Product Data 2.pdf
PDF 5 MB Posted
- Solicitation number
- 36c25920q0229
About this file
This document is a solicitation for the installation of emergency eyewash stations at various Department of Veterans Affairs medical centers. The solicitation is seeking quotes to install Guardian G5026 eyewash/drench hose units, Speakman SEF-9000 service sink fittings with eyewash, and PL-G3600LF thermostatic mixing valves at multiple VA facilities located in Region 19. Quotes are due by February 29, 2022. Installation must be completed by June 30, 2022 in accordance with ANSI Z358.1 standards. The selected contractor will be responsible for providing all necessary equipment, supplies, and labor to properly install and commission the new eyewash stations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25920Q0229 0003.docx | DOCX document | |
| Description of Changes for Solicitation Amendment 200617.docx | DOCX document | |
| Drawings Rev 2_2 of 3.zip | ZIP file | |
| Product Data Rev 2.zip | ZIP file | |
| 554-21-101 Install RMR EyeWash Stations - Locations_Rev-3.xlsx | XLSX spreadsheet | |
| Drawings Rev 2_3 of 3.zip | ZIP file | |
| Drawings Rev 2_1 of 3.zip | ZIP file | |
| RFI Answers.docx | DOCX document | |
| 36C25920Q0229 0002.docx | DOCX document | |
| Cabinet Work Pictures.docx | DOCX document | |
| 55-21-101 Eyewash Specifications.pdf | ||
| Photos - Temp controlled room D2-213.zip | ZIP file | |
| Drawings 1.pdf | ||
| Drawings 3.pdf | ||
| Drawings 2.pdf | ||
| 554-21-101 Install RMR EyeWash Stations - Locations_Rev-2.pdf | ||
| Product Data 1.pdf | ||
| 36C25920Q0229_1.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ANSI / ISEA Z358.1-2014
Compliance Checklist
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
INTRODUCTION
The selection of emergency eyewash and shower equipment is often a complicated process. In addition to addressing design and engineering issues, specifiers must be aware of regulatory requirements and compliance standards.
A common reference point when selecting emergency equipment is ANSI/ISEA Z358.1, “Emergency Eyewash and Shower Equipment.” This standard is a widely accepted guideline for the proper selection, installation, operation and maintenance of emergency equipment.
To assist specifiers in understanding the provisions of this standard, Guardian Equipment has prepared this ANSI Compliance Checklist. In this Checklist, we have summarized and graphically presented the provisions of the standard.
This Checklist can serve as a starting point for designing emergency eyewash and shower systems.
LEGAL REQUIREMENTS
The Occupational Safety and Health Act of 1970 was enacted to assure that workers are provided with “safe and healthful working conditions.” Under this law, the Occupational Safety and Heath Administration (OSHA) was created and authorized to adopt safety standards and regulations to fulfill the mandate of improving worker safety.
OSHA has adopted several regulations that refer to the use of emergency eyewash and shower equipment. The primary regulation is contained in 29 CFR 1910.151, which requires that...
“...where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.”
ANSI Z358.1
The OSHA regulation regarding emergency equipment is quite vague, in that it does not define what constitutes “suitable facilities” for drenching the eyes or body. In order to provide additional guidance to employers, the American National Standards Institute (ANSI) has established a standard covering emergency eyewash and shower equipment. This standard—ANSI Z358.1—is intended to serve as a guideline for the proper design, certification, performance, installation, use and maintenance of emergency equipment. As the most comprehensive guide to emergency showers and eyewashes, it has been adopted by many governmental health and safety organizations within and outside the US, as well as the Uniform Plumbing Code (UPC) and International Plumbing Code (IPC). The ANSI standard is part of the building code in locations that have adopted the International Plumbing Code.
(IPC-Sec. 411)
ANSI Z358.1 was originally adopted in 1981. It was revised in 1990, 1998, 2004, 2009 and again in 2014. This Compliance Checklist summarizes and graphically presents the provisions of the 2014 version of the standard.
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Emergency eyewash and shower units are designed to deliver water to rinse contaminants from a user’s eyes, face or body.
