Revised Attachment A Equipment Schedule.pdf

PDF 19 KB Posted

Attached to
Cooling Tower
Solicitation number
S000000201
Issued by
Pulaski County, Little Rock City, Arkansas

About this file

This document is an Equipment Schedule for a Cooling Tower system for a state and local contract opportunity in Arkansas, specifically Pulaski County and the City of Little Rock. The schedule details the specifications for two Cooling Towers, including the flow rate, horsepower, RPM, voltage, and kilowatt requirements. It also provides information on the Cooling Tower Filtration System, including the pump package system and location. The contract opportunity involves the procurement of this Cooling Tower equipment and related services.

The document indicates that the Cooling Towers will be equipped with VFDs provided by the tower manufacturer, specifically ABB model ACH580 or an approved equivalent. Additional requirements include providing the VFDs with circuit breakers, bypass, BACnet interface, RTD, and NEMA 12 enclosures. The Cooling Towers have an operating weight of approximately 53,528 and 53,529 pounds.

View the file

Other files

File Type Posted
Contract and Grant Disclosure Form.~4.pdf PDF
Addenda 1 S000000201 Cooling Tower.pdf PDF
S000000201 Bid Response Packet~1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EWT LWT

FLOW

RATE

HP RPM VOLT. PH kW VOLT. PH

CT-1

MECH

YARD

80 °F 95 °F 85 °F 3000 GPM 40 1800 460 V 3 12 Kw 460 V 3

CT-2

MECH

YARD

80 °F 95 °F 85 °F 3000 GPM 40 1800 460 V 3 12 Kw 460 V 3

MARK

SERVE

S

VOLTAGE

SSF-1 CT-1 460 V

SSF-2 CT-2 460 V

COOLING TOWERS

WATER DATA FAN DATA PER CELL BASIN HEATER DATA PER CELL

MARK LOCATION OSA WBTYPE REMARKS

2 Cell Crossflow

Cooling Tower

VFD PROVIDED BY TOWER MANUFACTURER,

VFD TO BE AN ABB MODEL ACH580, OR A

MODEL APPROVED BY ADH. PROVIDE WITH

CIRCUIT BREAKER, BYPASS, BACNET

INTERFACE, RTD AND A NEMA 12 ENCLOSURE

VFD PROVIDED BY TOWER MANUFACTURER,

VFD TO BE AN ABB MODEL ACH580, OR A

MODEL APPROVED BY ADH. PROVIDE WITH

CIRCUIT BREAKER, BYPASS, BACNET

INTERFACE, RTD AND A NEMA 12 ENCLOSURE

OPER. WEIGHT

53528 lb

53529 lb

ATTACHMENT A: COOLING TOWER EQUIPMENT SCHEDULE

S000000201 COOLING TOWER

REMARKS

PUMP PACKAGE SYSTEM

PUMP PACKAGE SYSTEM330 GPMPUMP ROOM

FLOW RATETYPE

Centrifugal Type Cooling Tower

Filtration System

330 GPM

Centrifugal Type Cooling Tower

Filtration System

LOCATION

PUMP ROOM

COOLING TOWER FILTER SYSTEM SCHEDULE

2 Cell Crossflow

Cooling Tower