RFB931200-01 - ABD ANK HVAC Controls - Drawings.pdf
PDF 2 MB Posted
- Attached to
- ABD Ankeny HVAC Controls Upgrade
- Solicitation number
- RFB931200-01
- Issued by
- Polk County, Ankeny City, Iowa
About this file
This document is a Request for Bid (RFB) issued by the Iowa Department of Administrative Services for the demolition and replacement of the existing HVAC controls system at the Alcoholic Beverages Division (ABD) facility located at 1918 SE Hulsizer Road, Ankeny, Iowa. The scope of work includes the removal of the existing building controls system, panels, wiring, conduit, controllers, sensors, and actuators, and the installation of a new controls system including control panels, controllers, wiring, conduits, sensors, software, and actuators. The existing HVAC system is a Siemens Desigo controls system. The project must be coordinated with the facility owner, as they are replacing the boilers under a separate project. Plenum rated cabling will be required in the office area, and protective plastic sheeting must be provided over office desks and equipment to prevent dust and debris. The owner has first salvage rights to all removed controls components.
Pricing and funding details are not provided in this document. The contract will be awarded to the responsive and responsible bidder that submits the lowest total bid price. There is no indication of any set asides or incumbents. The contract term and any renewal options are also not specified.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTE:
IT IS THE INTENT OF THIS PROJECT TO COMPLETELY REPLACE
THE ENTIRETY OF THE EXISTING CONTROLS SYSTEMS. THE
SCOPE OF WORK SHALL INCLUDE THE REMOVAL OF THE
EXISTING BUILDING CONTROLS SYSTEM, PANELS, WIRING,
CONDUIT, CONTROLLERS, SENSORS, ACTUATORS, ETC.
THE NEW SYSTEM SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
FOLLOWING: CONTROL PANELS, CONTROLLERS, WIRING,
CONDUITS, SENSORS, SOFTWARE, ACTUATORS, ETC. THE
EXISTING SYSTEM IS SIEMENS DESIGO.
SCHEDULING AND PHASING OF PROJECT MUST BE
COORDINATED WITH OWNER.
NOTE THAT THE OWNER IS REPLACING THE BOILERS AS PART OF
A SEPARATE PROJECT. COORDINATE REQUIREMENTS WITH
OWNER.
PLENUM RATED CABLING WILL BE REQUIRED IN THE OFFICE
AREA.
PROVIDE PROTECTIVE PLASTIC SHEETING OVER OFFICE DESKS,
EQUIPMENT, ETC. TO PREVENT DUST AND DEBRIS WHILE
WORKING IN OFFICE AREA.
OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL CONTROLS
COMPONENTS. SPECIFIC EQUIPMENT MENTIONED FOR SALVAGE
ARE TECs, VALVES, DAMPER ACTUATORS, AND T-STATS.
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
SHEET INDEX CERTIFICATIONS
H
BA D E FC G H
AAuuttooddeesskk RReevviitt 22002222
ID
A
S R
F B
:9 -0
/8
/2
:2
:2
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
ABD Ankeny HVAC Controls Upgrade - #9312.00
Iowa Department of Administrative Services 1918 SE Hulsizer Dr, Ankeny, IA 50021
G000
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
P R
O J E
C T
N U
M B
E R
IS
S
U E
D F
O R
C
O N
S T
R U
C T
IO
N
P R
O J E
C T
I S
S U
E D
A T
E
/0
/2
General
G000 COVERSHEET
Mechanical
M101 HVAC FLOOR PLANS - HVAC
M500 RTU-1 AND RTU-2 CONTROLS
M502 BOILER PLANT CONTROLS
M503 MECHANICAL CONTROLS MISCELLANEOUS
M504 MECHANICAL CONTROLS MISCELLANEOUS
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
MY LICENSE RENEWAL DATE IS DECEMBER 31,
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
PRINTED OR TYPED NAME
SIGNATURE DATE
LICENSE NUMBER
Travis L. Sprenger
MECHANICAL SHEETS
24039
MECHANICAL ENGINEER
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
MY LICENSE RENEWAL DATE IS DECEMBER 31,
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
PRINTED OR TYPED NAME
SIGNATURE DATE
LICENSE NUMBER
Kevin J. Bruxvoort
ELECTRICAL PORTIONS OF MECHANICAL SHEETS
19927
ELECTRICAL ENGINEER
IDAS RFB: 931200-01
AMumm Text Box 9/8/2023
AMumm Text Box 9/11/2023
T
T T
T T
T
T T
T T
T
P
P P
M
P
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
C O
T
T
T
T
T
FPVAV-1A
FPVAV-1B
FPVAV-1D
FPVAV-1E
FPVAV-105
FPVAV-106
FPVAV-103
FPVAV-108
FPVAV-104
FPVAV-107
FPVAV-102 FPVAV-109
FPVAV-101 FPVAV-110
RTU-2 RTU-1
FPVAV-111 FPVAV-120
FPVAV-112 FPVAV-119
FPVAV-114 FPVAV-117
FPVAV-115
FPVAV-116
15,000 GALLON FUEL TANK
GENERATOR
JP-1
FP-1
B-1
B-2
B-3
P-1 P-2
M01
M05
M03 M04
M06
M07
M02
M02
M02
M02
M02
M02
M02
M02
M02
M02
M02 M02
M02
EF-1
RF-1
M23
M23
FPVAV-113 FPVAV-118
FPVAV-O103
M02
WAREHOUSE
WAREHOUSE
WAREHOUSE
WAREHOUSE
AC-3
M17
BP-1
BP-2
BP-3
M13
FPVAV-O104
FPVAV-1C
M02
P1
P2
M
A
B
C
D
E
F
G
H
I
J
K
L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M14
M14
M14
M14
M14
M14
M14
M14
M14
M14
M14 M14
M14
M14
M14
M14
M15
M15 M15
M16
EF-FP
PRESSURE SENSOR
PANEL ON MEZZANINE
M15
M10
M10
H
SPACE HUMIDITY SENSOR
P
BUILDING PRESSURE
SENSOR (ON ROOF)
P
AC-3 DUCT
PRESSURE SENSOR
P
HOT WATER
DIFFERENTIAL
PRESSURE SENSOR
P
BUILDING
PRESSURE
SENSOR
TUR-231
TUR-230A
TUR-230B
TUR-227
TUR-232
TUR-226
TUR-225
TUR-224
TUR-234
TUR-200B
TUR-201B
TUR-201A
TUR-217
TUR-216
TUR-206
TUR-207
TUR-253
FCU-1
FCU-2
TUR-213
M08
M09
M08
M08
M08
M08
M08
M08
M08
M08
M08 M08
M08
M08
M08
M08
M08
M08
M08
TUR-200A
STAIR
S22
WELLNESS
ELEVATOR
MENS
STORAGE
SERVER ROOM
OFFICE
WORK ROOM
CORRIDOR
WOMENS
STORAGE
CORRIDOR
WORKSTATION
WORKSTATION
WORKSTATION
WORKSTATION
OPEN OFFICE
WORKSTATION
WORKSTATION
OPEN OFFICE
STAIR
S21
CORRIDOR
CORRIDOR
STAIR
S23
OFFICE
TRAIING
WAREHOUSE
STORAGE
OFFICE
OFFICE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
WORKSTATION
OFFICE
OPEN OFFICE
EF-157
EF-158
EF-253
EF-252
CU-2
CU-1
EF-153
EF-177
M10
M10
M10
M10
M10
M10
M12
M
A
B
C
D
E
F
G
H
I
J
K
L
15 16 17 18 19
EF-ELEV
M10
M18
M18
M18
M18
M19
M20
M21
M22 M24
MENS
WOMENS
STAIR
S12
ELEVATOR
OFFICE
TUR-157
TUR-109
TUR-110
TUR-108
TUR-112A TUR-107
TUR-106
TUR-105TUR-112B
TUR-119
TUR-104
TUR-120 TUR-102 TUR-103
TUR-101B
TUR-100B
TUR-100A
TUR-101A
TUR-153
TUR-121
TUR-127
TUR-170
TUR-122
TUR-126
BREAK ROOM
COPY ROOM
Room
CORRIDOR
OFFICE
108WORKSTATION
WORKSTATION
WORKSTATION
WORKSTATION
WORKSTATION
WORKSTATION
WORKSTATION
OPEN OFFICE
OFFICE
OFFICE
CONFERENCE
OFFICE
CONFERENCE
SEC
OFFICE
120OFFICE
BOARD ROOM
RECEPTION
WORKSTATION
WORKSTATION
STAIR
S11
VESTIBULE
MENS
WOMENS
CORRIDOR
OPEN OFFICE
WORKSTATION
STORAGE
OFFICE
TELECOM
OFFICE
122 OFFICE
OFFICE
OFFICE
STORAGE
STORAGE
125A
WAREHOUSE
MAINTENANCE
LOCKERS
WOMENS
176MENS
SHOWER
CORRIDOR
BREAK ROOM
STAIR
S13
M08
M08 M08
M08
M08 M08
M08
M08
M08
M08 M08
M08
M08M08
M08
M08 M08
M08
M08
M08
M08
M08
M08
M08
17 18 19
TUR-174
M08
TUR-172 M08
TUR-177
M08
M18
M18
M18
M18
M11
EF-158
GENERAL NOTE:
IT IS THE INTENT OF THIS PROJECT TO COMPLETELY REPLACE
THE ENTIRETY OF THE EXISTING CONTROLS SYSTEMS. THE
SCOPE OF WORK SHALL INCLUDE THE REMOVAL OF THE
EXISTING BUILDING CONTROLS SYSTEM, PANELS, WIRING,
CONDUIT, CONTROLLERS, SENSORS, ACTUATORS, ETC.