As such, they are a form of first aid equipment to be used in the event of an accident. However, they are not a substitute for primary protective devices (including eye and face protection and protective clothing) or for safe procedures for handling hazardous materials.
2. LOCATION OF EMERGENCY EQUIPMENT
In general, the ANSI standard provides that emergency equipment be installed within 10 seconds walking time from the location of a hazard (approximately 55 feet) (Appendix B5). The equipment must be installed on the same level as the hazard (i.e. accessing the equipment should not require going up or down stairs or ramps). The path of travel from the hazard to the equipment should be free of obstructions and as straight as possible.
However, there are certain circumstances where these guidelines may not be adequate. Previous versions of the standard expressly provided that, where workers are handling particularly strong acids, caustics or other materials where the consequences of a spill would be very serious, emergency equipment should be installed immediately adjacent to the hazard. Although Appendix B5 of the 2014 standard briefly reviews the proper location of emergency equipment under such scenarios, we still believe the previous versions of the standard to be correct.
Laboratory environments may also require special consideration. It has been common in many laboratory buildings to install emergency equipment in a corridor or hallway outside of the lab room. Since a door is considered an obstruction, this violates the provisions of the standard.
For laboratory environments, we recommend installing (i) recessed laboratory eyewash/shower cabinets inside the lab room and (ii) dual purpose eyewash/drench hose units at lab sinks (see page 8). The recessed cabinet units are a space saving design that satisfy the standard’s requirements for both a shower and an eye/face wash, and are wheelchair accessible, while the eyewash/drench hoses provide immediate protection for the eyes, face or body when a spill involves a relatively small amount of hazardous material.
3. WATER TEMPERATURE
The 2014 version of the standard states that the water temperature delivered by emergency equipment should be ‘tepid.’ Tepid is defined to be between 60°F (16°C) and 100°F (38°C). However, in circumstances where a chemical reaction is accelerated by flushing fluid temperature, a facilities safety/health advisor should be consulted to determine the optimum water temperature for each application.
The delivery of tepid water to emergency equipment may raise complicated engineering issues. At a minimum, it generally involves providing both hot and cold water to the unit, and then installing a mixing valve to blend the water to the desired temperature. Guardian offers a variety of mixing valves and turnkey, recirculating tempering systems to provide tempered water. Please contact our office for further information.
4. SHUT OFF VALVES
Plumbed emergency equipment must be connected to a potable water supply line. It may be advisable to install a shut off valve on the water line, upstream of the unit, to facilitate maintenance of the equipment. If a shut off valve is installed, provision must be made to prevent unauthorized closure of the shut off valve. (Sections 4.1.2, 4.5.5, 5.1.6, 5.4.5, 6.1.6, 6.4.5, 8.2.3.3) Such provision can include removing the handle of the shut off valve or locking the valve in the open position.
Only maintenance personnel should be authorized to place a handle on or unlock the valve.
5. CORROSION RESISTANCE
Once connected to a water supply line, water will enter the emergency equipment and stand in the unit up to the valve(s). When activated, water will flow through the entire unit. Therefore, the unit must be constructed of materials that will not corrode when exposed to water for extended periods of time. (Sections 4.1.6, 5.1.5, 6.1.5) In addition to this general provision, the standard specifically requires that valves be resistant to corrosion. (Sections 4.2, 5.2, 6.2, 8.2.2) Emergency equipment should therefore be constructed of materials that will resist rusting and corrosion. Materials that are considered
GENERAL CONSIDERATIONS
ANSI Z358.1- 2014 contains provisions regarding the design, certification, performance, installation, use and maintenance of various types of emergency equipment (showers, eyewashes, drench hoses, etc.). In addition to the provisions in the standard, there are additional considerations that are not part of the standard. We believe that these considerations should also be addressed when considering emergency equipment. These include the following:
1. FIRST AID DEVICES
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
acceptable for this purpose include brass, galvanized steel and many types of plastics (ABS, nylon, etc.). However, these materials may not provide durable service when exposed to harsh industrial conditions, may deteriorate in direct sunlight or be subject to other limitations. Therefore, for maximum durability, the following materials should also be considered:
• Epoxy coated galvanized steel
• Epoxy coated brass
• Stainless steel
• PVC
6. FREEZING
There are many applications where emergency equipment must be installed in areas that are subject to freezing conditions. Such areas may include any type of outdoor area (bulk material handling facility, tank farm, etc.), as well as some interior areas (loading docks, low temperature facilities, etc.). In these cases, the emergency equipment must be protected against freezing (Sections 4.5.5, 5.4.5, 6.4.5, 7.4.4, 8.2.3.3). Equipment that is designed and manufactured to be freeze-resistant should be installed. There are a number of different types of freeze-resistant equipment, including:
• Units that have a temperature actuated bleed valve that permits water to flow through the unit when the temperature drops below freezing. These units are generally used only where the possibility of freezing is very infrequent.
