PSXE172003 Ground Base PV Array -Final Drawings1.pdf
PDF 14 MB Posted
- Attached to
- PV Array Federal contract opportunity
- Solicitation number
- W50S98-23-B-0001
About this file
This solicitation is for a construction contract to construct a ground-based photovoltaic (PV) array at McGhee Tyson Air National Guard Base in Tennessee. The project magnitude is between $5 million and $10 million. The North American Industry Classification System code is 237130 for electrical contractors with a small business size standard of $45 million in average annual receipts. This opportunity is set aside for small businesses. Interested parties are encouraged to attend a pre-bid conference onsite. Funding is not presently available but is expected to be appropriated prior to award as this project is on the National Guard's priority list. The award will be made to the responsible bidder whose bid conforms to the solicitation and is most advantageous to the Government based on price and price-related factors. The soliciting agency is the Department of the Army Tennessee Army National Guard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF_1419..pdf | ||
| PV Array Bid Opening Sign In Sheet.pdf | ||
| Abstract PV Array.pdf | ||
| W50S98-23-B-00010001.pdf | ||
| Sheet E6.2 Ground Base PV Array.pdf | ||
| AC Wire and Conduit Specifications.png | PNG image | |
| Pre-Bid Slides PV Array.pdf | ||
| Site Visit Sign in PV Array.pdf | ||
| W50S98-23-B-0001 PV Array.pdf | ||
| B3 Project Manual - 03202023 (Rev 1).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Printed on ___% Post-Consumer Recycled Content Paper
AR
C
H D
4" x
6" La st s av ed b y:
M
AR
K.
LO
M O
N
IC
O (2
2-
-1
1)
L as t P lo tte d:
2-
-1
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
Fi le na m e:
L
:\D C
S\
PR
O
JE
C
TS
\B D
L\
_T
N _A
N G
_P V\
0_
C
AD
_G
IS
\9
_C
AD
\C
IV
IL
\C
-S H
EE
TS
\C -0
S
IT
E
PL
AN
.D W
G M
C L
G H
F
JR
O MCGHEE TYSON AIR NATIONAL GUARD BASE
CONSTRUCT GROUND BASE PV ARRAY
PSXE172003
134TH AIR REFUELING WING
123 BRISCOE DRIVE
MCGHEE TYSON AIR NATIONAL GUARD BASE
TN, 37777
300 SOUTH GRAND AVENUE
LOS ANGLES, CA 90071
213.593.8100 TEL
213.593.8178 FAX
SHEET INDEX
C1.0 SITE LAYOUT
C2.0 POI LAYOUT
C3.0 EROSION AND SEDIMENT CONTROL PLAN
C3.1 EROSION AND SEDIMENT CONTROL PLAN AND NOTES
E1.0 SOLAR ELECTRICAL NOTES, SYMBOLS, AND ABBREVIATIONS
E2.0 SOLAR ELECTRICAL OVERALL SITE PLAN
E2.1 SOLAR ELECTRICAL DC CIRCUIT PLAN
E2.2 INVERTER/TRANSFORMER STATION DETAILS
E3.0 POINT OF INTERCONNECTION OVERALL SITE PLAN
E3.1 POINT OF INTERCONNECTION DETAILS
E4.0 SOLAR ELECTRICAL SIGNAGE, LABELS, AND MARKINGS
E4.1 ELECTRICAL DETAILS (SOLAR EQUIP. MOUNTING)
E4.2 ELECTRICAL DETAILS (DC SYSTEM GROUNDING)
E4.3 ELECTRICAL DETAILS (AC SYSTEM GROUNDING)
E4.4 ELECTRICAL DETAILS (GROUNDING)
E4.5 ELECTRICAL DETAILS (TRENCH SECTIONS)
E5.0 ELECTRICAL SITE SINGLE LINE DIAGRAM
E5.1 ELECTRICAL SOLAR SINGLE LINE DIAGRAM
E5.2 ELECTRICAL DATA ACQUISITION SYSTEM AND COMM BLOCK DIAGRAM
E5.3 ELECTRICAL MV SWITCHGEAR SINGLE LINE DIAGRAM
E5.4 ELECTRICAL MV SWITCHGEAR SINGLE LINE DIAGRAM
E5.5 ELECTRICAL POWER MONITORING AND CONTROL SIGNAL LIST
E6.0 ELECTRICAL FEEDER SCHEDULE
E6.1 ELECTRICAL PANEL SCHEDULES
E6.2 LOW VOLTAGE ELECTRICAL PANEL SCHEDULE
S1.0 STRUCTURAL NOTES
S1.1 STATEMENT OF SPECIAL INSPECTIONS
S2.0 INVERTER/TRANSFORMER FOUNDATION PLAN AND DETAILS
S2.1 POINT OF INTERCONNECTION FOUNDATION PLAN AND DETAILS
PROJECT REVIEW
GROUND SAFETY__________________ DATE:_______
FIRE DEPARTMENT_________________ DATE:_______
COMMUNICATIONS________________ DATE:_______
ENVIRONMENTAL MANAGEMENT_____ DATE:_______
USING ORGANIZATION______________ DATE:_______
PROJECT MANAGER_________________DATE:_______
SECURITY_________________________ DATE:_______
ATO_____________________________ DATE:_______
WING / CC________________________ DATE:_______
CONTRACTING OFFICER_____________ DATE:_______
CIVIL ENGINEER____________________ DATE:_______
DOCUMENTS UPDATED FOR
RE-BID MARCH 14, 2023
W
24" RCP24" RCP
" R
C P
24" RCP
" R
C P
" R
C P
" R
C P
4"PE 3408
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
W
24" RCP24" RCP
" R
C P
24" RCP
" R
C P
" R
C P
" R
C P
4"PE 3408
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
Th is dra win g h as be en pr ep are d f or the us e o f A
EC
OM
's c lie nt an d m ay no t b e u se d, rep rod uc ed or re lie d u po n b y t hir d p art ies , e xc ep t a s a gre ed by
AE
CO
M an d i ts clie nt, as re qu ire d b y l aw or fo r u se by go ve rnm en tal re vie win g a ge nc ies . A
EC
OM
ac ce pts no re sp on sib ility , a nd de nie s a ny lia bil ity w ha tso ev er, to an y p art y t ha t m od ifie s t his dr aw ing w ith ou t A
EC
OM
's e xp res s w ritt en co ns en
t. D o n ot sc ale th is do cu me nt.
Al l m ea su rem en ts mu st be ob tai ne d f rom st ate d d im en sio ns
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
M
AR
K.
LO
M
O N
IC
O
(2
3-
6) t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
L
:\D C
S\
PR
O
JE
C
TS
\B D
L\
_T
N _A
N G
_P V\
0_
C
AD
_G
IS
\9
_C
AD
\C
IV
IL
\C
-S H
EE
TS
\C -0
S
IT
E
PL
AN
.D W
G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing 123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
MCGHEE TYSON ANG
SITE LAYOUT
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 FINAL DESIGN
C1.0
1. SITE ACCESS WILL BE THROUGH EXISTING ACCESS DRIVES AND
PARKING AREAS OFF OF EITHER HANDLEY AVENUE OR BRISCOE
DRIVE. SEE BASE ACCESS NOTES SHEET C2.0
2. SEE ELECTRICAL DRAWINGS FOR SYSTEM DESCRIPTION.
3. FINAL GRADE FOR SITE AND ROADWAYS SHALL MATCH
EXISTING GRADE. AERIAL VIEWS SHOW EXISTING GRAVEL
DRIVE WHERE THE NEW SITE DRIVE IS PROPOSED.
CONTRACTOR TO INVESTIGATE EXISTING DRIVE AND
SUPPLEMENT AS NECESSARY ACCORDING TO THE PLAN
DETAILS.
GENERAL NOTES:
LEGEND:
SOLAR PV TABLE
INVERTER/TRANSFORMER STATION
EXISTING COMPACTED AGGREGATE
ROAD TO BE PAVED WITH ASPHALT
SEE DETAIL THIS SHEET
CONTRACTOR STAGING AREA
LIMIT OF LOW GROWING SEED
MIXTURE
EXISTING RIP RAP
SCALE:
A
C1.0
ASPHALT PAVEMENT
NTS
BASE PV ARRAY
SCALE:
D
C1.0
GRADING AT INVERTER
1"=20'
LEGEND
TP = TOP OF
CONCRETE PAD
ELEVATION
BP=GROUND
ELEVATION AT
BOTTOM OF PAD
G
G
W
24" RCP24" RCP
" R
CP
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82 CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
G
G
W
24" RCP24" RCP
" R
CP
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82 CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
Th is dra win g h as be en pr ep are d f or the us e o f A
EC
OM
's c lie nt an d m ay no t b e u se d, rep rod uc ed or re lie d u po n b y t hir d p art ies , e xc ep t a s a gre ed by
AE
CO
M an d i ts clie nt, as re qu ire d b y l aw or fo r u se by go ve rnm en tal re vie win g a ge nc ies . A
EC
OM
ac ce pts no re sp on sib ility , a nd de nie s a ny lia bil ity w ha tso ev er, to an y p art y t ha t m od ifie s t his dr aw ing w ith ou t A
EC
OM
's e xp res s w ritt en co ns en
t. D o n ot sc ale th is do cu me nt.