THE NEW SYSTEM SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
FOLLOWING: CONTROL PANELS, CONTROLLERS, WIRING,
CONDUITS, SENSORS, SOFTWARE, ACTUATORS, ETC. THE
EXISTING SYSTEM IS SIEMENS DESIGO.
SCHEDULING AND PHASING OF PROJECT MUST BE
COORDINATED WITH OWNER.
NOTE THAT THE OWNER IS REPLACING THE BOILERS AS PART OF
A SEPARATE PROJECT. COORDINATE REQUIREMENTS WITH
OWNER.
PLENUM RATED CABLING WILL BE REQUIRED IN THE OFFICE
AREA.
PROVIDE PROTECTIVE PLASTIC SHEETING OVER OFFICE DESKS,
EQUIPMENT, ETC. TO PREVENT DUST AND DEBRIS WHILE
WORKING IN OFFICE AREA.
OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL CONTROLS
COMPONENTS. SPECIFIC EQUIPMENT MENTIONED FOR SALVAGE
ARE TECs, VALVES, DAMPER ACTUATORS, AND T-STATS.
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
AAuuttooddeesskk RReevviitt 22002222
ID
A
S R
F B
:9 -0
/8
/2
:2
:3
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
H V
A C
F L O
O R
P L A
N S
H
V A
C
C O
N S
T R
U C
T
IO
N
T L S
L D
F
/0
/2
M101
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
N
03/64" = 1'-0"A6
FIRST FLOOR PLAN - HVAC
32'
N
03/64" = 1'-0"G6
SECOND FLOOR PLAN - HVAC
32'
KEYNOTES
KEY NOTE
M01 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO RTU. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR ROOF TOP UNITS RTU-1 AND RTU-2.
M02 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO FAN POWERED VAV BOXES. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR FAN POWERED VAV
BOXES.
M03 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO BOILERS AND PUMPS. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR BOILERS AND PUMPS.
M04 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO SECONDARY PUMPS. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR SECONDARY PUMPS.
M05 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO FIRE AND JOCKEY PUMPS. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR MONITORING THE FIRE
PUMP AND JOCKEY PUMP.
M06 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO GENERATOR. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR MONITORING THE STATUS OF THE
GENERATOR.
M07 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO FUEL TANK MONITORING SYSTEM. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR MONITORING
THE FUEL TANK MONITORING SYSTEM.
M08 REMOVE ALL EXISTING BAS COMPONENTS, THERMOSTATS, ACCESSORIES, AND WIRING CONNECTED TO VAV BOXES. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR VAV BOXES. INSTALL A LABEL ON THE CEILING GRID/TILE BELOW THE VAV BOX INDICATING THE VAV IDENTIFICATION NUMBER.
M09 PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS TO PROVIDE MONITORING FOR THE STATUS OF FCUS SERVING THE SERVER ROOM.
M10 CONNECT FAN TO BAS TO MONITOR FAN STATUS.
M11 TUR-101A AND TUR-101B SHALL OPERATE IN TANDEM USING ONE THERMOSTAT.
M12 LOCATION OF EXISTING COMPUTER WORKSTATION. PROVIDE NEW COMPUTER WORKSTATION. TURN EXISTING COMPUTER WORKSTATION OVER TO OWNER.
M13 LOCATION OF EXISTING DDC CONTROL PANELS. REMOVE EXISTING PANELS AND PROVIDE NEW PANELS.
M14 REMOVE EXISTING THERMOSTAT AND PROVIDE NEW THERMOSTAT. THERMOSTAT TO BE LOCATED ON COLUMN ADJACENT TO FPVAV AT AN ELEVATION OF 12' AFF.
M15 REMOVE EXISTING PRESSURE SENSOR AND PROVIDE AN NEW PRESSURE SENSOR IN THIS LOCATION.
M16 REMOVE EXISTING MONITORING FOR WATER PUMPS. PROVIDE NEW MONITORING FOR PUMP STATUS BY BAS.
M17 REMOVE ALL EXISTING BAS COMPONENTS, ACCESSORIES, AND WIRING CONNECTED TO AC-3. PROVIDE NEW BAS COMMUNICATION DEVICES AND CONTROLS FOR AIR HANDLING UNIT AC-3.
M18 REMOVE AND REINSTALL CEILING TILES AS REQUIRED TO REMOVE EXISTING CONTROLS COMPONENTS AND FOR INSTALLATION OF NEW CONTROLS. REPLACE ANY CEILING TILES DAMAGED DURING
CONSTRUCTION.
M19 PROVIDE MONITORING OF LIEBERT EXM UPS SYSTEM. MONITOR NORMAL POWER LOSS, LOW BATTERY ALARM AND OVER VOLTAGE ALARMS.
M20 PROVIDE MONITORING OF ENCELIUM LIGHTING CONTROL SYSTEM. MONITOR TROUBLE ALARMS FROM LIGHTING CONTROL SYSTEM.
M21 PROVIDE MONITORING OF SIEMENS FIRE ALARM SYSTEM. MONITOR COMMON ALARM, SUPERVISORY ALARM AND PANEL IN TEST MODE.
M22 PROVIDE MONITORING FOR CCTV AND SECURITY SYSTEM. MONITOR ALARM ACTIVATION, TROUBLE ALARM AND DOOR AJAR.
M23 REMOVE ALL EXISTING BAS COMPONENTS, THERMOSTATS, ACCESSORIES, AND WIRING CONNECTED TO FAN POWERED VAV BOXES. PROVIDE NEW THERMOSTAT, BAS COMMUNICATION DEVICES AND
CONTROLS FOR FAN POWERED VAV BOXES.
M24 BAS SYSTEM SHALL BE CONNECTED TO UPS AND GENERATOR.
N.C.
DX
SA
LOCATE ¾ DISTANCE
DOWN LONGEST DUCT
H
L
AI - SUPPLY AIR STATIC PRESSURE 3
EA
BV - MIXED AIR DAMPER STATUS
N.O.
N.C.