• Units on which the valve is mounted behind a wall or buried below the frost line and is remote-activated.
• Combination units that are electrically heated (heat-traced) and insulated.
• Units that have a heated enclosure to fully contain and protect both the equipment and the user.
7. DISPOSAL OF WATER
The standard does not include any specific provisions regarding the disposal of waste water (Appendix A3).
However, designers must give consideration to where waste water will go. In particular, care must be taken that waste water not create a hazard (i.e. by creating a pool in which someone might slip) or freeze.
Generally, Guardian eyewash, eye/face wash and safety station units are designed with waste connections for connection to drain piping. WE RECOMMEND THAT EMERGENCY
EYEWASH AND SHOWER UNITS BE CONNECTED TO DRAIN
PIPING. FOR EMERGENCY SHOWERS AND FOR OTHER UNITS
WITHOUT WASTE CONNECTIONS, FLOOR DRAINS SHOULD
BE PROVIDED.
After an emergency eyewash or shower unit has been used, the waste water may contain hazardous materials that cannot or should not be introduced into a sanitary sewer. It may be necessary to connect the drain piping from the emergency equipment or floor drain to the building’s acid waste disposal system or to a neutralizing tank.
8. EMERGENCY RESPONSE
Simply installing emergency equipment is not sufficient to assure worker safety. Employees must be trained in the location of emergency equipment and in its proper use. Emergency equipment must be regularly maintained (including weekly activation of the equipment) to assure that it is in working order and inspected at least annually for compliance with the standard. Most importantly, employers should develop a response plan to be used in the event that an accident does occur. The focus of the response plan should be to provide assistance to the injured worker as quickly as possible.
Guardian offers a variety of alarm systems that may be installed in conjunction with our emergency equipment. They serve to alert personnel and summon assistance if an eyewash or shower is activated. WE RECOMMEND INSTALLING AN
ALARM UNIT WITH ANY EMERGENCY EYEWASH OR SHOWER
UNIT.
9. O&M INFORMATION
Under the standard, the manufacturer of the emergency equipment must provide detailed instructions on the proper operation, inspection and maintenance of the emergency equipment. (Sections 4.6.1, 5.5.1, 6.5.1, 7.5.1, 8.2.4.1) This information should be accessible to maintenance personnel. Guardian offers detailed installation, operation and maintenance guides for its equipment. These guides are available on the Guardian website (gesafety.com) and from our sales representatives.
Note: This ANSI Compliance Checklist is intended to assist design personnel, facility owners and others in selecting, specifying, installing and maintaining emergency equipment. We have tried to assure that it is comprehensive and accurate. However, please refer to the complete ANSI/ISEA Z358.1-2014 standard before purchasing or installing emergency equipment. Guardian Equipment cannot be responsible for any errors or omissions from this Checklist, and cannot assure that any particular product will perform satisfactorily in any particular application.
F Location: Install shower within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path. Where strong acids or caustics are being handled, emergency showers should be located adjacent to the hazard, and an appropriate professional should be consulted for advice on the proper distance. (Section 4.5.2; B5)
F Identification: Identify shower location with highly visible sign. Area around shower shall be well-lit. (Section 4.5.3)
F Water Temperature: Water delivered by shower shall be tepid (60-100°F). (Section 4.5.6; B6)
F Training: Instruct all employees in the location and proper use of emergency showers. (Section 4.6.4)
F Maintenance/Inspection: Activate plumbed shower at least weekly. (Section 4.6.2) Inspect all emergency showers annually for compliance with standard. (Section 4.6.5)
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Emergency Showers This checklist is a summary of the provisions of ANSI Z358.1-2014 relating to emergency showers. Please refer to the standard for a complete listing of these provisions.
