QQQ-20013605-M002.pdf
PDF 420 KB Posted
- Attached to
- QQQA RCAG HVAC Replacement Project in Barstow, CA Federal contract opportunity
- Solicitation number
- 697DCK24R00313
About this file
This document appears to be a set of technical drawings and specifications for the replacement of HVAC equipment at a Federal Aviation Administration (FAA) facility in Barstow, California. The key details are:
The project involves replacing two redundant 4-ton split HVAC units that use the outdated R-22 refrigerant. The new equipment includes two new air handling units (AH-1 and AH-2) and two new condensing units (CU-1 and CU-2), along with associated refrigerant piping, condensate drains, and electrical safety switches. The work must be completed with one HVAC unit operational at all times to maintain the required room temperature. No hot work is allowed when working on the electrical systems, which will require a shutdown coordinated with the FAA. The new equipment must be tested for a minimum of 24 hours before the second unit is replaced. The technical specifications provide details on the required equipment models, dimensions, materials, and installation. The related federal contract opportunity has a solicitation number of 697DCK24R00313 for the "QQQA RCAG HVAC Replacement Project in Barstow, CA" with a site visit scheduled for 05/08/2024.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QA - 697DCK24R00313 QQQA RCAG HVAC Replacement Project in Barstow.pdf | ||
| Wage Determination - CA20230026.pdf | ||
| 697DCK-24-R-00313.pdf | ||
| QQQ-20013605-M004.pdf | ||
| QQQ-20013605-M003.pdf | ||
| QQQ-20013605-M001.pdf | ||
| QQQA RCAG Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/0
/2
:1
:0
P
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
Q Q
Q -2
-M
.d w g
8 234567
H
G
F
E
D
C
A
B
GENERAL NOTES:
1. EXISTING AH/CU-1 AND AH/CU-2 ARE REDUNDANT UNITS SERVING A CRITICAL SPACE. ONLY ONE UNIT
MUST BE REPLACED AT A TIME, WITH ONE UNIT OPERATIONAL AT ALL TIMES DURING CONSTRUCTION IN
ORDER TO MAINTAIN ROOM TEMPERATURE SETPOINT. CONTRACTOR MUST RUN TEST EACH UNIT FOR A
MINIMUM OF 24 HOURS AND VERIFY WITH THE FAA RESIDENT ENGINEER THAT THE UNIT IS FULLY
OPERATIONAL BEFORE REPLACING THE SECOND UNIT.
2. NO HOTWORK IS ALLOWED WHEN WORKING ON THE ELECTRICAL. COORDINATE WITH THE FAA RESIDENT
ENGINEER ONE WEEK IN ADVANCE FOR ELECTRICAL PANEL WORK, WHICH WILL REQUIRE A SHUTDOWN.
1 NEW AIR HANDLING UNIT, AH-1, MOUNTED ON STAND, WITH
SUPPLY AIR PLENUM AND GRILLE.
2 NEW AIR HANDLING UNIT, AH-2, MOUNTED ON STAND, WITH
SUPPLY AIR PLENUM AND GRILLE.
3 NEW CONDENSING UNIT, CU-1.
4 NEW CONDENSING UNIT, CU-2.
5 NEW REFRIGERANT PIPING, TYP.
6 NEW PIPE SUPPORTS, MINIMUM 6" ABOVE CONCRETE FLOOR.
7 PROVIDE 2 EACH - NEW THERMOSTATS ON EXISTING CONTROL
PANEL, HONEYWELL TH6320WF2003/U, OR APPROVED EQUAL.
8 NEW SAFETY SWITCH - NEMA 1, 2P, 3 WIRE, FUSIBLE, HEAVY
DUTY, 240VAC, 30A RATED; WITH 15A TIME DELAY FUSES.
SAFETY SWITCH MUST BE SQUARE D (SCHNEIDER ELECTRIC)
VH221N, OR APPROVED EQUAL. TYP. OF 2.
9 NEW SAFETY SWITCH - NEMA 3R, 2P, 3 WIRE, FUSIBLE, HEAVY
DUTY, 240VAC, 60A RATED; WITH 50A TIME DELAY FUSES.
SAFETY SWITCH MUST BE SQUARE D (SCHNEIDER ELECTRIC)
VH222NRB, OR APPROVED EQUAL. TYP. OF 2.
CONSTRUCTION NOTES:
10 NEW CONDENSATE DRAIN PIPE, WITH TRAP, PIPE TO OUTSIDE.
TYP. OF 2.
11 EXISTING AND EQUIPMENT PAD, 60" X 60" X 4"
12 NEW SUPPLY AIR PLENUM, 22 GAUGE SHEEETMETAL, 1" DUCT
LINER, 21X21 OUTSIDE DUCT DIMENSIONS, 1" FLANGE IN ON
BOTH OPENINGS. SECURE TO AIR HANDLING UNIT.
13 AIR HANDLING UNIT STAND - FABRICATE OUT OF 2"X2"X1/8"
ANGLE IRON, WELDED, BASE DIMENSIONS MUST BE SAME AS
AIR HANDLING UNIT DIMENSIONS. HEIGHT OF STAND MUST BE
22". PAINT TO A BRONZE ANODIZED COLOR. SECURE UNIT TO
STAND USING 14"X1"X
8" FLAT IRON WELDED ONTO THREE
SIDES OF STAND, EXCEPT FROM FRONT FILTER ACCESS AREA.
14 SUPPLY AIR GRILLE, DOUBLE DEFLECTION, 19"X19" NOMINAL
DUCT SIZE, ALUMINUM, TITUS 272FL, OR EQUAL.
15 TIE DOWN SUPPLY PLENUM AND UNIT ASSEMBLY TO WALL
USING 2"WIDE X 1/8" FLAT STEEL, 4 STRAPS PER UNIT. TYP.
16 EXISTING SUNSHIELD COVERING WITH OPENING ABOVE
CONDENSING UNIT
EQUIPMENT ROOM
ELECTRONIC
EQUIPMENT
AUTOMATIC LOUVER
AUTOMATIC LOUVER
GENERATOR ROOM
POWER
PANEL 'B'
T
T
EXISTING CONTROL
PANEL
POWER
PANEL 'A'
(FOR REF. ONLY)
AH
AH
CU
CU
REUSE EXISTING
WALL PENETRATIONS,
SEAL EXTERIOR WITH
SILICONE, AND MAKE WATER
TIGHT., TYP.
3 4
8 8
11 1116 16
AH
CU
EXISTING CONCRETE
PADS
SUPPLY
CEILING
RETURN
EXISTING WIREWAYS,
TYP. INDOOR AND
OUTDOOR
EXISTING SUNSHIELD
IS
S
U E
D F
O R
E D
M
04/01/2024
MGR: OPERATIONS SUPPORT
NL
BARSTOW
QQQ-20013605-M002
SW
SW
RCAG
AIR CONDITIONING REPLACEMENT PROJECT
MECHANICAL PLAN & SECTION
Q Q
Q -2
-M
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
C O
N S
T R
U C
T
IO
N
DRAWING PRODUCED ON WSA MICROSTATION SYSTEM
PROJECT ENGINEER
20013605
CA
SCALE: 3/8" = 1'-0"
MECHANICAL PLAN
M002
A
SCALE: 1/2" = 1'-0"
SECTION
M002
B
B
M
2' 0 2' 6'
SCALE: 3/8" = 1'-0"
4'
1' 0 3' 5'
SCALE: 1/2" = 1'-0"
1' 2' 4'
QQQ-20013605-M002