Project Drawings_Part2.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24923R0147
About this file
This package includes construction documents for a project to correct deficiencies at the Lexington VA Medical Center in Lexington, Kentucky. The project involves electrical, technology, and architectural work. Key aspects of the project include upgrading electrical panels and switchgear, replacing door hardware and controls, installing new cabling and wireless access points, and correcting fire protection deficiencies. The work will take place in multiple buildings on the medical center campus.
The documents provide specifications and drawings for the planned upgrades. Sheets show demolition and new construction plans, details for grounding systems and penetrations, riser diagrams, and schedules. Notes indicate standards and codes that must be followed, including NFPA, NEC, TIA standards, and VA requirements. The project appears aimed at modernizing critical building systems and improving life safety and physical security at the medical facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Site Visit Sign-in Sheet.pdf | ||
| 36C24923R0147 0001.docx | DOCX document | |
| Solicitation Questions - Answers.pdf | ||
| Project Drawings_Part1.pdf | ||
| Pricing Schedule.xlsx | XLSX spreadsheet | |
| Statement of Work.pdf | ||
| Past Performance Questionnaire.pdf | ||
| Project Specifications.pdf | ||
| 36C24923R0147_1.docx | DOCX document | |
| Wage Determination KY20230090 9-8-2023.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064
5/23/2023
L L
ELECTRICAL ABBREVIATIONS LIST
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE, VA ELECTRICAL DESIGN GUIDE AND VA STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING
HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT
DURING CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST
COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S
SCREW TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED
(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE
GOVERNMENT, SHALL BE PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
JUNCTION BOXAS
NOTED
J
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
EQUIPMENT CONNECTIONAS
NOTED
E
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED7'-0"
CENTER
OS
OS
LS
4' STRIP LIGHT---
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects
E-001
ELECTRICAL GENERAL NOTES, SYMBOL
LEGENDS, AND ABBREVIATIONS
1, 2, 3, 12, 17, 22, 25
B25
B17
B1
B3
B2
B22
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
ES101
SITE PLAN
1 DOOR REPLACEMENT SITE PLAN
SCALE: 1" = 50
A. SEE 'EP' SHEETS FOR POWER PLANS AND E-401
FOR DOOR POWER ENLARGEMENTS.
NORTH
TRUE
0 25' 50' 100'
1, 2, 3, 12, 17, 22, 25
E-401
E-401
E-401
EP104
EP105
E-401
EP105
EP101
EP103
EP102
E-401
E-401
E-401
E-401
E-401
E-401
UP
CUSTOMER
WAITING
CORRIDOR
C-G-2-2
CORRIDOR
C-G-2-1
CORRIDOR
C-G-2-3
ASST CHIEF
CASHIER
5A
SUPERVISOR
5B
MENS
TOILET
EMS
3A
TRI-WEST
TENANT
2LOBBY
ATM
VHA MRSA /
MDRO
TENANT
STAIR
POLICE
TRAINING
STORE
ELEVATOR
MACH RM
ELEVATOR KITCHEN
EMS
9A
SVC
RM 7
STORAGE
CANTEEN
STORAGE
CANTEEN
STORAGE
ELECTRICAL
EXISTING 2EM
EXISTING
MP-2
EXISTING 225
kVA PMT-2
TRANSFORMER
BUILDING 3
NEW MP2
NEW 2EM
CORRIDOR
C-G-2-3
SUPERVISOR
5B
MENS
TOILET
EMS
3A
NEW 2EM
S
A
B
S
A
S
J
J
'2LP3'-26
'2LP3'-16
NEW MP2
A
ELECTRICAL
CORRIDOR
C-G-2-3
SUPERVISOR
5B
MENS
TOILET
EMS
3A
STORE
5C
S
S
STORE
5D
ALL LIGHT SWITCHES AND
RECEPTACLES IN 5C AND
5D TO BE DEMOLISHED.
CIRCUITS TO BE REUSED
IN NEW CONSTRUCTION.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
KEYPLAN:
AREA OF WORK
BLDG
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
EP101
BUILDING 2 GROUND FLOOR DEMOLITION
AND POWER PLAN
1 BUILDING 2 GROUND FLOOR POWER PLAN
SCALE: 1/8" = 1' 0"
1. EXISTING 'MP-2' AND '2EM' TO BE DEMOLISHED
AFTER NEW 'MP-2' AND '2-EM' HAVE BEEN
INSTALLED.
2. EXISTING INCOMING SECONDARY FROM XFMR
'PMT2' IN APPROXIMATE LOCATION OF CRAWL
SPACE BELOW ROOM 6 CANTEEN STORAGE.
REMOVE SECONDARY AFTER NEW HAS BEEN
INSTALLED.