All Guardian emergency showers are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
F Water supply is sufficient to provide at least 20 GPM for 15 minutes. (Section 4.1.2, 4.5.5)
F Hands-free valve activates in one second or less and remains open until manually closed. (Section 4.2, 4.1.5)
F Shower delivers 20 gallons (75.7 liters) of water per minute for 15 minutes in the required pattern. (Section 4.1.2, 4.5.5)
F Height of water column is between 82” (208.3 cm) and 96” (243.8 cm) above the floor. (Section 4.1.3, 4.5.4)
F Center of the water pattern is at least 16” (40.6 cm) from any obstruction. (Section 4.1.4, 4.5.4)
F Easily located, accessible actuator is no more than 69” (173.3 cm) above floor.
(Section 4.2)
F At 60” (152.4 cm) above the floor, the water pattern is at least 20” (50.8 cm) in diameter.
(Section 4.1.4)
F If provided, shower enclosure has a minimum diameter of 34” (86.4 cm).
(Section 4.3)
82-96" above floor
60" above floor
Ø20" water pattern
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Eye/Face Washes This checklist is a summary of the provisions of ANSI Z358.1-2014 relating to emergency eye/face washes. Please refer to the standard for a complete listing of these provisions.
All Guardian eye/face wash units are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
F Controlled, low velocity flow completely rinses eyes and face and is not injurious to user. (Section 6.1.1)
F Water flow is sufficiently high to allow user to hold eyes open while rinsing. (Section 6.1.7)
F Spray heads are protected from airborne contaminants. Covers are removed by water flow.
(Section 6.1.3)
F Unit delivers at least 3.0 gallons (11.4 liters) of water per minute for 15 minutes. (Section 6.1.6, 6.4.5)
F Water flow pattern is positioned between 33” (83.8
cm) and 53” (134.6 cm) from the floor and at least 6” (15.3 cm) from the wall or nearest obstruction.
(Section 6.4.4)
F Hands-free stay-open valve activates in one second or less. (Section 6.1.4, 6.2)
F Valve actuator is easy to locate and readily accessible to user. (Section 6.2)
F Unit washes both eyes simultaneously. Water flow covers area indicated on Guardian test gauge at no more than 8” above spray heads. (Section 6.1.8)
3.25” (83mm)
1.25” (32mm)
33-53" above floor
F Location: Install eye/face wash unit within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path. Where strong acids or caustics are being handled, emergency eye/face wash units should be located adjacent to the hazard, and an appropriate professional should be consulted for advice on the proper distance. (Section 6.4.2; B5)
F Identification: Identify eye/face wash location with highly visible sign. Area around eye/face wash unit shall be well-lit. (Section 6.4.3)
F Water Temperature: Water delivered by eye/face wash shall be tepid (60-100°F). (Section 6.4.6; B6)
F Training: Instruct all employees in the location and proper use of eye/face wash units. (Section 6.5.4)
F Maintenance/Inspection: Activate plumbed eye/face wash units at least weekly. (Section 6.5.2) Inspect all eye/face wash units annually for compliance with standard. (Section 6.5.5)
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Eyewashes This checklist is a summary of the provisions of ANSI Z358.1-2014 relating to emergency eyewashes. Please refer to the standard for a complete listing of these provisions.
All Guardian eyewash units are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
F Controlled, low velocity flow rinses both eyes and is not injurious to user. (Section 5.1.1)
F Water flow is sufficiently high to allow user to hold eyes open while rinsing. (Section 5.1.7)
F Spray heads are protected from airborne contaminants. Covers are removed by water flow.
(Section 5.1.3)
F Unit delivers at least 0.4 gallons (1.5 liters) of water per minute for 15 minutes. (Section 5.1.6, 5.4.5)
F Water flow pattern is positioned between 33” (83.8
cm) and 53” (134.6 cm) from the floor and at least 6” (15.3 cm) from the wall or nearest obstruction.
