Project Drawings_Part2.pdf

PDF 9 MB Posted

Attached to
Y1DA--Project # 596-19-104, Construction to Correct FCA Deficiencies - FSC
Solicitation number
36C24923R0147
Issued by

About this file

This package includes construction documents for a project to correct deficiencies at the Lexington VA Medical Center in Lexington, Kentucky. The project involves electrical, technology, and architectural work. Key aspects of the project include upgrading electrical panels and switchgear, replacing door hardware and controls, installing new cabling and wireless access points, and correcting fire protection deficiencies. The work will take place in multiple buildings on the medical center campus.

The documents provide specifications and drawings for the planned upgrades. Sheets show demolition and new construction plans, details for grounding systems and penetrations, riser diagrams, and schedules. Notes indicate standards and codes that must be followed, including NFPA, NEC, TIA standards, and VA requirements. The project appears aimed at modernizing critical building systems and improving life safety and physical security at the medical facility.

View the file

Other files

File Type Posted
Site Visit Sign-in Sheet.pdf PDF
36C24923R0147 0001.docx DOCX document
Solicitation Questions - Answers.pdf PDF
Project Drawings_Part1.pdf PDF
Pricing Schedule.xlsx XLSX spreadsheet
Statement of Work.pdf PDF
Past Performance Questionnaire.pdf PDF
Project Specifications.pdf PDF
36C24923R0147_1.docx DOCX document
Wage Determination KY20230090 9-8-2023.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064

5/23/2023

L L

ELECTRICAL ABBREVIATIONS LIST

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL

ELECTRICAL CODE, VA ELECTRICAL DESIGN GUIDE AND VA STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING

HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT

DURING CONSTRUCTION.

ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST

COMPLY WITH "BUY AMERICAN ACT".

ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S

SCREW TERMINALS.

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED

(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED

THIRD PARTY TESTING AGENCY.

FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE

GOVERNMENT, SHALL BE PROVIDED.

COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

ELECTRICAL SYMBOL LEGEND

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

JUNCTION BOXAS

NOTED

J

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

EQUIPMENT CONNECTIONAS

NOTED

E

LIGHTING SYMBOL LEGEND

2' X 2' RECESSED DIRECT/INDIRECT TROFFER

2' X 4' RECESSED DIRECT/INDIRECT TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER

WALL SCONCE6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY

VS: VACANCY SENSOR, DUAL TECHNOLOGY

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

48"

CENTER

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

2' LINEAR - WALL MOUNTED7'-0"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE

LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

4' LINEAR - WALL MOUNTED7'-0"

CENTER

OS

OS

LS

4' STRIP LIGHT---

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects

E-001

ELECTRICAL GENERAL NOTES, SYMBOL

LEGENDS, AND ABBREVIATIONS

1, 2, 3, 12, 17, 22, 25

B25

B17

B1

B3

B2

B22

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

ES101

SITE PLAN

1 DOOR REPLACEMENT SITE PLAN

SCALE: 1" = 50

A. SEE 'EP' SHEETS FOR POWER PLANS AND E-401

FOR DOOR POWER ENLARGEMENTS.

NORTH

TRUE

0 25' 50' 100'

1, 2, 3, 12, 17, 22, 25

E-401

E-401

E-401

EP104

EP105

E-401

EP105

EP101

EP103

EP102

E-401

E-401

E-401

E-401

E-401

E-401

UP

CUSTOMER

WAITING

CORRIDOR

C-G-2-2

CORRIDOR

C-G-2-1

CORRIDOR

C-G-2-3

ASST CHIEF

CASHIER

5A

SUPERVISOR

5B

MENS

TOILET

EMS

3A

TRI-WEST

TENANT

2LOBBY

ATM

VHA MRSA /

MDRO

TENANT

STAIR

POLICE

TRAINING

STORE

ELEVATOR

MACH RM

ELEVATOR KITCHEN

EMS

9A

SVC

RM 7

STORAGE

CANTEEN

STORAGE

CANTEEN

STORAGE

ELECTRICAL

EXISTING 2EM

EXISTING

MP-2

EXISTING 225

kVA PMT-2

TRANSFORMER

BUILDING 3

NEW MP2

NEW 2EM

CORRIDOR

C-G-2-3

SUPERVISOR

5B

MENS

TOILET

EMS

3A

NEW 2EM

S

A

B

S

A

S

J

J

'2LP3'-26

'2LP3'-16

NEW MP2

A

ELECTRICAL

CORRIDOR

C-G-2-3

SUPERVISOR

5B

MENS

TOILET

EMS

3A

STORE

5C

S

S

STORE

5D

ALL LIGHT SWITCHES AND

RECEPTACLES IN 5C AND

5D TO BE DEMOLISHED.

