This file is a Standard Operating Procedure (SOP) document detailing the fire alarm response protocols for the Statue of Liberty National Monument's Liberty Island facility. The document outlines three types of alarms (Fire Alarm/Urgent, Supervisory Alarm, and Trouble Alarm) and their respective notification and response requirements.

The document specifies that the fire alarm system is monitored by both an onsite Command Center and offsite Central Station Monitoring (CSM) providers - Advanced Electronic Solutions during operating hours and Rapid Response after hours. For Fire Alarm/Urgent responses, specific notification protocols are established for both operating and after-hours scenarios, requiring coordination between U.S. Park Police, Division of Safety and Emergency Management, Buildings & Utilities (B&U), and the Mechanical Contractor. The document mandates that only authorized personnel (including U.S. Park Police Officers, Park Emergency Medical Technicians, and maintenance staff) can clear alarms after physical inspection. When the system needs to be disabled, mandatory fire watch patrols must be conducted every 30 minutes until the system is restored. Post-alarm notifications must be emailed to specified personnel within one hour of any alarm activation.

View the file

Other files

File Type Posted
PWS_Attch_S009_1.pdf PDF
PWS_Attch_S017_1.pdf PDF
PWS_Attch_S012_1.pdf PDF
PWS_Attch_S015_1.pdf PDF
PWS_Attch_S004_1.pdf PDF
PWS_Attch_S011_1.pdf PDF
PWS_Attch_S007_1.pdf PDF
PWS_Attch_S003_1.pdf PDF
PWS_Attch_S001_1.pdf PDF
PWS_Attch_S008_1.pdf PDF
PWS_Attch_S014_1.pdf PDF
PWS_Attch_S006_1.pdf PDF
PWS_Attch_S016_1.pdf PDF
PWS_Attch_S010_1.pdf PDF
PWS_Attch_S002_1.pdf PDF
DRAFT_PWS_STLI_Mechanical_Services_2025_1_2_1.pdf PDF
PWS_Attch_S013_1.pdf PDF
140P4525R004_STLI_Mechanical_Services_SSS_1.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment S005

STU Mechanical Contractor/ Park Fire Alarm Response

Response to Fire Alarms at Liberty Island

Liberty Island Fire Alarm Response 11/26/2016

National Park Service

Response to Fire Alarm Activation

The Libe1ty lsland Fire Alann system is monitored onsite by the park dispatch center (hereafter referred to as the "Command Center") and off-site by an alarm monitoring company (hereafter referred to as the "Central Station Monitoring" or "CSM")

Note: The Ellis Island Fire Alarm system is NOT monitored by the central station monitoring and will be monitored after the Hurricane Sandy construction repairs are completed.

The CSM for Liberty Island is:

During Operating Hours:

Advanced Electronic Solutions (AES Fire) 1-973-887-3500 11 Melanie Lane Unit #8 East Hanover NJ, 07936

After Operating Hours (l 700hrs to 0800hrs) Rapid Response 800-932-3822 Account Number: L270095

The Fire Alann System has three (3) types of alarms: Fire Alann/Urgent, Supervisory Alann and

Trouble Alann. Each type of alann has different notification and response requirements.

Wl1en an alarm is activated in the Liberty Island fire alann system, a signal is simultaneously sent to the fire monitor screen located in the command center and to the central monitoring station who upon receipt of an alam1 will call the command center by phone to notify them of the alann activation at Liberty Island. The central station monitoring will only notify the command center of an alann activation and will not provide a location.

When the central station monitoring calls to notify the Command Center staff of an alann at

Liberty Island, the command center staff will use the fire alann monitor located in the command center to obtain the type of alarm and location. Once the location and alann type is determined then the command center staff will dispatch the appropriate personnel to the scene. Command

�enter slaff will documenl all alarms in the Fire Alarms Command Center Log Oook

Fire Alann/Urgcnt

A Fire Alarm/Urgent Alarm is an alarm triggered by a signaling device within the.fire alarm system, these include, smoke detectors, heat detectors, pull stations and certain duct detectors.

'nze activation of any of these device types will trigger an alarm notf/ication to the CMS. release door magnets so that doors will ciose to contain the.fire and activate the audibie alarm and strobes to alert the public.

NOTIFICATIONS:

Upon Receipt of a Fire Alann/ Urgent, The command center will make the following notifications:

During operating hours

1. Notify the United States Park Police Via Radio

2. Notify the Division of Safety and Emergen�y Managemeul via radio

3. Notify B&U via radio.

A. lf unable to reach by radio after two attempts, continue calling by radio & call 646-285-5255 until contact is made.

8. After notifying B&U, contact Frank Cook 732-546-4826 and Sean Reynolds 646-739-2437

4. Notify the Mechanical Contractor via radio

After operating hours

1. Notify the United States Park Police Via Radio

2. Notify the Division of Facilities Management by Landlinc:

Dave Crotty 732-894-1046

Frank Cook 732-546-4826

Sean Reynolds 646-739-2437

After operating hours, a member of Facilities will be respond to the park to reset the system

3. Notify the Division of Safety and Emergency Management

By landline: Franco Paolino 646-265-6636

4. Notify the Mechanical Contractor via radio

The command center will notify the above personnel of:

(1) The location of the alann,

(2) The type of alarm (Pull Station, Smoke head, Heat sensor)

(3) The smoke head number.

