Product_Data_Sheets.pdf
PDF 12 MB Posted
- Attached to
- HOCU Fire & Security Alarms System Replacement Federal contract opportunity
- Solicitation number
- 140P6425B0005
About this file
These are product data sheets for various fire alarm, security, and access control system components from manufacturers like Honeywell, System Sensor, Potter Electric Signal, George Risk Industries, and Bosch. The documents provide technical specifications, features, and ordering information for devices including:
Fire and intrusion alarm control units, motion detectors, manual pull stations, smoke detectors, duct smoke detectors, sirens/strobes, power supplies, shock sensors, access control readers, magnetic door contacts, and hold-up buttons. The sheets cover technical details like voltage requirements, mounting options, credential compatibility, communication protocols, environmental ratings, and compatibility with various control panels and systems. Most devices are designed for commercial and industrial security applications, with features like wireless connectivity, tamper protection, multiple credential support, and integration with access control platforms.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6425B0005_Amd_0002.pdf | ||
| Addendum__1_-_Revised_Drawing_FD7_0002.pdf | ||
| UPDATED_Questions___Answers_0002.pdf | ||
| Questions___Answers_0001.pdf | ||
| Sol_140P6425B0005_Amd_0001.pdf | ||
| Drawings.pdf | ||
| Addendum_to_Project_Specifications.pdf | ||
| Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| Project_Specifications.pdf | ||
| Sol_140P6425B0005.pdf | ||
| DBA_WD_-_Ross_County__OH.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hopewell Culture National Historical Park
(HOCU 247356)
Replace Fire and Security Alarms Project
System Equipment Data Sheets
TABLE OF CONTENTS
Fire and Intrusion Alarm Control Unit
� !�,��,���&0��'�.�12�2�.��!������������/����� !�3$�%���&��� �����
,� ���.$,,���.�$,������%'��,������� .�� !�$,����)*+�4� �.5,�� �.�
$.� %�'��!6���!7�6�����..�� !��(���8���!!��..�3������' ���%��.0�
��!�-��.���� ���/�9� �&6����9����� ������ %�!�-���.7� ���/������ �
����$��.7�����$ ������ �!�-���.7�:�&,�!.7�;"������-��.�� !�����&.�
������.��.$,,����!0��'�������()*+"#��'�.�3�� �!�.�% �!������$ ��
<$��:�&�� !���.��&�� �� ������:���.�.�� ����3� ��7�� !��.��-����3���
� �)*��� !�*=����!��.0
">��1;>�
?@ABCDE@DFGHIBGJH@KLMJN@NEFMHFGHO
JPQFMHFRSJ@EL@TUV@WXYSJP
FHHGJNNFRSJ@QLBMENZKLMJN@LG
TU[@IBGJSJNN@QLBMENZKLMJN
?@\FM@]LMEGLS@JBCDE@NJQFGFEJ@FGJFN
BMHJQJMHJMEŜ@_[@QFGEBEBLMǸ
?@abQQLGEN@]LccJG]BFS@IBGJSJNN@dGJ
FMH@RbGCSFĜ@HJeB]JN
?aELGJN@bQ@EL@fTU@JeJMEN
?@g]]LccLHFEJN@TfV@bNJG@]LHJN
FMH@bQ@EL@UfV@F]]JNN@]FGH@DLSHJGN bNBMC@WhaigjAkl
?@abQQLGEN@WXYSJP@FHHGJNNFRSJ
WhaigjAk@F]]JNN@]LMEGLS
_T@EL@[@HLLGǸ
?iIL@LMXRLFGH@MLEBd]FEBLM@_RJSS̀
]BG]bBEN@HJSBeJGBMC@Umng@o@TUW
?@gbELcFEB]@NcLpJ@HJEJ]ELG@NJMNBEBeBÊ@ cFBMEJMFM]J@EJNEBMC
?qLbGXIBGJ@NcLpJ@GJNJE@bNBMC
LMRLFGH@rU@LbEQbE@EGBCCJG
?@abQQLGEN@ĤMFcB]@NBCMFSBMC@sLG gSFGctJEl@\LccbMB]FELGN
?@abQQLGEN@hMEJGMJE@FMH@uav
FSFGc@GJQLGEBMCw
?abQQLGEN@CGFQDB]FS@bNJG@BMEJGsF]JN sLG@RbGCSFĜ@bNJ
?@abQQLGEN@xTxV\yXU@cbSEBXzA{ dGJ@pĴQFH
?zBNEJH@EL@|z[x}@~ED@AHBEBLM
?|QSLFHZHLIMSLFH@eBF@AEDJGMJEw
?@\FGRLM@cLMLPBHJ@_\�̀
KLMJ@NbQQLGE w@�DJM@bNJH@IBED@gSFGctJEl@HJeB]JNm
./01234562317/899:3675;/<3=5>32?/@2A1BC
D����%�����E��
D����F�������!�����F��� �
D�� !�G�!$���&�H��� ���E��
.I=1J=6KK6L:;/17ML16=N
6>O3:36=P/=;:6P
./Q6:?;/6:6=K/=;N>52317/R;62>=;?C
D�+S�����������%��
D�+S���!���&���H���
D����HH�T� � %
D������U���� %�!�V����
D�-��� �����H����F���
.//W>991=2?/51KK;=536:/X6=NA3=;NY/
6NN=;??6L:;/ZMI:;O[/91::37J/:119
67N/A3=;:;??/\17;?
./]6=NA3=;N/\17;?
./I=1̂3N;?/;3JX2/?2P:;/_
X6=NA3=;N/\17;?
D��+(*-�H$F��G�H�!�V���"����� !�,*
E$�%���&�� H�������� HD��$FF���H
)̀(̀����)̀��H� H��H
D��� !�G�!$���&��HH�% �E������� &
��V���%a��F������� H
D�,F����bc��U�DU����H��d��!�������H
���a�� �T� ��� ��� !��U�
�efg������h
D,F����ij��U�DU����%��HHE���d
!�������H�� �T� ����%a�
./I62;72;N/6NN=;??6L:;/ZMI:;O
91::37J/:119/2;5X71:1JP
D��$FF���H�bgj��U�DU����T� �H
F�� �H
Dk��E���F���� %����a ���%&�V��
V�H����F����HH� %
D��$F��G�H�!�E&�F� ��
Dl� �H�� !�G�!$���&��HH�% �E�����
F������� Hm� ���n����� �����$���eE���h
�$�F$������$S�����&�����&
Domjjj�V�̀���F�E����&�U��a�$���a��$H�
�V�Ha���!�!���E��
D+S�� !��p�H������ �E$H���!$��H
D+�%a��T� ��D����HH���� !�#
�SF� !�����!$��
D+�%a��T� ��D����HH�#
�SF� !�����!$��
D��� %��DT� ��H$F��G�H�!
