Response to Queries_19NP4026Q0027_Supply, Installation and Commissioning of UPS systems
Solicitation number
19NP4026Q0027
Issued by

About this file

This document is a Questions and Answers (Q&A) clarification related to a Statement of Work (SOW) for Uninterruptible Power Supply (UPS) installation at the US Embassy Chancery compound in Maharajgunj.

The solicitation originally specified installation of two (2) 15kVA UPS units in parallel mode operation. However, site visits revealed insufficient space to accommodate two units while maintaining required installation and maintenance clearances. In response, the Embassy has clarified that offerors may propose a single 30kVA UPS unit (or approved equivalent) in lieu of the two 15kVA units, provided the proposed unit meets or exceeds all technical, environmental, and safety specifications outlined in Section IV of the SOW. The minimum battery backup time requirement of 10 minutes at full rated load remains a firm requirement regardless of configuration selection. Additionally, the Embassy acknowledges that the Eaton 9355 model referenced in the SOW is no longer in production and permits offerors to propose the Eaton 93T (30kVA Tower with internal battery) or another currently manufactured equivalent meeting the specifications. Offerors must verify and document the manufacturer-required clearances (front 900mm, rear 300mm, and top 300mm for ventilation) and confirm in their technical proposal that the proposed installation location in Closet across from Ground Floor North Wing Electrical Room 1181 can accommodate these clearances. Manufacturer documentation demonstrating the 10-minute backup time performance must be submitted as part of the technical proposal.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. UPS Configuration:

During the site visit, we observed that the available installation space is relatively small and limited for accommodating two UPS units while maintaining the required installation and maintenance clearances. However, the SOW specifies the installation of two (2) 15kVA UPS units. Kindly confirm whether we may propose one (1) 30kVA UPS unit (or approved equivalent) instead of two (2) 15kVA UPS units, provided that it meets the required electrical performance and can be installed within the available space, or whether our proposal should be based on the installation of two (2) 15kVA UPS units in accordance with the SOW.

We confirm that a single thirty (30) kVA UPS unit (or approved equivalent) may be proposed in lieu of two (2) 15kVA units, given the space constraints identified during the site visit. Offerors selecting this configuration must ensure the proposed unit meets or exceeds all technical, environmental, and safety specifications outlined in Section IV of the SOW

2. Battery Backup Time Requirement:

The SOW specifies a minimum battery backup time of 10 minutes at full load (for a 15kVA UPS). However, based on the manufacturer's technical specifications, the backup time depends on the UPS model, battery configuration, and the actual connected load. Kindly confirm whether the required battery backup duration shall be provided in accordance with the manufacturer's standard specifications for the proposed UPS configuration.

The minimum battery backup time requirement of 10 minutes at full rated load remains a firm requirement, regardless of whether the offeror proposes two (2) 15kVA units or one (1) 30kVA unit. Offerors shall submit manufacturer documentation demonstrating this performance as part of their technical proposal.

3. Site visit:

After our site visit at US embassy Chancery compound Maharajgunj for Verification, compatibility of Eaton 15 KVA UPS and location Inspection. Embassy requirement are two unit of Eaton 9355 15 KVA or equivalent UPS in parallel mode operation; for that required space is not enough, need two DB one for input with MCB Breaker and the other for System parallel Module. Space available is very limited not enough for all those items installation in this small room, Technically not suitable for two unit in parallel mode .

Eaton 9355 model 15 KVA UPS is obsolete model ( no more production). It is discontinued. New model of equivalent is Eaton 93T which is more advance in technology with touch screen and many more features.

It is recommended to use 30 KVA UPS Tower type with internal battery instead of two UPS due to lack of available space. Only single UPS will be suitable .

Minimum space requirement for UPS in front side 900 mm (fan and filter location) back side 300mm( in/out cable connectors ) and above 300 mm for proper ventilation and smooth running for long life.

Propose Eaton 93T 30 KVA UPS size are W=380mm D=740mm Height 1328mm.

Input/ Output AC cable shall be replace with High ratting , Input MCB and output DB/ MCB can be used existing one which has high ratting capable for handling 30 KVA .

• The Embassy accepts installation of a single thirty (30) kVA UPS Tower unit with internal battery, in lieu of two (2) 15kVA units in parallel, based on the space limitations identified during site visits by multiple offerors

• The Embassy acknowledges that the Eaton 9355 model referenced in the SOW is no longer in production. Offerors may propose the Eaton 93T (30kVA Tower, internal battery) or another currently manufactured equivalent, provided the proposed unit meets or exceeds all technical specifications in Section IV of the SOW

• The Embassy confirms that offerors are responsible for verifying and providing the manufacturer-required clearances (front, rear, and top) for the proposed unit and shall include this information in their technical proposal, along with confirmation that the proposed installation location (Closet across from Ground Floor North Wing Electrical Room 1181) can accommodate these clearances