**U.S Park Police: See Page 06 for Post Alarm Notifications**

Fire Alarm/Urgent (Continued)

RESPONSE

Once notified by the command center, the personnel will proceed to the location:

If no immediate danger to life and health (IDLH) is found, the unit on scene will verify with the command center the location of the alann to make sure that they are at the correct location. Once confinned, then the Facilities Division and the Mechanical Contractor will respond to the Alann

Panel and confirm the number and location of the activated detector/head.

If a smoke or a fire condition exists then further assistance and resources will be requested via radio and the command center staff will make the appropriate notifications.

RE-SETTING AN ALARM

- If no IDLH is found, the command center shall request that maintenance or the Mechanical

Contractor can attempt to reset the alarm.

- ONLY the Mechanical Contractor or B&U can reset an alarm

- After operating hours, a member of the Park Facilities will be respond to Ellis Island and will be transported to Liberty Island via U.S Park Police Boat to re-set the alarm

- Fire alarms will only be cleared after physical .inspection is conducted by authorized staff.

Authorized staff includes:

A. Officers and Supervisors of the United States Park Police B. Park Emergency Medical Technicians, EMS Coordinator or Division Chief C. Employees of the Park maintenance Division & the Mechanical Contractor.

- Upon determination that the structure is safe to enter, the U.S Park Police Supervisor will be responsible for coordinating reentry into building.

- Once the alarm system has been re-set, the Mechanical Contractor will notify the CMS of the disposition and that the system has been reset.

DOCUMENTATION:

The Command center staff is responsible for documenting all information related to the alarm.

Supervisory Alarm

A Supervisory Alarm is activated when a monitored device which is not a threat has been activated

A Supervisory Alarm can include the activation o..f"sprinkler valves and certain duel detectors

NOTIFICATIONS:

Upon receipt of a Supervisory Alann, the Command Center will notify the Facilities

Division and the Mechanical Contractor via radio.

If unable to reach the Facilities Division and the Mechanical Contractor by radio after two c1ttcmpts, the command center will continue calling hy radio and hy landline at the numbers below until contact is made.

1. B&U Frank Cook 732-546-4826

2. Mechanical Contractor 646-416-7343

The Command Center will notify the above personnel of:

(1) The location of the alarm.

(2) That it is a Supervisory Alarm

**U.S Park Police: See Page 06 for Post Alarm Notifications**

DOCUMENTATION:

The Command center staff is responsible for documenting all information related to the a\ann.

Trouble Alarm

A Trouble Alarm is activated when there is a.fault in the system, this does not mean the system will not function but that it requires attention.

A trouble Alarm can include Ground Faults, Dirty Smoke Detectors, Wiring Faults, etc

NOTIFICATIONS:

Upon receipt of a Trouble Alarm, the Command Center will notify the Facilities Division and C&S via radio.

If unable to reach the Facilities Division and the Mechanical Contractor by radio after two attempts, the command center will continue calling by radio and by landline at the numbers below until contact is made.

1. B&U Frank Cook 732-546-4826

2. Mechanical Contractor 646-416-7343

The Command Center will notify the above personnel of:

( 1) The location of the alarm,

(2) That it is a Trouble Alarm

**U.S Park Police: See Page 06 for Post Alarm Notifications**

DOCUMENTATION:

The Command center staff is responsible for documenting all information related to the alann.

Post Alarm Notifications

Within one hour of receipt of a notification of any type of fire alarm by the Command Center, the United States Park Police shall E-mail the following personnel with the details (location of alarm, alarm type, personnel that responded, start and clear times and the disposition):

Mike Amato

Cherie Butler

Dave Crotiy

Pete Culver

Frank Cook

Tom Duncan

Mike_Amato@nps.gov

Cherie_butler@nps.gov

Dave_ Crotty@nps.gov

Peter _culver@nps.gov

Arthur_ cook@nps.gov

German Epshteyn

T omd@cnsbuilding.com

German_epshteyn@nps.gov

Ben_hanslin@nps.gov

Christopher _Kyriakou@nps.gov

Anthony _lordo@nps.gov

Chris_parsons@nps.gov

Franco_paolino@nps.gov

Sean_reynolds@nps.gov

Ben Hanslin

Chris Kyriakou

Anthony Lordo

Chris Parsons

Franco Paolino

Sean Reynolds

Disabling of the Fire Alarm System

1. In the event that the fire alarm system must be disabled, the command center must be notified prior to the system being disabled.

2. Once notified that the fire system is being disabled, the command center must make the following notifications:

1. Notify the U.S Park Police via radio

2. Notify EMTs via radio (If after hours contact: Franco Paolino 646-265-6636)

3. Notify the Division of Facilities Management by Landline

3. Upon Notification that the Fire System is being disabled, U.S Park Police Officers and

Park Emergency Medical Technicians will conduct fire watch patrols every 30 minutes to check for fire and/or smoke conditions in the areas covered by the fire alarm system until the fire alam, system is placed back into service