OA
RA
AI - SUPPLY AIR TEMP
SF
M
M
TMM
BI - BUILDING STATIC SENSOR
HL
M
BO - SUPPLY DAMPER
BI - SUPPLY AIR DAMPER STATUS
TO OTHER RTU
RTU-1 AND RTU-2
BI - HIGH STATIC SHUTDOWN
H L
BI - RETURN AIR SMOKE DETECTOR
S
AI - RETURN AIR TEMP
T
B U
IL
D
IN
G
I N
T E
R
IO
R
B U
IL
D
IN
G
E X
T E
R
IO
R
AI - ZONE HUMIDITY
H
AI - OUTSIDE AIR TEMPERATURE
T
BI - SUPPLY AIR SMOKE DETECTOR
S
AO - ZONE HUMIDITY SETPOINT
BI - RTU ALARM
BO - RTU ENABLE
RF
M
SMOKE DETECTOR TO COMMUNICATE WITH
FIRE ALARM SYSTEM AS WELL AS BAS
SMOKE DETECTOR TO COMMUNICATE WITH
FIRE ALARM SYSTEM AS WELL AS BAS
BV - RELIEF FAN STATUS
CT
BV - SUPPLY FAN STATUS
CT
REPLACE DAMPER ACTUATORS
REPLACE DAMPER ACTUATORS
AI - FILTER DIFFERENTIAL
PRESSURE
H L H
PROVIDE FILTER DIFFERENTIAL SENSOR
SA
LOCATE ¾ DISTANCE
DOWN LONGEST DUCT
H
L
AI - SUPPLY AIR STATIC PRESSURE 2
SA
LOCATE ¾ DISTANCE
DOWN LONGEST DUCT
H
L
AI - SUPPLY AIR STATIC PRESSURE 1
HARDWIRED
WITH AIR DAMPENING DEVICE
(VAISALA SPH-20 OR SIMILAR)
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2022Autodesk Revit 2022
ID
A
S R
F B
:9 -0
/8
/2
:3
:0
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
R T
U -1
A N
D R
T U
-2 C
O N
T R
O L S
C O
N S
T R
U C
T
IO
N
T L S
T L S
/0
/2
M500
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
NOT TO SCALED4
RTU-1 AND RTU-2 CONTROLS SCHEMATIC - RF DX GAS
RTU-1 AND RTU-2 - ON-OFF CONTROL WITH SUPPLY AIR ISOLATION DAMPER
GENERAL REQUIREMENTS
THE RTUS SHALL BE CONTROLLED BY THEIR OWN PACKAGED CONTROL SYSTEM. THE UNITS ARE
MANUFACTURED BY TRANE, MODEL INTELLIPAK II SXHJ13040A0162LA5J55K1000B00C0000F01A0.
THE BAS MONITORS AND COMMUNICATES BUILDING INFORMATION AND SETPOINTS TO THE
PACKAGED CONTROL SYSTEMS OF RTU-1 AND RTU-2.
RTU-1 AND RTU-2 CAN SUPPLY CONDITIONED AIR TO THE SPACE INDIVIDUALLY OR TOGETHER AS A
DUPLEX SYSTEM. BOTH AHUS ARE CONNECTED BY A COMMON SUPPLY AIR DUCT HEADER. EACH
RTU HAS A SEPARATE WILD RETURN AIR DUCT FROM THE WAREHOUSE AREA.
EACH RTU IS SERVED BY A SUPPLY AIR ISOLATION DAMPER. THE SUPPLY AIR RTU ISOLATION
DAMPER IS OPENED-CLOSED BY THE BAS DDC PANEL.
TO START THE RTU, FIRST THE BAS OPENS THE APPROPRIATE RTU ISOLATION DAMPER. THE
DAMPER END SWITCH STATUS INDICATES TO THE BAS DDC PANEL THAT THE DAMPER IS OPEN AND
THE BAS SYSTEM COMMANDS THE RTU TO START.
WHEN AN RTU IS ONLINE AND IS UNABLE TO MAINTAIN SPACE SETPOINT TEMPERATURE FOR A
PERIOD OF 30 MINUTES (ADJ.), THE LEAD RTU IS STOPPED, BOTH RTU ISOLATION DAMPERS ARE
PROVEN OPENED AND THEN BOTH RTUS ARE COMMANDED ON BY THE BAS SYSTEM. THEY SHALL
RAMP UP THEIR FANS IN UNISON TO MEET SUPPLY DUCT STATIC PRESSURE SETPOINT.
WHEN AN RTU FAILS, SUCH THAT THE RTU IS SHUTDOWN, ITS ISOLATION DAMPER IS CLOSED BY THE BAS AND THE LAG RTU IS STARTED UP PER THE SEQUENCE DESCRIBED ABOVE OR CONTINUES
TO RUN AND AN ALARM IS ISSUED TO THE BAS SYSTEM.
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
RTU RUNTIME:
THE BAS SHALL MONITOR AND LOG RTU RUNTIME. IMPORT RUNTIME FROM EXISTING CONTROLS
SYSTEM.
LEAD AHU WILL SWAP EACH WEEK. IF THE CURRENT LEAD AHU SUPPLY FAN RUNTIME EXCEEDS
THAT OF THE LAG AHU, IT WILL MAINTAIN LEAD STATUS.
HIGH STATIC SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC
SHUTDOWN SIGNAL. HIGH STATIC SHUTDOWN SHALL BE SET AT 3 IN WC (ADJ).
SUPPLY AND RETURN AIR SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR OR
RETURN AIR SMOKE DETECTOR STATUS.
AHU OPTIMAL START:
THE UNIT SHALL START PRIOR TO SCHEDULED OCCUPANCY BASED ON THE TIME NECESSARY FOR
THE ZONES TO REACH THEIR OCCUPIED SETPOINTS. THE START TIME SHALL AUTOMATICALLY
ADJUST BASED ON CHANGES IN OUTSIDE AIR TEMPERATURE AND ZONE TEMPERATURES.
SUPPLY FAN:
THE PACKAGED UNIT CONTROLLER SHALL CONTROL THE SUPPLY FAN. THE PACKAGED UNIT
CONTROLLER SHALL COMMUNICATE SUPPLY FAN STATUS WITH THE BAS.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE BAS SHALL MEASURE DUCT STATIC PRESSURE AT THE END OF EACH BRANCH MAIN. THE BAS
SHALL REPORT THE LOWEST DUCT STATIC PRESSURE TO THE RTU. THE UNIT PACKAGED
CONTROLLER SHALL MODULATE THE SUPPLY FAN SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT. THE STATIC PRESSURE SETPOINT SHALL BE RESET BASED UPON THE POSITION OF THE ZONE DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE UNTIL AT LEAST ONE ZONE
DAMPER IS NEARLY WIDE OPEN.
• THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.5 IN H2O (ADJ.).
• IF NO ZONE DAMPER IS NEARLY WIDE OPEN, THE SETPOINT SHALL INCREMENTALLY RESET
DOWN TO A MINIMUM OF 1.3 IN H2O (ADJ.) .
• AS ONE OR MORE DAMPERS NEARS THE WIDE OPEN POSITION, THE SETPOINT SHALL
INCREMENTALLY RESET UP TO A MAXIMUM OF 1.8 IN H2O (ADJ.).
THE BAS SHALL ALSO COMMUNICATE WITH RTU-1 AND RTU-2 TO DETERMINE IF THE COOLING
COMPRESSORS ARE ON. IF THE COMPRESSORS ARE ON, THE STATIC PRESSURE SETPOINT SHALL
BE SET AT 2.5 IN H20 (ADJ.) UNTIL THE COMPRESSORS ARE TURNED OFF.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.)
GREATER THAN SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.)
LESS THAN SETPOINT.
SUPPLY AIR TEMPERATURE SETPOINT - OPTIMIZED:
THE BAS SHALL SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY
AIR TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING REQUIREMENTS. THE BAS SHALL
COMMUNICATE THE SETPOINT WITH THE PACKAGED UNIT CONTROLLER.
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING BASED ON ZONE
COOLING REQUIREMENTS AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.).
• AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO
A MINIMUM OF 53°F (ADJ.).
• AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A
MAXIMUM OF 62°F (ADJ.) .
DEHUMIDIFICATION:
THE BAS CONTROLLER SHALL MEASURE THE SPACE HUMIDITY AND PLACE THE RTU INTO
DEHUMIDIFICATION MODE AS FOLLOWS.
• WHEN THE ZONE HUMIDITY IS GREATER THAN 60% (ADJ) RH, THE BAS SHALL
INCREMENTALLY RESET THE SUPPLY AIR TEMPERATURE SETPOINT DOWN TO A MINIMUM
TEMPERATURE OF 53°F (ADJ.).
COOLING STAGES:
THE UNIT PACKAGED CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STAGE
THE COOLING TO MAINTAIN ITS COOLING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN
SETPOINT FOR 15 MINUTES (ADJ.).