3. NEW LOCATION OF PANELS 'MP2' AND '2EM'.
EXTEND FEEDERS, CONDUCTORS AND BRANCH
CIRCUITS TO THIS NEW LOCATION. PROVIDE NEW
BREAKERS FOR RELOCATED BRANCH CIRCUITS.
4. NEW 4" CONDUIT ROUTED UNDERGROUND TO
NEW ELECTRICAL ROOM. SEE DETAIL 5/E-501
5. NEW PULL BOX TO INTERCEPT EXISTING FEEDERS
AND/OR BRANCH CIRCUITS.
6. PROPOSED ROUTE FOR INTERCEPTING EXISTING
BRANCH CIRCUITS BACK TO NEW MP2 LOCATED IN
NEW ELECTRICAL ROOM. CONDUITS TO BE
ROUTED ABOVE CEILING OR IN CRAWL SPACE. SEE
1/E-501 AND 2/E-501 FOR PENETRATION DETAIL.
7. EXISTING FEEDER CONDUITS TO BE INTERCEPTED.
SEE 1/E-604 FOR MORE INFORMATION.
8. NEW GROUND BAR. SEE 4/E-501.
9. SEE 1/EP101 FOR CONTINUATION.
10. EXISTING WINDOW TO SEALED OFF. SEE
ARCHITECTURAL DRAWINGS FOR MORE
INFORMATION.
11. TIE TO EXISTING EMERGENCY CIRCUIT.
12. TIE TO EXISTING NORMAL CIRCUIT.
13. TIE TO EXISTING RECEPTACLE CIRCUIT IN THIS
AREA. 2LP3-16.
14. REUSE EXISTING FIXTURE AND CIRCUIT. CONNECT
TO NEW SWITCH.
15. CONDUIT FROM ABOVE TO J-BOX. CONDUIT
THROUGH WALL. SEE REFERENCE PICTURES
4/EP101.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING
AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT
ORIGINATE, PASS THROUGH, OR TERMINATE IN THE
AREA OF WORK.
2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED
REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO
SOURCE, INCLUDING THOSE CONCEALED WITHIN
WALLS, LEAVING NO ABANDONED ITEMS.
3. WHERE CONDUIT IS REMOVED FROM AN EXISTING
RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE
REMAINING HOLE SHALL BE PATCHED/REPAIRED TO
MAINTAIN THE RATING OF THE ASSEMBLY.
4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING
AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE
GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK
TO THE GREATEST EXTENT POSSIBLE PRIOR TO
PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY
COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE
OF AREA OF WORK PRIOR TO PERFORMING THE WORK.
5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DE-ENERGIZE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN
3/4" CONDUIT UNLESS NOTED OTHERWISE.
7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE
PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A
LABEL PERMANENTLY ADHERED TO THE FACE PLATE.
8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS
WITH THE LED DRIVERS TO BE CONTROLLED.
9. PROVIDE RATED PENETRATIONS MATCHING EXISTING
RATED WALL CONDITIONS.
10. SEE SINGLE-LINE SHEETS E-601 & E-604.
11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,
FUEL, AND ALL NECESSARY CABLING, TO PROVIDE
TEMPORARY POWER TO THE FACILITY DURING THE
TRANSITIONING OF CIRCUITS FROM THE EXISTING TO
THE NEW PANEL. ALL WORK SHALL BE DONE AFTER
HOURS IN ORDER TO MINIMIZE IMPACTS ON THE
FACILITY.
NORTH
PLAN
0 4 8 16
3 ENLARGED ELECTRICAL ROOM
SCALE: 1/4" = 1' 0"
0 2 4 8
NORTH
PLAN
2 ENLARGED DEMOLITION PLAN
SCALE: 1/4" = 1' 0"
BUILDING 2 GROUND FLOOR
BUILDING 2 GROUND FLOOR
0 2 4 8
NORTH
PLAN
4 JUNCTION BOX REFERENCE PHOTOS
SCALE: No Scale
CONC
PLATFORM
TRANSFORMER
RM
N&FS STORAGE
ENGINEERING
5-4" C.
STUBBED UP
EXISTING PULLBOX
3EMLS
3EM
3ATS-LS
3MP-1
3ATS-EM
PULLBOX
NEW
'MP3'
EXISTING 'MP3'. REPLACE
WITH 2500A, SE RATED, PANEL
AND LSIG CIRCUIT BREAKER
EXISTING
'PMT-3'
TRANSFORMER
EXISTING
UNDERGROUND
SECONDARY
3EMMC1
3EMDP
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
KEYPLAN:
AREA OF WORK
BLDG
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
EP102
BUILDING 3 GROUND FLOOR POWER PLAN
1 BUILDING 3 GROUND FLOOR POWER PLAN
SCALE: 1/4" = 1' 0"
1. UTILIZE EXISTING CONDUIT PENETRATIONS FOR
ROUTING OF NEW CONDUIT TO 'MP3'. SEE 1/E-501.