CIRCUITS TO BE REUSED

IN NEW CONSTRUCTION.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

KEYPLAN:

AREA OF WORK

BLDG

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

EP101

BUILDING 2 GROUND FLOOR DEMOLITION

AND POWER PLAN

1 BUILDING 2 GROUND FLOOR POWER PLAN

SCALE: 1/8" = 1' 0"

1. EXISTING 'MP-2' AND '2EM' TO BE DEMOLISHED

AFTER NEW 'MP-2' AND '2-EM' HAVE BEEN

INSTALLED.

2. EXISTING INCOMING SECONDARY FROM XFMR

'PMT2' IN APPROXIMATE LOCATION OF CRAWL

SPACE BELOW ROOM 6 CANTEEN STORAGE.

REMOVE SECONDARY AFTER NEW HAS BEEN

INSTALLED.

3. NEW LOCATION OF PANELS 'MP2' AND '2EM'.

EXTEND FEEDERS, CONDUCTORS AND BRANCH

CIRCUITS TO THIS NEW LOCATION. PROVIDE NEW

BREAKERS FOR RELOCATED BRANCH CIRCUITS.

4. NEW 4" CONDUIT ROUTED UNDERGROUND TO

NEW ELECTRICAL ROOM. SEE DETAIL 5/E-501

5. NEW PULL BOX TO INTERCEPT EXISTING FEEDERS

AND/OR BRANCH CIRCUITS.

6. PROPOSED ROUTE FOR INTERCEPTING EXISTING

BRANCH CIRCUITS BACK TO NEW MP2 LOCATED IN

NEW ELECTRICAL ROOM. CONDUITS TO BE

ROUTED ABOVE CEILING OR IN CRAWL SPACE. SEE

1/E-501 AND 2/E-501 FOR PENETRATION DETAIL.

7. EXISTING FEEDER CONDUITS TO BE INTERCEPTED.

SEE 1/E-604 FOR MORE INFORMATION.

8. NEW GROUND BAR. SEE 4/E-501.

9. SEE 1/EP101 FOR CONTINUATION.

10. EXISTING WINDOW TO SEALED OFF. SEE

ARCHITECTURAL DRAWINGS FOR MORE

INFORMATION.

11. TIE TO EXISTING EMERGENCY CIRCUIT.

12. TIE TO EXISTING NORMAL CIRCUIT.

13. TIE TO EXISTING RECEPTACLE CIRCUIT IN THIS

AREA. 2LP3-16.

14. REUSE EXISTING FIXTURE AND CIRCUIT. CONNECT

TO NEW SWITCH.

15. CONDUIT FROM ABOVE TO J-BOX. CONDUIT

THROUGH WALL. SEE REFERENCE PICTURES

4/EP101.

1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING

AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT

ORIGINATE, PASS THROUGH, OR TERMINATE IN THE

AREA OF WORK.

2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED

REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO

SOURCE, INCLUDING THOSE CONCEALED WITHIN

WALLS, LEAVING NO ABANDONED ITEMS.

3. WHERE CONDUIT IS REMOVED FROM AN EXISTING

RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE

REMAINING HOLE SHALL BE PATCHED/REPAIRED TO

MAINTAIN THE RATING OF THE ASSEMBLY.

4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING

AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE

GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK

TO THE GREATEST EXTENT POSSIBLE PRIOR TO

PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY

COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE

OF AREA OF WORK PRIOR TO PERFORMING THE WORK.

5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO

DE-ENERGIZE EQUIPMENT.

6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN

3/4" CONDUIT UNLESS NOTED OTHERWISE.

7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE

PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A

LABEL PERMANENTLY ADHERED TO THE FACE PLATE.

8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS

WITH THE LED DRIVERS TO BE CONTROLLED.

9. PROVIDE RATED PENETRATIONS MATCHING EXISTING

RATED WALL CONDITIONS.

10. SEE SINGLE-LINE SHEETS E-601 & E-604.

11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,

FUEL, AND ALL NECESSARY CABLING, TO PROVIDE

TEMPORARY POWER TO THE FACILITY DURING THE

TRANSITIONING OF CIRCUITS FROM THE EXISTING TO

THE NEW PANEL. ALL WORK SHALL BE DONE AFTER

HOURS IN ORDER TO MINIMIZE IMPACTS ON THE

FACILITY.

NORTH

PLAN

0 4 8 16

3 ENLARGED ELECTRICAL ROOM

SCALE: 1/4" = 1' 0"

0 2 4 8

NORTH

PLAN

2 ENLARGED DEMOLITION PLAN

SCALE: 1/4" = 1' 0"

BUILDING 2 GROUND FLOOR

BUILDING 2 GROUND FLOOR

0 2 4 8

NORTH

PLAN

4 JUNCTION BOX REFERENCE PHOTOS

SCALE: No Scale

CONC

PLATFORM

TRANSFORMER

RM

N&FS STORAGE

ENGINEERING

5-4" C.