Al l m ea su rem en ts mu st be ob tai ne d f rom st ate d d im en sio ns
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
M
AR
K.
LO
M
O N
IC
O
(2
3-t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
L
:\D C
S\
PR
O
JE
C
TS
\B D
L\
_T
N _A
N G
_P V\
0_
C
AD
_G
IS
\9
_C
AD
\C
IV
IL
\C
-S H
EE
TS
\C -0
S
IT
E
PL
AN
.D W
G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing 123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
MCGHEE TYSON ANG
POI LAYOUT
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 FINAL DESIGN
C2.0
BASE PV ARRAY
SEED MIXTURE SCHEDULE
CREEPING THYME Thymus praecox
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
24" RCP24" RCP
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
CW
Th is dra win g h as be en pr ep are d f or the us e o f A
EC
OM
's c lie nt an d m ay no t b e u se d, rep rod uc ed or re lie d u po n b y t hir d p art ies , e xc ep t a s a gre ed by
AE
CO
M an d i ts clie nt, as re qu ire d b y l aw or fo r u se by go ve rnm en tal re vie win g a ge nc ies . A
EC
OM
ac ce pts no re sp on sib ility , a nd de nie s a ny lia bil ity w ha tso ev er, to an y p art y t ha t m od ifie s t his dr aw ing w ith ou t A
EC
OM
's e xp res s w ritt en co ns en
t. D o n ot sc ale th is do cu me nt.
Al l m ea su rem en ts mu st be ob tai ne d f rom st ate d d im en sio ns
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
M
AR
K.
LO
M
O N
IC
O
(2
3-t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
L
:\D C
S\
PR
O
JE
C
TS
\B D
L\
_T
N _A
N G
_P V\
0_
C
AD
_G
IS
\9
_C
AD
\C
IV
IL
\C
-S H
EE
TS
\C -2
E
R O
SI
O
N A
N D
S
ED
IM
EN
T C
O N
TR
O
L
PL
AN
.D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing 123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
MCGHEE TYSON ANG
EROSION AND SEDIMENT
CONTROL PLAN
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 FINAL DESIGN
C3.0
1. SITE ACCESS WILL BE THROUGH EXISTING ACCESS DRIVES AND PARKING
AREAS OFF OF EITHER HANDLEY AVENUE OR BRISCOE DRIVE. SEE BASE
ACCESS NOTES SHEET C2.0.
2. SEE ELECTRICAL DRAWINGS FOR SYSTEM DESCRIPTION.
3. THERE WILL BE NO GRADING ACTIVITIES ASSOCIATED WITH THIS PROJECT.
THE ONLY TIME THE SOIL WILL BE EXPOSED IS WHEN THE EXISTING
VEGETATION IS TERMINATED TO ALLOW FOR PERMANENT SEEDING.
THEREFORE, THE THREE PHASE PLAN SET DESCRIBING THE DIFFERENT
STAGES OF GRADING WILL NOT BE PROVIDED.
GENERAL NOTES:
LEGEND:
SOLAR PV TABLE
INVERTER/TRANSFORMER STATION
EXISTING COMPACTED AGGREGATE
ROAD TO BE PAVED WITH ASPHALT
SEE DETAIL C1.0
LOW GROWING NATIVE SEED
MIXTURE
SILT FENCE OR STRAW WATTLE
CONSTRUCTION ENTRANCE
CONCRETE WASHOUT
SCALE:
A
C3.0
SILT FENCE
NTS
SCALE:
D
C3.0
MULCH / EROSION CONTROL BLANKET
NTS
SCALE:
B
C3.0
STABILIZED CONSTRUCTION ENTRANCE
NTS
BASE PV ARRAY
EROSION CONTROL
BLANKETS STAPLING
PATTERN PER MANUF.
RECOMMENDATIONS
TOE-IN BLANKET
8" MIN. AT TOP
(TYP. BOTH
SIDES) REFER TO PLANS
FOR SLOPES &
WIDTHS
REFER TO SPECS FOR EROSION
CONTROL BLANKET MANUFACTURER &
MODEL NUMBERS
N
SCALE:
C
C3.0
CONCRETE WASHOUT AREA
NTS
CW
SCALE:
E
C3.0
STRAW WATTLE
NTS
G
G
W
24" RCP24" RCP
" R
CP
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82 CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
G
G
W
24" RCP24" RCP
" R
CP
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82 CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
CW
Th is dra win g h as be en pr ep are d f or the us e o f A
EC
OM
's c lie nt an d m ay no t b e u se d, rep rod uc ed or re lie d u po n b y t hir d p art ies , e xc ep t a s a gre ed by
AE
CO
M an d i ts clie nt, as re qu ire d b y l aw or fo r u se by go ve rnm en tal re vie win g a ge nc ies . A
EC
OM
ac ce pts no re sp on sib ility , a nd de nie s a ny lia bil ity w ha tso ev er, to an y p art y t ha t m od ifie s t his dr aw ing w ith ou t A
EC
OM
's e xp res s w ritt en co ns en
t. D o n ot sc ale th is do cu me nt.
Al l m ea su rem en ts mu st be ob tai ne d f rom st ate d d im en sio ns
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
M
AR
K.
LO
M
O N
IC
O
(2
3-t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
L
:\D C
S\
PR
O
JE
C
TS
\B D
L\
_T
N _A
N G
_P V\
0_
C
AD
_G
IS
\9
_C
AD
\C
IV
IL
\C
-S H
EE
TS
\C -2
E
R O
SI
O
N A
N D
S
ED
IM
EN
T C
O N
TR
O
L
PL
AN
.D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing 123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
MCGHEE TYSON ANG
EROSION AND SEDIMENT CONTROL
PLAN AND NOTES
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 FINAL DESIGN
C3.1
BASE PV ARRAY
N
1. NOT ALL SYMBOLS AND/OR ABBREVIATIONS INCLUDED
IN THIS SHEET ARE NECESSARILY USED IN THIS
PROJECT.
2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE
ADOPTED NEC (NFPA 70) AND THE AUTHORITY HAVING
JURISDICTION. IN CASES OF CONFLICT, THE MORE
STRINGENT REQUIREMENTS SHALL BE MET.
3. SOLAR PHOTOVOLTAIC SYSTEM INSTALLATION SHALL
CONFORM TO NEC ARTICLE 690.
4. MINIMUM CONDUCTOR SIZES SHALL BE #12 WITH A #12
GND, UNLESS LARGER SIZES ARE NOTED.
5. COMPONENTS ARE SHOWN IN THEIR GENERAL VICINITY
AND MAY NOT NECESSARILY MATCH LOCATIONS SHOWN
ON THE DRAWINGS. FIELD VERIFY LOCATIONS OF
COMPONENTS, RUN ASSOCIATED CONDUITS AND PLACE
MODULES ACCORDINGLY.
6. ALL CONDUCTOR FEEDS SHALL BE CONTINUOUS RUNS,
NO SPLICES.
7. APPROXIMATE LENGTHS OF LONG FEEDER RUNS.
CONDUCTOR SIZES MAY HAVE BEEN UPSIZED TO
COMPENSATE FOR VOLTAGE DROP.
8. ALL DC AND AC CIRCUITS IN PULL SECTIONS, COMBINER
BOXES, INVERTERS, AND DISCONNECTS SHALL BE
CLEARLY IDENTIFIED FOR CIRCUIT NUMBER, POLARITY,
AND PHASE BY PERMANENT MEANS.
9. CONDUIT SHALL BE INSTALLED IN A NEAT,
INCONSPICUOUS AND ORDERLY MANNER. THE
INSTALLER SHALL VERIFY THE OVERALL LENGTH TO
ENSURE NO ADDITIONAL VOLTAGE DROP.
10. ALL EXPOSED POWER FEEDS SHALL BE PROTECTED IN
CONDUIT. SUPPORT CONDUIT RUNS PER NEC.
11. ALL EXPOSED EXTERNAL CONDUIT SHALL BE RMC
UNLESS OTHERWISE NOTED.
12. MINIMUM 2KV RATED PV CABLE (RHW-2 2KV) OR
EQUIVALENT FOR ALL EXTERNAL EXPOSED CABLES
SHALL BE USED.
13. THE FOLLOWING PERMANENT SIGNAGE, PER NEC
ARTICLE 690.53, IS REQUIRED AT ALL DISCONNECTING
MEANS (INCLUDING COMBINERS AND INVERTERS):
(1) MAXIMUM VOLTAGE
(2) MAXIMUM CIRCUIT CURRENT
14. INSTALLER SHALL READ AND FOLLOW ALL
MANUFACTURER INSTALLATION INSTRUCTIONS IN
ADDITION TO DRAWINGS AND SPECIFICATIONS.
15. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH
OTHER TRADES AT THE SITE. ANY COSTS TO INSTALL
WORK TO ACCOMPLISH SAID COORDINATION WHICH
DIFFERS FROM THE WORK AS SHOWN ON THE
DRAWINGS SHALL BE INCURRED BY THE CONTRACTOR.