(Section 5.4.4)
F Hands-free stay-open valve activates in one second or less. (Section 5.1.4, 5.2)
F Valve actuator is easy to locate and readily accessible to user. (Section 5.2)
F Unit washes both eyes simultaneously. Water flow covers area indicated on Guardian test gauge at no more than 8” above spray heads. (Section 5.1.8)
3.25” (83mm)
1.25” (32mm)
F Location: Install eyewash unit within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path. Where strong acids or caustics are being handled, emergency eyewash unit should be located adjacent to the hazard, and an appropriate professional should be consulted for advice on the proper distance. (Section 5.4.2; B5)
F Identification: Identify eyewash location with highly visible sign. Area around eyewash unit shall be well-lit. (Section 5.4.3)
F Water Temperature: Water delivered by eyewash shall be tepid (60-100°F). (Section 5.4.6; B6)
F Training: Instruct all employees in the location and proper use of eyewash units. (Section 5.5.4)
F Maintenance/Inspection: Activate plumbed eyewash units at least weekly. (Section 5.5.2) Inspect all eyewash units annually for compliance with standard. (Section 5.5.5)
33-53" above floor
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Eyewash/Drench Hose Units ANSI Standard Z358.1-2014 states that drench hose units may supplement, but may not be used in place of dedicated eyewash units. Guardian offers a series of units that meet the provisions of the ANSI standard as both an eyewash and a drench hose.
These dual purpose units can be used to combine an eyewash and a drench hose into a single versatile, economic unit.
This checklist summarizes the provisions of ANSI Z358.1-2014 for both eyewashes and drench hoses. Please refer to the standard for a complete listing of these provisions.
All Guardian eyewash/drench hose units are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
F Water flow is sufficiently high to allow user to hold eyes open while rinsing. (Section 5.1.7)
F Spray heads are protected from airborne contaminants. Covers are removed by water flow. (Section 5.1.3)
F Controlled, low velocity flow rinses both eyes and is not injurious to user. (Section 5.1.1, 8.2.1)
F Unit delivers at least 0.4 gallons (1.5 liters) of water per minute for 15 minutes. (Section 5.1.6)
F Hands-free stay-open valve activates in one second or less. (Section 5.2, 8.2.2)
F Valve actuator is easy to locate and readily accessible to user. (Section 5.2, 8.2.2)
F Water flow pattern is positioned between 33” (83.8 cm) and 53” (134.6 cm) from the floor and at least 6” (15.3 cm) from the wall or nearest obstruction. (Section 5.4.4)
F Unit washes both eyes simultaneously. Water flow covers area indicated on Guardian test gauge at no more than 8” above spray heads.
(Section 5.1.8)
F Location: Install eyewash/drench hose unit within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path. Where strong acids or caustics are being handled, emergency eyewash/drench hose unit should be located adjacent to the hazard, and an appropriate professional should be consulted for advice on the proper distance. (Section 5.4.2; B5)
F Identification: Identify eyewash/drench hose location with highly visible sign. Area around eyewash/drench hose unit shall be well-lit. (Section 5.4.3, 8.2.3.2)
F Water Temperature: Water delivered by eyewash/drench hose unit shall be tepid (60-100°F). (Section 5.4.6, 8.2.3.4; B6)
F Training: Instruct all employees in the location and proper use of eyewash/drench hose units. (Section 5.5.4, 8.2.4.4)
F Maintenance/Inspection: Activate eyewash/drench hose units at least weekly. (Section 5.5.2, 8.2.4.2) Inspect all eyewash/drench hose units annually for compliance with standard. (Section 5.5.5, 8.2.4.5)
33-53" above floor
3.25” (83mm)
1.25” (32mm)
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Drench Hose Units Under ANSI Z358.1-2014, drench hose units support plumbed and self-contained emergency eyewash and shower units, but cannot replace them. In other words, drench hoses are intended solely as supplemental equipment providing additional protection to personnel.