BUILDING STATIC PRESSURE CONTROL:
WAREHOUSE BUILDING STATIC PRESSURE CONTROL IS CONTROLLED WITH THE BAS BUILDING
STATIC PRESSURE SENSOR AND DDC CONTROLLER SIGNAL AND LOOP OUTPUT TRANSFERRED TO
THE RTU CONTROLLER FOR CONTROL OF THE RELIEF FAN. THE SIGNAL ADJUSTS THE SET-POINT OF THE RTU CONTROLLER RELIEF AIR CONTROL LOOP. WAREHOUSE WILL CONTROL AT A POSITIVE
0.05 IN WC (ADJ.) COMPARED TO OUTSIDE AIR.
THE PACKAGED UNIT CONTROLLER SHALL COMMUNICATE RELIEF FAN STATUS WITH THE BAS.
ECONOMIZER:
THE UNIT PACKAGED CONTROLLER SHALL CONTROL ECONOMIZER MODE. THE BAS SHALL BE ABLE
TO COMMUNICATE SETPOINTS TO THE UNIT PACKAGED CONTROLLER.
RETURN AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SUPPLY AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
LOW SUPPLY AIR TEMP x
LOW SUPPLY AIR STATIC PRESSURE x
LOW RETURN AIR TEMP x
LOW ZONE HUMIDITY x
HIGH SUPPLY AIR TEMP x
HIGH SUPPLY AIR STATIC PRESSURE x
HIGH RETURN AIR TEMP x
HIGH ZONE HUMIDITY x
FILTER CHANGE REQUIRED x
SCHEDULE x
SUPPLY AIR TEMP SETPOINT x x x
SUPPLY AIR STATIC PRESSURE SETPOINT x x x
SPACE HUMIDITY SETPOINT x x x
RTU ENABLE x x x
SUPPLY DAMPER x x x
SUPPLY AIR DAMPER STATUS x x x
RTU ALARM x x x
BUILDING STATIC PRESSURE x x x
RELIEF FAN STATUS x x x
SUPPLY FAN STATUS x
MIXED AIR DAMPER STATUS x x
SUPPLY AIR SMOKE DETECTOR x x x x
RETURN AIR SMOKE DETECTOR x x x x
HIGH STATIC SHUTDOWN x x x x
FILTER DIFFERENTIAL PRESSURE x x x x
SUPPLY AIR TEMP x x x
SUPPLY AIR STATIC PRESSURE 3 x x x x
SUPPLY AIR STATIC PRESSURE 2 x x x x
SUPPLY AIR STATIC PRESSURE 1 x x x x
RETURN AIR TEMP x x x
ZONE HUMIDITY x x x
OUTSIDE AIR TEMP x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - RTU-1 AND RTU-2
EF
N.C.
DX
BV - COOLING STAGE 1
BV - COOLING STAGE 2
VFD
BV - SUPPLY FAN START/STOP
BV - SUPPLY FAN STATUS
AV - SUPPLY FAN VFD SPEED
BV - SUPPLY FAN VFD FAULT
SA
LOCATE ¾ DISTANCE
DOWN LONGEST DUCT
H
L
AI - SUPPLY AIR STATIC PRESSURE
BV - EXHAUST FAN START/STOP
BV - EXHAUST FAN STATUS
AV - EXHAUST FAN VFD SPEED
BV - EXHAUST FAN VFD FAULT
VFD
EA
BI - RETURN AIR SMOKE DETECTOR
AI - FILTER DIFFERENTIAL
PRESSURE
AV - MIXED AIR TEMP
AV - EXHAUST AIR DAMPER
N.C.
AI - RETURN AIR TEMP
OA
RA
AI - SUPPLY AIR TEMP
SF
GAS
BV - HEATING STAGE 1
BV - HEATING STAGE 2
AV - OUTSIDE AIR DAMPER
T
M M
CT
S
T
M
CT
H L
H TM
BI - BUILDING STATIC SENSOR
HL
AC-3 PACKAGED UNIT
BI - SUPPLY AIR SMOKE DETECTOR
S
SMOKE DETECTOR TO COMMUNICATE WITH
FIRE ALARM SYSTEM AS WELL AS BAS
SMOKE DETECTOR TO COMMUNICATE WITH
FIRE ALARM SYSTEM AS WELL AS BAS
REPLACE DAMPER
ACTUATORS
REPLACE DAMPER
ACTUATORS
PROVIDE FILTER DIFFERENTIAL SENSOR
B U
IL
D
IN
G
I N
T E
R
IO
R
B U
IL
D
IN
G
E X
T E
R
IO
R
BI - HIGH STATIC SHUTDOWN
H L
HARDWIRED
WITH AIR DAMPENING DEVICE
(VAISALA SPH-20 OR SIMILAR)
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2022Autodesk Revit 2022
ID
A
S R
F B
:9 -0
/8
/2
:3
:2
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
A C
-3 C
O N
T R
O L
S
C O
N S
T R
U C
T
IO
N
T L S
T L S
/0
/2
M501
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
NOT TO SCALEE4
AC-3 CONTROLS SCHEMATIC - RF DX GAS
AC-3 SEQUENCE OF OPERATIONS
GENERAL REQUIREMENTS
AC-3 SHALL BE CONTROLLED BY ITS OWN PACKAGED CONTROL SYSTEM. THE UNIT IS
MANUFACTURED BY TRANE, MODEL YCH600B4LW6B4NH50B0D0000JB02.
THE BAS MONITORS AND COMMUNICATES BUILDING INFORMATION AND SETPOINTS TO THE
PACKAGED CONTROL SYSTEM OF AC-3.
AC-3 SUPPLIES CONDITIONED AIR TO THE OFFICE AREA, WHERE VAV BOXES DISTRIBUTE AIR TO
EACH ZONE.
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
SUPPLY AND RETURN AIR SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY OR RETURN
AIR SMOKE DETECTOR STATUS.
AHU OPTIMAL START:
THE UNIT SHALL START PRIOR TO SCHEDULED OCCUPANCY BASED ON THE TIME NECESSARY FOR
THE ZONES TO REACH THEIR OCCUPIED SETPOINTS. THE START TIME SHALL AUTOMATICALLY
ADJUST BASED ON CHANGES IN OUTSIDE AIR TEMPERATURE AND ZONE TEMPERATURES.
SUPPLY FAN:
THE PACKAGED UNIT CONTROLLER SHALL CONTROL THE SUPPLY FAN.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE BAS SHALL MEASURE DUCT STATIC PRESSURE AND REPORT DUCT STATIC PRESSURE TO AC-3.
THE UNIT PACKAGED CONTROLLER SHALL MODULATE THE SUPPLY FAN SPEED TO MAINTAIN A
DUCT STATIC PRESSURE SETPOINT. THE STATIC PRESSURE SETPOINT SHALL BE RESET BASED
UPON THE POSITION OF THE ZONE DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE
UNTIL AT LEAST ONE ZONE DAMPER IS NEARLY WIDE OPEN.
• THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.5 IN H2O (ADJ.).
• IF NO ZONE DAMPER IS NEARLY WIDE OPEN, THE SETPOINT SHALL INCREMENTALLY RESET
DOWN TO A MINIMUM OF 1.3 IN H2O (ADJ.).
• AS ONE OR MORE DAMPERS NEARS THE WIDE OPEN POSITION, THE SETPOINT SHALL
INCREMENTALLY RESET UP TO A MAXIMUM OF 1.8 IN H2O (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.)
GREATER THAN SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.)
LESS THAN SETPOINT.
• SUPPLY FAN VFD FAULT.
EXHAUST FAN:
THE EXHAUST FAN SHALL RUN TO MAINTAIN OFFICE STATIC PRESSURE SETPOINT. THE BAS
BUILDING PRESSURE SENSOR SHALL COMMUNICATE WITH THE UNIT PACKAGED CONTROLS TO
MAINTAIN A BUILDING POSITIVE PRESSURE OF 0.05 IN WC (ADJ.) COMPARED TO OUTSIDE AIR.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH BUILDING STATIC PRESSURE
• LOW BUILDING STATIC PRESSURE
• EXHAUST FAN FAULT
SUPPLY AIR TEMPERATURE SETPOINT - OPTIMIZED:
THE BAS SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY AIR
TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING AND HEATING REQUIREMENTS. THE
BAS SHALL COMMUNICATE THE SETPOINT WITH THE PACKAGED UNIT CONTROLLER.
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING BASED ON ZONE
COOLING REQUIREMENTS AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.).
• AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO
A MINIMUM OF 53°F (ADJ.).
• AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A
MAXIMUM OF 62°F (ADJ.) .
COOLING STAGES:
THE UNIT PACKAGED CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STAGE
THE COOLING TO MAINTAIN ITS COOLING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN
SETPOINT FOR 15 MINUTES (ADJ.)
GAS HEATING STAGES:
THE PACKAGED UNIT CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STAGE
THE HEATING TO MAINTAIN ITS HEATING SETPOINT.
ECONOMIZER:
THE PACKAGED UNIT CONTROLLER SHALL CONTROL THE ECONOMIZER MODE. THE BAS SHALL BE
ABLE TO COMMUNICATE SETPOINTS TO THE UNIT PACKAGED CONTROLLER.
FILTER DIFFERENTIAL PRESSURE MONITOR:
THE PACKAGED UNIT CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE
FILTER AND COMMUNICATE THE FILTER CHANGE STATUS TO THE BAS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE
LIMIT (ADJ.).
MIXED AIR TEMPERATURE:
THE PACKAGED UNIT CONTROLLER SHALL MONITOR THE MIXED AIR TEMPERATURE AND USE AS
REQUIRED FOR ECONOMIZER CONTROL OR PREHEATING CONTROL.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
RETURN AIR TEMPERATURE:
THE BAS SHALL MONITOR THE RETURN AIR TEMPERATURE AND COMMUNICATE TO THE PACKAGED
UNIT CONTROLLER FOR USE AS REQUIRED FOR SETPOINT CONTROL OR ECONOMIZER CONTROL.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SUPPLY AIR TEMPERATURE:
THE BAS SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SUPPLY FAN RUNTIME EXCEEDED x
SUPPLY FAN IN HAND x
SUPPLY FAN FAILURE x
EXHAUST FAN RUNTIME EXCEEDED x
EXHAUST FAN IN HAND x
EXHAUST FAN FAILURE x
LOW SUPPLY AIR TEMP x
LOW SUPPLY AIR STATIC PRESSURE x
LOW RETURN AIR TEMP x
LOW MIXED AIR TEMP x
HIGH SUPPLY AIR STATIC PRESSURE x
HIGH RETURN AIR TEMP x
HIGH MIXED AIR TEMP x
FILTER CHANGE REQUIRED x x
SCHEDULE x
EMERGENCY SHUTDOWN x x x x
SUPPLY AIR TEMP SETPOINT x x x
SUPPLY AIR STATIC PRESSURE SETPOINT x x x
ECONOMIZER MIXED AIR TEMP SETPOINT x x x
SUPPLY FAN START/STOP x x x
EXHAUST FAN START/STOP x x x
HEATING STAGE 2 x x x
HEATING STAGE 1 x x x
COOLING STAGE 2 x x x
COOLING STAGE 1 x x x
SUPPLY FAN VFD FAULT x x x
SUPPLY FAN STATUS x x x
EXHAUST FAN VFD FAULT x x x
EXHAUST FAN STATUS x x x
BUILDING STATIC SENSOR x x x
SUPPLY AIR SMOKE DETECTOR x x x x
RETURN AIR SMOKE DETECTOR x x x x
SUPPLY FAN VFD SPEED x x x
EXHAUST FAN VFD SPEED x x x
OUTSIDE AIR DAMPER x x x
EXHAUST AIR DAMPER x x x
FILTER DIFFERENTIAL PRESSURE x x x
SUPPLY AIR STATIC PRESSURE x x x x
RETURN AIR TEMP x x x
OUTSIDE AIR TEMP x x x
MIXED AIR TEMP x x x
FILTER DIFFERENTIAL PRESSURE x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - AC-3
AI - OUTSIDE AIR TEMPERATURE
AI - BOILER 3 HOT
WATER SUPPLY TEMP
AI - BOILER 3 HOT
WATER SUPPLY TEMP
AI - PRIMARY HOT WATER RETURN TEMP
AI - PRIMARY HOT
WATER SUPPLY TEMP
BOILER2
BO - BOILER 2 ENABLE
BI - BOILER 2 STATUS
BI - BOILER 2 ALARM STATUS
BI - BOILER 2 LOW WATER LEVEL
BOILER3
BO - BOILER 3 ENABLE
BI - BOILER 3 STATUS
BI - BOILER 3 ALARM STATUS
BI - BOILER 3 LOW WATER LEVEL
AO - BOILER 3 HOT WATER
SUPPLY TEMP SETPOINT RESET
AO - BOILER 2 HOT WATER
SUPPLY TEMP SETPOINT RESET
STARTER
BO - CIRCULATION PUMP 3 START/STOP
BI - CIRCULATION PUMP 3 STATUS
BO - CIRCULATION PUMP 2 START/STOP
BI - CIRCULATION PUMP 2 STATUS
HWS
HWR
HWS
HWR
P1
P2
VFD
VFD
BO - HOT WATER PUMP 1 START/STOP
BI - HOT WATER PUMP 1 STATUS
BI - HOT WATER PUMP 2 STATUS
BO - HOT WATER PUMP 2 START/STOP
H
L
AI - HOT WATER
DIFFERENTIAL PRESSURE
AO - HOT WATER PUMP 1 VFD SPEED
BI - HOT WATER PUMP 1 VFD FAULT
AO - HOT WATER PUMP 2 VFD SPEED
BI - HOT WATER PUMP 2 VFD FAULT
M
CT
M
CT
T
T
T
T
M
CT
STARTER
M
CT
T
AI - BOILER 3 HOT
WATER RETURN TEMP
T
AI - BOILER 3 HOT
WATER RETURN TEMP
BOILER1
BO - BOILER 1 ENABLE
BI - BOILER 1 STATUS
BI - BOILER 1 ALARM STATUS
BI - BOILER 1 LOW WATER LEVEL
AO - BOILER 1 HOT WATER
SUPPLY TEMP SETPOINT RESET
BO - CIRCULATION PUMP 1 START/STOP
BI - CIRCULATION PUMP 1 STATUS
T
STARTER
M
CT
T
AI - BOILER 1 HOT
WATER SUPPLY TEMP
AI - BOILER 1 HOT
WATER RETURN TEMP
THREE BOILER SYSTEM WITH CONDENSING BOILERS, PRIMARY SECONDARY FLOW.
COORDINATE CONTROLS SCOPE OF WORK WITH BOILER REPLACEMENT PROJECT UNDER A
SEPARATE CONTRACT. CONTACT OWNER FOR MORE INFORMATION.
BOILER SYSTEM RUN CONDITIONS:
THE BOILER SYSTEM SHALL BE ENABLED TO RUN WHENEVER:
• A DEFINABLE NUMBER OF HOT WATER COILS NEED HEATING.
• AND OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
TO PREVENT SHORT CYCLING, THE BOILER SYSTEM SHALL RUN FOR AND BE OFF FOR MINIMUM
ADJUSTABLE TIMES (BOTH USER DEFINABLE), UNLESS SHUTDOWN ON SAFETIES OR OUTSIDE AIR
CONDITIONS.
THE BOILER SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.
THE BOILER SYSTEM SHALL ALSO RUN FOR FREEZE PROTECTION WHENEVER THE OUTSIDE AIR
TEMPERATURE IS LESS THAN 38°F (ADJ.).
THE BAS SHALL MONITOR AND LOG BOILER AND PUMP RUNTIME. IMPORT RUNTIME FROM EXISTING
CONTROLS SYSTEM.
BOILER SAFETIES:
THE FOLLOWING SAFETIES SHALL BE MONITORED:
• BOILER ALARM.
• LOW WATER LEVEL.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• BOILER ALARM.
• LOW WATER LEVEL ALARM.
HOT WATER PUMP LEAD/LAG OPERATION:
THE TWO HOT WATER PUMPS SHALL OPERATE IN A LEAD/LAG FASHION.
• THE LEAD PUMP SHALL RUN FIRST.
• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE LEAD PUMP SHALL
TURN OFF.
• ON DECREASING HOT WATER DIFFERENTIAL PRESSURE, THE LAG PUMP SHALL STAGE ON
AND RUN IN UNISON WITH THE LEAD PUMP TO MAINTAIN HOT WATER DIFFERENTIAL
PRESSURE SETPOINT.
THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER
SELECTABLE):
• MANUALLY THROUGH A SOFTWARE SWITCH
• IF PUMP RUNTIME (ADJ.) IS EXCEEDED
• DAILY
• WEEKLY
• MONTHLY
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HOT WATER PUMP
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.
• VFD FAULT.
HOT WATER DIFFERENTIAL PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE HOT WATER DIFFERENTIAL PRESSURE AND MODULATE THE
HOT WATER PUMP VFDS IN SEQUENCE TO MAINTAIN ITS HOT WATER DIFFERENTIAL PRESSURE
SETPOINT.
THE FOLLOWING SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS SHALL BE FIELD
ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET THE REQUIREMENTS OF ACTUAL FIELD
CONDITIONS.
THE CONTROLLER SHALL MODULATE HOT WATER PUMP SPEEDS TO MAINTAIN A HOT WATER
DIFFERENTIAL PRESSURE OF 12 PSI (ADJ.). THE VFDS MINIMUM SPEED SHALL NOT DROP BELOW
20% (ADJ.).
ON DROPPING HOT WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL STAGE ON AND RUN TO
MAINTAIN SETPOINT AS FOLLOWS:
• THE CONTROLLER SHALL MODULATE THE LEAD VFD TO MAINTAIN SETPOINT.
• IF THE LEAD VFD SPEED IS GREATER THAN A SETPOINT OF 90% (ADJ.), THE LAG VFD SHALL
STAGE ON.
• THE LAG VFD SHALL RAMP UP TO MATCH THE LEAD VFD SPEED AND THEN RUN IN UNISON
WITH THE LEAD VFD TO MAINTAIN SETPOINT.
ON RISING HOT WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL STAGE OFF AS FOLLOWS:
• IF THE VFDS SPEEDS DROPS BACK TO 60% (ADJ.) BELOW SETPOINT, THE LAG VFD SHALL
STAGE OFF.
• THE LEAD VFD SHALL CONTINUE TO RUN TO MAINTAIN SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH HOT WATER DIFFERENTIAL PRESSURE: IF 25% (ADJ.) GREATER THAN SETPOINT.
• LOW HOT WATER DIFFERENTIAL PRESSURE: IF 25% (ADJ.) LESS THAN SETPOINT.
CIRCULATION PUMPS:
EACH CIRCULATION PUMP SHALL RUN ANYTIME ITS ASSOCIATED BOILER IS CALLED TO RUN AND
SHALL HAVE A USER DEFINABLE DELAY (ADJ.) ON STOP.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• CIRCULATION PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• CIRCULATION PUMP RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• CIRCULATION PUMP RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER-DEFINABLE
LIMIT.
BOILER LEAD / LAG / STANDBY OPERATION:
THE THREE BOILERS SHALL OPERATE IN A LEAD / LAG / STANDBY FASHION WHEN CALLED TO RUN
AND FLOW IS PROVEN.
• THE LEAD BOILER SHALL RUN FIRST.
• IF THE LEAD BOILER IS UNABLE TO MAINTAIN HEATING WATER SUPPLY TEMPERATURE
SETPOINT, THE LAG BOILER SHALL RUN IN COMBINATION WITH THE LEAD BOILER TO
MAINTAIN HEATING WATER SUPPLY TEMPERATURE SETPOINT.
• ON FAILURE OF THE LEAD BOILER, THE STANDBY BOILER SHALL RUN AND THE LEAD BOILER
SHALL TURN OFF.
THE DESIGNATED LEAD BOILER SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS: (USER
SELECTABLE):
• MANUALLY THROUGH A SOFTWARE SWITCH
• IF BOILER RUNTIME (ADJ.) IS EXCEEDED
• DAILY
• WEEKLY
• MONTHLY
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• EACH BOILER
• FAILURE: COMMANDED ON BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.
• LEAD BOILER FAILURE: THE LEAD BOILER IS IN FAILURE AND THE STANDBY BOILER IS ON.
HOT WATER SUPPLY TEMPERATURE SETPOINT RESET:
THE HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL RESET BASED ON OUTSIDE AIR
TEMPERATURE.
AS THE FACILITY'S HOT WATER VALVES OPEN BEYOND A USER DEFINABLE THRESHOLD (90% OPEN, TYP.), THE SETPOINT SHALL RESET TO A HIGHER VALUE WITH A MAXIMUM OF 140°F (ADJ.). ONCE THE HOT WATER COILS ARE SATISFIED (VALVES CLOSING) THEN THE SETPOINT SHALL GRADUALLY
LOWER TO A MINIMUM OF 90°F (ADJ.) OVER TIME TO REDUCE HEATING ENERGY USE.
THE BOILERS SHALL BE STAGED ON TO OPERATE WITHIN THEIR CONDENSING TEMPERATURE
RANGE. IF BOILERS CANNOT MAINTAIN BUILDING HEATING LOAD WITHIN THE CONDENSING
TEMPERATURE RANGE, THE HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL BE RESET UP AS FOLLOWS. AS THE FACILITY'S HOT WATER VALVES OPEN BEYOND A USER DEFINABLE THRESHOLD (90% OPEN, TYP.), AND THE WATER TEMPERATURE FAILS TO MAINTAIN SETPOINT FOR 30 MINUTES (ADJ) WHEN ALL BOILERS ARE OPERATING, AND OUTSIDE AIR FALLS BELOW 0 F, THE SETPOINT SHALL RESET TO A HIGHER VALUE (ADJ.). AS OUTSIDE AIR TEMPERATURE RISES FROM -20 F (ADJ.)
TO 0 F (ADJ.) THE HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL RESET DOWNWARDS
FROM 180 F (ADJ.) TO 140 F (ADJ.) FROM THE CURRENT BOILER SETPOINT. ONCE THE HOT WATER COILS ARE SATISFIED (VALVES CLOSING) THEN THE SETPOINT SHALL GRADUALLY LOWER OVER
TIME TO REDUCE HEATING ENERGY USE.
PRIMARY HOT WATER TEMPERATURE MONITORING:
THE FOLLOWING TEMPERATURES SHALL BE MONITORED:
• PRIMARY HOT WATER SUPPLY.
• PRIMARY HOT WATER RETURN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH PRIMARY HOT WATER SUPPLY TEMP: IF GREATER THAN 190°F (ADJ.).
• LOW PRIMARY HOT WATER SUPPLY TEMP: IF LESS THAN 80°F (ADJ.).
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2022Autodesk Revit 2022
ID
A
S R
F B
:9 -0
/8
/2
:2
:3
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
B O
IL
E
R P
L A
N T
C O
N T
R O
L S
C O
N S
T R
U C
T
IO
N
T L S
L D
F
/0
/2
M502
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
TOTAL HARDWARE (29) TOTAL SOFTWARE (59)
TOTALS 9 5 16 8 2 0 0 0 34 42 41
LOW PRIMARY HOT WATER SUPPLY TEMP x
LOW HOT WATER DIFFERENTIAL PRESSURE x
LEAD BOILER FAILURE x x
HOT WATER PUMP 2 RUNTIME EXCEEDED x
HOT WATER PUMP 2 RUNNING IN HAND x
HOT WATER PUMP 2 FAILURE x
HOT WATER PUMP 1 RUNTIME EXCEEDED x
HOT WATER PUMP 1 RUNNING IN HAND x
HOT WATER PUMP 1 FAILURE x
HIGH PRIMARY HOT WATER SUPPLY TEMP x
HIGH HOT WATER DIFFERENTIAL PRESSURE x
CIRCULATION PUMP 3 RUNTIME EXCEEDED x
CIRCULATION PUMP 3 RUNNING IN HAND x
CIRCULATION PUMP 3 FAILURE x
CIRCULATION PUMP 2 RUNTIME EXCEEDED x
CIRCULATION PUMP 2 RUNNING IN HAND x
CIRCULATION PUMP 2 FAILURE x
CIRCULATION PUMP 1 RUNTIME EXCEEDED x
CIRCULATION PUMP 1 RUNNING IN HAND x
CIRCULATION PUMP 1 FAILURE x
BOILER 3 RUNTIME EXCEEDED x
BOILER 3 RUNNING IN HAND x
BOILER 3 LOW HOT WATER SUPPLY TEMP x
BOILER 3 HIGH HOT WATER SUPPLY TEMP x
BOILER 3 FAILURE x
BOILER 2 RUNTIME EXCEEDED x
BOILER 2 RUNNING IN HAND x
BOILER 2 LOW HOT WATER SUPPLY TEMP x
BOILER 2 HIGH HOT WATER SUPPLY TEMP x
BOILER 2 FAILURE x
BOILER 1 RUNTIME EXCEEDED x
BOILER 1 RUNNING IN HAND x
BOILER 1 LOW HOT WATER SUPPLY TEMP x
BOILER 1 HIGH HOT WATER SUPPLY TEMP x
BOILER 1 FAILURE x
OUTSIDE AIR TEMP x x
HOT WATER DIFFERENTIAL PRESSURE SETPOINT x x x
HOT WATER PUMP 2 START/STOP x x x
HOT WATER PUMP 1 START/STOP x x x
CIRCULATION PUMP 3 START/STOP x x x
CIRCULATION PUMP 2 START/STOP x x x
CIRCULATION PUMP 1 START/STOP x x x
BOILER 3 ENABLE x x
BOILER 2 ENABLE x x
BOILER 1 ENABLE x x
HOT WATER PUMP 2 VFD FAULT x x x
HOT WATER PUMP 2 STATUS x x x
HOT WATER PUMP 1 VFD FAULT x x x
HOT WATER PUMP 1 STATUS x x x
CIRCULATION PUMP 3 STATUS x x x
CIRCULATION PUMP 2 STATUS x x x
CIRCULATION PUMP 1 STATUS x x x
BOILER 3 STATUS x x x
BOILER 3 LOW WATER LEVEL x x x x
BOILER 3 ALARM STATUS x x x x
BOILER 2 STATUS x x x
BOILER 2 LOW WATER LEVEL x x x x
BOILER 2 ALARM STATUS x x x x
BOILER 1 STATUS x x x
BOILER 1 LOW WATER LEVEL x x x x
BOILER 1 ALARM STATUS x x x x
HOT WATER PUMP 2 VFD SPEED x x x
HOT WATER PUMP 1 VFD SPEED x x x
BOILER 3 HOT WATER SUPPLY TEMP SETPOINT RESET x x x
BOILER 2 HOT WATER SUPPLY TEMP SETPOINT RESET x x x
BOILER 1 HOT WATER SUPPLY TEMP SETPOINT RESET x x x
PRIMARY HOT WATER SUPPLY TEMP x x x
PRIMARY HOT WATER RETURN TEMP x x x
HOT WATER DIFFERENTIAL PRESSURE x x x
BOILER 3 HOT WATER SUPPLY TEMP x x x
BOILER 3 HOT WATER RETURN TEMP x x x
BOILER 2 HOT WATER SUPPLY TEMP x x x
BOILER 2 HOT WATER RETURN TEMP x x x
BOILER 1 HOT WATER SUPPLY TEMP x x x
BOILER 1 HOT WATER RETURN TEMP x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - BOILERS
NOT TO SCALEB3
CONTROLS SCHEMATIC - THREE BOILER, PRIMARY/SECONDARY SYSTEM
AO - REHEATING VALVE
HWS HWR
HW
AI - AIRFLOW AI - DISCHARGE AIR TEMP
AO - ZONE DAMPER
DASA
T M
BI - ZONE OVERRIDE
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
T
M
AI - ZONE CARBON DIOXIDE PPM
CO₂
BOARD ROOM ONLY
REPLACE VALVE ACTUATOR
REPLACE DAMPER ACTUATOR
VAV - HYDRONIC REHEAT
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING
MODES:
• OCCUPIED MODE (5 AM (ADJ.) TO 6 PM (ADJ.)): THE UNIT SHALL MAINTAIN
• A 72°F (ADJ.) SETPOINT WITH 5F DEADBAND
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
• A 85°F (ADJ.) COOLING SETPOINT.
• A 65°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT
BY A USER DEFINABLE AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A
USER DEFINABLE AMOUNT (ADJ.).
MINIMUM VENTILATION ON CARBON DIOXIDE (CO2) CONCENTRATION (IN BOARD ROOM):
WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE
THE ZONE CO2 CONCENTRATION AND MODULATE THE ZONE DAMPER OPEN ON RISING CO2
CONCENTRATIONS, OVERRIDING NORMAL DAMPER OPERATION TO MAINTAIN A CO2 SETPOINT OF
NOT MORE THAN 1620 PPM (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE CARBON DIOXIDE CONCENTRATION: IF THE ZONE CO2 CONCENTRATION
IS GREATER THAN 2000 PPM (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO TEMPORARILY ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR. THE SETPOINT SHALL REVERT BACK TO ITS ORIGINAL
SETTING AT 6 PM (ADJ.).
ZONE OPTIMAL START:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM
SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING
COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE:
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE
AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE
EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE
SCHEDULE.
VARIABLE VOLUME TERMINAL UNIT - FLOW CONTROL:
THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF
THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER
SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM
COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING
SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED ZONE
VENTILATION (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL
ENABLE HEATING TO MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SETPOINT.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM
UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE
DAMPER SHALL MODULATE BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE
MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SETPOINT, THE
CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE ZONE TEMPERATURE AT THE
SETPOINT.
REHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEATING
COIL VALVE OPEN ON DROPPING TEMPERATURE TO MAINTAIN ITS HEATING SETPOINT.
IF MORE HEAT IS REQUIRED, THE ZONE DAMPER SHALL MODULATE TO THE AUXILIARY HEATING
AIRFLOW (ADJ.).
REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:
THE CONTROLLER SHALL MEASURE THE DISCHARGE AIR TEMPERATURE AND LIMIT REHEATING IF
THE DISCHARGE AIR TEMPERATURE IS MORE THAN 95°F (ADJ.).
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F
(ADJ.).
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F
(ADJ.).
EXHAUST AND RELIEF FANS
RUN CONDITIONS - SCHEDULE:
THE FAN(S) SHALL RUN DURING OCCUPIED HOURS.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
BI - FAN STATUS
BO - FAN START/STOP
EA
M
CT
AO - REHEATING VALVE
HWS HWR
HW
AI - AIRFLOW
AI - DISCHARGE AIR TEMP
AO - ZONE DAMPER
DASA
T M
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
T
M
RA
3-WAY VALVES
LOCATED AT
END OF LOOPS
M
CT
CONTROL SCHEDULE
HEATING
SETPOINT
COOLING
SETPOINTROOM TEMPERATURE
VALVE OPEN
MAXIMUM AIR
SUPPLY AIR
REHEAT COIL VALVE
MINIMUM AIR
VALVE CLOSED
FAN OPERATION OCCUPIED
FAN OPERATION UNOCCUPIED
ON
OFF ONON
BO - FAN START/STOP
AO - FAN VFD SPEED
BI - FAN VFD FAULT
VFD
BI - FAN STATUS
REPLACE VALVE ACTUATOR
REPLACE DAMPER ACTUATOR
FAN POWERED VAV - HYDRONIC REHEAT
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING
MODES:
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN
• A 80°F (ADJ.) COOLING SETPOINT
• A 60°F (ADJ.) HEATING SETPOINT.
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
• A 90°F (ADJ.) COOLING SETPOINT.
• A 50°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT
BY A USER DEFINABLE AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A
USER DEFINABLE AMOUNT (ADJ.).
ZONE OPTIMAL START:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM
SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING
COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.
FAN OPERATION:
DURING OCCUPIED HOURS, THE FAN SHALL RUN CONTINUOUSLY AND SHALL MODULATE ITS
AIRFLOW TO MAINTAIN COOLING AND HEATING SETPOINTS.
WAREHOUSE UNITS EAST OF GRIDLINE 3: THE MAXIMUM AIRFLOW IS 3000 CFM AND THE MINIMUM
AIRFLOW IS 900 CFM.
WAREHOUSE UNITS WEST OF GRIDLINE 3: THE MAXIMUM AIRFLOW IS 1200 CFM AND THE MINIMUM
AIRFLOW IS 400 CFM.
SOUTHWEST OFFICE - FPVAV-O103: THE MAXIMUM AIRFLOW IS 600 CFM AND THE MINIMUM AIRFLOW
IS 300 CFM.
