20KVA / 18KW Industrial Backup Uninterruptable Power Supply (UPS) to replace the existing Gaseous Effluent Monitoring System (GEMS) UPS at the LaSalle Nuclear Generating Station. The UPS is required to be a double conversion, 3Ø, 208/120V AC, 4 Wire + Gnd, Wye Input / 3Ø, 208/120V AC, 4 Wire + Gnd, Wye Output. The successful vendor is required to be manufacturer certified to perform initial startup/commission and have the ability to perform initial startup on-site at the LaSalle Nuclear Generating Station. IEMA personnel will perform equipment installation at the LaSalle Nuclear Generating Station. Vendor will perform initial startup once installation is complete
GEMS UPS Technical Specifications
Tech Specs
Power
| Ratings |
| 20 KVA / 18W @ 0.9 P.F. |
| Topology |
| Double Conversion |
Input
| Input Voltage |
| 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Input Frequency |
| 60 Hz ± 5 Hz |
| Voltage Correction Range |
| 176-228.8V AC |
| Power Factor (Full Load) |
| 0.99 typical |
Output
| Waveform (On-Line) |
| Sinewave |
| Waveform (On-Battery) |
| Sinewave |
| Output Voltage (RMS) |
| 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Efficiency (Full Load / On-Line) |
| 91% typical |
| Input Current Distortion |
| < 5% THD |
| Overload Capabilities |
| 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) |
Battery
| Battery Type |
| VRLA, 9AH, maintenance free (Field replacable) |
| Typical Backup Time (Full Load) |
| > 100 min @ full load (> 10 hours @ 15% full load) |
Operation / General
| Diagnostics |
| Full system self-test @ startup |
| UPS Bypass |
| Automatic on overload or UPS failure |
| On-Line Transfer Time |
| 1 ms typical |
| Audible Noise (Full Load @ 1m) |
| < 58 dBA |
Communications
| Minimum Requirements |
| Graphical LCD w/ backlight display, RS-232, dry contact relay outputs for On-Battery/Power Loss and UPS On-Bypass status signals, network communications card |
| Network type |
| Factory Installed MS Network Card (SNMP) |
Certifications
Warranty
| Standard |
| 1 Year Full Parts & Labor |
| Extended |
| Up to 4 Years additional coverage, including 8 hour or less onsite emergency response and annual preventative maintenance. |
Customer Service
| Initial Start Up |
| Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ LaSalle Nuclear Generating Station |
| Tech Support Availability |
| 24/7 (Unlimited) |