QQQ-20013605-M002.pdf

PDF 420 KB Posted

Attached to
QQQA RCAG HVAC Replacement Project in Barstow, CA Federal contract opportunity
Solicitation number
697DCK24R00313
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document appears to be a set of technical drawings and specifications for the replacement of HVAC equipment at a Federal Aviation Administration (FAA) facility in Barstow, California. The key details are:

The project involves replacing two redundant 4-ton split HVAC units that use the outdated R-22 refrigerant. The new equipment includes two new air handling units (AH-1 and AH-2) and two new condensing units (CU-1 and CU-2), along with associated refrigerant piping, condensate drains, and electrical safety switches. The work must be completed with one HVAC unit operational at all times to maintain the required room temperature. No hot work is allowed when working on the electrical systems, which will require a shutdown coordinated with the FAA. The new equipment must be tested for a minimum of 24 hours before the second unit is replaced. The technical specifications provide details on the required equipment models, dimensions, materials, and installation. The related federal contract opportunity has a solicitation number of 697DCK24R00313 for the "QQQA RCAG HVAC Replacement Project in Barstow, CA" with a site visit scheduled for 05/08/2024.

View the file

Other files for this federal contract opportunity

Other files attached to QQQA RCAG HVAC Replacement Project in Barstow, CA, newest first.
File Type Posted
QA - 697DCK24R00313 QQQA RCAG HVAC Replacement Project in Barstow.pdf PDF
Wage Determination - CA20230026.pdf PDF
697DCK-24-R-00313.pdf PDF
QQQ-20013605-M004.pdf PDF
QQQ-20013605-M003.pdf PDF
QQQ-20013605-M001.pdf PDF
QQQA RCAG Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/0

/2

:1

:0

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

Q Q

Q -2

-M

.d w g

8 234567

H

G

F

E

D

C

A

B

GENERAL NOTES:

1. EXISTING AH/CU-1 AND AH/CU-2 ARE REDUNDANT UNITS SERVING A CRITICAL SPACE. ONLY ONE UNIT

MUST BE REPLACED AT A TIME, WITH ONE UNIT OPERATIONAL AT ALL TIMES DURING CONSTRUCTION IN

ORDER TO MAINTAIN ROOM TEMPERATURE SETPOINT. CONTRACTOR MUST RUN TEST EACH UNIT FOR A

MINIMUM OF 24 HOURS AND VERIFY WITH THE FAA RESIDENT ENGINEER THAT THE UNIT IS FULLY

OPERATIONAL BEFORE REPLACING THE SECOND UNIT.

2. NO HOTWORK IS ALLOWED WHEN WORKING ON THE ELECTRICAL. COORDINATE WITH THE FAA RESIDENT

ENGINEER ONE WEEK IN ADVANCE FOR ELECTRICAL PANEL WORK, WHICH WILL REQUIRE A SHUTDOWN.

1 NEW AIR HANDLING UNIT, AH-1, MOUNTED ON STAND, WITH

SUPPLY AIR PLENUM AND GRILLE.

2 NEW AIR HANDLING UNIT, AH-2, MOUNTED ON STAND, WITH

SUPPLY AIR PLENUM AND GRILLE.

3 NEW CONDENSING UNIT, CU-1.

4 NEW CONDENSING UNIT, CU-2.

5 NEW REFRIGERANT PIPING, TYP.

6 NEW PIPE SUPPORTS, MINIMUM 6" ABOVE CONCRETE FLOOR.

7 PROVIDE 2 EACH - NEW THERMOSTATS ON EXISTING CONTROL

PANEL, HONEYWELL TH6320WF2003/U, OR APPROVED EQUAL.

8 NEW SAFETY SWITCH - NEMA 1, 2P, 3 WIRE, FUSIBLE, HEAVY

DUTY, 240VAC, 30A RATED; WITH 15A TIME DELAY FUSES.