2. EXISTING 'MP3' TO BE DEMOLISHED AFTER NEW
'MP3' HAS BEEN INSTALLED. REMOVE UNUSED
CONDUIT AND WIRE.
3. NEW LOCATION OF PANEL 'MP3'.
EXTEND/REROUTE FEEDERS, CONDUCTORS AND
BRANCH CIRCUITS TO THIS NEW LOCATION.
PROVIDE NEW BREAKERS FOR RELOCATED
BRANCH CIRCUITS. PROVIDE HOUSEKEEPING
PAD FOR NEW 'MP3'. SEE 1/A-601 FOR
HOUSEKEEPING PAD DETAIL.
4. EXISTING PULLBOX TO REMAIN. PROVIDE NEW
FEEDERS TO NEW 'MP3'.
5. PROVIDE CODE REQUIRED PULL BOX.
0 2 4 8
NORTH
PLAN
1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING
AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT
ORIGINATE, PASS THROUGH, OR TERMINATE IN THE
AREA OF WORK.
2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED
REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO
SOURCE, INCLUDING THOSE CONCEALED WITHIN
WALLS, LEAVING NO ABANDONED ITEMS.
3. WHERE CONDUIT IS REMOVED FROM AN EXISTING
RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE
REMAINING HOLE SHALL BE PATCHED/REPAIRED TO
MAINTAIN THE RATING OF THE ASSEMBLY.
4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING
AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE
GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK
TO THE GREATEST EXTENT POSSIBLE PRIOR TO
PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY
COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE
OF AREA OF WORK PRIOR TO PERFORMING THE WORK.
5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DE-ENERGIZE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN
3/4" CONDUIT UNLESS NOTED OTHERWISE.
7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE
PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A
LABEL PERMANENTLY ADHERED TO THE FACE PLATE.
8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS
WITH THE LED DRIVERS TO BE CONTROLLED.
9. PROVIDE RATED PENETRATIONS MATCHING EXISTING
RATED WALL CONDITIONS.
10. SEE SINGLE-LINE SHEETS E-601 & E-604.
11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,
FUEL, AND ALL NECESSARY CABLING, TO PROVIDE
TEMPORARY POWER TO THE FACILITY DURING THE
TRANSITIONING OF CIRCUITS FROM THE EXISTING TO
THE NEW PANEL. ALL WORK SHALL BE DONE AFTER
HOURS IN ORDER TO MINIMIZE IMPACTS ON THE
FACILITY.
OVER HEAD DOOR
ENTRY
WAREHOUSE
AREA
STAIR
NO 1
STORAGE
6C
EMER.
SHOWER
6B
STORAGE
6A
BREAK RM
OFFICE
WOMENS
TOILET
2B
MENS
TOILET
2A
STOR
WAREHOUSE AREA
WAREHOUSE
AREA
EXISTING 12LP2
'12LP1' - 26,28
EXISTING 12LP1
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
KEYPLAN:
AREA OF WORK
BLDG
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
EP103
SHEET KEY NOTES:
SHEET NOTES:
BUILDING 12 GROUND FLOOR POWER PLAN
1 BUILDING 12 GROUND FLOOR POWER PLAN
SCALE: 1/8" = 1' 0"
1. NEW DOCK LEVELER CONTROLLER.
2. NEW MOTORIZED DOCK LEVELER 208V, 1ɸ.
3. NEW 3 POLE 30A FUSED DISCONNECT.
NORTH
PLAN
0 4 8 16
1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING
AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT
ORIGINATE, PASS THROUGH, OR TERMINATE IN THE
AREA OF WORK.
2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED
REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO
SOURCE, INCLUDING THOSE CONCEALED WITHIN
WALLS, LEAVING NO ABANDONED ITEMS.
3. WHERE CONDUIT IS REMOVED FROM AN EXISTING
RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE
REMAINING HOLE SHALL BE PATCHED/REPAIRED TO
MAINTAIN THE RATING OF THE ASSEMBLY.
4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING
AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE
GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK
TO THE GREATEST EXTENT POSSIBLE PRIOR TO
PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY
COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE
OF AREA OF WORK PRIOR TO PERFORMING THE WORK.
5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DE-ENERGIZE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN
3/4" CONDUIT UNLESS NOTED OTHERWISE.
7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE
PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A
LABEL PERMANENTLY ADHERED TO THE FACE PLATE.
8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS
WITH THE LED DRIVERS TO BE CONTROLLED.
9. PROVIDE RATED PENETRATIONS MATCHING EXISTING
RATED WALL CONDITIONS.
10. SEE SINGLE-LINE SHEETS E-601 & E-604.
11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,
FUEL, AND ALL NECESSARY CABLING, TO PROVIDE
TEMPORARY POWER TO THE FACILITY DURING THE
TRANSITIONING OF CIRCUITS FROM THE EXISTING TO
THE NEW PANEL. ALL WORK SHALL BE DONE AFTER
HOURS IN ORDER TO MINIMIZE IMPACTS ON THE
FACILITY.
DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064
5/23/2023
VHALEXFaulkB Line
VHALEXFaulkB Line
VHALEXFaulkB Text Box
BUILDING 12 DOCK LEVELERS AND ASSOCIATED ELECTRICAL WORK ARE NOT IN CONTRACT
TRANSFORMER RM
TOILET PIPE
BASEMENT
AIR
CONDITION
SHOP
EX. FACP
EX. HVAC
CONTROLS
NEW
MP22
EXISTING
MP22 2
EXISTING
'PMT-22'
TRANSFORMER
NEW 800A ENCLOSED CIRCUIT BREAKER IN NEMA 3R
ENCLOSURE. INTERCEPT EXISTING FEEDERS TO
MP22. PROVIDE UNISTRUT STRUCTURE TO MOUNT
ENCLOSED SERVICE ENTRANCE CIRCUIT BREAKER.
EXISTING J-BOX. REPLACE WITH
ENCLOSED 800A CB LSI
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
KEYPLAN:
AREA OF WORK
BLDG
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
EP104
SHEET KEY NOTES:
SHEET NOTES:
BUILDING 22 GROUND FLOOR POWER PLAN
1 BUILDING 22 GROUND FLOOR POWER PLAN
SCALE: 1/8" = 1' 0"
1. INTERCEPT EXISTING FEEDER TO 'MP22' AND
EXTEND MATCHING FEEDER TO NEW PANEL. SEE
SINGLE LINE 1/E-607.
2. EXISTING 'MP22' TO BE DEMOLISHED AFTER NEW
'MP22' HAS BEEN INSTALLED.
3. NEW LOCATION OF PANEL 'MP22'. EXTEND
FEEDERS, CONDUCTORS AND BRANCH CIRCUITS
TO THIS NEW LOCATION. PROVIDE NEW
BREAKERS FOR RELOCATED BRANCH CIRCUITS.
4. PROVIDE NEW CODE REQUIRED PULL BOX.
NORTH
PLAN
0 4 8 16
1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING
AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT
ORIGINATE, PASS THROUGH, OR TERMINATE IN THE
AREA OF WORK.
2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED
REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO
SOURCE, INCLUDING THOSE CONCEALED WITHIN
WALLS, LEAVING NO ABANDONED ITEMS.
3. WHERE CONDUIT IS REMOVED FROM AN EXISTING
RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE
REMAINING HOLE SHALL BE PATCHED/REPAIRED TO
MAINTAIN THE RATING OF THE ASSEMBLY.
4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING
AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE
GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK
TO THE GREATEST EXTENT POSSIBLE PRIOR TO
PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY
COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE
OF AREA OF WORK PRIOR TO PERFORMING THE WORK.
5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DE-ENERGIZE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN
3/4" CONDUIT UNLESS NOTED OTHERWISE.
7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE
PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A
LABEL PERMANENTLY ADHERED TO THE FACE PLATE.
8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS
WITH THE LED DRIVERS TO BE CONTROLLED.
9. PROVIDE RATED PENETRATIONS MATCHING EXISTING
RATED WALL CONDITIONS.
10. SEE SINGLE-LINE SHEETS E-601 & E-604.
11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,
FUEL, AND ALL NECESSARY CABLING, TO PROVIDE
TEMPORARY POWER TO THE FACILITY DURING THE
TRANSITIONING OF CIRCUITS FROM THE EXISTING TO
THE NEW PANEL. ALL WORK SHALL BE DONE AFTER
HOURS IN ORDER TO MINIMIZE IMPACTS ON THE
FACILITY.
CORRIDOR
C-G-25-4
SECY`S
PSYCHOLOGY
SVC
OFFICE
OFFICE
MENTAL HEALTH PHARMACY
TRANSFORMER
RM
SECY
OFFICE
25ATSEM
LIGHTING
PANEL
25EMLS
25ATSLS
NEW MP-25
NEW 800A LSI ENCLOSED CIRCUIT BREAKER
IN NEMA 1R SE RATED ENCLOSURE.
INTERCEPT EXISTING FEEDERS TO MP25
EXISTING
PANEL EM-25
EXISTING MP-25
NEW MCC25
EXISTING MCC25 EXISTING EMCC25
NEW EMCC25
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects
KEYPLAN:
AREA OF WORK
BLDG
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
EP105
BUILDING 25 GROUND FLOOR/PENTHOUSE
POWER PLAN
1 BUILDING 25 GROUND FLOOR POWER PLAN
SCALE: 1/4" = 1' 0"
SHEET KEY NOTES:
SHEET NOTES:
2 BUILDING 25 PENTHOUSE POWER PLAN
SCALE: 1/4" = 1' 0"
1. EXISTING 'MP-25' TO BE DEMOLISHED AFTER NEW
'MP-25' HAS BEEN INSTALLED.