Drench hoses are useful in cases where the user is in a prone position or where it is necessary to reach areas of the face and body inaccessible to the fixed stream of a shower or eyewash unit. They are also advantageous in areas (such as laboratories) where they can be installed close to where accidents might occur.
This checklist summarizes the provisions of ANSI Z358.1-2014 relating to drench hoses. Please refer to the standard for a complete listing of these provisions.
All Guardian drench hose units are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
F Drench hose unit supplements shower and eyewash units installed in vicinity. (Section 8)
F Controlled, low velocity flow is not injurious to user. (Section 8.2.1)
F Valve goes from ‘off’ to ‘on’ in one second or less. (Section 8.2.2)
F Valve actuator is easy to locate and readily accessible to the user. (Section 8.2.2)
F Location: Install drench hose unit in area free of debris or obstructions. (Section 8.2.3.2)
F Identification: Identify drench hose unit with highly visible sign. Area around drench hose unit shall be well-lit. (Section 8.2.3.2)
F Water Temperature: Water delivered by drench hose unit shall be tepid (60-100°F). (Section 8.2.3.4)
F Training: Instruct all employees in the location and proper use of drench hose units. (Section 8.2.4.4)
F Maintenance/Inspection: Activate drench hose units at least weekly. (Section 8.2.4.2) Inspect all drench hose units annually for compliance with standard. (Section 8.2.4.5)
F Location: Install safety station within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path. Where strong acids or caustics are being handled, safety station should be located adjacent to the hazard, and an appropriate professional should be consulted for advice on the proper distance. (Section 7.4.2; B5)
F Identification: Identify safety station location with highly visible sign. Area around safety station shall be well-lit. (Section 7.4.3)
F Water Temperature: Water delivered by safety station shall be tepid (60-100°F). (Section 7.4.5; B6)
F Training: Instruct all employees in the location and proper use of safety station. (Section 7.5.4)
F Maintenance/Inspection: Activate safety station at least weekly. (Section 7.5.2) Inspect all safety stations annually for compliance with standard. (Section 7.5.5)
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Safety Stations This checklist is a summary of the provisions of ANSI Z358.1-2014 relating to eye or eye/face wash and shower combination stations.
Please refer to the standard for a complete listing of these provisions.
All Guardian safety stations are third-party certified to meet or exceed the provisions of ANSI Z358.1-2014.
33-53" above floor
Ø20" water patern
60" above floor
82"-96" above floor
F Water supply delivers required flow when shower and eye or eye/face wash are operated simultaneously.
(Section 4.5.5, 7.4.4)
F Hands-free stay-open valve activates in one second or less. (Section 4.2)
F Height of water column is between 82” (208.3 cm) and 96” (243.8 cm) above the floor. (Section 4.1.3, 4.5.4)
F Shower delivers 20 gallons (75.7 liters) of water per minute for 15 minutes in the required pattern.
(Section 4.1.2, 4.5.5)
F Easily located, accessible actuator is no more than 69” (173.3 cm) above floor. (Section 4.2)
F Center of the water pattern is at least 16” (40.6 cm) from any obstruction. (Section 4.1.4, 4.5.4)
F At 60” (152.4 cm) above the floor, the water pattern is at least 20” (50.8 cm) in diameter. (Section 4.1.4)
F Spray heads are protected from airborne contaminants.
Covers are removed by water flow. (Section 5.1.3, 6.1.3)
F Unit delivers at least 3.0 GPM (11.4 liters) (for eye/face wash) or 0.4 GPM (1.5 liters) (for eyewash) for 15 minutes.
(Section 5.1.6, 6.1.6, 6.4.5)
F Hands-free stay-open valve activates in one second or less. (Section 5.2, 6.1.4, 6.2)
F Valve actuator is easy to locate and readily accessible to user. (Section 5.2, 6.2)
F Water flow pattern is positioned between 33” (83.8 cm) and 53” (134.6 cm) from the floor and at least 6” (15.3
cm) from the wall or nearest obstruction.