ANY DISCREPANCIES, AMBIGUITIES OR CONFLICTS
SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER FOR CLARIFICATION.
16. INSTALLER SHALL SUBMIT A FORMAL RFI FOR
CLARIFICATIONS, CONFLICTS, AND ANY ERRORS OR
OMISSIONS OF DRAWINGS AND SPECIFICATIONS
PERTAINING TO THE DESIGN AND INSTALLATION OF THE
SYSTEM.
17. ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE
NEW AND SHALL BE LISTED BY UNDERWRITER'S
LABORATORIES (UL) AND BEAR THEIR LABEL, OR LISTED
AND CERTIFIED BY A NATIONALLY RECOGNIZED
TESTING AUTHORITY WHERE UL DOES NOT HAVE A
LISTING
18. ENTIRE SYSTEM TO BE PROPERLY GROUNDED.
GROUNDING ELECTRODE SYSTEM FOR INVERTER,
GROUNDING CONDUCTOR IS 8 AWG OR SIZED
ACCORDING TO CODE AND CONTINUOUS OR
IRREVERSIBLY SPLICED.
19. THE CONTRACTOR SHALL PROVIDE AND KEEP
UP-TO-DATE A COMPLETE RECORD SET OF DRAWINGS.
THESE PRINTS SHALL BE CORRECTED DAILY AND SHOW
EVERY CHANGE FROM THE ORIGINAL DRAWINGS. THIS
SET OF DRAWINGS SHALL BE KEPT ON THE JOB SITE
AND SHALL BE USED ONLY AS A RECORD SET. THIS
SHALL NOT BE CONSTRUED AS AUTHORIZATION FOR
THE CONTRACTOR TO MAKE CHANGES IN THE LAYOUT
WITHOUT DEFINITE INSTRUCTION IN EACH CASE. UPON
COMPLETION OF THE WORK, A SET OF REPRODUCIBLE
CONTRACT DRAWINGS SHALL BE OBTAINED FROM THE
ENGINEER, AND ALL CHANGES AS NOTED ON THE
RECORD SET OF DRAWINGS SHALL BE INCORPORATED
THEREON WITH RED INK IN A NEAT, LEGIBLE,
UNDERSTANDABLE AND PROFESSIONAL MANNER.
FAILURE TO KEEP RECORD DRAWINGS UP-TO-DATE
SHALL CONSTITUTE CAUSE FOR WITHHOLDING OF
PROGRESS PAYMENTS.
20. AFTER ALL REQUIREMENTS OF THE DRAWINGS HAVE
BEEN FULLY COMPLETED, REPRESENTATIVES OF THE
OWNER WILL INSPECT THE WORK. THE CONTRACTOR
SHALL PROVIDE COMPETENT PERSONNEL TO
DEMONSTRATE THE OPERATION OF ANY ITEM OR
SYSTEM TO THE FULL SATISFACTION OF EACH
REPRESENTATIVE. FINAL ACCEPTANCE OF THE WORK
WILL BE MADE BY THE CONTRACTING OFFICER AFTER
RECEIPT OF APPROVAL AND RECOMMENDATION OF
ACCEPTANCE FROM EACH REPRESENTATIVE.
21. ALL FINAL CONNECTIONS TO OWNER FURNISHED
EQUIPMENT SHALL BE MADE BY THE CONTRACTOR.
22. CONTRACTOR IS RESPONSIBLE TO COORDINATE
LOCATION OF EXISTING UTILITIES. THE CONTRACTOR
SHALL USE EXTREME CAUTION WHEN TRENCHING,
BORING, OR DRILLING. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PROPER AND APPROVED
REPAIR OF ANY AND ALL DAMAGES CAUSED.
23. BEFORE CORE DRILLING THROUGH FLOOR SLABS FOR
CONDUIT RUNS, CONTRACTOR TO USE GROUND
PENETRATING RADAR/X-RAY DEVICE TO LOCATE ANY
EXISTING IMBEDDED CONDUIT OR PIPING IF CONDITION
EXISTS.
24. REFER TO SINGLE LINE DIAGRAM AND FEEDER
SCHEDULES FOR CONDUIT AND CONDUCTOR SIZE TO
PANELS, ETC. CONDUIT RUNS MAY NOT BE SHOWN ON
DRAWINGS, BUT ARE PART OF THIS CONTRACT.
25. CONTRACTOR IS RESPONSIBLE TO RESTORE ALL
SURFACES REGARDLESS OF TYPE (LANDSCAPE,
PAVING, CEMENT OR OTHER).
26. INVERTERS SHALL BE CERTIFIED AND TESTED IN
ACCORDANCE WITH THE MOST RECENT VERSION OF UL
1741 and UL 1741SA.
27. AUTOMATIC DISCONNECT DEVICE(S) SHALL MEET ALL
APPLICABLE LOCAL AND FEDERAL CODES AND
OPERATED BY OVER AND UNDER VOLTAGE AND OVER
AND UNDER FREQUENCY PROTECTION IN ACCORDANCE
WITH IEEE1547.
28. DISCONNECT SWITCH TO BE EXTERNAL, MANUAL,
VISIBLE, GANG-OPERATED, LOAD BREAK TYPE LOCATED
WITHIN THE SPECIFIED DISTANCE OF ALCOA'S
EXTERNAL ELECTRIC SERVICE AS DEPICTED IN
DRAWINGS.
29. CONTRACTOR SHALL BE RESPONSIBLE TO COMMISSION
AND PROVIDE A FULLY OPERATIONAL SYSTEM.
30. CONTRACTOR TO COORDINATE ALL UNDERGROUND
AND INTERCONNECTION WORK WITH AECOM
ELECTRICAL ENGINEER.
31. SOLAR PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH
ALL REQUIREMENTS IN THE 2012 IFC SECTION 605.11,
AND ALL OTHER APPLICABLE LOCAL CODES.
32. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
THAT ALL GROUND WORK FOR THE GROUND MOUNTED
SOLAR ARRAY AVOIDS ALL UNDERGROUND UTILITIES
DURING CONSTRUCTION.
33. CONTRACTOR TO BE NABCEP CERTIFIED
ABBREVIATIONS
GENERAL NOTES:
NON-FUSED DISCONNECT
DESCRIPTION
ELECTRICAL
SYMBOL
FLEXIBLE CONDUIT CONNECTION
GROUND
FUSE
CONTACTOR
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
POWER TRANSFORMER
UTILITY GRADE METERM
ELECTRICAL
DESCRIPTIONSYMBOL
XXXX
CONTINUED ON SAME DWG OR ANOTHER
CONDUCTOR/CONDUIT NUMBER
SEE DC + AC WIRE AND CONDUIT ~700' APPROXIMATE LENGTH OF RUN
SEE GENERAL NOTE 5
CONDUIT EXPOSED
FUSED DISCONNECT
DC TO AC POWER INVERTER
PHOTOVOLTAIC FLAT PLATE
MODULE ARRAY
STRING IDENTIFIER
POSITIVE QUICK CONNECTOR
NEGATIVE QUICK CONNECTOR
CIRCUIT BREAKER
LEGEND & SYMBOLS:
X
GENERAL SYMBOLS
DESCRIPTIONSYMBOL
SECTION
ELEVATION
DETAIL (ENLARGED)
DETAIL NUMBER
SHEET NUMBER
A EQUIPMENT CALLOUT
SEE NOTE INDICATED
EXX-YY DRAWING REFERENCE WHERE
EQUIPMENT IS LOCATED.
