Product_information_sheet.pdf

PDF 534 KB Posted

Attached to
FPCM-MCSP-I001145-M001-KR-C Jacketed wire
Solicitation number
0000040635
Issued by
California

About this file

I apologize, but I cannot provide a summary of the file because the actual content of "Product_information_sheet.pdf" was not included in your message. You provided the file metadata and contract opportunity information, but the document itself—its text, images, or data—was not transmitted.

To provide an accurate and comprehensive summary, please share the complete contents of the Product_information_sheet.pdf file.

View the file

Other files

File Type Posted
Plan_sheet.pdf PDF
12_-_FPCM-MCSP-I001145-M001-KR-C.pdf PDF
Specs.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Armorlite® Type MC THHN/THWN 600V Circuit Size Copper Conductor PVC Jacketed 120/208V Colors. Silicone Free Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1.

Lightweight Aluminum Interlocked Armor. PVC Jacketed, Sunlight Resistant.

Image not to scale. See Table 1 for dimensions.

CONSTRUCTION:

1. Conductor: Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8

2. Insulation: All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN

3. Ground: Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN

4. Binder: Mylar tape

5. Armor: Aluminum Interlocked Armor

6. Jacket: Polyvinyl Chloride (PVC) Jacket, sunlight resistant, corrosion resistant

APPLICATIONS AND FEATURES:

Southwire Armorlite® Jacketed Type MC Cable is suitable for use as follows:

- Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.

- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.

- Fished or embedded in plaster.

- Concealed or exposed installations.

- Suitable for Wet Location per NEC 330.10(A)(11)

- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.

- Installation in cable tray and approved raceways, or as aerial cable on a messenger.

- Under raised floors for information technology equipment conductors and cables per NEC Article 645

- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet

- Anti-Short bushing not required

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:

- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )

- Federal Specification A-A59544 (formerly J-C-30B)

- NFPA 70 (National Electrical Code), Article 330

- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

SPECIFICATIONS:

• ASTM B3 Soft or Annealed Copper Wire

• ASTM B8 Concentric-Lay-Stranded Copper Conductors

Copyright © 2026 Southwire Company, LLC. All Rights Reserved UPDATED: June 24, 2025, 3:25 p.m.UTC REVISION: 1.000.012

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Stock # 610059 | SPEC 60103

• UL 83 Thermoplastic Insulated Wires and Cables

• UL 1569 Metal-Clad Cables

• UL 1479 Standard for Safety Fire Tests of Penetration Firestops

• UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test

• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

• RoHS-2 (European Directive 2011/65/EU)

• Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA

Only!” when ordering to ensure your project receives American made products.

• VW-1 (Vertical-Wire) Flame Test

SAMPLE PRINT LEGEND:

{SQFTG} SOUTHWIRE {UL} E96627 X/C XX AWG CU THHN OR THWN CDRS 600 VOLTS GG 1 X X AWG CU TYPE MC EZ-

JKT FOR CT USE SUN. RES. 90°C

Table 1 – Weights and Measurements

Stock Number

Cond.

Size

Conductor Number

Color Diameter

Over Conductor

Conductor Stranding

Insulation Thickness

Ground Size

Diameter Over Armor

Jacket Thickness

Approx.

OD

Copper Weight

Overall Weight

AWG/

Kcmil inch mils No. x

AWG

inch mil inch lbs/

1000ft lbs/

1000ft

12 AWG | Solid

610059◊ 12 4 BK,RD,BE,WE 0.080 Solid 20 1x12 0.553 50 0.659 99 240

All dimensions are nominal and subject to normal manufacturing tolerances ◊ Cable marked with this symbol is a standard stock item

Table 2 – Electrical and Engineering Data

Cond.

Size

Conductor Number

Min. Bend Radius

DC Resistance at 25°C

AC Resistance at 75°C

Inductive Reactance @ 60Hz

Allowable Ampacity Raceway 75°C

Allowable Ampacity Raceway 90°C

AWG/

Kcmil Inches Ω/1000ft Ω/1000ft Ω/1000ft Amp Amp

12 AWG | Solid

12 4 4.6 1.662 2.002 0.054 20 24

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections

310.15 and 110.14(C) for additional requirements.

* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Copyright © 2026 Southwire Company, LLC. All Rights Reserved UPDATED: June 24, 2025, 3:25 p.m.UTC REVISION: 1.000.012

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Stock # 610059 | SPEC 60103