.emsl.com> for a complete listing of parameters for which EMSL is certified.

[TOC_1]Certifications[TOC]

Notes and Definitions

Item Definition

D Analyte was reported from a dilution run.

(Dig) For metals analysis, sample was digested.

[2C] Reported from the second channel in dual column analysis.

DF Dilution Factor

MDL Method Detection Limit.

ND Analyte was NOT DETECTED at or above the detection limit.

NR Spike/Surrogate showed no recovery.

Q Qualifier

RL Reporting Limit

For paint chips, the RL is 0.008% by wt. (equiv. to 80 mg/kg, or ppm) based upon a minimum sample weight of 0.25 grams.

For soils, the RL is 40 mg/kg (ppm) based upon a minimum sample weight of 0.5 grams.

For dust wipes, the RL is 10 µg/wipe; reporting units of µg/sq. ft. are not validated by the lab based upon data provided by non-lab personnel.

Wet Sample is not dry weight corrected.

Measurement of uncertainty and any applicable definitions of method modifications are available upon request. Per EPA NLLAP policy, sample results are not blank corrected.

[TOC_1]Qualifiers, Definitions and Disclaimer[TOC]

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 10/03/2024 10:00

10/04/2024 15:45

Anthony DeRosa

EMSL Order ID: 012432420

LIMS Reference ID: AC32420

EMSL Customer ID: ATC55

Woodward Tunnel Survey 204BS07475

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. QC sample results are within quality control criteria and met method specifications unless otherwise noted. All results for soil samples are reported on a dry weight basis, unless otherwise noted.

Owen McKenna Laboratory Manager or other approved signatory

Analysis following EMSL SOP for the Determination of Environmental Lead by FLAA. The laboratory has a reporting limit of 0.008% by wt., based upon a minimum sample weight of

0.25g submitted to the lab, and is not responsible for any result or reporting limit provided in mg/cm2 since it is dependent upon an area value provided by non-lab personnel. A "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty and definitions of modifications are available upon request. Results in this report are not blank corrected unless specified.

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 11/22/2024 10:00

11/27/2024 11:00

Anthony DeRosa

EMSL Order ID: 012438017

LIMS Reference ID: AC38017

EMSL Customer ID: ATC55

Woodward Tunnels // 204BS07475

Analytical Results

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g)

Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: PCB - 15/Window Lintel and Mullions White Date Sampled: 11/20/24

Matrix: Chips LIMS Reference ID: AC38017-01

100Lead D11/25/24 KD1 11/26/24 PMX10 % wt 0.78 % wt SW-846 3050B SW846-7000B0.2571

Sample Comments:

[TOC_1]Sample Results[TOC]

EMSL Sales Rep:

Reported:

Atlas Technical [ATC55]

11117 Mockingbird Drive

Omaha, NE 68137

EMSL Analytical, Inc.

200 Route 130, Cinnaminson, NJ, 08077

Telephone: 856-858-4800 Fax:856-786-5974

EMSL-CIN-01

Steve HudsonAttention:

(402) 697-9747 steve.hudson@oneatlas.com Received: 11/22/2024 10:00

11/27/2024 11:00

Anthony DeRosa

EMSL Order ID: 012438017

LIMS Reference ID: AC38017

EMSL Customer ID: ATC55

Woodward Tunnels // 204BS07475

CertificationsAnalyte

Certified Analyses included in this Report

SW846-7000B in Chips

AIHA LAPLead

[TOC_1]Certified

Analyses[TOC]

List of Certifications

Code Description Number Expires

NJDEP…