DWG. a - CONTINUATION REFERENCE
THREE PHASE WYE (GROUNDED)
GROUND ROD
STUB-OUT & CAP
A AMPERES
AC ALTERNATING CURRENT
ACD ASBESTOS CEMENT DUCT
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
C CONDUIT
CB CIRCUIT BREAKER
CBX COMBINER BOX
CKT CIRCUIT
CO CONDUIT ONLY
CP CONTROL PANEL
DAS DATA ACQUISITION SYSTEM
DB DUCT BANK
DC DIRECT CURRENT
DS DISCONNECT SWITCH
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
ELEC ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
F FLUORESCENT
GND GROUND
G GFCI
H HALOGEN
HID HIGH INTENSITY DISCHARGE
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
ICP INSTRUMENTATION CONTROL PANEL
Imp CURRENT, MAX POWER POINT
INSTR INSTRUMENTATION
INV INVERTER
Isc CURRENT, SHORT CIRCUIT
JB JUNCTION BOX
JBOX JUNCTION BOX
kcmil THOUSAND CIRCULAR MILS
KV THOUSAND VOLTS, KILOVOLTS
KVA KILOVOLT-AMPERE
kW KILOWATT
LCP LOCAL CONTROL PANEL
LO LOCKOUT
LOS LOCKOUT SWITCH
LV LOW VOLTAGE
MAX MAXIMUM
MET METEOROLOGICAL (WEATHER)
MTR METER
MV MEDIUM VOLTAGE
(N) NEW
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
O/C OPEN/CLOSE
OAE OR APPROVED EQUIVALENT
OFC OIL FILLED CONDUIT
P POLE
PB PULLBOX
PNL PANEL
PT POTENTIAL TRANSFORMER
PTC PV USA TEST CONDITIONS
POCC POINT OF COMMON COUPLING
POI POINT OF INTERCONNECTION
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
REF REFERENCE
RMC RIGID METAL CONDUIT
SEC SECOND
SIM SIMILAR
SP SPARE
STC STANDARD TEST CONDITIONS
SWGR SWITCHGEAR
TEMP TEMPERATURE
TJB TERMINAL JUNCTION BOX
TSP TWISTED SHIELDED PAIR
TST TWISTED SHIELDED TRIAD
TTC TELEPHONE TERMINAL CABINET
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
Vmp VOLTAGE, MAX POWER POINT Voc VOLTAGE, OPEN CIRCUIT
W WATT
WP WEATHERPROOF
WS WEATHER STATION
XFMR TRANSFORMER
X
XX
X
RECLOSER
CABLE TERMINATION
SEPARABLE CONNECTOR
FUSED CUT OUT DISCONNECT
DRAWOUT BREAKER WITH RELAY CONTROL
DC FUSE
SURGE ARRESTOR
CADWELD CONNECTION
SPECIFICATION TABLE
XAF
XAT AF = AMP FRAME, AT = AMP TRIP
XX
X
XX
X
UNDERGROUND ELECTRICAL
UNDERGROUND TELECOM
UNDERGROUND GROUND CONDUCTOR
E
C
GC
RECEPTACLE
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
F
AR
ES
A(
-0
5-
La st
P lo tte d:
2-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
FA
R
ES
A\
AE
C
O M
\E N
ER
G
Y G
R O
U P-
SO
LA
R T
EA
M
G
EN
ER
AL
\S
AM
D
O W
N
LO
AD
\M
C G
H
EE
T
YS
O N
N
AT
IO
N
AL
G
U
AR
D \C
AD
\M
C G
H
EE
T
YS
O N
N G
B
SO
LA
R
P R
O
JE
C T_
B-
-1
1-
IF
C .D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
SOLAR ELECTRICAL NOTES,
SYMBOLS AND ABBREVIATIONS
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-01 B2 DESIGN
F 2022-04-11 B3 DESIGN
G 2022-05-09 B4 DESIGN
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E1.0
W
36" R
CP
" R
C P
24" RCP
" R
C P
18" RCP
" R
C P
" R
C P
4"PE 3408
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
EXISTING FAA CABLE CONSIST OF (3) DIRECT
BURIED CABLES SIDE BY SIDE. VERIFY PRIOR TO
DIGGING THAT FAA HAS LOCATED AND MARKER
UNDERGROUND UTILITIES IN THE AREA
PROPOSED SITE
ACCESS ROAD, SEE
CIVIL DRAWINGS
AC INVERTERS, PV
SWITCHBOARD, AND MV
TRANSFORMER
A E2.0
PV TABLE TYP. OF 126 (24 PV
MODULES IN SERIES) (1.451 MW)
DC CONDUITAND TRENCH
MV ROUTE TO POINT OF INTERCONNECTION
B E2.0
NOTE: SLOPE OF TERRAIN VARIES
THROUGHOUT SITE, NOT SHOWN
FOR CLARITY
SEE RACKING MANUFACTURER
LAYOUT AND SHOP DRAWINGS
10'-0"
22'-11"
2'-0" MIN
CLEARANCE
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
S
D G
U
SE
R
(2
3-
4) t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
SD
G
U
SE
R
\O N
ED
R
IV
E
- A
EC
O M
\C
AD
\M C
G H
EE
T
YS
O
N N
G B
SO
LA
R P
R O
JE
C
T_ B-
-1 3-
IF
C
R
EV
H
U N
SE
AL
ED
B
ID
S
ET
.D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
SOLAR ELECTRICAL OVERALL
SITE PLAN
S M
D D
0 2023-03-13 ISSUE FOR BID
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E2.0
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. THIS IS A CONCEPTUAL LAYOUT FOR ELECTRICAL DESIGN, SEE
THE RACKING MANUFACTURER LAYOUT AND SHOP DRAWINGS
FOR MORE DETAIL ON RACKING STRUCTURES.
3. SITE ACCESS WILL BE THROUGH EXISTING ACCESS DRIVES AND
PARKING AREAS OFF OF EITHER HANDLEY AVENUE OR BRISCOE
DRIVE.
4. SEE CIVIL DRAWINGS FOR PROPOSED SITE ACCESS ROAD
DETAILS
5. SEE SHEET E3.1 FOR INTERCONNECTION DETAILS.
6. UNDERGROUND ELECTRICAL AND COMM SHALL BE INSTALLED
THROUGH TRENCHING, SEE UNDERGROUND NON-ENCASED
CONDUIT DETAIL 3/E4.4 FOR LOCATIONS REQUIRING DIRECT
BURY.
7. MANHOLE LOCATIONS CAN BE FOUND ON SHEET E3.0.
GENERAL NOTES:
LEGEND:
SOLAR PV TABLE
SYSTEM DESCRIPTION
MODULE Q.PEAK DUO XL-10.2 480W
NUMBER OF PV MODULES 3024
NUMBER OF STRINGS
(24 MODULES IN SERIES) 126
SYSTEM SIZE(DC) 1,451 kW
SYSTEM SIZE(AC) 1,200 kW
INVERTER CAPACITY (QTY.) SMA PEAK3 150-US (8)
ARRAY TILT 20°
ARRAY AZIMUTH 195°
GROUND COVER RATIO 0.56
SYSTEM OPERATING
VOLTAGE 1500 V
1 OVERALL SITE PLAN - PV LAYOUT
Scale: 1" = 50'
A
E2.2
SCALE:
A
E2.0
PV TABLE PROFILE
1" = 8'
INVERTER/TRANSFORMER STATION
UNDER PV TABLE TO
BE NATIVE GRASS.
REFER TO CIVIL
DRAWINGS
NOTE: SLOPE OF TERRAIN VARIES THROUGHOUT SITE, NOT SHOWN
FOR CLARITY
SEE RACKING MANUFACTURER LAYOUT AND SHOP DRAWINGS
10'-0"
22'-11"
2'-0" MIN
CLEARANCE
SCALE:
B
E2.0
PV TABLE PROFILE
1" = 8'
PV SUBARRAY 'SA-1'
DC COMBINER BOX
'CBX-2'
DC COMBINER BOX
'CBX-3'
DC COMBINER BOX
'CBX-4'
DC COMBINER BOX
'CBX-5'
DC COMBINER BOX
'CBX-6'
DC COMBINER BOX
'CBX-7'
DC COMBINER BOX
'CBX-8'
AC INVERTERS, PV
SWITCHBOARD, AND MV
TRANSFORMER
DC CONDUIT
AND TRENCH
DC COMBINER BOX
'CBX-1'
PV SUBARRAY 'SA-2'
PV SUBARRAY 'SA-3'
PV SUBARRAY 'SA-4'
PV SUBARRAY 'SA-5'
PV SUBARRAY 'SA-7'
PV SUBARRAY 'SA-8'
B E4.5
C E4.5
D E4.5
E E4.5
F E4.5
G E4.5
H E4.5
DC CONDUIT
AND TRENCH
FOR STRINGS
BETWEEN ROWS
I E4.5
PV SUBARRAY 'SA-6
1-1 2-1 3-1
4-1 5-1 6-1 7-1
9-1
14-1
4-2
11-2
2-3
9-3
1-4
9-4
1-5
9-5
8-6
10-1
15-1
5-2
12-2
3-3
10-3
2-4
10-4
2-5
10-5
9-6
11-1
16-1
6-2
13-2
4-3
11-3
3-4
11-4
3-5
11-5
10-6
12-1
1-2
7-2
14-2
5-3
12-3
4-4
12-4
4-5
12-5
4-6
2-2
8-2
15-2
6-3
13-3
5-4
8-1
13-1
3-2
10-2
1-3
8-3
16-3
8-4
16-4
8-5
7-6
9-2
16-2
7-3
15-3
7-4
15-4
7-5
6-6
14-3
6-4
14-4
6-5
5-6
13-4
5-5
17-5 1-6 2-6 3-616-515-514-513-5
8-6 9-66-65-64-6
5-7 6-7 7-74-73-72-71-7
11-810-89-88-87-8
14-6 15-6 16-6 17-613-612-611-6
11-7 12-7 13-7 14-710-79-78-7
14-813-812-8
3-82-81-8 4-8 5-8 6-8
A E4.5
PV TABLE
(2 X 12 PV MODULES IN
PORTRAIT)
DC STRINGS: 24 MODULES IN
SERIES
LOCATION ID "A"
NOTE: SEE SHEET E6.0 FOR
CABLE, CONDUIT AND
ELECTRICAL DETAILS
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
S
D G
U
SE
R
(2
3-t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
SD
G
U
SE
R
\O N
ED
R
IV
E
- A
EC
O M
\C
AD
\M C
G H
EE
T
YS
O
N N
G B
SO
LA
R P
R O
JE
C
T_ B-
-1 3-
IF
C
R
EV
H
U N
SE
AL
ED
B
ID
S
ET
.D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
SOLAR ELECTRICAL
DC CIRCUIT PLAN
S M
D D
0 2023-03-13 ISSUE FOR BID
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E2.1
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. COMBINER BOXES TO BE MOUNTED ON UNISTRUT DIRECTLY
BEHIND THE SOLAR RACKING FOLLOWING THE
MANUFACTURER'S MOUNTING INSTRUCTIONS AND
RECOMMENDED CLEARANCES PER NEC. SEE SHEET E4.1 FOR
MOUNTING DETAILS.