STUBBED UP

EXISTING PULLBOX

3EMLS

3EM

3ATS-LS

3MP-1

3ATS-EM

PULLBOX

NEW

'MP3'

EXISTING 'MP3'. REPLACE

WITH 2500A, SE RATED, PANEL

AND LSIG CIRCUIT BREAKER

EXISTING

'PMT-3'

TRANSFORMER

EXISTING

UNDERGROUND

SECONDARY

3EMMC1

3EMDP

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

KEYPLAN:

AREA OF WORK

BLDG

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

EP102

BUILDING 3 GROUND FLOOR POWER PLAN

1 BUILDING 3 GROUND FLOOR POWER PLAN

SCALE: 1/4" = 1' 0"

1. UTILIZE EXISTING CONDUIT PENETRATIONS FOR

ROUTING OF NEW CONDUIT TO 'MP3'. SEE 1/E-501.

2. EXISTING 'MP3' TO BE DEMOLISHED AFTER NEW

'MP3' HAS BEEN INSTALLED. REMOVE UNUSED

CONDUIT AND WIRE.

3. NEW LOCATION OF PANEL 'MP3'.

EXTEND/REROUTE FEEDERS, CONDUCTORS AND

BRANCH CIRCUITS TO THIS NEW LOCATION.

PROVIDE NEW BREAKERS FOR RELOCATED

BRANCH CIRCUITS. PROVIDE HOUSEKEEPING

PAD FOR NEW 'MP3'. SEE 1/A-601 FOR

HOUSEKEEPING PAD DETAIL.

4. EXISTING PULLBOX TO REMAIN. PROVIDE NEW

FEEDERS TO NEW 'MP3'.

5. PROVIDE CODE REQUIRED PULL BOX.

0 2 4 8

NORTH

PLAN

1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING

AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT

ORIGINATE, PASS THROUGH, OR TERMINATE IN THE

AREA OF WORK.

2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED

REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO

SOURCE, INCLUDING THOSE CONCEALED WITHIN

WALLS, LEAVING NO ABANDONED ITEMS.

3. WHERE CONDUIT IS REMOVED FROM AN EXISTING

RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE

REMAINING HOLE SHALL BE PATCHED/REPAIRED TO

MAINTAIN THE RATING OF THE ASSEMBLY.

4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING

AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE

GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK

TO THE GREATEST EXTENT POSSIBLE PRIOR TO

PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY

COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE

OF AREA OF WORK PRIOR TO PERFORMING THE WORK.

5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO

DE-ENERGIZE EQUIPMENT.

6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN

3/4" CONDUIT UNLESS NOTED OTHERWISE.

7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE

PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A

LABEL PERMANENTLY ADHERED TO THE FACE PLATE.

8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS

WITH THE LED DRIVERS TO BE CONTROLLED.

9. PROVIDE RATED PENETRATIONS MATCHING EXISTING

RATED WALL CONDITIONS.

10. SEE SINGLE-LINE SHEETS E-601 & E-604.

11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,

FUEL, AND ALL NECESSARY CABLING, TO PROVIDE

TEMPORARY POWER TO THE FACILITY DURING THE

TRANSITIONING OF CIRCUITS FROM THE EXISTING TO

THE NEW PANEL. ALL WORK SHALL BE DONE AFTER

HOURS IN ORDER TO MINIMIZE IMPACTS ON THE

FACILITY.

OVER HEAD DOOR

ENTRY

WAREHOUSE

AREA

STAIR

NO 1

STORAGE

6C

EMER.

SHOWER

6B

STORAGE

6A

BREAK RM

OFFICE

WOMENS

TOILET

2B

MENS

TOILET

2A

STOR

WAREHOUSE AREA

WAREHOUSE

AREA

EXISTING 12LP2

'12LP1' - 26,28

EXISTING 12LP1

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

KEYPLAN:

AREA OF WORK

BLDG

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

EP103

SHEET KEY NOTES:

SHEET NOTES:

BUILDING 12 GROUND FLOOR POWER PLAN

1 BUILDING 12 GROUND FLOOR POWER PLAN

SCALE: 1/8" = 1' 0"

1. NEW DOCK LEVELER CONTROLLER.

2. NEW MOTORIZED DOCK LEVELER 208V, 1ɸ.

3. NEW 3 POLE 30A FUSED DISCONNECT.

NORTH

PLAN

0 4 8 16

1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING

AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT

ORIGINATE, PASS THROUGH, OR TERMINATE IN THE

AREA OF WORK.

2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED

REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO

SOURCE, INCLUDING THOSE CONCEALED WITHIN

WALLS, LEAVING NO ABANDONED ITEMS.

3. WHERE CONDUIT IS REMOVED FROM AN EXISTING

RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE

REMAINING HOLE SHALL BE PATCHED/REPAIRED TO

MAINTAIN THE RATING OF THE ASSEMBLY.

4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING

AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE

GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK

TO THE GREATEST EXTENT POSSIBLE PRIOR TO

PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY

COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE

OF AREA OF WORK PRIOR TO PERFORMING THE WORK.

5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO

DE-ENERGIZE EQUIPMENT.

6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN

3/4" CONDUIT UNLESS NOTED OTHERWISE.

7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE

PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A

LABEL PERMANENTLY ADHERED TO THE FACE PLATE.

8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS

WITH THE LED DRIVERS TO BE CONTROLLED.

9. PROVIDE RATED PENETRATIONS MATCHING EXISTING

RATED WALL CONDITIONS.

10. SEE SINGLE-LINE SHEETS E-601 & E-604.

11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,

FUEL, AND ALL NECESSARY CABLING, TO PROVIDE

TEMPORARY POWER TO THE FACILITY DURING THE

TRANSITIONING OF CIRCUITS FROM THE EXISTING TO

THE NEW PANEL. ALL WORK SHALL BE DONE AFTER

HOURS IN ORDER TO MINIMIZE IMPACTS ON THE

FACILITY.

DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064

5/23/2023

VHALEXFaulkB Line

VHALEXFaulkB Line

VHALEXFaulkB Text Box

BUILDING 12 DOCK LEVELERS AND ASSOCIATED ELECTRICAL WORK ARE NOT IN CONTRACT

TRANSFORMER RM

TOILET PIPE

BASEMENT

AIR

CONDITION

SHOP

EX. FACP

EX. HVAC

CONTROLS

NEW

MP22

EXISTING

MP22 2

EXISTING

'PMT-22'

TRANSFORMER

NEW 800A ENCLOSED CIRCUIT BREAKER IN NEMA 3R

ENCLOSURE. INTERCEPT EXISTING FEEDERS TO

MP22. PROVIDE UNISTRUT STRUCTURE TO MOUNT

ENCLOSED SERVICE ENTRANCE CIRCUIT BREAKER.

EXISTING J-BOX. REPLACE WITH

ENCLOSED 800A CB LSI

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

KEYPLAN:

AREA OF WORK

BLDG

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

EP104

SHEET KEY NOTES:

SHEET NOTES:

BUILDING 22 GROUND FLOOR POWER PLAN

1 BUILDING 22 GROUND FLOOR POWER PLAN

SCALE: 1/8" = 1' 0"

1. INTERCEPT EXISTING FEEDER TO 'MP22' AND

EXTEND MATCHING FEEDER TO NEW PANEL. SEE

SINGLE LINE 1/E-607.

2. EXISTING 'MP22' TO BE DEMOLISHED AFTER NEW

'MP22' HAS BEEN INSTALLED.

3. NEW LOCATION OF PANEL 'MP22'. EXTEND

FEEDERS, CONDUCTORS AND BRANCH CIRCUITS

TO THIS NEW LOCATION. PROVIDE NEW

BREAKERS FOR RELOCATED BRANCH CIRCUITS.

4. PROVIDE NEW CODE REQUIRED PULL BOX.

NORTH

PLAN

0 4 8 16

1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING

AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT

ORIGINATE, PASS THROUGH, OR TERMINATE IN THE

AREA OF WORK.

2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED

REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO

SOURCE, INCLUDING THOSE CONCEALED WITHIN

WALLS, LEAVING NO ABANDONED ITEMS.

3. WHERE CONDUIT IS REMOVED FROM AN EXISTING

RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE

REMAINING HOLE SHALL BE PATCHED/REPAIRED TO

MAINTAIN THE RATING OF THE ASSEMBLY.

4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING

AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE

GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK

TO THE GREATEST EXTENT POSSIBLE PRIOR TO

PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY

COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE

OF AREA OF WORK PRIOR TO PERFORMING THE WORK.

5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO

DE-ENERGIZE EQUIPMENT.

6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN

3/4" CONDUIT UNLESS NOTED OTHERWISE.

7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE

PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A

LABEL PERMANENTLY ADHERED TO THE FACE PLATE.

8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS

WITH THE LED DRIVERS TO BE CONTROLLED.

9. PROVIDE RATED PENETRATIONS MATCHING EXISTING

RATED WALL CONDITIONS.

10. SEE SINGLE-LINE SHEETS E-601 & E-604.

11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,

FUEL, AND ALL NECESSARY CABLING, TO PROVIDE

TEMPORARY POWER TO THE FACILITY DURING THE

TRANSITIONING OF CIRCUITS FROM THE EXISTING TO

THE NEW PANEL. ALL WORK SHALL BE DONE AFTER

HOURS IN ORDER TO MINIMIZE IMPACTS ON THE

FACILITY.

CORRIDOR

C-G-25-4

SECY`S

PSYCHOLOGY

SVC

OFFICE

OFFICE

MENTAL HEALTH PHARMACY

TRANSFORMER

RM

SECY

OFFICE

25ATSEM

LIGHTING

PANEL

25EMLS

25ATSLS

NEW MP-25

NEW 800A LSI ENCLOSED CIRCUIT BREAKER

IN NEMA 1R SE RATED ENCLOSURE.

INTERCEPT EXISTING FEEDERS TO MP25

EXISTING

PANEL EM-25

EXISTING MP-25

NEW MCC25

EXISTING MCC25 EXISTING EMCC25

NEW EMCC25

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects

KEYPLAN:

AREA OF WORK

BLDG

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

EP105

BUILDING 25 GROUND FLOOR/PENTHOUSE

POWER PLAN

1 BUILDING 25 GROUND FLOOR POWER PLAN

SCALE: 1/4" = 1' 0"

SHEET KEY NOTES:

SHEET NOTES:

2 BUILDING 25 PENTHOUSE POWER PLAN

SCALE: 1/4" = 1' 0"

1. EXISTING 'MP-25' TO BE DEMOLISHED AFTER NEW

'MP-25' HAS BEEN INSTALLED.

2. NEW LOCATION OF PANEL 'MP-25'. EXTEND

FEEDERS, CONDUCTORS AND BRANCH CIRCUITS

TO THIS NEW LOCATION. PROVIDE NEW

BREAKERS FOR RELOCATED BRANCH CIRCUITS.

3. NEW MATCHING FEEDER CIRCUITS.

4. EXISTING 'MCC-25' AND 'EMCC-25' TO BE

DEMOLISHED AFTER NEW 'EMCC-25' AND

INTEGRATED PANEL 'EMCC-25' HAVE BEEN

INSTALLED.

5. PROVIDE NEW CODE REQUIRED PULL BOX.

INTERCEPT EXISTING FEEDERS AND BRANCH

CIRCUITS AND EXTEND MATCHING WIRE AND

CONDUIT TO NEW LOCATION. SEE SINGLE LINE

1/E-608.

6. PROVIDE HOUSEKEEPING PAD FOR NEW

EQUIPMENT 'MCC-25' AND 'EMCC-25'. SEE 1/A-601

FOR HOUSEKEEPING PAD DETAIL.

0 2 4 8

NORTH

PLAN

0 2 4 8

NORTH

PLAN

1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING

AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT

ORIGINATE, PASS THROUGH, OR TERMINATE IN THE

AREA OF WORK.

2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED

REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO

SOURCE, INCLUDING THOSE CONCEALED WITHIN

WALLS, LEAVING NO ABANDONED ITEMS.

3. WHERE CONDUIT IS REMOVED FROM AN EXISTING

RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE

REMAINING HOLE SHALL BE PATCHED/REPAIRED TO

MAINTAIN THE RATING OF THE ASSEMBLY.

4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING

AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE

GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK

TO THE GREATEST EXTENT POSSIBLE PRIOR TO

PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY

COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE

OF AREA OF WORK PRIOR TO PERFORMING THE WORK.

5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO

DE-ENERGIZE EQUIPMENT.

6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN

3/4" CONDUIT UNLESS NOTED OTHERWISE.

7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE

PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A

LABEL PERMANENTLY ADHERED TO THE FACE PLATE.

8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS

WITH THE LED DRIVERS TO BE CONTROLLED.

9. PROVIDE RATED PENETRATIONS MATCHING EXISTING

RATED WALL CONDITIONS.

10. SEE SINGLE-LINE SHEETS E-601 & E-604.

11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,

FUEL, AND ALL NECESSARY CABLING, TO PROVIDE

TEMPORARY POWER TO THE FACILITY DURING THE

TRANSITIONING OF CIRCUITS FROM THE EXISTING TO

THE NEW PANEL. ALL WORK SHALL BE DONE AFTER

HOURS IN ORDER TO MINIMIZE IMPACTS ON THE

FACILITY.

DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064

5/23/2023

AutoCAD SHX Text x

CR

ES

DC

RX

ENTRY

PASSAGE

CLOSET

INSIDE

OUTSIDE

J

JUNCTION BOX TO PROVIDE POWER FOR

120V CONNECTION TO PACS HARDWARE

CR

ES DC RX

CORRIDOR

C-G-17-1

OFFICE

19A

OUTSIDE

INSIDE

J

CR

ES DC RX

STAIR

NO 1

IT

CLOSET

SOCIAL

WORKER

OUTSIDE

INSIDE

JEXISTING JUNCTION BOX TO

PROVIDE POWER FOR 120V

CONNECTION TO PACS HARDWARE

EC

ES

DC

RX

CORRIDOR

C-G-25-1

OFFICE

18A

OFFICE

18B

OUTSIDE

INSIDE

J

EXISTING JUNCTION BOX TO

PROVIDE POWER FOR 120V

CONNECTION TO PACS HARDWARE

CR

ES

DC

RX

TRANSFORMER

RM

OUTSIDE INSIDE

4J

JUNCTION BOX TO PROVIDE

POWER FOR 120V CONNECTION TO

PACS HARDWARE

ES DC RX

CONNECTION TO

BUILDING 2

OUTSIDE

INSIDE2 J

EXISTING JUNCTION BOX TO

PROVIDE POWER FOR 120V

CONNECTION TO PACS HARDWARE

EC

ES

DC

RX

TO BUILDING 17

TO BUILDING 25

OUTSIDE

INSIDE

2J

EXISTING JUNCTION BOX TO

PROVIDE POWER FOR 120V

CONNECTION TO PACS HARDWARE

CAFETERIA

INSIDE

OUTSIDE

J

EXISTING JUNCTION BOX TO PROVIDE POWER

FOR 120V CONNECTION TO PACS HARDWARE

2 J EXISTING JUNCTION BOX TO PROVIDE POWER

FOR 120V CONNECTION TO PACS HARDWARE

05E

ES DC RX

CR

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects

WALL RATING LEGEND

1 HR - FIRE

SEPARATION

2 HR - FIRE

SEPARATION

SMOKE RESISTIVE HAZARDOUS

AREA

S S S S

ENLARGED PLANS - EXTERIOR DOORS

1 BLDG 1 - DOOR 007

SCALE: 1/4" = 1' 0"

1. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT

TO EXISTING PACS POWER IN OIT ROOM 31. FOR

BID PURPOSES USE A DISTANCE OF 100', TO BE

VERIFIED DURING PRE-BID WALKTHROUGH.

2. REUSE EXISTING POWER FOR NEW PACS

HARDWARE.

3. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT

TO EXISTING PACS POWER IN OIT ROOM 13B. FOR

BID PURPOSES USE A DISTANCE OF 85', TO BE

VERIFIED DURING PRE-BID WALKTHROUGH.

4. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT

TO EXISTING PACS POWER IN OIT ROOM 19. FOR

BID PURPOSES USE A DISTANCE OF 125', TO BE

VERIFIED DURING PRE-BID WALKTHROUGH.

5. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT

TO EXISTING PACS POWER IN OIT ROOM 112. FOR

BID PURPOSES USE A DISTANCE OF 50', TO BE

VERIFIED DURING PRE-BID WALKTHROUGH.

6. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT

TO EXISTING PACS POWER IN OIT ROOM 122. FOR

BID PURPOSES USE A DISTANCE OF 125', TO BE

VERIFIED DURING PRE-BID WALKTHROUGH.

0 2 4 8

7 BLDG 17 - DOOR 022

SCALE: 1/4" = 1' 0"

5 BLDG 17 - DOOR 017

SCALE: 1/4" = 1' 0"

6 BLDG 17 - DOOR 019

SCALE: 1/4" = 1' 0"10 BLDG 25 - DOOR 025

SCALE: 1/4" = 1' 0"

9 BLDG 25 - DOOR 024

SCALE: 1/4" = 1' 0"

8 BLDG 25 - DOOR 016

SCALE: 1/4" = 1' 0"

0 2 4 8

0 2 4 8

0 2 4 80 2 4 8

0 2 4 8

0 2 4 8

1, 2, 3, 17, 25

E-401

CARD READER

LEGEND

CR

EXIT BUTTON TO RELEASE DOOR

ELECTRONIC LOCKING MECHANISMES

DOOR CONTACTDC

REQUEST FOR EXIT SENSORRX

PHYSICAL ACCESS CONTROLPACS

A. DASHED LINE REPRESENTS AREA OF WORK.

EXISTING CARD READER TO REMAINEC

2 BLDG 2 - DOOR 010

SCALE: 1/4" = 1' 0"

0 2 4 8

PB

PB

4 BLDG 3 - DOOR 022

SCALE: 1/4" = 1' 0"

0 2 4 8

EC

OUTSIDE

INSIDE

PHARMACY

CACHE

EC

012 DOOR TAG

CR

JUNCTION BOX TO PROVIDE

POWER FOR 120V CONNECTION

TO PACS HARDWARE

3 BLDG 2 - DOOR 020

SCALE: 1/4" = 1' 0"

0 2 4 8

PUSH BUTTONPB

DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064

5/23/2023

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text C-G-2-3

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text 5B

AutoCAD SHX Text

MENS

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

ELECT

2' - 0" MIN

[610mm]

1 - 1/2" TYP

[38mm]

1" [25mm]

1" [25mm]

1" [25mm]

2" [51mm]

1" [2

5m m

5/ 8"

[1 6m m

4" [1 m m

2" [5

1m m

5" [1 m m

2" [51mm]

MIN

SECTION

1.

2.

3.

GENERAL NOTES:

ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.

PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.

HOLES MAY BE ADDED IF REQUIRED.

3/8" DIA HOLE

TYP. OF (6)

3" DEEP FIBERGLASS

CHANNEL SAME LENGTH

AS CU BUSS

1/4" DIA HOLE

TYP OF (8)

1/4" THICK

CU BUSS

1/4" DIA

MOUNTING

HOLES TYP.

OF (4)

1/2" NUT

1/2" DIA. x2"L.

BOLT TYP. OF (2)

1/2" LOCK

WASHER

1/2" STANDARD WASHER

1/2" FENDER WASHES (EACH SIDE)

STEEL

EXPANSION

ANCHOR

NEUTRAL (GROUNDED CONDUCTOR) BAR,

CONNECT TO NEUTRAL CONDUCTOR(S) PER

NEC 250.24

EQUIPMENT GROUNDING

CONDUCTOR

BOND EQUIPMENT

GROUNDING

CONDUCTOR TO SERVICE

RACEWAY(S) IF METAL

BOND TO METAL

UNDERGROUND WATER PIPE

ON SUPPLY SIDE OF MAIN COLD

WATER VALVE

BOND TO INTERIOR COLD WATER PIPE

WITHIN 5 FEET OF BUILDING ENTRY POINT

3/4" CONDUIT (TYPICAL)

BOND RACEWAY IF METAL (TYPICAL)

BOND TO (3) 3/4" x 10'

COPPERCLAD STEEL DRIVEN

GROUND RODS- SPACE 10' APART

EQUILATERALLY

BOND TO STRUCTURAL STEEL (MIN. 1/2" BAR,

20' ENCASED PER NEC 250.52). IN-FOOTING

CONDUCTOR SHALL BE CONTINUOUS FROM

GROUND BAR TO GROUND ROD

GROUNDING ELECTRODE CONDUCTOR.

SIZE PER RISER.

COMMUNICATION GROUND BAR.

SEE DETAIL 4/E-501.

GROUND BAR. BOND TO ENCLOSURE.

1.

2.

NOTES:

GROUNDING CONDUCTORS AND MAIN BONDING

JUMPER SHALL BE BARE COPPER UNO AND

SHALL BE SIZED AS INDICATED IN ELECTRICAL

RISER.

BONDS TO STRUCTURAL STEEL, BELOW-GRADE

PIPES, AND GROUND RODS SHALL BE BY

EXOTHERMIC WELD.PANEL

N G

TMGB

SYSTEM BONDING JUMPER.

SERVICE

DISCONNECT

1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE.

EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2 IN. (114 MM). FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS* . WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32 IN. (813 MM).

MAX DIAM OF OPENING IN FLOOR CONSTRUCTED OF HOLLOW-CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM).

SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE RESISTANCE

DIRECTORY FOR NAMES OF MANUFACTURERS.

1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - MAX 15 IN. (381 MM) ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX 16 IN. (406 MM) ID (OR SMALLER) MIN 0.028 (0.71 MM) WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE

MAY EXTEND A MAX OF 1/2 IN. (13 MM) BEYOND EITHER SURFACE OF FLOOR OR WALL.

2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4. MIN ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0 IN. (0 MM) (POINT CONTACT). PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND

SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.

D. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.

E. COPPER - TUBING NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.

F. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO

ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).

4. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE. AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE OF FLOOR AND AT BOTH SURFACES OF WALL. THE HOURLY F RATINGS AND THE MIN REQUIRED CAULK THICKNESSES

ARE DEPENDENT UPON A NUMBER OF PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:

(A)MIN 2 IN. (51 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE.

(B)MIN 1 IN. (25 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. MIN 1 IN. (25 MM) THICKNESS OF CAULK TO BE INSTALLED FLUSH WITH EACH SURFACE

OF FLOOR OR WALL ASSEMBLY.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT. (NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT

IS USED.)

*BEARING THE UL CLASSIFICATION MARKING

MIN FLOOR OR

WALL THKNS IN.

(MM)

2-1/2 (64)

2-1/2 (64)

4-1/2 (114)

NOM PIPE TUBE OR

CONDUIT DIAM IN.

(MM)

1/2-12 (13-305)

1/2-12 (13-305)

1/2-6 (13-152)

MAX

ANNULAR

SPACE IN.

(MM)

1-3/8 (35)

3-1/4 (83)

MIN. CAULK

THKNS IN.

(MM)

1/2 (13)

1 (25)

1/4 (6) (a)

System No. C-AJ-1044 June 15, 2005

F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

W Rating - Class I (See Item 4)

SECTION A-A

A

A

F

RATING

HR

1-3/8 (35)

1/2 (13)

1 (25)

1 (25)

1 (25)

2 (51)

1 (25) (b)1-3/8 (35)

3-1/4 (83)

2 (51)

2 (51)

2 (51)

1-1/4 (32)1/2-12 (13-305)

1/2-12 (13-305)

22-30 (558-762)

1/2-20 (13-508)

1/2-6 (13-152)

1/2-20 (13-508)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

4-1/2 (114)

5-1/2 (140)

20" 20" 20"

20"

SECT. 1 SECT. 2 SECT. 3

4" CONCRETE PAD WITH

CHAMFERED EDGES

72"

PLASTIC

SPACER

INNERDUCT,

SEE NOTE 5

DUCT

[SIZE AS

INDICATED

ON DWGS.] 6-WAY DUCT LINE 4-WAY DUCT LINE

2-WAY DUCT LINE

GENERAL NOTES:

1.

2.

3.

4.

5.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS

SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF

DUCTS WHEN CROSSING OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm

(24") OR AS OTHERWISE SPECIFIED IN SECTION 26 05 41.

PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.

TIE WIRE

(3")

(3")

76mm

(3 m m (3 m m

76mm

(3")

76mm

3" m m

3" m m

(3 m m

(3")

(3")

76mm

(3")

76mm76mm

(3

3" m m m m m m

3"

76mm

(3")

76mm (3")

(3") 76mm

152mm

(6")(SEE NOTE 4)

(T

YP

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects

E-501

ELECTRICAL DETAILS

5 CONCRETE ENCASED DUCTBANK DETAIL

SCALE: No Scale

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.

(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL

ELECTRICAL METALLIC TUBING

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS

PIPING MAY BE USED:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

OMEGA FLEX INC

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

TITEFLEX CORP

A BUNDY CO

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

WARD MFG INC

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN

WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

SYSTEM NO.W-L-1001

JUNE 15, 2005

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

MAX PIPE OR

CONDUIT DIAM

IN. (mm)

1 (25) 1 (25) 4 (102) 6 (152)

12 (305)

F RATING

HR

1 OR 2

3 OR 4

1 OR 2

3 OR 4

1 OR 2

T RATING

HR

0+, 1 OR 2

3 OR 4

SECTION A-A

1B

1A A

A

1 UL PENETRATION DETAIL W-L-1001

SCALE: No Scale

4 GROUND BAR DETAIL

SCALE: N.T.S.

3 SERVICE GROUNDING DETAIL

SCALE: No Scale

2 UL PENETRATION DETAIL C-AJ-1044

SCALE: No Scale

6 TYPICAL MOTOR CONTROL CENTER DETAIL

SCALE: No Scale

225A 3P

4-#4/0, #4 GRD.

IN 2.5" C.

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

100A 3P

175A 3P

200A 3P

3-#2/0, #6 GRD. IN 2" C.

4-#2, #6 GRD. IN 1.25" C.

SPARE

600A 3P

EXISTING UTILITY

TRANSFORMER PMT-2

2LP2 2LP1 2LP3 2LP7 2LP4 2LP9 2LP11 2LP12 2LP15 MCC-2 2LP5 2DP

76LP1

2LP6 2LP10 2LP8 2LP13

VA POLICE

BIKE PATROL SHOP

MP2

600A, 208Y/120V-3PH-4W

TO NEW MP2

SPARE

FROM 2ATS/EM

4#250+1#4G-2.5" C

(CRITICAL)

2EM

250, MCB 208Y/120V-3PH-4W

250A 3P

100A 3P

100A 3P

100A 3P

100A 3P

30A 3P

20A 1P

200A 1P

2EM-4 2EM-3

HWH

PUMP

(SUB

BSMT)

HWH

(SUB

BSMT)

EMCC-2 2EM-1

TO NEW 2EM3

MP3

2500A, 208Y/120V-3PH-4W

2500A 3P

TO PMT-3

400A 3P

800A

700A TRIP

3P

400A 3P

LSI

1200A 3P

LSI

M

DIGITAL

METER

MP3

3LP15

3ATS/EM

CRITICAL

3MP-2 3MP-1

EXISTING PULL

BOX TO REMAIN TO NEW MP3

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C E

Dwg. of

LocationLocation

Office of Construction and Facilities Management

PROJECT MANAGER: ACG Project Number

Revisions: Date

CONSULTANTS:

MAY 25, 2023 WEMKTK

CORRECT FCA

DEFICIENCIES - FSC

596-19-104

LEXINGTON VA MEDICAL CENTER

2250 LEESTOWN RD

LEXINGTON, KENTUCKY 40511

19-064

100% BID DOCUMENTS

FULLY SPRINKLERED

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

X

17Engineers Architects E-601

PARTIAL SINGLE-LINE DIAGRAMS -

BUILDING 2 AND 3 (DEMO)

1 PARTIAL SINGLE LINE DIAGRAM - BUILDING 2 (MP2)

SCALE: No Scale

2 PARTIAL SINGLE LINE DIAGRAM - BUILDING 2 (EM2)

SCALE: No Scale

1. PANEL TO BE DEMOLISHED AFTER NEW PANEL

HAS BEEN INSTALLED.

2. INTERCEPT ALL CIRCUITS AND FEEDERS AND

EXTEND TO NEW MATCHING PANEL.

3. INTERCEPT EXISTING SERVICE CONDUCTORS

WITH CODE SIZE PULL BOX AND EXTEND

MATCHING FEEDER TO NEW PANEL.

A. SQUARE D EQUIPMENT WAS USED AS BASIS OF

DESIGN. VERIFY NEW EQUIPMENT FITS WITHIN

REQUIRED SPACE

B. COORDINATE ALL DOWNTIME WITH COR MINIMUM

48 HOURS PRIOR TO ANY ROUGH-IN.

2, 3

GENERAL NOTES:

A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL.

CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.

B. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

C. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS.

This is the start of the file's text. The full file is on GovTribe.