./qr/r3?2;N/A3=;:;??/;O967?317
D�$FF���H�$F����bgs�U�����HH
T� �HpF�� �H
D�$F��G�H�!�E&��� �����V��
�a��dD� �H�% ��H
D���F���F�������� �V������ H������H
�� !�G�!$���&��HH�% �E���$F���
��%a��F������� H
D��$FF���H������������U�����HH
H��d��!�������H tuvwxywz{|}xw~yy��w��{�|w��������
����z�w���z��w�y�x�y�
.�̂;72/=;91=237J
.r156:/9=372;=/R1=/;̂;72/:1J/9=37237J
.<1KK>73562317
D����a� ���� �m�k���� !���
����$ �������H$FF���
D���� ����F������ �!$�� %�!�U ���!
*%�* �$ !�."*!�(�/"��* (�0'".#*",� �� !"�#1���2���)�!���*--#$�*!$� %� %'--�"!�(�*"�3�2�($�*#�* (� -"�)�%%$� *#�0'$#($ .%4���'"���%��"� %, *.�.'�%4��)/���0'$#($ .%4�%����#%4� %!"$-�2*##%4�#*".�"�"�%$(� ��%�* (� )*�!�",��"�&*"���'%��� +$"� 2� !%1��
5�6��7
��87 9�7:;��<67��������=�>���� ?� �,&�##� �1��@A�
B���7��;���6�;CD
6��6��;�D776��;
E7�<��FGG2�
H��ID�;J���67:�
���K�4����?�2$ �!��F@1@�?�2*L M�*(�*�$(�0*!!�",�N.�#�!,-�O
��79;��<67�����K�4��1>��2*L� )�"��*��� �!$/�*!$� �N0�##O��$"�'$!� �'!-'!���!*#��1F�����
DPQ;����EJ:;�<7�����K�4����2*L
R����;��<67���1F��*!����K�
S���EJ:;�
96���@���'"%�&$!����� %!* (0,�#�*(�'%$ .�F@1@�?�0*!!�", TD�
�U���*!!�",�$ -'!4�*'L1�* (� �!$/�*!$� �N0�##O��$"�'$!��'!-'!%�*"�� -"�!��!�(�'%$ .������$"�'$!�-"�!��!�"%1� �##��'!-'!%�*"��-�&�"�#$2$!�(1 �-!$� *#��@�+�#!�V$!
W� �;X ��67�
�Y �6;�6 Z6��K�'0#����#�
�U67;6CD
\��G1>�
;T�79������K�]��^�M�&��-��(4� �K�]���@_���L-"�%%4��K�]��� ?$.���-��(4��K�]����� !*�!��K4�
H��ID�;B�99D�
K'*#�-�� ��#$ ���*-*0$#$!,�'%$ .� A�@GKM]�2�('#���#*"2 �!^�a�]4� $�a�]�* (������22' $�*!�"%
B�J �6�;X 96��
��b�?�L��@1Ab�c�L�@1FbK�
5�\ 7��96�����
S��7�U6;�69��;�@d��!���A�d�� N��Gd��!��>Gd�O
�e�67�� �U;�69���F�d��!�����d�� NGd��!��AGd�O
;fD9 E �:���Ag�̀?
5Wh��]��!%��"��L���(%�!���)�##�&$ .� "�i'$"�2� !%3
�������*"!��A4��#*%%���K�+$��
�������*"!�j�
�������]��K$"��!$+�
U6��:;Y �U��� kMjGl�a"*(����M��*#�]�"�* !$#�� �"�2$%�%�* (�]�"�* !$#���*)�� kMj��m�j�G�a"*(�%��4���4�
��kMFjA�a"*(�%��4������#$����� ��!�
��kM�j@m ���>��M��*#4��� !"*#�� �!*!$� �* (�̀�2�!���!*!$� kMl�A
�� mkM���FG@�n��� !"*#�* (� ]� $!�"$ .��!*!$� ��'".#*"��#*"2�k $!
�� mkM���A�>�n��� !"*#�k $!�)�"��$"�� �#*"2��,%!�2%
��� mkM���FGF�n�M��*#��'".#*"�� �#*"2�k $!
��� mkM���A�A�n��'($0#�� opqrstuvwxyz{ouvwxyztv| �����^���22�"�$*#��*"!$!$� �(��$"��* (��'".#*",��#*"2��� !"�#��* �#
./012/345/678393:1/0;4<86=
�?����@�$#A#
B�������(�CD���EAE
�F�##FGAHFEA$�
I3J4K3J/418L3JKMN138
?&!O&)CP
QRSTUVWXY Z[\\]̂_̀abcd̀̂]caefcgâh̀h̀[e]fciĵkbâlcmbâ\cZ[eĥ[bcgae]bcnopcq[f]b
QRSTUVWYXSr Z[\\]̂_̀abcd̀̂]caefcgâh̀h̀[e]fciĵkbâlcmbâ\cZ[eĥ[bcgae]bcospcq[f]b t<u5vwxyzI{|}txyzI{|wy~
>?B ���)��O�!O���)>O�
G�G#>&F��F�&����������
G�G#�F��*�'���
A�#A�F�&��� �B��*��(���*�������>�
A�#A>��F�����
H���������
H���-�&����������
G��#��F�� A�##�B�
O��
P����@
H�A#B �F�
H�A#B �F�
�A�#�¦�¦����� ���O�'��F§����O@��� B��*��
A�#��C����'���&��� �̈����B��*��
A�#��C��>��
�����O@�������B��*��
A�$#�C�&������ �����B��*���F
�A�$��C�����A�$��C ����F§���� O@�������B��*��
¢�¡����©����¤���ª��������� �¤����
A�$E�O@�������) �������B��*��
�������B��*��
�H�$��!�
H�$��!��
¢�¡����¡�������ª�«����¤����������
�$$�B¬
)��H##�C
�!�EH##�C
A$�$�CF�-
A$AA�CF�-
A$H$�C
�P�G�H�C
®̄ �������°±¢�²��
?������*�+��³������� $�A��
H�#����F� ���������������� ��-����
H�#G���F� ���������������� ��
H�#$�F�������
H��E>��F�������
H�G$�F�-���F¦������
H���OC->�F�&��&�������
H���-�F�&��&�������
�)����OD���F ��@�́�����
�+��µ�
�)����ODF��������������
�)����ODFO¬�O@���
E�AH�FOC��F�)��������)��������
E�AHP�B�F�!�'�����>���*����
E�AH�FP�B�F�)������������!�'�����
P�B>���P�B>��F�>��������������� �́�����������+��µ
) P�BF! �)������������!�'�����>���*����
BO�
>�C�¦�>���#A�¶�>����������� B��������'����������*�'����������¦���
>�C�¦�>��H�E�¶�>�������¦�������������
�>�C�¦�>���#��¶��������*�'�����
>�C�¦�>��H�H�¶��*��+�����'����
'()*+,-./-01+-230+40+5-26**.47-*662-0+8146*679-0130-*.0+:3**9-5+;4+/-2:.8+-345-2+:<6:=348+-
64-3-/.=2*+-23.:-6<->.:+/?