3. PV ARRAY SUPPORT FOUNDATION IS DELEGATED DESIGN AND
SHALL CONFORM TO THE DESIGN CRITERIA INDICATED ON S1.0
AND GEOTECHNICAL REPORT.
GENERAL NOTES:
LEGEND:
SOLAR PV TABLE
INVERTER/TRANSFORMER STATION
DC STRING X-A (STRING # - ARRAY)
DC CONDUIT AND TRENCH
SUBARRAY (SA-1-4) DESCRIPTION
MODULE Q.PEAK DUO XL-G10.2 480W
NUMBER OF PV MODULES 384
NUMBER OF STRINGS
(24 MODULES IN SERIES) 16
SYSTEM SIZE(DC) 184.32 kW
SYSTEM SIZE(AC) 150 kW
INVERTER CAPACITY (QTY.) SMA PEAK3 150-US (1)
ARRAY TILT 20°
ARRAY AZIMUTH 195°
SYSTEM OPERATING
VOLTAGE 1500 V
1 SOLAR ELECTRICAL - DC CIRCUIT PLAN
Scale: 1" = 30'
A
E2.1
SCALE:
A
E2.1
TYP DC STRING
1" = 8'
SUBARRAY (SA-5-6) DESCRIPTION
MODULE Q.PEAK DUO XL-G10.2 480W
NUMBER OF PV MODULES 408
NUMBER OF STRINGS
(24 MODULES IN SERIES) 17
SYSTEM SIZE(DC) 195.84 kW
SYSTEM SIZE(AC) 150 kW
INVERTER CAPACITY (QTY.) SMA PEAK3 150-US (1)
ARRAY TILT 20°
ARRAY AZIMUTH 195°
SYSTEM OPERATING
VOLTAGE 1500 V
SUBARRAY (SA-7-8) DESCRIPTION
MODULE Q.PEAK DUO XL-G10.2 480W
NUMBER OF PV MODULES 336
NUMBER OF STRINGS
(24 MODULES IN SERIES) 14
SYSTEM SIZE(DC) 161.28 kW
SYSTEM SIZE(AC) 150 kW
INVERTER CAPACITY (QTY.) SMA PEAK3 150-US (1)
ARRAY TILT 20°
ARRAY AZIMUTH 195°
SYSTEM OPERATING
VOLTAGE 1500 V
6'
7'-3"
PV XFMR
B E2.2
C E2.2
2' -7
2'-2"
1' -6
" T H
IC
KE
N
ED
S
LA
B
ED
G E
AT
P
ER
IM
ET
ER
, T
YP
CONCRETE
EQUIPMENT PAD
44'-3''
'-2
" 1'-7"
INV-1 INV-2 INV-3 INV-4
INV-5 INV-6 INV-7 INV-8
LV
PANEL
1' -8
CONCRETE
EQUIPMENT PAD
WP
G
WP
G
1'-7"
3' 2'
-6
2' -6
DC DISCONNECT
ENCLOSURE 2
"DC-DISCO-2"
DC DISCONNECT
ENCLOSURE 1
"DC-DISCO-1"
6'-2"
LV
XFMR
PV
SWBD
WEATHER
STATION
COMM
CABINET
3' -1
1"
PV SWBD
1'-8"
MINIMUM
2'-6"
2' -9
INV-1 INV-2 INV-3 INV-4
1-1/4"
UNISTRUT
PV XFMR
7'-3"
3-1/4"
UNISTRUT
6"
3" C
LR
8" T
H
IC
K C
O N
C . S
LA
B
1'-6"
TYP.
6" 1'
-6
M
IN
FINISHED
GRADE
PROVIDE CONDUIT
STUB-UPS FOR ALL
PRESENT AND SPARE
INVERTER LOCATIONS
FOR FUTURE EXPANSION
PV SWBD
PV XFMR
LV XFMR
7'-3"
LV
PANEL
COMM
CABINET
WEATHER
STATION
1-1/4" UNISTRUT
3-1/4"
UNISTRUT
FINISHED
GRADE
NOTE: SEE ELEVATION B/E2.2 FOR ADDITIONAL INFO NOT SHOWN
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
F
AR
ES
A(
-0
5-
P lo tte d:
2-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
FA
R
ES
A\
AE
C
O M
\E N
ER
G
Y G
R O
U P-
SO
LA
R T
EA
M
G
EN
ER
AL
\S
AM
D
O W
N
LO
AD
\M
C G
H
EE
T
YS
O N
N
AT
IO
N
AL
G
U
AR
D \C
AD
\M
C G
H
EE
T
YS
O N
N G
B
SO
LA
R
P R
O
JE
C T_
B-
-1
1-
IF
C .D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
INVERTER/TRANSFORMER
STATION DETAILS
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-01 B2 DESIGN
F 2022-04-11 B3 DESIGN
G 2022-05-09 B4 DESIGN
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
SCALE:
A
E2.2
INVERTER/TRANSFORMER STATION PLAN VIEW
1" = 4'
SCALE:
B
E2.2
INVERTER/TRANSFORMER STATION ELEVATION VIEW
1" = 4'
SCALE:
C
E2.2
INVERTER/TRANSFORMER STATION ELEVATION VIEW
1" = 4'
E2.2
GENERAL NOTES:
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. CONCRETE PAD SHOULD CLEAR EQUIPMENT BY A MINIMUM OF
EIGHT INCHES.
3. INVERTERS 6-10 ARE SHOWN FOR ADDITIONAL EXPANSION
4. INVERTERS 1-5 ARE SHOWN TO BE INSTALLED FOR BASE BID
OPTION
G
G
W
24" RCP
24" RCP
R
C
P
P
P
24" RCP
R
C P
18" RCP
R
C P
R
C P
P
E
STMH
T.C. 928.70
I.E. IN = 922.50 NW
I.E. IN = 920.94 NE
I.E. OUT = 920.50
STMH
T.C. 925.50
I.E. IN = 918.00
I.E. OUT = 917.86
CB2X2
T.C. 929.00
I.E. OUT = 922.10 (SUMP)
STMH
T.C. 937.98
I.E. IN = 932.16 NE
I.E. IN = 931.08 SE
I.E. OUT = 931.22
STMH
T.C. 938.34
I.E. OUT = 932.82
18" RCP
I.E. = 939.47
18" RCP
I.E. = 942.82
CB2X2
T.C. 947.36
I.E. OUT = 940.96 (SUMP)
STMH
T.C. 948.12
I.E. IN = 940.20 NE
I.E. IN = 941.72 SE
I.E. OUT = 940.34
STMH
T.C. 948.13
I.E. IN = 940.55
I.E. OUT = 940.33
STMH
T.C. 958.16
I.E. OUT = 952.62
STMH
T.C. 958.05
I.E. IN = 952.29
I.E. OUT = 952.19
V
T
O
U
M
P
H
O
U
S
E
V
F
R
M
M
P
H
O
U
S
E
AVOID WATER TANK
FOUNDATION
MV ROUTE TO POINT OF
INTERCONNECTION, ~3,450 FT
(NOTE 3)
SOLAR PV ARRAY
AC INVERTERS, PV
SWITCHBOARD, AND MV
TRANSFORMER
NOTE 5.
MV ROUTE TO POINT OF
INTERCONNECTION, ~3,450 FT
REFER TO E4.4 DETAIL 3
UNDERGROUND DUCT BANK DETAIL
10'
SETBACK FROM FAA
DUCT BANK
PV2
NOTE 4.
PV3
PV4
PV5
PV6
PV7
PV8
PV10
PV9
PV11
ELECTRICAL VAULT PV12
REFER TO DETAIL 1 ON SHEET E4.4
(NOTES 8, 9 & 10) TYPICAL
PV1
NOTE 3
Printed on ___% Post-Consumer
Recycled Content Paper
REGISTRATION
KEY PLAN
A R
H
D x
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue
Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
L a s t s a v e d b y
A
S S
E F
A A a s t
P l o t t e d
CLIENT
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
PROJECT
F i l e n a m e
C
U
S E
R S
A
S S
E F
A A
A
E C
O M
T
N
A
G
C G
H E
E
T
Y S
E N
E R
A L
C
A D
M
C G
H E
E
T
Y S
B
S
L
A
O
J E
C T
B
M
V
S
H E
E T
S D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
BASE PV ARRAY
134th Air Refueling Wing
123 Briscoe Drive
McGhee Tyson Air National
Guard Base, TN 37777
MCGHEE TYSON ANG
POINT OF INTERCONNECTION
OVERALL SITE PLAN
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 DESIGN
E3.0
NOTES:
1 MV ROUTE TO POI PLAN
Scale: 1" = 200'
A
E3.1
1. SEE SHEET E1.0 FOR GENERAL NOTES, LEGEND AND SYMBOLS,
AND ABBREVIATIONS.
