QQQ-20013605-M003.pdf

PDF 395 KB Posted

Attached to
QQQA RCAG HVAC Replacement Project in Barstow, CA Federal contract opportunity
Solicitation number
697DCK24R00313
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document appears to be a set of technical drawings and specifications for the refrigerant piping, air handler stand, condensate drain, and supply plenum details for an HVAC replacement project. The drawings provide specific dimensions, materials, and installation requirements for these HVAC components.

The related federal contract opportunity is for the HVAC Replacement Project at the QQQA RCAG site in Barstow, CA. The solicitation seeks to replace two existing 4-ton split HVAC systems that use outdated R-22 refrigerant. The new units must use R-410 or an accepted equivalent refrigerant. A site visit is scheduled for 05/08/2024 and attendees must be registered by 05/07/2024. The solicitation is being issued by the Department of Transportation Federal Aviation Administration Southwestern Region.

View the file

Other files for this federal contract opportunity

Other files attached to QQQA RCAG HVAC Replacement Project in Barstow, CA, newest first.
File Type Posted
QA - 697DCK24R00313 QQQA RCAG HVAC Replacement Project in Barstow.pdf PDF
QQQ-20013605-M004.pdf PDF
QQQ-20013605-M002.pdf PDF
697DCK-24-R-00313.pdf PDF
Wage Determination - CA20230026.pdf PDF
QQQ-20013605-M001.pdf PDF
QQQA RCAG Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/0

/2

:1

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

Q Q

Q -2

-M

.d w g

8 234567

H

G

F

E

D

C

A

B

TXV

AIR HANDLING UNIT

CONDENSING UNIT

WALL

FILTER DRIER, SPORLAN CATCH-ALL, OR APPROVED EQUAL

SIGHT GLASS, EMERSON HMI, OR APPROVED EQUAL

CONDENSING UNIT.

ON LIQUID AND SUCTION LINE ADJACENT

REFRIGERANT SCHRADER VALVE PORT,

ON SUCTION LINE, TYP.

AND ALUMINUM JACKETING

PIPE INSULATION (1" THICK)

LIQUID LINE

SUCTION LINE

NOTES:

1. THIS DETAIL IS TYPICAL FOR EACH REFRIGERANT CIRCUIT.

2. ALL REFRIGERANT PIPING MUST BE TYPE ''ACR' COPPER'.

3. ALL JOINTS MUST BE BRAZED.

4.SEE SPECIFICATIONS.

REFRIGERANT PIPE SIZE

LIQUID LINE: 3/8" O.D.

SUCTION LINE: 7/8" O.D.

EXTERIORINTERIOR

COOLING

COIL

NOTES:

1. CONDENSATE DRAIN MUST BE SIZED FULL SIZE OF AIR

HANDLER DRAIN OUTLET AND MUST BE CONSTRUCTED WITH

TYPE 'M' COPPER PIPE AND FITTINGS.

2. ALL DRAIN PIPING LOCATED INDOORS MUST BE INSULATED

WITH 1/2" THICK ELASTOMERIC INSULATION.

3" MIN.

1.5"

TEE (TYP.)

CONCRETE PAD

DRAIN OR EDGE OF

PIPE TO FLOOR

MESH SCREEN

SS INSECT

VENT

ANTI-SIPHON

WITH THREADED PLUG

CLEANOUT: ADAPTER

DRAIN

PAN

SS HOSE CLAMP

AIR HANDLER

OUTLINE

MATCH AIR HANDLER

BASE DIMENSIONS

MATCH AIR HANDLER

BASE DIMENSIONS

1"X16"X1/8" FLAT

STEEL, ON 3 SIDES

OF STAND, EXCEPT

FILTER ACCESS SIDE,

TYP.

2"X2"X1/8" ANGLE

IRON, TYP FOR

ENTIRE STAND.

FRONT VIEWSIDE VIEW

SIDE

VIEW

ANCHORS, RED HEAD

TRUBOLT, OR EQUAL.

AIR HANDLER

OUTLINE

NOTES: 1. DUCT DIMENSIONS ARE ACTUAL EXTERIOR DUCT DIMENSIONS.

2. 1" FLANGE-IN ON ALL OPENINGS.

3. FABRICATE USING 22 GAUGE GALVANIZED SHEETMETAL.

4. 1" DUCT LINER

1" DUCT LINER

TURNING VANE, TYP.

19"X19"

OPENING

19"X19" OPENING

AIR HANDLER

OUTLINE

SUPPLY AIR

GRILLE

AIRFLOW

A

IR

F L O

W

IS

S

U E

D F

O R

E D

M

04/01/2024

MGR: OPERATIONS SUPPORT

NL

BARSTOW

QQQ-20013605-M003

SW

SW

RCAG

AIR CONDITIONING REPLACEMENT PROJECT

DETAILS

Q Q

Q -2

-M

.d w g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N S

T R

U C

T

IO

N

DRAWING PRODUCED ON WSA MICROSTATION SYSTEM

PROJECT ENGINEER

20013605

CA

NOT TO SCALE

TYPICAL REFRIGERANT PIPING DIAGRAM

M003

A

NOT TO SCALE

TYPICAL AIR HANDLER STAND DETAIL

M003

B

NOT TO SCALE

TYPICAL CONDENSATE TRAP AND PIPING DETAIL

M003

D

NOT TO SCALE

TYPICAL SUPPLY PLENUM DETAIL

M003

C

NOTES:

1. PROVIDE METAL STAND FABRICATED OUT OF 2"X2"X1/8" ANGLE IRON. THE TOP AND ALL SIDES OF THE STAND MUST BE OPEN FOR FREE AIR FLOW.

2. ALL SEAMS OF STAND MUST BE WELDED ALONG THE ENTIRE SEAM.

3. PROVIDE SPRAY PAINT FINISH USING RUSTOLEUM 7754830, OR EQUAL - SEMI GLOSS ANODIZED BRONZE COLOR.

QQQ-20013605-M003

2024-04-04T10:53:32-0700
EDWARD I CHAU
2024-04-04T09:43:45-0700
Sharon Shan Wean Wu

File details come from the government source that posted it. Updated .