@9-A/.47-0>6->.:+/-.4/0+35-6<-<6A:B-'()*+,-6<<+:/-/.74.;8340-35C34037+/-6C+:-16=+-
:A4->.:.47-6:-01+-864C+40.643*-<6A:(>.:+-=A*0.2*+,D2:6C.5.47-+8646=.83*-+,234/.64-
6<-2+:.21+:3*-5+C.8+/-345-26.40-.5+40.;830.64-06-96A:-8+40:3*-=64.06:.47-/030.64?
E���F�G
H���%���I&���
J.48+-+381-'()*+,-/+4/6:-834-K+-.4/03**+5-A/.47-0>6->.:+/-<6:-26>+:-345-5303D
.48*A5.47-+,./0.47->.:.47-.4-=349-83/+/D86/0/-3:+-/AK/0340.3**9-:+5A8+5?-
H���%���L&M���I&���NO� &�
'()*+,-5+C.8+/-5:3>-=.4.=3*-3=6A40/-6<-8A::+40B-=.4.=.P.47-01+-4++5-<6:-3A,.*.3:9-
26>+:-/A22*.+/?-
Q���R�"%%����������� S %�� &������H��O&���
)6.40-TU-3**6>/-96A-06-VA.8W*9-345-+3/.*9-2.426.40-01+-/6A:8+-6<-3*3:=-6:-0:6AK*+-
<:6=-01+-W+9235-345-86==A4.830+-01+-.4<6:=30.64-06-01+-2:62+:-3A016:.0.+/D345-
*+0/-96A-K923//-2:60+80.64-30-349-/2+8.;8-26.40?-
H���%���� N��������#&�
'()*+,-6<<+:/-3-*3K6:-345-0.=+(/3C.47-=3.40+4348+-<+30A:+-0130-7.C+/-96A-01+-3K.*.09-
06-5.3746/+-345-2.426.40-5+<+80/?-X/-3-:+/A*0B-.4/03**30.64-345-/+:C.8+-2:6<+//.643*/-
834-3::.C+-30-01+-/.0+-3*:+359-W46>.47-01+-+,380-*6830.64-6<-01+-2:6K*+=?-J+:C.8+-
83**/-K+86=+-=A81-=6:+-+<;8.+40B-/3C.47-96A-01+-0.=+-345-*3K6:-86/0/-3//68.30+5-
>.01-:+2+30-C./.0/?-
H���%���Y� ������%��I&���
'()*+,-834-.4.0.30+-<A480.643*-/=6W+-5+0+806:-0+/0.47-<:6=-3-'TJZX([\]@B-'TJZX(
\̂_]@)-6:-'TJZX(\̀ a]@)-/+:.+/-/9/0+=-W+9235D3A06=30.83**9-*677.47-:+/A*0/-
*683**9-345-/+45.47-01+=-06-3-=64.06:.47-8+40+:?-Z1./-5:3/0.83**9-:+5A8+/-/9/0+=-
=3.40+4348+-86/0/->1+4-344A3*-0+/0/-6:-.4/2+80.64/-3:+-2+:<6:=+5?
Z1+-b64+9>+**-b6=+-'()*+,-355:+//3K*+-0+8146*679-6<<+:/-=349-4+>-345-+,8.0.47-
.446C30.64/->1.*+-<A**9-/A226:0.47-+,./0.47-355:+//3K*+-*662-2:65A80/?-c6Ad**-
+,2+:.+48+-+<;8.+48.+/-.4-.4/03**30.64-345-:+*.3K.*.09-0130->.**-355-A2-VA.8W*9-64-96A:-
K6006=-*.4+?-@+7.4-+,2+:.+48.47-01+-'()*+,-35C34037+-06539e
���-.//*#+�0"+/.1+'*+/��
.+2�3.//*#+�,4.31+5�
/4#"654�789.+2��
'10#":.;*�
/*04+")"5<
@ �75(�,*)*0/.>)*��
3*/�1''6+1/<�:1/4�
"3/1"+.)�)*+,�
ABC��D
ABC���
���E�
�F������E���E
�G�H� ����E���
��� &I�JKL�M*./6#*,�
%&� NOP QNR(�4*./�
SB
B��
�TT����UV��
�W��F�UT
����UE�
���X655*2�.)6'1+6'�
4"6,1+5�.+2�
.2Y6,/.>)*�Z�>#.0[*/�
/<3*�'.5+*/
���J/.+2.#2�5.3\��
��L.'3*#
SABC��DŜ BC��
��E���G���U�_��
�T���
���a.[*,�.+<�
4.#2:1#*2�2*;10*� b8-)*c�#*.2<
���961)/81+�,*#1.)�
+6'>*#��
M"#�.22#*,,1+5
���d+*�,63*#;1,*2=�"+*�
6+,63*#;1,*2�e"+*
���$=�@$=�f$�)>,�%$=�&f=�
�g�75(�,*)*0/.>)*�
3*/�1''6+1/<�:1/4�
"3/1"+.)�)*+, ĥB�� i��T_̀ �j��EF
��O6))<�,63*#;1,*2
���X*,*/�[*<�M"#�/*,/1+5�
.+2�#*,*/�"M�.).#'
���J/.1+)*,,�,/**)�
3#"/*0/1;*�0";*#
SBCB��
�TT����UV��
�_�kUE�
����UE�
���L#.21/1"+.)�l�Im��,/<)*�
:1/4�,+.3�"+��
0";*#�/"�0"+0*.)�
'"6+/1+5�,0#*:, ���J/.+2.#2�5.3\��
&n? ]�%�?''(
��� !�%&n '(�RZ�))��
Y.0[*/*2�0.>)*
SAB���
�j� o���
��G��� ��T_��
���Kp-�,:1/04�
3#"5#.''.>)*
���Z*M/�q"+*8rdZX��
,63*#;1,*2=�"3*+�
"#�0)",*2�01#061/�
���X154/�q"+*8
6+,63*#;1,*2=�0)",*2�
01#061/�,*+,"#, stAĥ s���t_U�Tu
���O)*cR"#*�,15+.)��
3#"0*,,"#
��J*)*0/.>)*�,*+,1/1;1/<
���r.,<�1+,/.))./1"+�
:1/4�Ov8Q$&�L*,/*#
���w"�'1+1'6'�#.+5*
��? !�%Ing'(�'.c�#.+5*
SABA���xi
��E����T
���&P?]�%&?nQ''(��
21.'*/*#�0.,*
���J/.+2.#2�5.3\��
QPf]�%??''(
���-#"5#.''.>)*�
#*0*,,*2�0"+/.0/�:1/4�
>61)/81+�X-a�%X*'"/*�
-"1+/�a"26)*(
���y),"�.;.1).>)*�:1/4��
,/**)�2""#�.2.3/*#
SA�A��
���Uz ��T_��
���O"#'�R�0"+/.0/,�#./*2�
./�?y=�?fbyRwKR�:1/4�
0"+/.0/�,63*#;1,1"+
���d+*�0).,,�9�9P,/<)*�9� rdZX�,63*#;1,*2�.6cn�
1+36/�e"+*
���d3*#./1+5�.+2�3":*#�
.+2�0"''6+10./1"+�
:1/4�0"+/#")�;1.�� b8-)*c�)""3
Ŝ �{��s ���W���U�
��U�� ��U��
��̀U�T�� ��T_��
���-#";12*,�63�/"�,1c�0).,,��
9�,63*#;1,*2�e"+*,�
.+2�0"+;*#/,�/:"�
3.+*)�e"+*,�/"�0).,,�y�
,63*#;1,*2�e"+*, ����-":*#*2�M#"'�
.22#*,,.>)*�)""3�"#�KR�
3":*#�,633)<
���J*#1.)�+6'>*#�
.22#*,,1+5�;1.�Kp-�
,:1/04
Ŝ B
�����T�� ��T_��
���p,")./*,�.+2�3#"/*0/,�
21MM*#*+/�.#*.,�"M��
3#"/*0/1"+
��rc/*+2,�)""3�21,/.+0*
���J*3.#./*�KR�1+36/=�+"�
)""3�06##*+/�2#.1+
Ŝ �{�� ���W���U�
��~F� o��� ��G���
��T_��
���X*'"/*�*c3.+,1"+�� e"+*��'"26)*
���J633"#/,�,*#1.)��
+6'>*#�.33)10./1"+
| � | �� | ||
| � | ������� | ������������� | ���� |
./012/345/678393:1/0;4<86=
��@� ��A ��B�
C��-����� DE
FBF
GH��GIB�GFB��
J3K4L3K/418M3KLNO138
PQRSTUVW
TXXYZZ[\]̂ _̀]a
D�*� '�! �$� b!��+�' $�� �$���' $�� $����� ���" ��
�-� ' "�#� '�! ���"$�� $ ��?�,c ��##� ��$� ���! �"'
�'�"�#� ���"$d�' #$A�#�e�� ���! �"' ��-��"#��"�
$�� ( � ��"��"��� ��"� $ ������ �'�"�#� E�! �$� �%%�
G
$�� $ !��b!� ��#&��$"��� �% ���! �"' $�� $�����
���" �� %�$"! ��f g , #� $�� ���$ #� ���! �"' �'�"�# *�"� $����� �$ � g >��-�����"�' ������"� "� "�� �G���A &!� g � $�+� �#���'�� ��� ��" ' $�� ���+��!����+� ��� � g ���" ��"� $����� &$��� �� h�& %!��"���� "�#� � ���$"��� g �-��"� �$� &� ��� ��� "� "�� ��?�, �-��" ���i
PjkVlmPRQ
PnjaYo[Rp]̀_[QZ]aq_]̀ g ��"��"� $�� ����$"�� ������� ���� & $����� *�"� g >$� &� !��� "� ����$"� &! ��$ ' ��-���� % �# ( � ��-����� g ��� �����$"� ��!��� " �!&������"��� "�#� $�� g ��*� �� �� ��"�' % �# "�� �G���A "*�G*� � ������� ���� g >$� &� ��$��� �� $�' #$h� � #��� & $��� �� $�'
Serialized Eight Zone Remote Point Module
4208SN
The 4208SN Remote Point Module (RPM) is an eight-zone expander that allows the use of available expansion zones on
ADEMCO controls that support V-Plex polling loop devices.
• Can be used on controls that support up to 250 zones
• Can be optionally powered from an external DC power supply to reduce the amount of current draw from the polling loop
• Uniquely identifies eight EOLR supervised zones (all zones use 10K resistors, supplied)
• Each zone is identified by a unique serial number, which is assigned via on-board DIP Switches
• Detects faults on all zones within 400ms of occurrence
• Loops A & B can be programmed for fast (10ms) response
• Provides cover tamper protection, which may be enabled or disabled via on-board DIP Switches
FEATURES
Physical
• 6-7/16”W X 4-1/4”H X 1-1/4” D 163mm x 108mm x 32mm
Electrical
Polling Loop Voltage
• 11V nominal; 8.7 - 14VDC range Current
• 33.6mA when polling loop provides power to module, 0.6mA when 12VDC input provides power to module. See chart below.
12VDC Input Voltage
• 12V nominal; 9.4 - 14VDC range
Expander Sensor Loop Response
• Slow: 400msec (all loops)
• Fast: 10msec (option for loops A and B) Expander Sensor Loop Current
• 0.52mA (normal)
• 1.3mA (shorted) NOTE: These currents apply when polling loop input = 11VDC and 10VDC input is not connected to external supply
Sensor Loop Max. Resistance
• Up to 300 ohms of wire resistance +
10K EOLR
Agency Listings
• UL 985 Household Fire
• UL 1023 Household Burglary
• UL 609 Commercial Burglary
• UL 864 Commercial Fire
• CSFM
• FM (Pending)
• CUL
• CE (requires #N6361)
SPECIFICATIONS
Power Input Source Current Draw (all zones shorted)
From Polling Loop From External Power
Polling Loop Only 33.6m AN/A
Polling Loop and 0.6mA 33mA External Power Input
For UL Listed Commercial Fire Usage:
Use N.O. contacts. Style B supervise these loops using Model #EOL 100 fire listed 10K EOLRs (purchased separately).
For UL Listed Commercial Burglary Usage:
Use N.O. or N.C. contacts.
Supervise using EOLRs supplied.
4208SN Eight Zone Expander
ORDERING
The 4208U Remote Point Module (RPM) is an eight-zone expander that allows the use of available expansion zones on
ADEMCO controls that support V-Plex polling loop devices.
• Can be optionally powered from an external DC power supply to reduce the amount of current draw from the polling loop
• Uniquely identifies eight EOLR supervised zones (all zones use 10K resistors, supplied)
• DIP Switches can be used to set zone numbers or serial numbers
• When used in the serial number mode, each serial number in the selected group can be assigned to any zone number
• Loops A & B can be programmed for fast (10msec) response
• Provides cover tamper protection, which may be enabled or disabled via on-board DIP Switches
FEATURES
Physical
• 6-7/16” W X 4-1/4”H X 1-1/4”D 163mm X 108mm X 32mm
Electrical
Polling Loop input:
• 7.3 - 14VDC range Current draw:
• 28.6mA max. External power and polling loop. See chart below.
External Power Input (optional):
• 12VDC @ 28mA (from control panel’s auxiliary power) Sensor Loop Response:
• Slow: 400 msec (all loops)
• Fast: 10msec (option for loops A and B) Sensor Loop Current:
• Polling loop input = 11VDC, no external power input):0.52mA (normal), 1.3mA (shorted)
Sensor Loop Max. Current:
• Up to 300 ohms of wire resistance +
10K EOLR
Agency Listings
• UL 985 Household Fire
• UL 1023 Household Burglary
• UL 609 Commercial Burglary
• UL 864 Commercial Fire
• CSFM
• FM
• CUL
• CE (requires #N6361)
SPECIFICATIONS
4208U Eight Zone Expander
ORDERING
Universal Eight Zone Remote Point Module
4208U
Power Input Source (Input Voltage: 11-14VDC)
Current Draw (all zones shorted)
From Polling Loop From External Power
Polling Loop Only 27.3mA N/A
Polling Loop and 0.6mA 33mA External Power Input
For UL Listed Commercial Fire Usage:
Use N.O. contacts. Style B supervise these loops using Model #EOL 100 fire listed 10K EOLRs (purchased separately).
For UL Listed Commercial Burglary Usage:
Use N.O. or N.C. contacts. Supervise using EOLRs supplied.
Honeywell Security & Custom Electronics PO Box 9035, Syosset, NY 11791 www.security.honeywell.com/sce
L/4208FAM/D
November 2004 ©2004 Honeywell International Inc.
| ����������� | �������������� | |
| ������� | � |
| ������������ | ���� | |
| �� | ��� |
| ����������� | ������#����� | � |
| ��� | ������ |
�*+,-*./0*123.4.5,*+6/7318
9�:��
@� "� �'�AB�;;C?C
;D���DE?�DC?>9�
F.G/H.G*/,3I.GHJK,.3
�#&����$������� ����$#��L�
MNOPQRSTUNQVRNWXSYRNZ[N\]̂ N̂_RẀRUNàWRbRUUNTRc̀dRU
MNeRdR̀cRUNXbXWfgNUQXQhUNXSTNdZSQWZbNfRUUXYRUN[WZfN\]̂ N̂eiN
TRc̀dRUgNXSTNWRjRXQUNQVRURNfRUUXYRUNQZNQVRNdZSQWZbNjXSRbNN c̀XNQVRNjẀfXWkNWRdR̀cRW
MNlZfjXQ̀mbRNàQVNXbbN\]̂ N̂_RẀRUNàWRbRUUNTRc̀dRUNN ǹSdbhT̀SYNm̀T̀WRdQ̀ZSXbNTRc̀dRUo
MNpqNWRÙTRSQ̀XbNmhWYbXWkNb̀UQRTNaVRSNhURTNàQVNZjQ̀ZSXbN
QWXSU[ZWfRWNnr̂ ŝ̂tt\roNZWNdZSÙUQsZ[sùQN\]̂ êvspqwxN n\]̂ êvNyNr̂ ŝ̂tt\ro
MNzlNjZaRWRTNàQVNXNÙPsVZhWNmXQQRWkNmXdushj
MNxXfjRWNjWZQRdQRT
!{|�}�{ �|A)�={A{!(�
�{:�A(:|~� �{:(!(:|�(<A
�� ¡¢£¤�¥¢¦§�̈ ©ª«¬���ª«���®��̄°±®��®�̄±²³�̄�́�®���²µ�������������
¦̧¢¢�·¹£ ¦¶º̈ »�¼��®½��¾²��́�®���¿�¾�®��������À�
¶�� ¦¢�̧�¥�¢¹ ¬±�́���¾²���������������ÁÂÃ�Ä�Å���°���²µ�À���»Æ�
À�À�»Æ��������°±®�ªÇÈÉ«Ê�̄µ̄���̄���³��²²�ÃËÂÌ�̄µ̄���̄
<�){�(AÍ
����»Î ��®�²�̄̄�»�́����®
��������� É®��̄°±®��®�°±®�ÏÃ�Ç�̄��²²̄�©ª«¬���ª«
����»Î�ÏÃÐÉ ����»Î����������������É®��̄°±®��®
�������À� »�́²�¼������»�¼��®½��¾²��Ñ����®µ
~L������)L)�����?L;>
�9�;>���
Ô���� ���Õ ����
������� ����������������
| ���&����� | �#�� | |
| �������������� | � |
Fire Alarm Field Devices
DF-52301:A3 • 11/4/2019 — Page 1 of 2
FCPS-24FS6(C/E)
6 Amp, 24 Volt Remote Power Supply
Power Supplies
DF-52301:A3 • D-25
The Fire•Lite FCPS-24FS6(C/E) is a compact, cost-effective, 6-amp remote power supplies with battery charger. The FCPS- 24FS6(C/E) may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may stand-alone. Primary applications include noti-fication appliance (bell) circuit (NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to sup-port 24 volt system accessories. The FCPS provides regulated and filtered 24 VDC power to four notification appliance circuits config-ured as either two Class B (Style Y) and Class A (Style Z, with ZNAC-4 option module) or four class B only. Alternately, the four out-puts may be configured as any combination of resettable/non-reset-table power outputs (optimal for powering four-wire smoke detectors. The FCPS-24FS6(C/E) also contains a battery charger capable of charging up to 7.0 AH batteries. The FCPS-24FS6C is ULC-listed.
NOTE: Unless otherwise specified, the term FCPS-24FS6 used in this document refers to the FCPS-24FS6, FCPS-24FS6C, and FCPS-
24FS6E.
Features
• UL-Listed Notification Appliance Circuit (NAC) synchronization using System Sensor®, Wheelock®, or Gentex® “Commander2” appliances
• Operates as a “sync-follower” or as a “sync-generator” (default) See note on page 2.
• Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped permanently “ON” (stand-alone mode)
• Two Class B (Style Y) or Class A (Style Z, with ZNAC-4 module) NACs (circuits 1 & 3)
• 6-amp full load output, with 3 amps maximum/circuit, in NAC expander mode (UL 864)
• 4-amp continuous output in stand-alone mode (UL 1481)
• Compatible with coded inputs; signals passed through
• Optional power-supervision relay (EOLR-1)
• In stand-alone mode, output power circuits may be configured as:
resettable, (reset line from FACP required), non-resettable, or a mix of two and two
• Fully regulated and filtered power output - optimal for powering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power
• Power-limiting technology meets UL power-limiting requirements
• Form-C normally-closed trouble relay
• Fully supervised power supply, battery, and NACs
• Selectable earth fault detection
• AC trouble report selectable for immediate 2-hour delay
• Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power)
• Requires input trigger voltage of 9 - 32 VDC
• Self-contained in compact, locking cabinet - 15”H x 14.5”W x 2.75”D (cm: 38.1H x 36.83W x 6.985D)
• Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batteries
• Battery charger may be disabled via DIP switch for applications requiring larger batteries
• Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1mm2) wire
Specifications Primary (AC) Power:
• FCPS-24FS6/C: 120 VAC, 60 Hz, 3.2A maximum
• FCPS-24FS6E: 240 VAC, 50 Hz, 1.6A maximum
• Wire Size: minimum #14 AWG (2.0mm2) with 600 V insulation
Control Input Circuit:
• Trigger Input Voltage: 9 to 32 VDC
• Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V)
Trouble Contact Rating: 5 A at 24 VDC
Auxiliary Power Output: Special application power 500 mA maxi-mum
Output Circuits:
• +24 VDC filtered, regulated
• 3.0 A maximum for any one circuit
• Total continuous current for all outputs (stand-alone mode):
4.0 A maximum
• Total short-term current for all outputs (NAC expander mode):
6.0 A maximum
Secondary Power (Battery) Charging Circuit:
• Supports lead-acid batteries only
• Float-charge voltage: 27.6 VDC
• Maximum current charge: 250 mA
• Maximum battery capacity: 7.0 AH
Fire•Lite® Alarms and System Sensor® are registered trademarks of Honeywell International, Inc. Wheelock® is a registered trademark of Cooper Technologies Company. Gentex® is a registered trademark of Gentex Corporation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Page 2 of 2 — DF-52301:A3 • 11/4/2019
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Country of Origin: USA
Applications Example 1: Expand notification appliance power an additional 6.0 A. Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP notification appli-ance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24-volt system power up to 4.0 A. Both resettable and non-resettable power options are available. Resettable outputs are created by connecting the resettable output from the FACP to one or both of the FCPS inputs.
Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance cir-cuits. This typically allows for mounting the FCPS at greater dis-tances* away from the FACP while expanding system architecture in various applications.
For example, an addressable control module is used to activate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS pro-vides power to the addressable control module.
*NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 10,000 feet (3,046 meters).
Sync Follower/Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24FS6 can track (i.e. “follow”) the strobe synchroni-zation timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS.
When the FCPS-24FS6 is configured (via DIP switch settings) as a “sync follower,” the FCPS’ NAC outputs track the strobe synchroni-zation pulses present at the FCPS’ sync input terminal. The pulses originate from an upstream FACP or other power supply.
When the FCPS-24FS6 is configured (via DIP switch settings) as a “sync generator,” the FCPS’ sync input terminals are not used.
Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS’ NAC outputs. In “sync generator” mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings.
Standards and Codes The FCPS-24FS6 complies with the following standards:
• NFPA 72 National Fire Alarm Code.
• UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode).
• UL 1481 Power Supplies for Fire Alarm Systems.
Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
• UL Listed: S2424, S1287
• ULC Listed: S2424
• CSFM Approved: 7315-0075:0206
• MEA: 387-94E
• FM Approved
Ordering Information FCPS-24FS6: 6.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions
FCPS-24FS6C: Same as FCPS-24FS6, ULC-listed
FCPS-24FS6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions
ZNAC-4: Class A (Style Y) NAC option module
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power
BAT-1270: Battery, 12-volt, 7.0 AH (two required)
PS-1270: Battery, 12-volt, 7.0 AH (two required)
90286: Optional module mounting kit, is required to install an addressable module on the power supply main circuit board
DN-6726:D • 4/13/2012 — Page 1 of 2
NBG-12LX
Addressable Manual Pull Station
Intelligent/Addressable Devices
DN-6726:D • H-240
The NBG-12LX Addressable Manual Pull Station co v1
.jp g
‘General The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm.
Features
• Maintenance personnel can open station for inspection and address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm.
• Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm² wire).
• Can be surface mounted (with SB-10 or SB-I/O) or semi-flush mounted. Semi-flush mount to a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box.
• Smooth dual-action design.
• Meets ADAAG controls and operating mechanisms guide-lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
maximum activation force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
• Includes Braille text on station handle.
• Optional trim ring (BG12TR).
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Up to 99 NBG-12LX stations per loop on CLIP protocol loops.
• Up to 159 NBG-12LX stations per loop on FlashScan® pro-tocol loops.
• Dual-color LED blinks green to indicate normal on FlashScan® systems.
Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish.
Specifications
• Shipping Weight: 9.6 oz. (272.15 g)
• Normal operating voltage: 24 VDC.
• Maximum SLC loop voltage: 28.0 VDC.
• Maximum SLC standby current: 375 �A.
• Maximum SLC alarm current: 5 mA.
• Temperature Range: 32°F to 120°F (0°C to 49°C)
• Relative Humidity: 10% to 93% (noncondensing)
• For use indoors in a dry location
Installation The NBG-12LX will mount semi-flush into a single-gang, dou-ble-gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O sur-face backbox. If the NBG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes).
Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word “ACTI- VATED” (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos-ing the door automatically resets the switch.
Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems).
Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a key-operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta-tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat-ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or
Page 2 of 2 — DN-6726:D • 4/13/2012
NOTIFIER® and FlashScan® are registered trademarks of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
4" (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the con-trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches.
The loop poll LED shall be clearly visible through the front of the station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm.
Product Line Information NBG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli-cations.)
NBG-12LXSP: Spanish/English labelled version.
NBG-12LXP: Portuguese labelled version.
SB-10: Surface backbox; metal.
SB-I/O: Surface backbox; plastic.
BG12TR: Optional trim ring.
17021: Keys, set of two.
NY-Plate: New York City trim plate.
Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status.
• UL/ULC Listed: S692 (listed for Canadian and non-Cana-dian applications).
• MEA: 67-02-E.
• CSFM: 7150-0028:0199.
• FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030).
• BSMI: CI313066760047.
• U.S. Coast Guard.
• Lloyd’s Register.
• FM Approved.
Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
6,632,108.
DF-52521:B1 • 4/13/2012 — Page 1 of 2 i3 Series Photoelectric Smoke Detectors
Conventional Initiating Devices
DF-52521:B1 • F-505
General System Sensor’s i³™ Series photoelectric and photoelectric/ thermal smoke detectors represent a significant advancement in conventional detection, incorporating three key features:
installation ease, intelligence, and instant inspection.
Installation ease. The i³ Series redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire-entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of backbox mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i³ Series heads plug into the base with a simple Stop-Drop ’N Lock™ action.
Intelligence. i³ Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensa-tion and smoothing algorithms, to minimize nuisance alarms, are standard in the i³ Series. When connected to the 2W-MOD loop test/maintenance module, two-wire i³ detectors are capa-ble of generating a remote maintenance signal when they need cleaning. This signal is indicated by LEDs located at the module and at the panel. To read the sensitivity of i³ detectors, the SENS-RDR is a wireless device that displays sensitivity in terms of percent-per-foot obscuration.
Instant inspection. The i³ Series provides wide-angle red and green LED indicators for instant inspection of detector condi-tion. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The “EZ Walk” loop test feature is available on two-wire i³ Series detectors when con-nected to the 2W-MOD loop test/maintenance module. The “EZ Walk” feature verifies the initiating loop wiring by providing LED status indication at each detector.
Features
• Plug-in detector line — mounting base included.
• Large wire-entry port.
• In-line terminals with SEMS screws.
• Mounts to octagonal and single-gang backboxes, 4" (101.6
mm) square backboxes, or directly to ceiling.
• Stop-Drop ’N Lock attachment to base.
• Removable detector cover and chamber for easy cleaning.
• Built-in remote maintenance signaling.
• Drift compensation and smoothing algorithms.
• Simplified sensitivity measurement.
• Wide-angle, dual-color LED indication.
• Loop testing via “EZ Walk” feature.
• Built-in test switch.
Specifications
PHYSICAL SPECIFICATIONS
Operating Temperature Range: For models 2W-B and 4W-B:
32°F to 120°F (0°C to 49°C); for thermal models 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C).
Operating Humidity Range: 0% – 95% RH, non-condensing.
Thermal Sensor: 135°F (57.2°C) fixed (models 2WT-B, 4WT-B).
Freeze Trouble: 41°F (5°C) (models 2WT-B and 4WT-B).
Sensitivity: 2.5%/foot (0.762%/meter) nominal.
Input Terminals: Utilize 14 to 22 AWG wire.
Dimensions (including base): 5.3" (134.62 mm) diameter, 2.0" inches (50.8 mm) high.
Weight: 6.3 oz. (178.6 grams).
Mounting Options: 3.5" (88.9 mm) octagonal backbox; 4" (101.6 mm) octagonal backbox; single-gang backbox; 4" (101.6 mm) square backbox with a plaster ring; or direct mount to ceiling.
ELECTRICAL SPECIFICATIONS
Operating Voltage: 12/24 V non-polarized nominal; 8.5 V minimum; 35 V maximum.
Maximum Alarm Current” For two-wire models: 130 mA lim-ited by control panel; For four-wire models: 20 mA @ 12 V, 23 mA @ 24 V.
Alarm Contact Ratings: For four-wire models: 0.5 A @ 30 VAC/VDC; not applicable for two-wire models.
LED Modes Green LED Red LED
Power Up Blink every 10 sec-onds
Blink every 10 sec-onds
Normal (Standby) Blink every 5 sec-onds
OFF
Out of Sensitivity OFF Blink every 5 sec-onds
Freeze Trouble OFF Blink every 10 sec-onds
Alarm OFF Solid ON
Power Up Sequence for LED Indication
Condition Duration
Initial LED Status Indication 80 Seconds ph o1
.jp g
Page 2 of 2 — DF-52521:B1 • 4/13/2012
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
FireLite® Alarms® is a registered trademark and i³™ and Stop-Drop ‘N Lock™ are trademarks of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Made in the U.S. A.
Architectural/Engineering Specifications Smoke detector shall be a System Sensor i³ Series model number ________, Listed to Underwriters Laboratories UL 268 Fire Protection Signaling Systems. The detector shall be a photoelectric type (models 2W-B, 4W-B) or a combination pho-toelectric/thermal (models 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3.5" (88.9 mm) and 4" (101.6 mm) octag-onal, single-gang, and 4" (101.6 mm) square backboxes with a plaster ring, or directly mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5%/foot (0.762%/meter) as measured in the UL smoke box. The detector shall be capable of auto-matically adjusting its sensitivity by means of drift compensa-tion and smoothing algorithms. The detector shall provide dual-color LED indication which blinks to indicate power-up, normal standby, out-of-sensitivity, alarm, and freeze trouble (models 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD module, two-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel, and shall provide a loop testing capa-bility to verify the circuit without testing each detector individu-ally.
Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac-tory for latest listing status.
• UL/ULC Listed: S911
• FM Approved
• CSFM: 7272-1653:152
• MEA: 290-01-E
• Maryland State Fire Marshal: Permit # 2093
Product Line Information 2W-B: Two-wire photoelectric smoke detector.
C2W-BA: Same as 2W-B, ULC listing.
2WT-B: Two-wire photoelectric smoke detector with 135°F (57.2°C) fixed thermal sensor.
C2WT-BA: Same as 2WT-B, ULC listing.
4W-B: Four-wire photoelectric smoke detector.
C4W-BA: Same as 4W-B, ULC listing.
4WT-B: Four-wire photoelectric smoke detector with 135°F (57.2°C) fixed thermal sensor.
C4WT-BA: Same as 4WT-B, ULC listing.
ACCESSORIES:
2W-MOD2: Two-wire loop test/maintenance module.
SENS-RDR: Sensitivity reader.
A77-AB2: Retrofit adapter bracket, 6.6” (167.7cm) diameter.
KIDDE® Catalog u Conventional Initiating Devices
Technology that saves lives
| Page 1 of 4 | D A T A S H E E T K85001-0589 |
| Not to be used for installation purposes. Issue 1.2 |
06-02-62
MEA
Rate Compensation Heat Detectors 302 Series
Box mount Surface Mount
Overview Series 302 heat detectors are designed for use in normal environ-ments as well as environments where the detectors are subject to weather, moisture (internal condensation), and explosive atmo-spheres. They are normally-open devices designed to close an electrical circuit upon activation. All models feature rate compen-sation and are available with either 135 °F (57.2 °C) or 194 °F (90 °C) ratings. They are self restoring, hermetically sealed, shock and corrosion resistant, and are tamperproof.
Standard Features
• Rate compensation offsets thermal lag
• Self-restoring – no manual reset required
• Explosion proof and weatherproof models available
• Weatherproof models available that do not require a special backbox
• Box mount and surface mount models available
Application Sensors rated at 135 °F (57.2 °C) will not respond to momentary temperature fluctuations less than 30 °F/minute between 60 °F (16 °C) and 100 °F (38 °C). Sensors rated at 194°F (90 °C) will not respond to momentary temperature fluctuations less than 50 °F/ minute between 60 °F (16 °C) and 150 °F (66 °C). 302 Series sen-sors should not be used in environments where conditions exceed these parameters. Do not install them in hot air ducts, in front of heaters, in paint booths that use heat to cure paint, or any other location subject to temperature fluctuation.
Sensor’s Rated Temperature
Minimum Ambient Air Temperature
Maximum Ceiling Temperature
135 °F (57.2 °C) -40 °F (-40 °C) 100 °F (38 °C) 194 °F (90 °C) -40 °F (-40 °C) 150 °F (66 °C)
The sensor's aluminum tube acts as a heat collector when sourc-es of heat radiate directly on the tube. Install these sensors out of direct sunlight and away from radiating heat sources including the direct flow from heaters and heat ducts.
| Page 2 of 4 | D A T A S H E E T K85001-0589 |
| Not to be used for installation purposes. Issue 1.2 |
Typical Wiring Black
302 Series Detectors
White
End of Line
Resistor
To control panel or next device
Electrical Rating Voltage Current
6-125 VAC 5 amps 6-25 VDC 1 amp 125 VDC 0.5 amp
Maintenance 302 Series heat sensors are low maintenance. Sensors automati-cally restore when temperatures drop below their rated tempera-tures. The accumulation of dust and dirt does not normally affect the sensors’ operation.
Testing Testing for operation is simple and can be done before or after the sensor has been installed. Heat the sensor with a hair dryer (do not use any device with an open flame to test sensors). The sen-sor should operate shortly after the hot air is applied.
Refer to NFPA 72, National Fire Alarm Code and/or the local authority having jurisdiction to determine testing frequency, record keeping, and other testing considerations.
Rate Compensation 302 Series sensors feature rate compensation, which improves performance by offsetting thermal lag, an inherent property of conventional fixed temperature heat sensors.
A slow rate of temperature rise allows the heat to penetrate the inner expansion struts. The tubular shell and the struts expand slowly until the total device has been heated to its rated tempera-ture level of 135 °F (57.2 °C) or 194 °F (90 °C). At this point, the silver contact points close and an alarm is initiated.
When subjected to a rapid rate temperature rise, there is not as much time for heat to penetrate the inner strut. However, the rapid lengthening of the shell allows the struts to come together at a lower level.
When the surrounding air temperature returns to below the rated level, the shell contracts, forcing the contacts to open, thus auto-matically resetting the sensor.
Fine silver contact
Expansion struts
High expansion sensing shell, 0.040 anodized aluminum Heat control sleeve
Setting screw Devcon hermetic seal
WARNING – Use For Property Protection Only: Heat detectors do not protect life against fire and smoke. In most fires, hazardous levels of smoke, heat and toxic gases can build up before a heat sensor would initiate an alarm. Independent studies indicate that heat sensors should only be used when property protection alone is involved. In cases where life safety is a factor, the use of smoke detectors is recommended.
Under no circumstances should heat detectors be relied upon as the sole measure to ensure fire safety. However, if they are spaced in accordance with the specifications found under Application, these sensors can contribute, within an overall fire safety program, to reducing the risk of avoid-able property losses.
When used with automatic fire suppression systems such as pre-action and deluge sprinkler systems, carbon dioxide systems, halon systems, and dry chemical systems, at least two sen-sors should be used to initiate the alarm. This is commonly referred to as cross-zoning or priority matrix zoning and is necessary to eliminate premature discharge of the system. Refer to NFPA 72 for more information.
Detector Spacing Model 302 302-AW 302-ET 302-EPM UL- Vertical Spacing (all models)
50' x 50' (15.2 x 15.2 m)
50' x 50' (15.2 x 15.2 m)
50' x 50' (15.2 x 15.2 m)
40' x 40' (12.2 x 12.2 m)
UL- Horizontal Spacing (all models)
40' x 40' (12.2 x 12.2 m)
40' x 40' (12.2 x 12.2 m)
40' x 40' (12.2 x 12.2 m)
30' x 30' (9.1 x 9.1m)
FM - Horizontal or vertical spacing.*
30' x 30' (9.1 x 9.1m)
30' x 30' (9.1 x 9.1m)
30' x 30' (9.1 x 9.1m)
Not Listed
Spacing is based on smooth ceilings that are up to 10' (3 m) high. Refer to NFPA 72 for ceilings that are not considered smooth or are higher than 10' (3 m).
* EPM models are not FM approved.
Dimensions Model ET EMP Tube Length 3" (76.2 mm) 3" (76.2 mm) Tube Diameter 0.5" (12.7 mm) 0.5" (12.7 mm) NPT Thread 0.5" (12.7 mm) 0.5" (12.7 mm)
Hex Base 1" (25.4 mm) plastic 1.25" (31.75 mm) brass
| Page 3 of 4 | D A T A S H E E T K85001-0589 |
| Not to be used for installation purposes. Issue 1.2 |
Ordering Information Interior applications Ship Wt.
302-135 Heat Detector - Rate Compensation, Interior Vertical Surface Mount FM & UL, 135 °F (57.2 °C)
For interior mounting.
0.2 lb. (0.09 kg)
302-194 Heat Detector - Rate Compensation, Interior Vertical Surface Mount FM & UL, 194°F (90 °C).
Moisture & dust proof applications Ship Wt.
302-AW-135
All-weather Heat Detector - Rate Compensation, Vertical Mounting FM & UL, 135 °F (57.2 °C)
Hermetically sealed for moisture proof or dust proof installations. Requires no special back box when the all-weather leads are properly spliced to “THW” or equivalent type wire and splices are moisture proof. For indoor or outdoor use.
0.2 lb. (0.09 kg)
302-AW-194
All-weather Heat Detector - Rate Compensation, Vertical Mounting FM & UL, 194°F (90 °C)
Moisture & dust proof applications (box mount) Ship Wt.
302-ET-135
All-weather Heat Detector - Rate Compensation, Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C). Requires STONCO27 or equivalent.
Hermetically sealed for moisture proof or dust proof installations. Requires no special back box. Has plastic hexagonal grip bushing with ½" conduit threads for attachment to threaded hub cover, or any outlet box. For indoor or outdoor use when watertight seal is required, use weatherproof box.
0.2 lb. (0.09 kg)
302-ET-194
All-weather Heat Detector - Rate Compensation, Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C). Requires STONCO27 or equivalent.
Explosion proof applications Ship Wt.
302-EPM-
Heat Detector - Rate Compensation, Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C). RequiresJALX-11 or equivalent
Explosion proof for installation in hazardous locations. Has hexagonal grip bushing with ½" conduit threads for attachment to threaded hub covers of series JL fixture fitting manufactured by Killark Electric Co., or equivalent. Must be hand tightened only. For indoor use only.
0.3 lb. (0.14 kg)
302-EPM-
Heat Detector - Rate Compensation, Explosionproof Mounting UL (not FM approved), 194°F (90 °C). RequiresJALX-11 or equivalent.
Adapter plate Ship Wt.
AP-P
Decorative white plastic adaptor plate for mounting 302 and 302-AW to any 3" outlet box or 4" octagon outlet box.
0.1 lb. (0.05 kg)
Outlet body Ship Wt.
Use with standard backboxes and covers such as those manufactured by Killark Electric Co., or equivalent.
Explosion proof outlet body Ship Wt.
JALX11 Explosion proof outlet body with cover (½" thread hubs back, four sides and cover) - Killark 3.5 lb. (1.6 kg)
Technology that saves lives
Contact us
| Phone: | 888.244.9979 (Option 4) | |
| Email: | kidde.fire@carrier.com | |
| Website: | kidde-esfire.com |
Kidde is a Carrier brand.
8985 Town Center Pkwy, Bradenton, FL 34202
© 2021 Carrier All rights reserved.
| 06-02-21Page 4 of 4 | D A T A S H E E T K85001-0589 |
| Not to be used for installation purposes. Issue 1.2 Page 25 of 64 |
Agency Listings
D4120 Duct Smoke Detector
The InnovairFlex™ Series are the only duct smoke detectors flexible enough to fit configurations from square to rectangular and everything in between.
Features
• 4-Wire Photoelectric, integrated low-flow technology
• �Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/sec)
• Versatile mounting options: square or rectangular configuration
• �Plug-in sensor offers superb false alarm immunity and the latest sensor technology
• �Broad ranges for operating temperature (–4°F to 158°F) and humidity (0% to 95% non-condensing)
• �Patented sampling tube installs from front or back of the detector with no tools required
• �Increased wiring space with a newly added ¾-inch conduit knockout
• One easy-access Test/Reset button and improved LED status
• Patented interconnect feature for multi-fan shutdown
• New high contrast terminal designations
• Built-in short circuit protection from operator wiring errors
• Field selectable settings for configuring the detector
• Two DPDT Form-C relay contacts
• 24 VAC/DC or 120 VAC
• �Backward compatibility with existing Innovair products, including remote accessories
The InnovairFlex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance.
The InnovairFlex housing provides ample wiring space, a ¾-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side).
As many as 50 InnovairFlex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source.
An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure field selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board has two LEDs that can be used to indicate the status of connected sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm).
The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring.