Revised Attachment A Equipment Schedule.pdf
PDF 19 KB Posted
- Attached to
- Cooling Tower
- Solicitation number
- S000000201
- Issued by
- Pulaski County, Little Rock City, Arkansas
About this file
This document is an Equipment Schedule for a Cooling Tower system for a state and local contract opportunity in Arkansas, specifically Pulaski County and the City of Little Rock. The schedule details the specifications for two Cooling Towers, including the flow rate, horsepower, RPM, voltage, and kilowatt requirements. It also provides information on the Cooling Tower Filtration System, including the pump package system and location. The contract opportunity involves the procurement of this Cooling Tower equipment and related services.
The document indicates that the Cooling Towers will be equipped with VFDs provided by the tower manufacturer, specifically ABB model ACH580 or an approved equivalent. Additional requirements include providing the VFDs with circuit breakers, bypass, BACnet interface, RTD, and NEMA 12 enclosures. The Cooling Towers have an operating weight of approximately 53,528 and 53,529 pounds.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Contract and Grant Disclosure Form.~4.pdf | ||
| Addenda 1 S000000201 Cooling Tower.pdf | ||
| S000000201 Bid Response Packet~1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EWT LWT
FLOW
RATE
HP RPM VOLT. PH kW VOLT. PH
CT-1
MECH
YARD
80 °F 95 °F 85 °F 3000 GPM 40 1800 460 V 3 12 Kw 460 V 3
CT-2
MECH
YARD
80 °F 95 °F 85 °F 3000 GPM 40 1800 460 V 3 12 Kw 460 V 3
MARK
SERVE
S
VOLTAGE
SSF-1 CT-1 460 V
SSF-2 CT-2 460 V
COOLING TOWERS
WATER DATA FAN DATA PER CELL BASIN HEATER DATA PER CELL
MARK LOCATION OSA WBTYPE REMARKS
2 Cell Crossflow
Cooling Tower
VFD PROVIDED BY TOWER MANUFACTURER,
VFD TO BE AN ABB MODEL ACH580, OR A
MODEL APPROVED BY ADH. PROVIDE WITH
CIRCUIT BREAKER, BYPASS, BACNET
INTERFACE, RTD AND A NEMA 12 ENCLOSURE
VFD PROVIDED BY TOWER MANUFACTURER,
VFD TO BE AN ABB MODEL ACH580, OR A
MODEL APPROVED BY ADH. PROVIDE WITH
CIRCUIT BREAKER, BYPASS, BACNET
INTERFACE, RTD AND A NEMA 12 ENCLOSURE
OPER. WEIGHT
53528 lb
53529 lb
ATTACHMENT A: COOLING TOWER EQUIPMENT SCHEDULE
S000000201 COOLING TOWER
REMARKS
PUMP PACKAGE SYSTEM
PUMP PACKAGE SYSTEM330 GPMPUMP ROOM
FLOW RATETYPE
Centrifugal Type Cooling Tower
Filtration System
330 GPM
Centrifugal Type Cooling Tower
Filtration System
LOCATION
PUMP ROOM
COOLING TOWER FILTER SYSTEM SCHEDULE
2 Cell Crossflow
Cooling Tower