SOUTHWEST BREAK ROOM - FPVAV-O104: THE MAXIMUM AIRFLOW IS 800 CFM AND THE MINIMUM
AIRFLOW IS 300 CFM.
DURING UNOCCUPIED HOURS, THE FAN SHALL CYCLE TO MEET BUILDING LOAD.
VARIABLE VOLUME TERMINAL UNIT - FLOW CONTROL:
THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF
THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER
SHALL MODULATE BETWEEN THE MINIMUM AND THE MAXIMUM COOLING AIRFLOW (ADJ.)
UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING
SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED ZONE
VENTILATION (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL
ENABLE HEATING TO MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SETPOINT.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM
UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE
DAMPER SHALL MODULATE BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE
MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SETPOINT, THE
CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE ZONE TEMPERATURE AT THE
SETPOINT.
REHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEATING
COIL VALVE OPEN ON DROPPING TEMPERATURE TO MAINTAIN ITS HEATING SETPOINT.
REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:
THE CONTROLLER SHALL MEASURE THE DISCHARGE AIR TEMPERATURE AND LIMIT REHEATING IF
THE DISCHARGE AIR TEMPERATURE IS MORE THAN 95°F (ADJ.).
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F
(ADJ.).
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F
(ADJ.).
DATA CENTER UNIT (FCU-1 AND FCU-2)
GENERAL REQUIREMENTS
THE BAS SHALL MONITOR THE STATUS OF THE FCU'S, THE TEMPERATURE OF THE ROOM AND THE ROOM SETPOINT. THE UNITS ARE MINI SPLIT COOLING SYSTEMS AND SHALL RUN ACCORDING TO
THEIR OWN INTERNAL CONTROLS.
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN:
• A 71°F (ADJ.) COOLING SETPOINT
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT
BY A USER DEFINABLE AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE COOLING SETPOINTS AT THE
ZONE SENSOR.
DX
AI - ZONE TEMP
AI - ZONE SETPOINT ADJUST
T
M
FCU-1 AND FCU-2
BI - FCU STATUS
BI - JOCKEY PUMP STATUS
BI - FIRE PUMP STATUS
M
CT
M
CT
P
AI - FIRE SUPPLY
PRESSURE
BI - FAN STATUS
BO - FAN START/STOP
EA
M
CT
BI - EXHAUST AIR DAMPER STATUS
N.C.
BO - EXHAUST AIR DAMPER
TA
BI - TRANSFER AIR
DAMPER STATUS
BO - TRANSFER AIR DAMPER
AI - ZONE TEMP
T
FIRE PUMP ROOM
REPLACE DAMPER ACTUATORS
REPLACE DAMPER ACTUATORS
M
M
FIRE AND JOCKEY PUMP
GENERAL REQUIREMENTS
THE BAS SHALL MONITOR THE STATUS OF THE FIRE PUMP, JOCKEY PUMP AND FIRE SUPPLY
PRESSURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FIRE PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• JOCKEY PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• LOW WATER PRESSURE
EXHAUST FAN AND DAMPERS
RUN CONDITIONS - CONTINUOUS:
THE EXHAUST FAN SHALL RUN TO WHENEVER THE ZONE TEMPERATURE RISES ABOVE A ZONE
TEMPERATURE SETPOINT OF 85°F (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT
BY A USER DEFINABLE AMOUNT (ADJ.).
TRANSFER AND EXHAUST AIR DAMPERS:
THE TRANSFER AND EXHAUST AIR DAMPERS SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE DAMPERS SHALL CLOSE 30 SEC (ADJ.) AFTER THE FAN STOPS.
DAMPER STATUS:
THE FAN SHALL BE ENABLED AFTER THE DAMPERS' STATUSES HAVE PROVEN OPEN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2022Autodesk Revit 2022
ID
A
S R
F B
:9 -0
/8
/2
:2
:3
A
M
A u to d e s k D o c s
/2
IA
D
A S
A
B D
A n k e n y B
A S
H
V A
C C o n tr o l R e p la c e m e n t/
-M
E P
-R .r v t
M E
C H
A N
IC
A
L C
O N
T R
O L S
M
IS
C E
L L
A N
E O
U S
C O
N S
T R
U C
T
IO
N
T L S
L D
F
/0
/2
M503
A B
D A n k e n y H
V A
C C o n tr o ls
U p g ra d e
.0
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
S
E H u ls iz e r
D r, A n k e n y
IA
NOT TO SCALEF2
CONTROLS SCHEMATIC - VAV - HW REHEAT
NOT TO SCALED3
SEQUENCE - VAV - HW REHEAT - OFFICE
LOW ZONE TEMP x
LOW DISCHARGE AIR TEMP x
HIGH ZONE TEMP x
HIGH ZONE CARBON DIOXIDE CONCENTRATION x
HIGH DISCHARGE AIR TEMP x
SCHEDULE x
HEATING MODE x x
ZONE CARBON DIOXIDE PPM SETPOINT x x x
PERCENT OF TIME SATISFIED x x
HEATING SETPOINT x x x
ENVIRONMENTAL INDEX x x
DAT HEATING LIMIT x
COOLING SETPOINT x x x
AIRFLOW SETPOINT x x x
ZONE OVERRIDE x x x
ZONE DAMPER x x x
REHEATING VALVE x x x
ZONE TEMP x x x
ZONE SETPOINT ADJUST x x
ZONE CARBON DIOXIDE PPM x x x
DISCHARGE AIR TEMP x x x
AIRFLOW x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - VAV - HW REHEAT
NOT TO SCALEB3
CONTROLS SCHEMATIC - FAN - ON/OFF
NOT TO SCALEA3
SEQUENCE - EF - ON/OFF
FAN IN HAND x
FAN FAILURE x
FAN START/STOP x x x
FAN STATUS x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - FAN - ON/OFF
NOT TO SCALEE5
CONTROLS SCHEMATIC - FAN POWERED VAV - HW REHEAT
NOT TO SCALED6
SEQUENCE - FAN POWERED VAV - HW REHEAT WAREHOUSE
LOW ZONE TEMP x
LOW DISCHARGE AIR TEMP x
HIGH ZONE TEMP x
HIGH DISCHARGE AIR TEMP x
SCHEDULE x
HEATING MODE x x
PERCENT OF TIME SATISFIED x x
DAT HEATING LIMIT x
HEATING SETPOINT x x x
COOLING SETPOINT x x x
AIRFLOW SETPOINT x x x
FAN START/STOP x x x
FAN VFD FAULT x x
FAN STATUS x x x
FAN VFD SPEED x x x
ZONE DAMPER x x x
REHEATING VALVE x x x
ZONE TEMP x x x
ZONE SETPOINT ADJUST x x
DISCHARGE AIR TEMP x x x
AIRFLOW x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - FAN POWERED VAV - HW REHEAT - WAREHOUSE
NOT TO SCALEB2
CONTROLS SCHEMATIC - DATA CENTER UNIT
NOT TO SCALEA2
SEQUENCE - DATA CENTER UNIT
HIGH ZONE TEMP x
COOLING SETPOINT x x x
FCU STATUS x x x
ZONE TEMP x x x x
ZONE SETPOINT ADJUST x x
POINT NAME AI AO BI BO AV BV TREND ALARM
ALARM
METHOD
SHOW ON
GRAPHIC
NOTES
POINTS LIST - DATA CENTER UNIT
NOT TO SCALEB5
CONTROLS SCHEMATIC - FIRE AND JOCKEY PUMP
NOT TO SCALEA5
SEQUENCE - FIRE AND JOCKEY PUMP
HIGH ZONE TEMP x
FAN IN HAND x
FAN FAILURE x
TRANSFER AIR DAMPER IN HAND x
TRANSFER AIR DAMPER FAILURE x
EXHAUST AIR DAMPER IN HAND x
EXHAUST AIR DAMPER FAILURE x
COOLING SETPOINT x x x
TRANSFER AIR DAMPER x x x
FAN START/STOP x x x
EXHAUST AIR DAMPER x x x
TRANSFER AIR DAMPER STATUS x x x
FAN STATUS x x x
EXHAUST AIR DAMPER STATUS x x x
JOCKEY PUMP STATUS x x x
FIRE PUMP STATUS x x x
FIRE SUPPLY PRESSURE x x x
ZONE TEMPERATURE x x x
AI AO BI…