B-27662 Question and Answer.docx

DOCX document 12 KB Posted

Attached to
EMA - LaSalle GEMS UPS - 20KVA
Solicitation number
22-588IEMA-MGMTA-B-28250
Issued by
Lasalle County, Manteno Village, Illinois

About this file

This document is a question and answer related to a state and local contract opportunity for the EMA - LaSalle GEMS UPS - 20KVA project in the state of Illinois. The question asks about the need for an external wall-mounted bypass system for the UPS, and the answer explains that the agency already has maintenance bypass cabinets at the GEMS buildings that they plan to reuse. The contract opportunity is for the procurement and installation of 20KVA UPS systems for the GEMS buildings in LaSalle, Illinois.

The pricing terms, set asides, incumbents, funding sources, and other salient details are not provided in the given document. The document focuses solely on the technical requirements and existing infrastructure for the bypass systems.

View the file

Other files

File Type Posted
COVID Standard Terms and Conditions v.20.1~10.pdf PDF
R-119613 Attachment A.docx DOCX document
COVID Standard Certifications V.18.1~13.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question: “I see that there is a bypass section but it doesn’t list if an external wall-mounted one was required (highly recommended). It only states “automatic on overload or UPS failure” and they all will do that. Each UPS typically comes with an internal bypass (static bypass) but if there should ever be a need to replace batteries, internal components, etc the UPS will need to be shut down completely if there is only a “static bypass” being used which in turn will keep your loads off until the system can be placed back online. IF you had an external bypass, the power can be wrapped around the UPS and you business can continue while the work is being done and then put back online when it is complete without any interruption in work flow.”

Answer: We currently already have maintenance bypass cabinets at each of the GEMS buildings and plan on re-using those.