2. NEW LOCATION OF PANEL 'MP-25'. EXTEND
FEEDERS, CONDUCTORS AND BRANCH CIRCUITS
TO THIS NEW LOCATION. PROVIDE NEW
BREAKERS FOR RELOCATED BRANCH CIRCUITS.
3. NEW MATCHING FEEDER CIRCUITS.
4. EXISTING 'MCC-25' AND 'EMCC-25' TO BE
DEMOLISHED AFTER NEW 'EMCC-25' AND
INTEGRATED PANEL 'EMCC-25' HAVE BEEN
INSTALLED.
5. PROVIDE NEW CODE REQUIRED PULL BOX.
INTERCEPT EXISTING FEEDERS AND BRANCH
CIRCUITS AND EXTEND MATCHING WIRE AND
CONDUIT TO NEW LOCATION. SEE SINGLE LINE
1/E-608.
6. PROVIDE HOUSEKEEPING PAD FOR NEW
EQUIPMENT 'MCC-25' AND 'EMCC-25'. SEE 1/A-601
FOR HOUSEKEEPING PAD DETAIL.
0 2 4 8
NORTH
PLAN
0 2 4 8
NORTH
PLAN
1. CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING
AND IDENTIFYING ALL CIRCUITS AND CONDUITS THAT
ORIGINATE, PASS THROUGH, OR TERMINATE IN THE
AREA OF WORK.
2. FOR ELECTRICAL CIRCUITS BEING DEMOLISHED
REMOVE BOXES, CONDUIT AND CONDUCTORS BACK TO
SOURCE, INCLUDING THOSE CONCEALED WITHIN
WALLS, LEAVING NO ABANDONED ITEMS.
3. WHERE CONDUIT IS REMOVED FROM AN EXISTING
RATED ASSEMBLY NOT SUBJECT TO DEMOLITION, THE
REMAINING HOLE SHALL BE PATCHED/REPAIRED TO
MAINTAIN THE RATING OF THE ASSEMBLY.
4. CONSTRUCTION IS TO BE PERFORMED WHILE LEAVING
AREAS OUTSIDE OF AREA OF WORK ACTIVE TO THE
GREATEST EXTENT POSSIBLE. ROUGH-IN NEW WORK
TO THE GREATEST EXTENT POSSIBLE PRIOR TO
PERFORMING SWITCH OVER TO NEW PANELS. NOTIFY
COR OF ANY WORK THAT WILL AFFECT AREAS OUTSIDE
OF AREA OF WORK PRIOR TO PERFORMING THE WORK.
5. FOLLOW ALL SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DE-ENERGIZE EQUIPMENT.
6. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG IN
3/4" CONDUIT UNLESS NOTED OTHERWISE.
7. ALL NEW RECEPTACLES SHALL HAVE THEIR SOURCE
PANEL AND CIRCUIT NUMBER CLEARLY DENOTED BY A
LABEL PERMANENTLY ADHERED TO THE FACE PLATE.
8. ENSURE COMPATIBILITY OF ALL LIGHTING CONTROLS
WITH THE LED DRIVERS TO BE CONTROLLED.
9. PROVIDE RATED PENETRATIONS MATCHING EXISTING
RATED WALL CONDITIONS.
10. SEE SINGLE-LINE SHEETS E-601 & E-604.
11. PROVIDE TEMPORARY 600KW PORTABLE GENERATOR,
FUEL, AND ALL NECESSARY CABLING, TO PROVIDE
TEMPORARY POWER TO THE FACILITY DURING THE
TRANSITIONING OF CIRCUITS FROM THE EXISTING TO
THE NEW PANEL. ALL WORK SHALL BE DONE AFTER
HOURS IN ORDER TO MINIMIZE IMPACTS ON THE
FACILITY.
DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064
5/23/2023
AutoCAD SHX Text x
CR
ES
DC
RX
ENTRY
PASSAGE
CLOSET
INSIDE
OUTSIDE
J
JUNCTION BOX TO PROVIDE POWER FOR
120V CONNECTION TO PACS HARDWARE
CR
ES DC RX
CORRIDOR
C-G-17-1
OFFICE
19A
OUTSIDE
INSIDE
J
CR
ES DC RX
STAIR
NO 1
IT
CLOSET
SOCIAL
WORKER
OUTSIDE
INSIDE
JEXISTING JUNCTION BOX TO
PROVIDE POWER FOR 120V
CONNECTION TO PACS HARDWARE
EC
ES
DC
RX
CORRIDOR
C-G-25-1
OFFICE
18A
OFFICE
18B
OUTSIDE
INSIDE
J
EXISTING JUNCTION BOX TO
PROVIDE POWER FOR 120V
CONNECTION TO PACS HARDWARE
CR
ES
DC
RX
TRANSFORMER
RM
OUTSIDE INSIDE
4J
JUNCTION BOX TO PROVIDE
POWER FOR 120V CONNECTION TO
PACS HARDWARE
ES DC RX
CONNECTION TO
BUILDING 2
OUTSIDE
INSIDE2 J
EXISTING JUNCTION BOX TO
PROVIDE POWER FOR 120V
CONNECTION TO PACS HARDWARE
EC
ES
DC
RX
TO BUILDING 17
TO BUILDING 25
OUTSIDE
INSIDE
2J
EXISTING JUNCTION BOX TO
PROVIDE POWER FOR 120V
CONNECTION TO PACS HARDWARE
CAFETERIA
INSIDE
OUTSIDE
J
EXISTING JUNCTION BOX TO PROVIDE POWER
FOR 120V CONNECTION TO PACS HARDWARE
2 J EXISTING JUNCTION BOX TO PROVIDE POWER
FOR 120V CONNECTION TO PACS HARDWARE
05E
ES DC RX
CR
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects
WALL RATING LEGEND
1 HR - FIRE
SEPARATION
2 HR - FIRE
SEPARATION
SMOKE RESISTIVE HAZARDOUS
AREA
S S S S
ENLARGED PLANS - EXTERIOR DOORS
1 BLDG 1 - DOOR 007
SCALE: 1/4" = 1' 0"
1. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT
TO EXISTING PACS POWER IN OIT ROOM 31. FOR
BID PURPOSES USE A DISTANCE OF 100', TO BE
VERIFIED DURING PRE-BID WALKTHROUGH.
2. REUSE EXISTING POWER FOR NEW PACS
HARDWARE.
3. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT
TO EXISTING PACS POWER IN OIT ROOM 13B. FOR
BID PURPOSES USE A DISTANCE OF 85', TO BE
VERIFIED DURING PRE-BID WALKTHROUGH.
4. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT
TO EXISTING PACS POWER IN OIT ROOM 19. FOR
BID PURPOSES USE A DISTANCE OF 125', TO BE
VERIFIED DURING PRE-BID WALKTHROUGH.
5. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT
TO EXISTING PACS POWER IN OIT ROOM 112. FOR
BID PURPOSES USE A DISTANCE OF 50', TO BE
VERIFIED DURING PRE-BID WALKTHROUGH.
6. PROVIDE 3-12 AWG CONDUCTORS IN 3/4" CONDUIT
TO EXISTING PACS POWER IN OIT ROOM 122. FOR
BID PURPOSES USE A DISTANCE OF 125', TO BE
VERIFIED DURING PRE-BID WALKTHROUGH.
0 2 4 8
7 BLDG 17 - DOOR 022
SCALE: 1/4" = 1' 0"
5 BLDG 17 - DOOR 017
SCALE: 1/4" = 1' 0"
6 BLDG 17 - DOOR 019
SCALE: 1/4" = 1' 0"10 BLDG 25 - DOOR 025
SCALE: 1/4" = 1' 0"
9 BLDG 25 - DOOR 024
SCALE: 1/4" = 1' 0"
8 BLDG 25 - DOOR 016
SCALE: 1/4" = 1' 0"
0 2 4 8
0 2 4 8
0 2 4 80 2 4 8
0 2 4 8
0 2 4 8
1, 2, 3, 17, 25
E-401
CARD READER
LEGEND
CR
EXIT BUTTON TO RELEASE DOOR
ELECTRONIC LOCKING MECHANISMES
DOOR CONTACTDC
REQUEST FOR EXIT SENSORRX
PHYSICAL ACCESS CONTROLPACS
A. DASHED LINE REPRESENTS AREA OF WORK.
EXISTING CARD READER TO REMAINEC
2 BLDG 2 - DOOR 010
SCALE: 1/4" = 1' 0"
0 2 4 8
PB
PB
4 BLDG 3 - DOOR 022
SCALE: 1/4" = 1' 0"
0 2 4 8
EC
OUTSIDE
INSIDE
PHARMACY
CACHE
EC
012 DOOR TAG
CR
JUNCTION BOX TO PROVIDE
POWER FOR 120V CONNECTION
TO PACS HARDWARE
3 BLDG 2 - DOOR 020
SCALE: 1/4" = 1' 0"
0 2 4 8
PUSH BUTTONPB
DocuSign Envelope ID: E51950FD-4980-4A48-9F78-0ABB44AA9064
5/23/2023
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text C-G-2-3
AutoCAD SHX Text
SUPERVISOR
AutoCAD SHX Text 5B
AutoCAD SHX Text
MENS
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
ELECT
2' - 0" MIN
[610mm]
1 - 1/2" TYP
[38mm]
1" [25mm]
1" [25mm]
1" [25mm]
2" [51mm]
1" [2
5m m
5/ 8"
[1 6m m
4" [1 m m
2" [5
1m m
5" [1 m m
2" [51mm]
MIN
SECTION
1.
2.
3.
GENERAL NOTES:
ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.
PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.
HOLES MAY BE ADDED IF REQUIRED.
3/8" DIA HOLE
TYP. OF (6)
3" DEEP FIBERGLASS
CHANNEL SAME LENGTH
AS CU BUSS
1/4" DIA HOLE
TYP OF (8)
1/4" THICK
CU BUSS
1/4" DIA
MOUNTING
HOLES TYP.
OF (4)
1/2" NUT
1/2" DIA. x2"L.
BOLT TYP. OF (2)
1/2" LOCK
WASHER
1/2" STANDARD WASHER
1/2" FENDER WASHES (EACH SIDE)
STEEL
EXPANSION
ANCHOR
NEUTRAL (GROUNDED CONDUCTOR) BAR,
CONNECT TO NEUTRAL CONDUCTOR(S) PER
NEC 250.24
EQUIPMENT GROUNDING
CONDUCTOR
BOND EQUIPMENT
GROUNDING
CONDUCTOR TO SERVICE
RACEWAY(S) IF METAL
BOND TO METAL
UNDERGROUND WATER PIPE
ON SUPPLY SIDE OF MAIN COLD
WATER VALVE
BOND TO INTERIOR COLD WATER PIPE
WITHIN 5 FEET OF BUILDING ENTRY POINT
3/4" CONDUIT (TYPICAL)
BOND RACEWAY IF METAL (TYPICAL)
BOND TO (3) 3/4" x 10'
COPPERCLAD STEEL DRIVEN
GROUND RODS- SPACE 10' APART
EQUILATERALLY
BOND TO STRUCTURAL STEEL (MIN. 1/2" BAR,
20' ENCASED PER NEC 250.52). IN-FOOTING
CONDUCTOR SHALL BE CONTINUOUS FROM
GROUND BAR TO GROUND ROD
GROUNDING ELECTRODE CONDUCTOR.
SIZE PER RISER.
COMMUNICATION GROUND BAR.
SEE DETAIL 4/E-501.
GROUND BAR. BOND TO ENCLOSURE.
1.
2.
NOTES:
GROUNDING CONDUCTORS AND MAIN BONDING
JUMPER SHALL BE BARE COPPER UNO AND
SHALL BE SIZED AS INDICATED IN ELECTRICAL
RISER.
BONDS TO STRUCTURAL STEEL, BELOW-GRADE
PIPES, AND GROUND RODS SHALL BE BY
EXOTHERMIC WELD.PANEL
N G
TMGB
SYSTEM BONDING JUMPER.
SERVICE
DISCONNECT
1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE.
EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2 IN. (114 MM). FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS* . WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32 IN. (813 MM).
MAX DIAM OF OPENING IN FLOOR CONSTRUCTED OF HOLLOW-CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM).
SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - MAX 15 IN. (381 MM) ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX 16 IN. (406 MM) ID (OR SMALLER) MIN 0.028 (0.71 MM) WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE
MAY EXTEND A MAX OF 1/2 IN. (13 MM) BEYOND EITHER SURFACE OF FLOOR OR WALL.
2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4. MIN ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0 IN. (0 MM) (POINT CONTACT). PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND
SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
D. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
E. COPPER - TUBING NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
F. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).
4. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE. AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE OF FLOOR AND AT BOTH SURFACES OF WALL. THE HOURLY F RATINGS AND THE MIN REQUIRED CAULK THICKNESSES
ARE DEPENDENT UPON A NUMBER OF PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:
(A)MIN 2 IN. (51 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE.
(B)MIN 1 IN. (25 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. MIN 1 IN. (25 MM) THICKNESS OF CAULK TO BE INSTALLED FLUSH WITH EACH SURFACE
OF FLOOR OR WALL ASSEMBLY.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT. (NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT
IS USED.)
*BEARING THE UL CLASSIFICATION MARKING
MIN FLOOR OR
WALL THKNS IN.
(MM)
2-1/2 (64)
2-1/2 (64)
4-1/2 (114)
NOM PIPE TUBE OR
CONDUIT DIAM IN.
(MM)
1/2-12 (13-305)
1/2-12 (13-305)
1/2-6 (13-152)
MAX
ANNULAR
SPACE IN.
(MM)
1-3/8 (35)
3-1/4 (83)
MIN. CAULK
THKNS IN.
(MM)
1/2 (13)
1 (25)
1/4 (6) (a)
System No. C-AJ-1044 June 15, 2005
F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
W Rating - Class I (See Item 4)
SECTION A-A
A
A
F
RATING
HR
1-3/8 (35)
1/2 (13)
1 (25)
1 (25)
1 (25)
2 (51)
1 (25) (b)1-3/8 (35)
3-1/4 (83)
2 (51)
2 (51)
2 (51)
1-1/4 (32)1/2-12 (13-305)
1/2-12 (13-305)
22-30 (558-762)
1/2-20 (13-508)
1/2-6 (13-152)
1/2-20 (13-508)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
5-1/2 (140)
20" 20" 20"
20"
SECT. 1 SECT. 2 SECT. 3
4" CONCRETE PAD WITH
CHAMFERED EDGES
72"
PLASTIC
SPACER
INNERDUCT,
SEE NOTE 5
DUCT
[SIZE AS
INDICATED
ON DWGS.] 6-WAY DUCT LINE 4-WAY DUCT LINE
2-WAY DUCT LINE
GENERAL NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS
SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF
DUCTS WHEN CROSSING OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm
(24") OR AS OTHERWISE SPECIFIED IN SECTION 26 05 41.
PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
TIE WIRE
(3")
(3")
76mm
(3 m m (3 m m
76mm
(3")
76mm
3" m m
3" m m
(3 m m
(3")
(3")
76mm
(3")
76mm76mm
(3
3" m m m m m m
3"
76mm
(3")
76mm (3")
(3") 76mm
152mm
(6")(SEE NOTE 4)
(T
YP
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 17Engineers Architects
E-501
ELECTRICAL DETAILS
5 CONCRETE ENCASED DUCTBANK DETAIL
SCALE: No Scale
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN
WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25) 1 (25) 4 (102) 6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A A
A
1 UL PENETRATION DETAIL W-L-1001
SCALE: No Scale
4 GROUND BAR DETAIL
SCALE: N.T.S.
3 SERVICE GROUNDING DETAIL
SCALE: No Scale
2 UL PENETRATION DETAIL C-AJ-1044
SCALE: No Scale
6 TYPICAL MOTOR CONTROL CENTER DETAIL
SCALE: No Scale
225A 3P
4-#4/0, #4 GRD.
IN 2.5" C.
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
100A 3P
175A 3P
200A 3P
3-#2/0, #6 GRD. IN 2" C.
4-#2, #6 GRD. IN 1.25" C.
SPARE
600A 3P
EXISTING UTILITY
TRANSFORMER PMT-2
2LP2 2LP1 2LP3 2LP7 2LP4 2LP9 2LP11 2LP12 2LP15 MCC-2 2LP5 2DP
76LP1
2LP6 2LP10 2LP8 2LP13
VA POLICE
BIKE PATROL SHOP
MP2
600A, 208Y/120V-3PH-4W
TO NEW MP2
SPARE
FROM 2ATS/EM
4#250+1#4G-2.5" C
(CRITICAL)
2EM
250, MCB 208Y/120V-3PH-4W
250A 3P
100A 3P
100A 3P
100A 3P
100A 3P
30A 3P
20A 1P
200A 1P
2EM-4 2EM-3
HWH
PUMP
(SUB
BSMT)
HWH
(SUB
BSMT)
EMCC-2 2EM-1
TO NEW 2EM3
MP3
2500A, 208Y/120V-3PH-4W
2500A 3P
TO PMT-3
400A 3P
800A
700A TRIP
3P
400A 3P
LSI
1200A 3P
LSI
M
DIGITAL
METER
MP3
3LP15
3ATS/EM
CRITICAL
3MP-2 3MP-1
EXISTING PULL
BOX TO REMAIN TO NEW MP3
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
MAY 25, 2023 WEMKTK
CORRECT FCA
DEFICIENCIES - FSC
596-19-104
LEXINGTON VA MEDICAL CENTER
2250 LEESTOWN RD
LEXINGTON, KENTUCKY 40511
19-064
100% BID DOCUMENTS
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
X
17Engineers Architects E-601
PARTIAL SINGLE-LINE DIAGRAMS -
BUILDING 2 AND 3 (DEMO)
1 PARTIAL SINGLE LINE DIAGRAM - BUILDING 2 (MP2)
SCALE: No Scale
2 PARTIAL SINGLE LINE DIAGRAM - BUILDING 2 (EM2)
SCALE: No Scale
1. PANEL TO BE DEMOLISHED AFTER NEW PANEL
HAS BEEN INSTALLED.
2. INTERCEPT ALL CIRCUITS AND FEEDERS AND
EXTEND TO NEW MATCHING PANEL.
3. INTERCEPT EXISTING SERVICE CONDUCTORS
WITH CODE SIZE PULL BOX AND EXTEND
MATCHING FEEDER TO NEW PANEL.
A. SQUARE D EQUIPMENT WAS USED AS BASIS OF
DESIGN. VERIFY NEW EQUIPMENT FITS WITHIN
REQUIRED SPACE
B. COORDINATE ALL DOWNTIME WITH COR MINIMUM
48 HOURS PRIOR TO ANY ROUGH-IN.
2, 3
GENERAL NOTES:
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL.
CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
C. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS.