QASP - Diesel Generator Maintenance.pdf

PDF 901 KB Posted

Attached to
Diesel Generator Maintenance Service Contract, Ames, IA Federal contract opportunity
Solicitation number
12505B23Q0018
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

About this file

This is a combined synopsis/solicitation issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area seeking quotes for a diesel generator maintenance service contract at a facility in Ames, Iowa. The solicitation requires OEM authorized preventative maintenance and repair services for generators, automatic transfer switches, and related equipment. Quotes are due by February 15, 2023 with an anticipated one base year of performance and four one-year option periods. Award will be made to the lowest priced technically acceptable offer based on experience requirements. Site visits are scheduled for January 24-25, 2023 and registration is required by January 23. The solicitation incorporates standard FAR clauses for commercial item acquisitions valued at an estimated $11 million annual small business size.

View the file

Other files for this federal contract opportunity

Other files attached to Diesel Generator Maintenance Service Contract, Ames, IA, newest first.
File Type Posted
12505B23Q0018 - Diesel Generator Maintenance QAs_2.7.23.pdf PDF
12505B23Q0018 - Generator contractor visitors 1-24-2023.pdf PDF
12505B23Q0018 - Generator contractor visitors 1-25-2023.pdf PDF
Wage Determination_12.27.22.pdf PDF
Statement of Work - Diesel Generator Maintenance.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUALITY ASSURANCE SURVEILLANCE PLAN (QASP)

FOR

Bldg 153 Caterpillar Diesel Generator maintenance

1. PURPOSE

This Quality Assurance Surveillance Plan (QASP) is a Government developed and applied document used to make sure that systematic quality assurance methods are used in the administration of the Performance Based Service Contract (PBSC) standards included in this contract and in subsequent task orders issued there under. The intent is to ensure that the Contractor performs in accordance with performance metrics set forth in the contract documents, that the Government receives the quality of services called for in the contract and that the Government only pays for the acceptable level of services received.

The QASP has been developed by the requiring activity. It is designed to provide direction to personnel performing contract surveillance activities. Personnel surveying the contract terms and conditions and SOW requirements will periodically review the QASP throughout the life of the contract.

The Contracting Officer’s Representative (COR) will monitor the performance of the Caterpillar Diesel Generator technician in performing operation, maintenance, and testing.

2. SCOPE

The QASP is put in place to provide Government surveillance oversight of the Contractor’s quality control efforts to ensure the products/results specified in the PR&C or task order are delivered on time and meet the requirements of the PR&C or task order. The QASP is not intended to duplicate the Contractor’s Management Plan.

3. GOVERNMENT RESOURCES

The following definitions for Government resources are applicable to this plan:

Contracting Officer - A person duly appointed with the authority to enter into, administer, or terminate contracts and make related determinations and findings on behalf of the Government.

Contracting Officer’s Representative (COR) - An individual designated in writing by the Contracting Officer to act as his authorized representative to assist in administering a contract. The source and authority for a COR is the Contracting Officer. COR limitations are contained in the written letter of appointment.

4. RESPONSIBILITIES:

The Government resources shall have responsibilities for the implementation of this QASP as follows:

Contracting Officer – The Contracting Officer ensures performance of all necessary actions for effective contracting, ensures compliance with the terms of the contract and safeguards the interests of the United States in the contractual relationship. It is the Contracting Officer that ensures the Contractor receives impartial, fair, and equitable treatment under the contract. The Contracting Officer is ultimately responsible for the final determination of the adequacy of the Contractor’s performance.

Contracting Officer’s Representative (COR) - The COR is responsible for technical administration of the project and ensures proper Government surveillance of the Contractor’s performance. The COR is not empowered to make any contractual commitments or to authorize any contractual changes on the Government’s behalf. Any changes that the Contractor deems may affect contract, price, terms, or conditions shall be referred to the Contracting Officer for action.

5. METHODS OF QA SURVEILLANCE

The below listed methods of surveillance shall be used in the administration of this QASP.

Customer Feedback – Customer feedback may be obtained from Utility Plant USDA personnel. Customer complaints, to be considered valid, must set forth clearly and in writing the detailed nature of the complaint, must be signed and must be forwarded to the COR. The COR shall maintain a summary log of all formally received customer complaints as well as a copy of each complaint in a documentation file.

Periodic Inspection – The COR shall monitor the performance of the Caterpillar Diesel Generator Technician as needed. during the standby and recovery period of the contracted period of performance. If there are not issues, then little monitoring is required.

100% Inspection –If issues occur during the period of performance, the COR will monitor the performance of the Caterpillar Diesel Generator technician in the operation, maintenance, and repair of the generators.

6. LEVELS AND STANDARDS OF SERVICE

The standards of services are held to and comply with the standards specified in the PR&C, commercial/industry, and military/government standards.

Location Make Serial Number Large generators Bldg 153, Gen #1 Caterpillar 0FDN01781 Bldg 153, Gen #2 Caterpillar 0ZAP00574 Bldg 153, Gen #4 Caterpillar 0FDN01780 Bldg 153, Gen #5 Caterpillar 0ZAP000576 Bldg 153, Gen #6 Caterpillar G3Z00332

Small generators Bldg 22 Caterpillar 09EP02880 Bldg 401MB Cummins K040710038 Bldg 402 Cummins 46549234 Bldg 417 C-3 Cummins 46562837

Automatic Transfer Switches Bldg 154 ATS #1 Caterpillar CTSCT 0TSE01025 Bldg 154 ATS #2 Caterpillar CTSCT 0TSE01056 Bldg 154 ATS #3 Caterpillar CTSCT 0TSE01055 Bldg 154 ATS #4 Caterpillar CTSCT 0TSE01026

Bldg 21 ATS #1

ASCO

7000 238630FP

Bldg 21 ATS #2

ASCO

7000 238629FP

Bldg 401MB OTPCF 5692526 K040710143

Bldg 402 OTPCF 5743004 J050841110

Bldg 417 OTPCF 5746017 L050865964

7. IDENTIFIED QA SURVEILLANCE ITEMS

Performance Requirements

Performance Requirements

Required Services Performance Objective Performance Requirement

Level 1: Comprehensive 64-Point Inspection

Inspect and test engine, generator, transfer switches, radiator, day tank, battery charger, engine block heater, gauges and meters. Scheduled service and maintenance.

Every 12 months.

Check emergency engine safety shutdown systems. Scheduled service and maintenance.

months.

Test oil and coolant quality and verify that they meet the manufacturer’s specifications. Scheduled service and maintenance.

Every 12 months.

Provide a written analysis of the inspection and identify any possible areas that need service within ten working days of completion of the work. Scheduled service and maintenance.

Every 12 months.

Provide a price list of recommended replacement parts and labor cost for installation of the same within ten working days of the written report. Scheduled service and maintenance.

Every 12 months.

COOLING SYSTEM

1.1 Radiator/Heat Exchanger/Cooling System- Visual

inspection for leaks and damage. Scheduled service and maintenance.

Every 12 months.

1.2 Fan Drive Pulley - Check for loose or worn

pulleys and lube fan drive when needed. Scheduled service and maintenance.

Every 12 months.

1.3 Fan Guard - Inspect for missing or broken parts.

Scheduled service and maintenance.

Every 12 months.

1.4 Fan Belts - Inspect for frayed or worn belts.

Check tension and adjust. Scheduled service and maintenance.

Every 12 months.

1.5 Coolant -Take Coolant Sample, indicate type of

coolant (DEAC, ELC or Conventional) on coolant sample tag. Scheduled service and maintenance.

Every 12 months.

1.6 Hoses - Visual inspection of all hoses for

condition. Check connections. Scheduled service and maintenance.

Every 12 months.

1.7 Filler Cap - Inspect filler cap gaskets and sealing

surfaces. Scheduled service and maintenance.

Every 12 months.

1.8 Inspect Jacket Water Heater - Check for proper

operation and thermostat settings. Record water jacket temperature. Scheduled service and maintenance.

Every 12 months.

1.9 Water Pump - Visual inspection for leaks

Scheduled service and maintenance.

LUBRICATION SYSTEM

2.1 Oil Level - Inspect for proper level inspect for

leaks. Record level. Scheduled service and maintenance.

Every 12 months.

2.3 Crankcase Breather System - Inspect hose and

connections. Note excessive blowby. Inspect for proper operation. Scheduled service and maintenance.

AIR SYSTEM

3.1 Air Filter - Inspect filter element and seals.

Scheduled service and maintenance.

3.2 Air Inlet System - Inspect piping for damage or

loose connections. Scheduled service and maintenance.

FUEL SYSTEM/GOVERNOR

4.1 Fuel Tank - Visually inspect for leaks and level.

Record level. Scheduled service and maintenance.

Every 12 months.

4.2 Day Tank Pump - Check for proper operation.

Check panel alarm lights. Scheduled service and maintenance.

Every 12 months.

4.3 Fuel Priming Pump - Inspect for proper

operation. Scheduled service and maintenance.

Every 12 months.

4.4 Fuel Filters - Primary/Secondary. Visual inspect

for damage or leaks. Scheduled service and maintenance.

Every 12 months.

4.5 Water/Trap Separator - Drain water from tank

or separator. Scheduled service and maintenance.

Every 12 months.

4.6 Fuel Lines - Check fuel line for leaks and tight

connections. Check line brackets. Scheduled service and maintenance.

EXHAUST SYSTEM

5.1 Silencer and Piping - Visually inspect for damage

or leakage. Visually check straps and rain cap.

Scheduled service and maintenance.

Every 12 months.

5.2 Exhaust Manifold/Turbo - Inspect for damage, missing parts, or oil slobbering. Scheduled service and maintenance.

GENERATOR

6.1 Coupling and Guards - Inspect for vibration and

loose or missing parts. Scheduled service and maintenance.

Every 12 months.

6.2 Wiring - Visually inspect for condition and loose

connections. Scheduled service and maintenance.

Every 12 months.

6.3 Rotating Rectifier - Visually inspect rotating

rectifier wiring for loose connections. Scheduled service and maintenance.

Every 12 months.

6.4 Stator and Rotor - Visually inspect for damage

and overall condition. Scheduled service and maintenance.

Every 12 months.

6.5 Visually inspect generator bearing.

Scheduled service and maintenance.

Every 12 months.

6.6 Generator Barrel Heater- If equipped check

generator barrel heater for proper operation. Scheduled service and maintenance.

STARTING SYSTEM

7.1 Starting Motor - Inspect connections and wiring.

Scheduled service and maintenance.

Every 12 months.

7.2 Battery Charger - Measure and record battery

charger float voltage. Scheduled service and maintenance.

7.2.1 Battery Charger - Measure and record battery

charger float voltage Scheduled service and maintenance.

Every 12 months.

7.3 Battery Charger & Cables - Visually check for

proper operation and loose terminals. Clean, lube and tighten all battery cable connections if needed.

Scheduled service and maintenance.

CONTROL PANEL/CABINETS

8.1 Visual Inspection - Check for loose or broken

wires and dirt accumulation. Scheduled service and maintenance.

Every 12 months.

Take picture of the EMCP Panel. Please note if panel is older than EMCP 3. Scheduled service and maintenance.

Every 12 months.

8.2 Panel Lights - Operational check of illumination

and safety lamps. Scheduled service and maintenance.

MAIN TRANSFER SWITCH & SWITCHGEAR

9.1 Exterior visual inspection of Transfer Switch -

Inspect overall condition and verify if control panel is operational. Scheduled service and maintenance.

Every 12 months.

9.2 Does this unit have Switchgear onsite? If Yes, Take photos. Scheduled service and maintenance.

Every 12 months.

9.3 Does this unit have stationary UPS batteries? If

Yes, Take photos of the string. Scheduled service and maintenance.

START UP & RUNNING CHECKS

10.1 Battery Voltage Drop - Check voltage drop, and

amp draw during cranking. Scheduled service and maintenance.

Every 12 months.

10.2 Start Controls - Manual/Auto check for proper

operation and general start ability. Scheduled service and maintenance.

Every 12 months.

10.3 Record Water Temp

Scheduled service and maintenance.

Every 12 months.

10.4 Record Oil Pressure

Scheduled service and maintenance.

Every 12 months.

10.6 Record Fuel Pressure

Scheduled service and maintenance.

Every 12 months.

10.7 Record AC Voltage on all three phases.

Scheduled service and maintenance.

Every 12 months.

10.3.1 Record Water Temperature

Scheduled service and maintenance.

Every 12 months.

10.4.1 Record Oil Pressure

Scheduled service and maintenance.

Every 12 months.

10.6.1 Record Fuel Pressure

Scheduled service and maintenance.

Every 12 months.

10.7.1 Record Phase 1 Line to Line

Scheduled service and maintenance.

10.7.2 Record Phase 2 Line to Line

Scheduled service and maintenance.

Every 12 months.

10.7.3 Record Phase 3 Line to Line

Scheduled service and maintenance.

Every 12 months.

10.8 Frequency Meter - Record Hz

Scheduled service and maintenance.

Every 12 months.

10.9 Record AC Amps on three phases. Amperage

will only be present if generator set is under load. If customer declines transfer, please note the customer representatives name that declined transfer. Scheduled service and maintenance.

Every 12 months.

10.10 Alternator - Check for proper operation.

Scheduled service and maintenance.

Every 12 months.

10.11 Remote Annunciators and Alarms - Test all

panel and system alarms for proper operation. Scheduled service and maintenance.

Every 12 months.

10.12 Safety Controls - Test Low Oil Pressure

Shutdown, High Water Temp Shutdown, Low Water Temp Shutdown, Low Water Level Shutdown for proper operation, with customer approval.

Scheduled service and maintenance.

COOLING SYSTEM

11.1 Water Pump - Check for leaks and unusual

noise or vibration during running and after shutdown. Scheduled service and maintenance.

GENERATOR - INSTALLATION/ENCLOSURE

12.1 Enclosure Condition

Scheduled service and maintenance.

Every 12 months.

12.2 Vibration Isolators - Inspect for broken springs

or damaged cases. Scheduled service and maintenance.

Every 12 months.

12.3 Louvers - Visually inspect louver operation. If

all louvers are not visible, please note. Scheduled service and maintenance.

AFTER SHUTDOWN

13.1 Take oil sample

Scheduled service and maintenance.

Every 12 months.

13.2 Change Engine Oil, CCV Elements, Oil Filters

and Fuel Filters. Scheduled service and maintenance.

Every 12 months.

13.3 After oil is changed start engine and check for

leaks. Take a picture of any leaks and note this on the report. Scheduled service and maintenance.

Every 12 months.

10.7.4 Phase 1 Line to Neutral

Scheduled service and maintenance.

10.7.5 Phase 2 Line to Neutral

Every 12 months.

10.7.6 Phase 3 Line to Neutral

Scheduled service and maintenance.

Every 12 months.

10.8.1 Record Hertz Reading

Scheduled service and maintenance.

Every 12 months.

10.9.1 Record Phase 1 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.9.2 Record Phase 2 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.9.3 Record Phase 3 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.10 Alternator - Check for proper operation.

Scheduled service and maintenance.

Every 12 months.

10.11 Remote Annunciators and Alarms - Test all

panel and system alarms for proper operation. Scheduled service and maintenance.

Every 12 months.

10.12 Safety Controls - Test Low Oil Pressure

Shutdown, High Water Temp Shutdown, Low Water Temp Shutdown, Low Water Level Shutdown for proper operation, with customer approval.

Scheduled service and maintenance.

noise or vibration during running and after shutdown. Scheduled service and maintenance.

Scheduled service and maintenance.

Every 12 months.

12.2 Vibration Isolators - Inspect for broken springs

or damaged cases. Scheduled service and maintenance.

Every 12 months.

12.3 Louvers - Visually inspect louver operation. If

all louvers are not visible, please note. Scheduled service and maintenance.

Scheduled service and maintenance.

Every 12 months.

13.4 Verify engine oil is at the proper level and

record level. Scheduled service and maintenance.

Every 12 months.

13.6 Visually inspect generator bearing.

Scheduled service and maintenance.

Every 12 months.

13.8 RESET ALL CONTROLS TO AUTOMATIC AND

CLOSE GENERATOR BREAKER. Scheduled service and maintenance.

TAKE PICTURES OF GENERATOR SET

14.1 Take pictures of Engine, Generator, Enclosure, Batteries, and Package Data tags. Scheduled service and maintenance.

2.2 Oil Heater/Prelube Pump - Inspect for proper

operation. Scheduled service and maintenance.

7.4 Batteries - Check electrolyte level and specific

gravity record readings. Scheduled service and maintenance.

Every 12 months.

7.4.1 Specific Gravity

Scheduled service and maintenance.

10.5 Record Oil Temp

Scheduled service and maintenance.

Every 12 months.

10.5.1 Record Oil Temperature

Scheduled service and maintenance.

TEST OIL QUALITY

WEAR/CONTAMINATION-

ADDITIVES/FORMULATION Scheduled service and maintenance.

Every 12 months.

Date, hour meter, hours on oil, fluid change, filter change, Cu, Fe, Cr, Al, Pb, Sn, Si, Na, K, Mo, Ni, Ag, Ti, V, Mn, Cd, Ca, P, Zn, Mg, Ba, B. Scheduled service and maintenance.

OIL FORMULATION- OIL CONDITION- OIL

CONTAMINATION Scheduled service and maintenance.

Every 12 months.

Date, Brand, Type, weight, fluid change, filter change, V100 ST OXI SUL NIT W A F PFc PQI Scheduled service and maintenance.

TEST RADIATOR COOLANT QUALITY

CORROSION ELEMENTS - COOLANT FORMULATION

Every 12 months.

Date, fluid brand, type, Cu Fe Pb Sn Al Zn NO2 Na K Mo MoO4 BO3 SiO3 Scheduled service and maintenance.

FREEZE/BOIL PROTECTION – CONTAMINATION

Every 12 months.

Date, meter, hours on fluid, fluid brand, type, fluid change, GL FP BP pH CON PO4 TH Oil Foam Scheduled service and maintenance.

COOLANT PHYSICALS

Scheduled service and maintenance.

Every 12 months.

Sample date, meter hours, meter on fluid, fluid brand, type, color, app, odor, PAmt, Papp, PCol, PProp Scheduled service and maintenance.

TEST AFTERCOOLER COOLANT QUALITY

CORROSION ELEMENTS - COOLANT FORMULATION

Every 12 months.

Date, fluid brand, type, Cu Fe Pb Sn Al Zn NO2 Na K Mo MoO4 BO3 SiO3 Scheduled service and maintenance.

FREEZE/BOIL PROTECTION – CONTAMINATION

Every 12 months.

Date, meter, hours on fluid, fluid brand, type, fluid change, GL FP BP pH CON PO4 TH Oil Foam Scheduled service and maintenance.

COOLANT PHYSICALS

Every 12 months.

Sample date, meter hours, meter on fluid, fluid brand, type, color, app, odor, PAmt, Papp, PCol, PProp Scheduled service and maintenance.

Level 2: Comprehensive 67-Point Inspection and maintenance

Inspect and test engine, generator, transfer switch, radiator, day tank, battery charger, engine block heater, gauges and meters. Scheduled service and maintenance.

Every 12 months.

Check emergency engine safety shutdown systems. Scheduled service and maintenance.

Every 12 months.

Test oil and coolant quality and verify that they meet the manufacturer’s specifications. Scheduled service and maintenance.

Every 12 months.

Provide a written analysis of the inspection and identify any possible areas that need service within ten working days of completion of the work. Scheduled service and maintenance.

Every 12 months.

Provide a price list of recommended replacement parts and labor cost for installation of the same within ten working days of the written report. Scheduled service and maintenance.

Every 12 months.

Change engine oil and replace with specified oil. Scheduled service and maintenance.

Replace oil and fuel filters. Scheduled service and maintenance.

months.

Dispose all parts and fluids per EPA standards. Scheduled service and maintenance.

1.1 Radiator/Heat Exchanger/Cooling System- Visual

inspection for leaks and damage. Scheduled service and maintenance.

Every 12 months.

1.2 Fan Drive Pulley - Check for loose or worn

pulleys and lube fan drive when needed. Scheduled service and maintenance.

Every 12 months.

1.3 Fan Guard - Inspect for missing or broken parts.

Scheduled service and maintenance.

Every 12 months.

1.4 Fan Belts - Inspect for frayed or worn belts.

Check tension and adjust. Scheduled service and maintenance.

Every 12 months.

1.5 Coolant -Take Coolant Sample, indicate type of

coolant (DEAC, ELC or Conventional) on coolant sample tag. Scheduled service and maintenance.

Every 12 months.

1.6 Hoses - Visual inspection of all hoses for

condition. Check connections. Scheduled service and maintenance.

Every 12 months.

1.7 Filler Cap - Inspect filler cap gaskets and sealing

surfaces. Scheduled service and maintenance.

Every 12 months.

1.8 Inspect Jacket Water Heater - Check for proper

operation and thermostat settings. Record water jacket temperature. Scheduled service and maintenance.

Every 12 months.

1.9 Water Pump - Visual inspection for leaks

Scheduled service and maintenance.

2.1 Oil Level - Inspect for proper level inspect for

leaks. Record level. Scheduled service and maintenance.

Every 12 months.

2.3 Crankcase Breather System - Inspect hose and

connections. Note excessive blowby. Inspect for proper operation. Scheduled service and maintenance.

AIR SYSTEM

3.1 Air Filter - Inspect filter element and seals.

Scheduled service and maintenance.

Every 12 months.

3.2 Air Inlet System - Inspect piping for damage or

loose connections. Scheduled service and maintenance.

FUEL SYSTEM/GOVERNOR

4.1 Fuel Tank - Visually inspect for leaks and level.

Record level. Scheduled service and maintenance.

4.2 Day Tank Pump - Check for proper operation.

Check panel alarm lights. Scheduled service and maintenance.

Every 12 months.

4.3 Fuel Priming Pump - Inspect for proper

operation. Scheduled service and maintenance.

Every 12 months.

4.4 Fuel Filters - Primary/Secondary. Visual inspect

for damage or leaks. Scheduled service and maintenance.

Every 12 months.

4.5 Water/Trap Separator - Drain water from tank

or separator. Scheduled service and maintenance.

Every 12 months.

4.6 Fuel Lines - Check fuel line for leaks and tight

connections. Check line brackets. Scheduled service and maintenance.

EXHAUST SYSTEM

5.1 Silencer and Piping - Visually inspect for damage

or leakage. Visually check straps and rain cap.

Scheduled service and maintenance.

Every 12 months.

5.2 Exhaust Manifold/Turbo - Inspect for damage, missing parts, or oil slobbering. Scheduled service and maintenance.

GENERATOR

6.1 Coupling and Guards - Inspect for vibration and

loose or missing parts. Scheduled service and maintenance.

Every 12 months.

6.2 Wiring - Visually inspect for condition and loose

connections. Scheduled service and maintenance.

Every 12 months.

6.3 Rotating Rectifier - Visually inspect rotating

rectifier wiring for loose connections. Scheduled service and maintenance.

Every 12 months.

6.4 Stator and Rotor - Visually inspect for damage

and overall condition. Scheduled service and maintenance.

Every 12 months.

6.5 Visually inspect generator bearing.

Scheduled service and maintenance.

Every 12 months.

6.6 Generator Barrel Heater- If equipped check

generator barrel heater for proper operation. Scheduled service and maintenance.

7.1 Starting Motor - Inspect connections and wiring.

Scheduled service and maintenance.

Every 12 months.

7.2 Battery Charger - Measure and record battery

charger float voltage. Scheduled service and maintenance.

Every 12 months.

7.2.1 Battery Charger - Measure and record battery

charger float voltage Scheduled service and maintenance.

Every 12 months.

7.3 Battery Charger & Cables - Visually check for

proper operation and loose terminals. Clean, lube and tighten all battery cable connections if needed.

Scheduled service and maintenance.

CONTROL PANEL/CABINETS

8.1 Visual Inspection - Check for loose or broken

wires and dirt accumulation. Scheduled service and maintenance.

Every 12 months.

Take picture of the EMCP Panel. Please note if panel is older than EMCP 3. Scheduled service and maintenance.

Every 12 months.

8.2 Panel Lights - Operational check of illumination

and safety lamps. Scheduled service and maintenance.

MAIN TRANSFER SWITCH & SWITCHGEAR

9.1 Exterior visual inspection of Transfer Switch -

Inspect overall condition and verify if control panel is operational. Scheduled service and maintenance.

Every 12 months.

9.2 Does this unit have Switchgear onsite? If Yes, Take photos. Scheduled service and maintenance.

Every 12 months.

9.3 Does this unit have stationary UPS batteries? If

Yes, Take photos of the string. Scheduled service and maintenance.

10.1 Battery Voltage Drop - Check voltage drop, and

amp draw during cranking. Scheduled service and maintenance.

Every 12 months.

10.2 Start Controls - Manual/Auto check for proper

operation and general start ability. Scheduled service and maintenance.

Every 12 months.

10.3 Record Water Temp

Scheduled service and maintenance.