2. POINT OF INTERCONNECTION (POI) WILL BE AT THE MEDIUM
VOLTAGE SWITCHGEAR.
3. UNDERGROUND ELECTRICAL AND COMMUNICATION CONDUITS
SHALL BE DIRECTLY BURIED. SEE UNDERGROUND DUCT BANK
DETAIL 3 ON SHEET E4.4 FOR DETAILS.
4. FIELD CONTRACTOR TO VERIFY CABLE ROUTING
INTERFERENCE WITH ALL UNDERGROUND UTILITIES PRIOR TO
CABLE INSTALLATIONS.
5. REFER TO E2.2 INVERTER/TRANSFORMER STATION DETAILS.
6. CONTRACTOR TO ROUTE 12 STRAND CORE, SINGLE MODE
FIBER OPTIC CABLE IN 2" INNERDUCT CONDUIT; INNERDUCT
CONDUIT SHALL BE INSTALLED AND ROUTED IN 4" PVC CONDUIT
ALONG WITH POWER CABLES WITH CONDUIT SPACING AS
INDICATED ON DETAIL 3, SHEET E4.4. CONTRACTOR TO SWEEP
FIBER OPTIC CABLE CONDUITS TO HANDHOLES FOR PULLING
AND SWEEP BACK TO TRENCH WITH THE POWER CABLES TO
CONTINUE. FIELD CONTRACTOR TO PROVIDE FIBER OPTIC
CABLE HANDHOLE SIZE 30" W X 36" L X 24" D EVERY 400 FEET IN
CLOSE PROXIMITY TO ELECTRICAL VAULTS.
7. REFER TO SHEET E6.0 FOR ELECTRICAL FEEDER SCHEDULE.
8. ALL ELECTRICAL ABOVE GROUND VAULTS SHALL BE PROVIDED
BY ALCOA AND SHALL BE INSTALLED BY CONTRACTOR.
CONTRACTOR TO CONTACT ALCOA FOR VAULTS INSTALLATION
DETAILS.
9. ALCOA SHALL PROVIDE MV CABLES AND CONDUITS TO THE
CONTRACTOR. CONTRACTOR SHALL INSTALL CONDUITS AND
CABLES BETWEEN ELECTRICAL VAULTS. ALCOA SHALL
TERMINATE CABLES AT VAULTS. CONTRACTOR TO CONTACT
ALCOA PRIOR TO CUTTING CABLES TO DETERMINE THE LENGTH
OF CABLES NEEDED FOR TERMINATION INSIDE THE VAULTS.
CONTRACTOR SHALL MAKE SURE THAT ADEQUATE CABLE
LENGTH IS PROVIDED FOR TERMINATION.
10. CABLE SHALL BE TAGGED AS INDICATED BELOW. EACH
CONDUIT SHALL CONTAIN A PHASE AND A GROUND CABLE.
ID LOCATION "F" DETAILS
(NOTE 10)
SOLAR PV
TRANSFORMER
PV1-A/B/C
+GND
3-4" CONDUIT
(TYPICAL)
PV2-A/B/C
+GND
PV3-A/B/C
+GND
PV1 PV2 PV3
PV5-A/B/C
+GND
PV6-A/B/C
+GND
PV4 PV5 PV6
PV8-A/B/C
+GND
PV9-A/B/C
+GND
PV7 PV8 PV9
PV11-A/B/C
+GND
PV12-A/B/C
+GND
PV10 PV11 PV12
PV4-A/B/C
+GND
PV7-A/B/C
+GND
PV10-A/B/C
+GND
EXISTING 15KV SWITCHGEAR
SECTIONALIZING CABINET WITH (4)
GANG OPERATED VACUUM
SWITCHES, SSC
MV SWGR
SWITCHGEAR
(NOTE 4.)
EXISTING ATS-1 (NOTE 4.)
EXISTING ATS-2
(NOTE 5.)
EXISTING PAD MOUNTED
TRANSFORMER, 13.2/7.6KV/480/277V,
3Ø, 4W 3500KVA (NOTE 4.)
FIBER OPTICS CABLE ROUTING FOR
COMMUNICATIONS (NOTE 6).
EXISTING UTILITY POWER
POLE
EXISTING
RECLOSURE
(NOTE 5.)
EXISTING LIGHT POLE
PV12
PV11
EXISTING VOLTAGE
REGULATORS.
(NOTE 5.)
PROVIDE NEW FEEDER FROM EXISTING TRANSFER
SWITCH TO NEW MV SWGR SWITCHGEAR.
(LOCATION ID "G")
PROVIDE NEW FEEDER FROM EXISTING
TRANSFORMER SECONDARY TO NEW MV SWGR
SWITCHGEAR. (LOCATION ID "G")
PROVIDE NEW FEEDER FROM EXISTING 15KV
SWITCHGEAR SECTIONALIZING CABINET TO NEW
MV SWGR SWITCHGEAR. (LOCATION ID "H")
NEW 45KVA
13.2KV-208/120V
PAD MOUNTED TRANSFORMER
PANELBOARDS AND MICRO-GRID
CONTROLLER STATION
UPS AND
BATTERY CABINET
(NOTE 8.)
C
E3.1
13'-0"
34'-0"
CONCRETE ELECTRICAL EQUIPMENT PAD
REFER TO STRUCTURAL DRAWING S2.1
4'-0"
MV
SWGR
2'-0"
45KVA XFMR
D
E
MICROGRID CONTROLLER
6'-8"
120/208V UPS PANEL
120/208V PANEL
5'-4"
UPS & BATTERY
CABINET
(NOTE 8.)
FRONT
REAR
HVAC UNIT
COOLING
FAN/FILTER
13'-0"
AUXILIARY
AUXILIARY
LOW VOLTAGE
PANEL
1200A CIRCUIT
BREAKER
LOW VOLTAGE
PANEL
1200A CIRCUIT
BREAKER
1200A CIRCUIT
BREAKER
LOW VOLTAGE
PANEL
1200A CIRCUIT
BREAKER
(SPARE)
1200A CIRCUIT
BREAKER
MV SWGR
SPACE
SPACE
FINISHED
GRADE
45KVA
TRANSFORMER
MICROGRID
CONTROLLER
120/208V
PANEL
120/208V
UPS
PANEL
4'-0"
FINISHED
GRADE
UPS & BATTERY CABINET
45KVA
TRANSFORMER
1-1/4"
UNISTRUT
3-1/4"
UNISTRUT
1200A CIRCUIT
BREAKER
HVAC UNIT
COOLING
FAN/FILTER
Printed on ___% Post-Consumer
Recycled Content Paper
REGISTRATION
KEY PLAN
A R x
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue
Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
L a s t s a v e d b y
A
S S
E F
A A s t
P l o t t e d
CLIENT
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
PROJECT
F i l e n a m e
C
U
S E
R S
A
S S
E F
A A
A
E C
O M
T
N
A
C G
H E
E
T
Y S
E N
E R
A L
C
A D
M
C G
H E
E
T
Y S
L
O
J E
C T
B
M
V
S
H E
E T
S D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
BASE PV ARRAY
134th Air Refueling Wing
123 Briscoe Drive
McGhee Tyson Air National
Guard Base, TN 37777
MCGHEE TYSON ANG
POINT OF INTERCONNECTION
DETAILS
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-18 B2 DESIGN
F 2022-04-29 B3 DESIGN
E3.1
NOTES:
1. SEE SHEET E1.0 FOR GENERAL NOTES, LEGEND AND SYMBOLS,
AND ABBREVIATIONS.
2. POINT OF INTERCONNECTION (POI) WILL BE AT THE
MEDIUM-VOLTAGE SWITCHGEAR.
3. REFER TO ELECTRICAL VAULTS LOCATIONS AND GENERAL
NOTES ON DRAWING E3.0.
4. REFER TO ONE LINE DRAWING E5.0 ELECTRICAL SITE SINGLE
LINE DIAGRAM FOR MEDIUM VOLTAGE CIRCUITS
REQUIREMENTS. REFER TO ONE LINE DRAWINGS E5.3 AND E5.4
FOR MEDIUM VOLTAGE "MV SWGR" SWITCHGEAR SINGLE LINE
DIAGRAM.
5. EXISTING ATS-2, RECLOSER, VOLTAGE REGULATORS AND ALL
ASSOCIATED CABLES SHALL BE DEMOLISHED. EXISTING ATS-2
AUXILIARY CABINET TO REMAIN IN PLACE FOR MICRO-GRID
CONTROLLER ADDITIONAL NETWORK TIE-IN CONNECTIONS.
6. CONTRACTOR TO ROUTE 12 STRAND CORE, SINGLE MODE
FIBER OPTIC CABLE IN 2" INNERDUCT CONDUIT; INNERDUCT
CONDUIT SHALL BE INSTALLED AND ROUTED IN 4" PVC CONDUIT
ALONG WITH POWER CABLES WITH CONDUIT SPACING AS
INDICATED ON DETAIL 3, SHEET E4.4. CONTRACTOR TO SWEEP
FIBER OPTIC CABLE CONDUITS TO HANDHOLES FOR PULLING
AND SWEEP BACK TO TRENCH WITH THE POWER CABLES TO
CONTINUE. FIELD CONTRACTOR TO PROVIDE FIBER OPTIC
CABLE HANDHOLE SIZE 30" W X 36" L X 24" D EVERY 400 FEET IN
CLOSE PROXIMITY TO ELECTRICAL VAULTS.
7. ALL EQUIPMENT DIMENSIONS ARE BASED ON VENDOR
INFORMATION. FINAL DIMENSIONS AND LAYOUT TO BE
COMPLETED BY THE CONTRACTOR AFTER PROCUREMENT OF
EQUIPMENT.
8. UPS INVERTERS AND BATTERIES ARE HOUSED IN A NEMA 3R
ENCLOSURE.
9. SWITCHGEAR LAYOUT, DIMENSIONS, AND ELEVATION ARE
BASED ON SIEMENS GM-SG METAL CLAD MEDIUM VOLTAGE
SWITCHGEAR.
10. REFER TO SHEET E6.0 FOR FEEDER SCHEDULE.
11. CONDUIT STUB UPS SHALL BE DETERMINED IN THE FIELD BY
CONTRACTOR. CONDUIT STUB UPS FOR FUTURE
INSTALLATIONS SHALL BE PROVIDED.
B/C/D
E3.1
SCALE:
C
E3.1
MV SWGR SWITCHGEAR ELEVATION VIEW
NONE
SCALE:
B
E3.1
MV SWGR SWITCHGEAR PLAN VIEW
NONE
SCALE:
A
E3.1
ELECTRICAL SWITCHGEAR YARD
1" = 20'
SCALE:
D
E3.1
LV PANEL AND MICRO-GRID CONTROLLER STATION ELEVATION VIEW
NONE
(NOTE 7&9.)
(NOTE 7.)
(NOTE 7&9.)
CONDUIT IDENTIFICATION 1 SIGNAGE ON 15KV CABINET
POINT OF INTERCONNECTION 2
SIGNAGE ON ALL
INVERTERS AND AC DISCONNECTS 3
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH LINE
AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN
POSITION
WARNING
RATED PV POWER: 1200 kW-AC
RATED AC OUTPUT CURRENT: 1208 A-AC
NOMINAL OPERATING AC VOLTAGE: 600V-AC
PHOTOVOLTAIC SYSTEM
DC DISCONNECT
SIGNAGE ON ALL
STRING INVERTER CIRCUITS 6
SIGNAGE ON
AC DISCONNECT (PV-SWBD) 4
MARKING IS REQUIRED ON ALL INTERIOR AND EXTERIOR DC
CONDUIT, RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, AND
JUNCTION BOXES TO ALERT THE FIRE SERVICE TO AVOID
CUTTING THEM.
SEE GENERAL NOTES FOR FONT SIZE AND COLORS
7" 3/
4"
X - A
"X" REPRESENTS THE CIRCUIT NUMBER IN A STRING
INVERTER
"A" REPRESENTS THE INVERTER AND ARRAY LETTER
CIRCUIT LEGEND:
STRING INVERTER XXX SIGNAGE
CHART
STRINGS /
INVERTER
INVERTER
RATING
(kW-AC)
QTY.
MAXIMUM
CIRCUIT
CURRENT
14 150.0 2 246.1
16 150.0 4 281.0
17 150.0 2 299.0
5"
9"
6"
7"
7"
5"
9"
6"
1 12"
1"
(1 PLACE)
(UP TO 8 PLACES) (8 PLACES)
ELECTRICAL POWER SOURCE
DIRECTORY PLACARD 8
8"
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCE WITH
DISCONNECTS LOCATED AS SHOWN.
SIGNAGE ON ALL
INVERTERS (DC DISCONNECTS)
(1 PLACE)
INTERCONNECTION POINT
MAIN SERVICE DISCONNECTS
3/4" MIN
1/4" MIN
1/8" MIN
TYP
PV SYSTEM
DISCONNECT
N
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
RATED AC OUTPUT
CURRENT: 87.48 AMPS
NOMINAL OPERATING
AC VOLTAGE: 13.2 kV
INTERACTIVE PHOTOVOLTAIC
POWER CONNECTED
SEE SIGNAGE CHART ABOVE FOR XXX VALUES
RATED PV POWER: 1200 kW-AC
RATED AC OUTPUT CURRENT: 87.48 A-AC
NOMINAL OPERATING AC VOLTAGE: 13.2kV-AC
SIGNAGE ON
AC DISCONNECT (15KV CABINET) 7
(1 PLACE)
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
7"
5"
MAXIMUM SYSTEM VOLTAGE: 1500 VDC
MAXIMUM CIRCUIT CURRENT (14 STRINGS): 246 ADC
MAXIMUM CIRCUIT CURRENT (16 STRINGS): 281 ADC
MAXIMUM CIRCUIT CURRENT (17 STRINGS): 299 ADC
G
G
W
4"PE 3408
8" PVC (TO PUMPHOUSE)
12" PVC (FROM PUMPHOUSE)
DC CONDUITAND TRENCH
B E2.0
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
S
D G
U
SE
R
(2
3-t P lo tte d:
3-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
SD
G
U
SE
R
\O N
ED
R
IV
E
- A
EC
O M
\C
AD
\M C
G H
EE
T
YS
O
N N
G B
SO
LA
R P
R O
JE
C
T_ B-
-1 3-
IF
C
R
EV
H
U N
SE
AL
ED
B
ID
S
ET
.D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
SOLAR ELECTRICAL SIGNAGE,
LABELS AND MARKINGS
S M
D D
0 2023-03-13 ISSUE FOR BID
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E4.0
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. ALL SIGNS SHOWN ARE FIELD INSTALLED. OTHER SIGNAGE MAY
BE SHOWN ON SHOP / FABRICATION DRAWINGS.
3. ALL SIGNAGE (EXCEPT FOR STRING LABELS AND DANGER
SIGNS) HAS: A RED BACKGROUND, WHITE LETTERING, MINIMUM
3/8" LETTER HEIGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR
FONT (NON BOLD), REFLECTIVE WEATHER RESISTANT MATERIAL
SUITABLE FOR THE ENVIRONMENT.
4. WARNING LETTERING IS MINIMUM 1/2" LETTER HEIGHT, ALL
CAPITAL LETTERS, ARIAL FONT (BOLD) EXCEPT AS
SPECIFICALLY NOTED.
5. ELECTRICAL POWER SOURCE DIRECTORY PLACARD (DETAIL 8)
SHALL BE INSTALLED AT EACH SERVICE EQUIPMENT LOCATION
AND AT THE LOCATION(S) OF THE SYSTEM DISCONNECT(S) PER
NEC 705.10.
6. AC AND DC SYSTEM ARC FLASH STUDY TO BE PERFORMED BY
OTHERS AND SUITABLE LABELS AFFIXED TO ELECTRICAL
ENCLOSURES.
GENERAL NOTES:
8"
3"
1' -8
M
IN
IM
U M
C
LE
AR
AN
C E
1' -3
/4
2' -7
STRINGS FROM ARRAY
NOTE: MODULES AND RACKING SHOWN FOR REFERENCE ONLY.
COMBINER
BOX
SCH 80 PVC FROM
INVERTER UP TO AND
INCLUDING SWEEP
2'-0"
3'-0"
2'-2"
2'-8"
1' -3
/4
SCH 80 PVC FROM
INVERTER UP TO AND
INCLUDING SWEEP
COMBINER
BOX2'
-0
1-3/4" UNISTRUT
1'
GROUND HEIGHT VARIES
BASED ON POST HEIGHT
RGD PVC SCH 80 CONDUIT
ABOVE GRADE
DRIP LOOP
NOTE: MODULES AND RACKING SHOWN FOR REFERENCE ONLY.
USE WEATHER HEAD
DRIP LOOP
NOTE: MODULES AND RACKING
SHOWN FOR REFERENCE ONLY.
WEATHER
HEAD
3"
3'-10"
1' -7
3 4" 8"
1' -3
1 2"
3'-2"
2'-6"
INVERTER
3-1/4" UNISTRUT
Th is dra win g h as be en pr ep are d f or the us e o f A
EC
OM
's c lie nt an d m ay no t b e u se d, rep rod uc ed or re lie d u po n b y t hir d p art ies , e xc ep t a s a gre ed by
AE
CO
M an d i ts clie nt, as re qu ire d b y l aw or fo r u se by go ve rnm en tal re vie win g a ge nc ies . A
EC
OM
ac ce pts no re sp on sib ility , a nd de nie s a ny lia bil ity w ha tso ev er, to an y p art y t ha t m od ifie s t his dr aw ing w ith ou t A
EC
OM
's e xp res s w ritt en co ns en
t. D o n ot sc ale th is do cu me nt.
Al l m ea su rem en ts mu st be ob tai ne d f rom st ate d d im en sio ns
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
F
AR
ES
A(
-0
5-
P lo tte d:
2-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
FA
R
ES
A\
AE
C
O M
\E N
ER
G
Y G
R O
U P-
SO
LA
R T
EA
M
G
EN
ER
AL
\S
AM
D
O W
N
LO
AD
\M
C G
H
EE
T
YS
O N
N
AT
IO
N
AL
G
U
AR
D \C
AD
\M
C G
H
EE
T
YS
O N
N G
B
SO
LA
R
P R
O
JE
C T_
B-
-1
1-
IF
C .D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
ELECTRICAL DETAILS
SOLAR EQUIPMENT MOUNTING
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-01 B2 DESIGN
F 2022-04-11 B3 DESIGN
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E4.1
COMBINER BOX MOUNTING
SIDE VIEW DETAIL 1NONE
SCALE
TRANSITION DETAIL
ROWS WITHOUT COMBINERS 4
NONE
SCALE
COMBINER BOX MOUNTING
ELEVATION DETAIL 2NONE
SCALE COMBINER BOX MOUNTING
ELEVATION DETAIL 3
NONE
SCALE
TRANSITION DETAIL
ROWS WITHOUT COMBINERS 5
NONE
SCALE
CHANNEL NUT
W/SPRING, 5/16-18
THREAD
(UNISTRUT P1007)
IN-FIELD
DRILLING WITH
11/32 BIT
METAL FRAME
(UNISTRUT
P1001)
2 1/2" PIPE
CLAMP
RACK POST, TYP
MULTIPLE STRING
WIRES BUNDLED FROM
RACK TO CONDUIT
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. PV ARRAY SUPPORT FOUNDATION IS DELEGATED DESIGN AND
SHAL CONFOMR TO THE DESIGN CRITERIA INDICATED ON S1.0
AND GEOTECHNICAL REPORT
GENERAL NOTES:
INVERTER MOUNTING
ELEVATION DETAIL 6
NONE
SCALE
NOTE: MODULES AND RACKING
SHOWN FOR REFERENCE ONLY.
NOTE: SUPPORT FRAMING AND
FOUNDATIONS DESIGNED AND
PROVIDED BY VENDOR TO MEET
PERFORMANCE CRITERIA
CLEARANCE
DETERMINED BY
CONTRACTOR FOR
EASE OF ACCESS
E-W TABLE GAP
(NOT REQUIRED
ON CONTINUOUS ROW)
#6 BARE STRANDED OR EQUIVALENT TIN
PLATED BRAID (12" IN LENGTH) GROUND
STRAP BONDED WITH COMPRESSION
LUG, FLAT WASHER, NUT AND BOLT ON
PURLIN
COMBINER BOX
GROUNDING LUG
SEE DETAIL C2
GROUND
LEVEL
CUT END OF PIPE
4/0 BARE STRANDED
GROUND CABLE, DIRECT
BURIAL, TO NEXT
BONDING POINT IN ARRAYCADWELD
WARNING
TAPE
3"Ø RIGID SCH 80
PVC CONDUIT
#6 GND FROM
RACK
FROM RACKS
QUANTITY TO
VARY
GROUND BUS (EXACT
LOCATION IN COMBINER
BOX MAY VARY)
CONDUCTORS TO
INVERTER
3"Ø RMC CONDUIT
4/0 BARE STRANDED GROUND CABLE
TO BE BONDED TO EQUIPMENT
GROUNDING CONDUCTOR WITHIN
TRENCH
THIS DETAIL IS REPRESENTATIVE FOR THE PURPOSE OF
GROUNDING AND NOT THE ACTUAL COMBINER BOX
Printed on ___% Post-Consumer Recycled Content Paper
REGISTRATION
KEY PLAN
AR
C
H D
4" x
6"
SHEET TITLE
DESIGNER
AECOM TECHNICAL SERVICES, INC
300 South Grand Avenue Los Angeles, CA 90071
213.593.8100 tel 213.593.8178 fax www.aecom.com
La st s av ed b y:
F
AR
ES
A(
-0
5-
P lo tte d:
2-
-1
CLIENT
Pr oj ec t M an ag em en t I ni tia ls
D es ig ne r:
C he ck ed
Ap pr ov ed
PROJECT
Fi le na m e:
C
:\U
SE
R S\
FA
R
ES
A\
AE
C
O M
\E N
ER
G
Y G
R O
U P-
SO
LA
R T
EA
M
G
EN
ER
AL
\S
AM
D
O W
N
LO
AD
\M
C G
H
EE
T
YS
O N
N
AT
IO
N
AL
G
U
AR
D \C
AD
\M
C G
H
EE
T
YS
O N
N G
B
SO
LA
R
P R
O
JE
C T_
B-
-1
1-
IF
C .D
W G
I/R DATE DESCRIPTION
SHEET
ISSUE/REVISION
MCGHEE TYSON AIR
NATIONAL GUARD BASE
CONSTRUCT GROUND
134th Air Refueling Wing
MCGHEE TYSON ANG
ELECTRICAL DETAILS
DC SYSTEM GROUNDING
S M
A 2020-05-01 A1 DESIGN
B 2020-10-19 A2 DESIGN
C 2021-01-26 A2 REDESIGN
D 2021-05-14 B1 DESIGN
E 2022-01-01 B2 DESIGN
F 2022-05-09 B3 DESIGN
BASE PV ARRAY
123 Briscoe Drive McGhee Tyson Air National Guard Base, TN 37777
E4.2
1. SEE SHEET E1.0 FOR LEGEND, SYMBOLOGY AND
ABBREVIATIONS.
2. ALL DETAILS ARE REPRESENTATIVE ONLY, FINAL GROUNDING
AND BONDING WILL FOLLOW NEC STANDARDS AND THE
RACKING MANUFACTURER INSTALLATION REQUIREMENTS AND
DRAWINGS.
GENERAL NOTES:
COPPER
LUG
TOP SECTION OF POST
(REPRESENTATIVE ONLY)
COPPER LUG
(ILSCO CP250
OAE)
C BEAM
(REPRESENTATIVE
ONLY)
4/0 BARE STRANDED
GROUND CABLE FROM
TRENCH
MODULE FRAME
VERTICAL MODULE SUPPORT
(MODULE RAIL)
JUNCTION BOX
PER RACKING MANUFACTURER,
MOUNTING BOLT
CONNECTIONS COMPLY TO UL
2703 AT FOUR PLACES ON
MODULE.
MOUNTED BOLT CONNECTION OF
MODULE TO RACK, (TYP 4 PLACES)
NOTES:
1. PRIOR TO MOUNTING LUGS ON ANODIZED ALUMINUM OR PAINTED METAL SURFACES, THE SURFACE MUST BE STRIPPED AND THEN COVERED WITH BURNDY PENETROX A-13 ANTI-OXIDANT COMPOUND
BELOW THE LUG TO ENSURE CONDUCTIVITY.
2. ON ANODIZED AL SURFACES, THE ANODIZATION SHALL BE CLEANED OFF WITH EMERY CLOTH.
3. ON PAINTED SURFACES, THE PAINT LAYER SHALL BE REMOVED.
SS NUT WITH INTEGRATED
STAR WASHER
METAL SURFACE - BOX OR
RACKING
BURNDY PENETROX A-13
ANTI-OXIDANT COMPOUND
TIN PLATED COPPER GROUND
LUG - ILSCO GBL-4DBT,
BURNDY CL50-1TN, OAE
SS #10-32 MACHINE SCREW
COPPER EQUIPMENT
GROUNDING
CONDUCTOR
TORQUE SET SCREW
TO MFR SPECS
GROUNDING OF THE RACK
STRUCTURE AT THE COMBINER BOX 1NONE
SCALE
MULTI-RACK GROUND BOND 4
NONE
SCALE
GROUNDING INSIDE
COMBINER BOX 2NONE
SCALE
MODULE GROUNDING DETAIL 5
NONE
SCALE
GROUNDING LUG DETAIL 3
NONE
SCALE
PV XFMR
LV
XFMR
TW
(NOTE 2, TYP)
G
N
G
N
#8 BARE COPPER CABLE
#8 AWG COPPER
CABLE (MIN)
#4/0 COPPER CABLE
#4/0 BARE COPPER CABLE
#4/0
BARE
COPPER
CABLE
#4/0 BARE STRANDED
GROUND CABLE FROM
DC TRENCH LEADING TO
SOLAR ARRAY
TW
1/4" STEEL COVER
MATCHING PIPE O.D.
24" LONG
10" PVC PIPE
BOLTED CONNECTION
GROUND COUNTERPOISE
GROUND ROD
CONDUCTOR #4/0
6" LAYER SAND
3/4" X 10' COPPER CLAD STEEL
CONCRETE GRADE
ORIGINAL GROUND
3/4" X 10' COPPER CLAD STEEL
GROUND ROD
TEST POCKET WITH GRAVEL
FILL AND SOIL TOPPING
M
I N
UNDISTURBED
ELEVATION
CONNECTION TO PARALLEL
STRANDED COPPER
#4/0 AWG BARE
CONTINUOUS
CABLES TO GND ROD AT 30°
U-BOLT GND…