SAFETY SWITCH MUST BE SQUARE D (SCHNEIDER ELECTRIC)

VH221N, OR APPROVED EQUAL. TYP. OF 2.

9 NEW SAFETY SWITCH - NEMA 3R, 2P, 3 WIRE, FUSIBLE, HEAVY

DUTY, 240VAC, 60A RATED; WITH 50A TIME DELAY FUSES.

SAFETY SWITCH MUST BE SQUARE D (SCHNEIDER ELECTRIC)

VH222NRB, OR APPROVED EQUAL. TYP. OF 2.

CONSTRUCTION NOTES:

10 NEW CONDENSATE DRAIN PIPE, WITH TRAP, PIPE TO OUTSIDE.

TYP. OF 2.

11 EXISTING AND EQUIPMENT PAD, 60" X 60" X 4"

12 NEW SUPPLY AIR PLENUM, 22 GAUGE SHEEETMETAL, 1" DUCT

LINER, 21X21 OUTSIDE DUCT DIMENSIONS, 1" FLANGE IN ON

BOTH OPENINGS. SECURE TO AIR HANDLING UNIT.

13 AIR HANDLING UNIT STAND - FABRICATE OUT OF 2"X2"X1/8"

ANGLE IRON, WELDED, BASE DIMENSIONS MUST BE SAME AS

AIR HANDLING UNIT DIMENSIONS. HEIGHT OF STAND MUST BE

22". PAINT TO A BRONZE ANODIZED COLOR. SECURE UNIT TO

STAND USING 14"X1"X

8" FLAT IRON WELDED ONTO THREE

SIDES OF STAND, EXCEPT FROM FRONT FILTER ACCESS AREA.

14 SUPPLY AIR GRILLE, DOUBLE DEFLECTION, 19"X19" NOMINAL

DUCT SIZE, ALUMINUM, TITUS 272FL, OR EQUAL.

15 TIE DOWN SUPPLY PLENUM AND UNIT ASSEMBLY TO WALL

USING 2"WIDE X 1/8" FLAT STEEL, 4 STRAPS PER UNIT. TYP.

16 EXISTING SUNSHIELD COVERING WITH OPENING ABOVE

CONDENSING UNIT

EQUIPMENT ROOM

ELECTRONIC

EQUIPMENT

AUTOMATIC LOUVER

AUTOMATIC LOUVER

GENERATOR ROOM

POWER

PANEL 'B'

T

T

EXISTING CONTROL

PANEL

POWER

PANEL 'A'

(FOR REF. ONLY)

AH

AH

CU

CU

REUSE EXISTING

WALL PENETRATIONS,

SEAL EXTERIOR WITH

SILICONE, AND MAKE WATER

TIGHT., TYP.

3 4

8 8

11 1116 16

AH

CU

EXISTING CONCRETE

PADS

SUPPLY

CEILING

RETURN

EXISTING WIREWAYS,

TYP. INDOOR AND

OUTDOOR

EXISTING SUNSHIELD

IS

S

U E

D F

O R

E D

M

04/01/2024

MGR: OPERATIONS SUPPORT

NL

BARSTOW

QQQ-20013605-M002

SW

SW

RCAG

AIR CONDITIONING REPLACEMENT PROJECT

MECHANICAL PLAN & SECTION

Q Q

Q -2

-M

.d w g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N S

T R

U C

T

IO

N

DRAWING PRODUCED ON WSA MICROSTATION SYSTEM

PROJECT ENGINEER

20013605

CA

SCALE: 3/8" = 1'-0"

MECHANICAL PLAN

M002

A

SCALE: 1/2" = 1'-0"

SECTION

M002

B

B

M

2' 0 2' 6'

SCALE: 3/8" = 1'-0"

4'

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

QQQ-20013605-M002

2024-04-04T10:51:34-0700
EDWARD I CHAU
2024-04-04T09:43:10-0700
Sharon Shan Wean Wu

File details come from the government source that posted it. Updated .