About this file

This document appears to be an electrical single line diagram related to a federal contract opportunity. The key details are:

The electrical single line diagram is for the QQQA RCAG HVAC Replacement Project in Barstow, CA. The project involves replacing two existing 4-ton split unit R-22 HVAC systems with new R-410 or accepted equivalent units. The site has an existing concrete pad for each condenser unit. The contract opportunity is solicitation number 697DCK24R00313, issued by the Department of Transportation Federal Aviation Administration Southwestern Region. A site visit is scheduled for 05/08/2024 at 08:45 AM PST, and attendees must be registered by 05/07/2024 at 5:00 pm PST. The diagram provides details on the new electrical wiring, conduits, and safety switches required for the HVAC unit replacements.

View the file

Other files for this federal contract opportunity

Other files attached to QQQA RCAG HVAC Replacement Project in Barstow, CA, newest first.
File Type Posted
QA - 697DCK24R00313 QQQA RCAG HVAC Replacement Project in Barstow.pdf PDF
QQQ-20013605-M002.pdf PDF
Wage Determination - CA20230026.pdf PDF
697DCK-24-R-00313.pdf PDF
QQQ-20013605-M003.pdf PDF
QQQ-20013605-M001.pdf PDF
QQQA RCAG Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/0

/2

:1

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

Q Q

Q -2

-M

.d w g

8 234567

H

G

F

E

D

C

A

B

3R

50A, 2P

3/4" C, 2 - #8, &

1 - #8 GND

30A3R

15A

20A, 2P

3/4" C, 2 - #10, &

1 - #10 GND

EXISTING CIRCUIT

BREAKERS, TYP.

2 - #8, &

1 - #8 GND

2 - #10, &

1 - #10 GND

125A, 120/240V, 1PH, 3WIRE

PANEL 'B'

60A 1

50A

50A, 2P

3/4" C, 2 - #8, &

1 - #8 GND

30A 1

15A

20A, 2P

3/4" C, 2 - #10, &

1 - #10 GND

2 - #8, &

1 - #8 GND

2 - #10, &

1 - #10 GND1 1 1 1

2 2 2 2

3 3 3 3

AH

CU

CU

AH

60A

50A

200A 3R

125A

SWITCH RATING, AMPS

NEMA RATING

FUSIBLE, HEAVY DUTY SAFETY SWITCH;

SIZE AND SELECT FOR EQUIPMENT

SERVED.

DUAL ELEMENT TIME

DELAY FUSE SIZE, AMPS

3/4" C, 2 - #12, &

1 - #12 GND

CONDUIT SIZE

QTY AND SIZE(AWG) OF POWER WIRES

QTY AND SIZE(AWG) OF GROUND WIRE

NEW (SHOWN IN HEAVY LINEWEIGHT)

EXISTING (SHOWN IN LIGHT LINEWEIGHT)

LEGEND

PROVIDE NEW WIRING FROM EXISTING PANEL 'B' TO

NEW EQUIPMENT SAFETY SWITCHES, TYP. FOR 4

CIRCUITS. REUSE EXISTING CONDUITS LOCATED IN

INTERIOR LOCATIONS. REPLACE LIQUIDTIGHT CONDUIT

LOCATED IN EXTERIOR LOCATIONS WITH NEW FLEXIBLE

METAL LIQUIDTIGHT CONDUIT.

PROVIDE NEW SAFETY SWITCHES, SQUARE D - HEAVY

DUTY, 240VAC, 30A RATED FOR AH, 60A RATED FOR CU, 2

POLE, 3 WIRE, WITH FUSE SIZING AND NEMA RATING, AS

SHOWN. NEW SAFETY SWITCHES AT LEAST 5' A.F.F.

CONSTRUCTION NOTES:

PROVIDE NEW CONDUIT AND CONDUCTORS.3

IS

S

U E

D F

O R

E D

M

04/01/2024

MGR: OPERATIONS SUPPORT

NL

BARSTOW

QQQ-20013605-M004

SW

SW

RCAG

AIR CONDITIONING REPLACEMENT PROJECT

ELECTRICAL SINGLE LINE DIAGRAM

Q Q

Q -2

-M

.d w g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N S

T R

U C

T

IO

N

DRAWING PRODUCED ON WSA MICROSTATION SYSTEM

PROJECT ENGINEER

20013605

CA

NOT TO SCALE

ELECTRICAL SINGLE LINE DIAGRAM

M004

A

QQQ-20013605-M004

2024-04-04T11:04:44-0700
EDWARD I CHAU
2024-04-04T09:45:32-0700
Sharon Shan Wean Wu