Every 12 months.

10.4 Record Oil Pressure

Scheduled service and maintenance.

Every 12 months.

10.6 Record Fuel Pressure

Scheduled service and maintenance.

Every 12 months.

10.7 Record AC Voltage on all three phases.

Scheduled service and maintenance.

Every 12 months.

10.3.1 Record Water Temperature

Scheduled service and maintenance.

Every 12 months.

10.4.1 Record Oil Pressure

Scheduled service and maintenance.

Every 12 months.

10.6.1 Record Fuel Pressure

Scheduled service and maintenance.

Every 12 months.

10.7.1 Record Phase 1 Line to Line

Scheduled service and maintenance.

Every 12 months.

10.7.2 Record Phase 2 Line to Line

Scheduled service and maintenance.

Every 12 months.

10.7.3 Record Phase 3 Line to Line

Scheduled service and maintenance.

Every 12 months.

10.8 Frequency Meter - Record Hz

Scheduled service and maintenance.

10.9 Record AC Amps on three phases. Amperage

will only be present if generator set is under load. If customer declines transfer, please note the customer representatives name that declined transfer. Scheduled service and maintenance.

Every 12 months.

10.10 Alternator - Check for proper operation.

Scheduled service and maintenance.

Every 12 months.

10.11 Remote Annunciators and Alarms - Test all

panel and system alarms for proper operation. Scheduled service and maintenance.

Every 12 months.

10.12 Safety Controls - Test Low Oil Pressure

Shutdown, High Water Temp Shutdown, Low Water Temp Shutdown, Low Water Level Shutdown for proper operation, with customer approval.

Scheduled service and maintenance.

noise or vibration during running and after shutdown. Scheduled service and maintenance.

Scheduled service and maintenance.

Every 12 months.

12.2 Vibration Isolators - Inspect for broken springs

or damaged cases. Scheduled service and maintenance.

Every 12 months.

12.3 Louvers - Visually inspect louver operation. If

all louvers are not visible, please note. Scheduled service and maintenance.

10.7.4 Phase 1 Line to Neutral

Scheduled service and maintenance.

Every 12 months.

10.7.5 Phase 2 Line to Neutral

Scheduled service and maintenance.

Every 12 months.

10.7.6 Phase 3 Line to Neutral

Scheduled service and maintenance.

Every 12 months.

10.8.1 Record Hertz Reading

Scheduled service and maintenance.

Every 12 months.

10.9.1 Record Phase 1 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.9.2 Record Phase 2 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.9.3 Record Phase 3 AC Amperage

Scheduled service and maintenance.

Every 12 months.

10.10 Alternator - Check for proper operation.

Scheduled service and maintenance.

10.11 Remote Annunciators and Alarms - Test all

panel and system alarms for proper operation. Scheduled service and maintenance.

Every 12 months.

10.12 Safety Controls - Test Low Oil Pressure

Shutdown, High Water Temp Shutdown, Low Water Temp Shutdown, Low Water Level Shutdown for proper operation, with customer approval.

Scheduled service and maintenance.

noise or vibration during running and after shutdown. Scheduled service and maintenance.

Scheduled service and maintenance.

Every 12 months.

12.2 Vibration Isolators - Inspect for broken springs

or damaged cases. Scheduled service and maintenance.

Every 12 months.

12.3 Louvers - Visually inspect louver operation. If

all louvers are not visible, please note. Scheduled service and maintenance.

Scheduled service and maintenance.

Every 12 months.

13.2 Change Engine Oil, CCV Elements, Oil Filters

and Fuel Filters. Scheduled service and maintenance.

Every 12 months.

13.2.1 Record Gallons of used oil collected

Scheduled service and maintenance.

Every 12 months.

13.2.2 Record Number of used oil filters collected

Scheduled service and maintenance.

Every 12 months.

13.3 After oil is changed start engine and check for

leaks. Take a picture of any leaks and note this on the report. Scheduled service and maintenance.

Every 12 months.

13.4 Verify engine oil is at the proper level and

record level. Scheduled service and maintenance.

Every 12 months.

13.6 Visually inspect generator bearing.

Scheduled service and maintenance.

Every 12 months.

13.8 RESET ALL CONTROLS TO AUTOMATIC AND

CLOSE GENERATOR BREAKER. Scheduled service and maintenance.

TAKE PICTURES OF GENERATOR SET

14.1 Take pictures of Engine, Generator, Enclosure, Batteries, and Package Data tags. Scheduled service and maintenance.

2.2 Oil Heater/Prelube Pump - Inspect for proper

operation. Scheduled service and maintenance.

7.4 Batteries - Check electrolyte level and specific

gravity record readings. Scheduled service and maintenance.

Every 12 months.

7.4.1 Specific Gravity

Scheduled service and maintenance.

10.5 Record Oil Temp

Scheduled service and maintenance.

Every 12 months.

10.5.1 Record Oil Temperature

Scheduled service and maintenance.

TEST OIL QUALITY

WEAR/CONTAMINATION-

ADDITIVES/FORMULATION

Every 12 months.

Date, hour meter, hours on oil, fluid change, filter change, Cu, Fe, Cr, Al, Pb, Sn, Si, Na, K, Mo, Ni, Ag, Ti, V, Mn, Cd, Ca, P, Zn, Mg, Ba, B. Scheduled service and maintenance.

OIL FORMULATION- OIL CONDITION- OIL

CONTAMINATION Every 12 months.

Date, Brand, Type, weight, fluid change, filter change, V100 ST OXI SUL NIT W A F PFc PQI Scheduled service and maintenance.

TEST RADIATOR COOLANT QUALITY

CORROSION ELEMENTS - COOLANT FORMULATION Every 12

Date, fluid brand, type, Cu Fe Pb Sn Al Zn NO2 Na K Mo MoO4 BO3 SiO3 Scheduled service and maintenance.

FREEZE/BOIL PROTECTION – CONTAMINATION Every 12

Date, meter, hours on fluid, fluid brand, type, fluid change, GL FP BP pH CON PO4 TH Oil Foam Scheduled service and maintenance.

Every 12 months.

Every 12 months.

COOLANT PHYSICALS Every 12

Sample date, meter hours, meter on fluid, fluid brand, type, color, app, odor, PAmt, Papp, PCol, PProp Scheduled service and maintenance.

TEST AFTERCOOLER COOLANT QUALITY

CORROSION ELEMENTS - COOLANT FORMULATION Every 12

Date, fluid brand, type, Cu Fe Pb Sn Al Zn NO2 Na K Mo MoO4 BO3 SiO3 Scheduled service and maintenance.

FREEZE/BOIL PROTECTION – CONTAMINATION Every 12

Date, meter, hours on fluid, fluid brand, type, fluid change, GL FP BP pH CON PO4 TH Oil Foam Scheduled service and maintenance.

COOLANT PHYSICALS Every 12

Sample date, meter hours, meter on fluid, fluid brand, type, color, app, odor, PAmt, Papp, PCol, PProp Scheduled service and maintenance.

Level 3: Cooling System Fluid Replacement

Drain and fill the cooling system. Scheduled service and maintenance.

Every 36 months.

Replace coolant hoses, including engine block heater hoses. Scheduled service and maintenance.

Every 36 months.

Replace engine thermostats and test for proper operation. Scheduled service and maintenance.

Every 36 months.

Dispose all parts and fluids per EPA standards. Scheduled service and maintenance.

Every 36 months.

Provide written report within 10 working days of the completion of the work. Scheduled service and maintenance.

Every 36

Level 4: Megohmeter Test

Perform a megohmeter test. Scheduled service and maintenance.

Every 12 months.

Provide a written analysis from the test within ten working days after completion of the test. Scheduled service and maintenance.

Every 12 months.

Scheduled service and maintenance.

Generator Polarization Index (PI) Test (Megohmeter test) Scheduled service and maintenance.

Every 12 months.

For each generator, over the 10-minute test period, record: Scheduled service and maintenance.

Raw megohmeter reading.

Every 12 months.

Temperature correction factor.

Scheduled service and maintenance.

Every 12 months.

20 degree C corrected reading.

Scheduled service and maintenance.

Every 12 months.

Provide a Polarization Index graph of these readings. Scheduled service and maintenance.

Level 5: Load Bank Test

Perform a two-hour load bank test. Scheduled service and maintenance.

Every 12 months.

Provide a written analysis from the test within ten working days after completion of the test. Scheduled service and maintenance.

Every 12 months.

Scheduled service and maintenance.

Over the 2-hour load bank testing period record:

Scheduled service and maintenance.

Every 12 months.

Time, volts of each phase, amps of each phase. KW, percent of load, Hertz, RPM, hour meter, power factor, oil pressure, fuel pressure, ambient temperature, engine water temperature, exhaust temperature (left and right), engine oil temperature, turbo boost psi, coolant temperature at heat exchanger or radiator (in and out), and coolant temperature at the engine (in and out)

Scheduled service and maintenance.

Level 6: Engine/Generator Inspection and Adjustment

Adjust engine valves and set to factory specification where applicable. Scheduled service and maintenance.

Every 36 months.

Check ignition and injector timing where applicable. Scheduled service and maintenance.

Every 36 months.

Check rear generator bearings, lubricate as necessary. Scheduled service and maintenance.

Every 36 months.

Inspect generator wiring. Scheduled service and maintenance.

Every 36 months.

Inspect space heaters. Scheduled service and maintenance.

Every 36 months.

Inspect coupling and guards. Scheduled service and maintenance.

Every 36 months.

Inspect the generator fan drive. Scheduled service and maintenance.

Every 36 months.

Inspect meters and voltage regulator as required. Scheduled service and maintenance.

Test run engine generator. Scheduled service and maintenance.

months.

Provide written report within ten working days of the completion of the work. Scheduled service and maintenance.

Level 9: Battery Replacement Program

Check complete electrical system, and make sure the battery charger is properly adjusted. Scheduled service and maintenance.

Every 36 months.

Check engine starter and amperage under normal operating conditions. Scheduled service and maintenance.

Every 36 months.

Remove and dispose of old lead acid batteries per EPA standards. Scheduled service and maintenance.

Every 36 months.

Install new low antimony batteries. Scheduled service and maintenance.

Every 36 months.

Provide written report within ten working days of the completion of the work. Scheduled service and maintenance.

Battery replacement: Every 36

Remove and properly dispose of lead acid batteries per EPA standards. Scheduled service and maintenance.

Every 36 months.

Clean and inspect battery cable ends.

Scheduled service and maintenance.

Every 36 months.

Clean battery box and required.

Scheduled service and maintenance.

Every 36 months.

Install new batteries.

Scheduled service and maintenance.

Every 36 months.

Inspect battery charger and electrical system.

Adjust charger as needed. Scheduled service and maintenance.

Every 36 months.

Check engine starter amperage.

Scheduled service and maintenance.

Fuel Level 31: Fuel Testing

Comprehensive. Provide written report within ten working days of the completion of the work. Scheduled service and maintenance.

Fuel sampling and testing: Every 12

ASTM D287 API Specific Gravity- 30.0 minimum.

Scheduled service and maintenance.

Every 12 months.

ASTM D86 Distillation rates at IBP, 10%, 50% 90% FBP Scheduled service and maintenance.

Every 12 months.

ASTM D4737 Cetane Index- 40.0 minimum Scheduled service and maintenance.

Biodiesel Content

Every 12 months.

ASTM D5453 sulfur- 15 ppm max Scheduled service and maintenance.

Every 12 months.

ASTM D93 Flash- 125 degrees F min Scheduled service and maintenance.

Every 12 months.

ASTM D6468 Stability- 80% minimum Scheduled service and maintenance.

Every 12 months.

ASTM D2500 Cloud Point- less than minus 40 degrees F Scheduled service and maintenance.

Every 12 months.

ASTM D6371 CFPP- less than minus 40 degrees F Scheduled service and maintenance.

Every 12 months.

Microbial- less than 1,000 RLU Scheduled service and maintenance.

Every 12 months.

ASTM D6304 Karl-Fisher- less than 100 ppm Scheduled service and maintenance.

Electrical Services

Level 11: Switches, breakers, relays. Transfer Switch and Switch gear Inspection, Adjustment, and Thermal Imaging.

Switches, breakers, relays. Clean transfer switch and cabinet, Replace PLC batteries. Check voltage drop across main contacts. Repair/replace incandescent lamps. Test bypass isolation feature. Visual inspection for evidence of arcing and/or hot spots.

Lubricate switch. Check operation of timers, remote start contacts and in-phase monitor. Dispose all parts and fluids per EPA standards. Scheduled service and maintenance.

Stationary Batteries for Emergency Switchgear Operation

Every 12 months.

Inspection and testing. Scheduled service and maintenance.

Every 12 months.

Bldg 154 batteries

Chiller MCC- 8 batteries- MTI Technologies, 6V-4- OPzS-200, 200 Ah Scheduled service and maintenance.

Every 12 months.

Bldg 153 batteries:

Generator BUS A- 24 batteries- FIAMM, SD5, 80 Ah Scheduled service and maintenance.

Every 12 months.

Generator BUS B2- 12 batteries- FIAMM, SD17, 320 Ah Scheduled service and maintenance.

Every 12 months.

Generator BUS B1- 24 batteries- FIAMM, SD7, 120 Ah Scheduled service and maintenance.

Utility BUS A- 24 batteries- FIAMM, SD7, 120 Ah

Every 12 months.

Utility BUS B- 24 batteries- FIAMM, SD5, 80 Ah Scheduled service and maintenance.

Battery cell water level. Specific gravity of each battery cell. Visual inspection of batteries. Battery voltage, impedance, and capacity testing. Clean battery terminals and all battery connections as needed. Scheduled service and maintenance.

Battery charger inspection and testing. Visual inspection, operation, voltage, and amperage. Clean all electrical connections as needed. Scheduled service and maintenance.

Every 12 months.

Provide a written analysis of all testing within ten working days after completion of the test. This service shall be completed every 12 months Scheduled service and maintenance.

Required Services Performance Objective Performance Requirement

Price quote Provide quote Provide during bidding period

Price quote Contractors shall supply a Quote on their letterhead.

Provide during bidding period

Price quote

Quoted price MUST INCLUDE all Materials, Labor, Equipment, Freight or Shipping, as well as any applicable Duties, Brokerage, or Custom’s fees.

Provide during bidding period

Price quote It is anticipated that a fixed Price Contract will be awarded.

Consider in quote

Price quote Award will be made for a 1-year base period with four optional 12 month option periods.

Consider in quote

Work requirements

Work requirements

Normal scheduled inspections and service work will be performed during regular workdays, 8:00 AM – 4:00 PM, local time. Federal holidays excluded. An extension of time before and after normal working hours will be considered upon a 2-week advance written request from the Contractor.

During the duration of the contract.

Work requirements

All service reports shall provide the required within 10 days of the service work.

During the duration of the contract.

Work requirements

Vendor will include by attachment to the proposal a contact phone number and the cell phone and other contact numbers for each representative assigned to service the account.

The vendor must have a representative available for phone calls during normal business hours.

During the duration of the contract.

8. DOCUMENTATION