(Section 5.4.4, 6.4.4)
1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone
312 447 8101 facsimile gesafety.com
ANSI / ISEA Z358.1 Compliance Checklist
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Barrier-Free Equipment The Americans with Disabilities Act (ADA) requires that employers provide accessible workplaces for all employees. These workplaces may therefore require emergency eyewash and shower equipment that is specially constructed for wheelchair accessibility.
Barrier-free emergency equipment must comply with the provisions of ANSI A117.1-2009 (“Accessible and Usable Buildings and Facilities”). These provisions include dimensions for minimum knee clearance, maximum height and reach, and minimum distance from obstructions.
Guardian offers an array of eyewash and shower units designed for barrier-free applications. These units meet the provisions of ANSI Z358.1-2014 for emergency equipment and the accessibility provisions of ANSI A117.1-2009. The provisions of ANSI Z358.1- 2014 are summarized on pages 2-10. The additional accessibility provisions of ANSI A117.1-2009 are shown here. Please refer to the standards for a complete description of these provisions.
Minimum clear floor space requirements for forward approach
(top view)
82-96" clear headroom
Spray heads 15" minimum from wall or obstruction
48” maximum height for forward reach
27” minimum knee clearance underneath unit
36” maximum height to spray heads
48"
30"
Safe workplaces demand advanced emergency eyewash and shower equipment. Guardian is proud to offer the most complete selection of emergency equipment designed for today’s industrial applications.
Characterized by enhanced performance and superior durability, all Guardian products feature the latest innovations in spray head technology. The unique GS-Plus™ and FS-
Plus™ spray heads deliver water in a soft, wide spray rather than a solid, narrow stream. The user receives more water over a wider area than with any other type of outlet head. In an emergency, contaminants are flushed away quickly, gently, and completely.
These heads incorporate a variety of unique and important features:
CONSISTENT, BALANCED FLOW
An engineered flow control located inside each spray head is calibrated to deliver 1.8 (GS-Plus™) or 3.2 (FS-Plus™) gallons per minute, at pressures from 20 to 100 PSI. The flow is consistent, and evenly balanced between the spray heads regardless of line pressure.
“FLIP TOP” DUST COVER
Each spray head is protected against dust and dirt by a “flip top” cover which nests into the top of the outlet head when equipment is not in use. Upon unit activation, water flow swings the cover off the head. The cover is permanently attached to the spray head by a stainless steel pin to prevent removal or loss.
Optional stainless steel covers are also available.
Guardian Emergency Eyewash and Shower Technology:
Engineered for today’s industrial environments.
FILTERED WATER
Each spray head contains an internal filter to remove particles and debris from the water flow. During flushing, the user’s eyes and face are protected against any potential foreign matter which may exist in the water or plumbing lines.
DURABILITY
The spray head bodies are molded from tough, impact-resistant and corrosion-resistant polypropylene, while the “flip top” dust covers are molded nylon. Both the GS-Plus™ and FS-Plus™ spray heads stand up to the harshest laboratory environments.
EASY MAINTENANCE
Water often contains dissolved minerals and foreign matter which, over time can build up and clog any spray head. The GS-Plus™ and FS-Plus™ spray heads are designed such that all working components are contained within the head itself, making cleaning and maintenance easy. Guardian’s emergency equipment should never need disassembly in the event of a clogged spray head.
Eyewash / Drench Hose Units
Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
F G5026 Eyewash/Drench Hose Unit, Wall Mounted F G5026BP Eyewash/Drench Hose Unit, Wall Mounted, with Backflow Preventer
Application: Dual purpose eyewash/drench hose for wall mounting. Unit meets the provisions of ANSI Z358.1-2014 as both an eyewash and a drench hose. Unit may be left in the mounting bracket for use as a fixed eyewash, leaving user’s hands free. Alternatively, unit may be removed for use as a drench hose to rinse any part of user’s eyes, face or body.
Spray Head Assembly: Two GS-Plus™ spray heads mounted side-by-side. Each head has a “flip top” dust cover, internal flow control and filter to remove impurities from the water flow.
Valve: Forged brass squeeze valve activated by stainless steel lever handle. Valve has replaceable stainless steel seat for exceptional durability. Locking clip engages when handle is depressed, providing “hands free” operation. Valve stays open until locking clip is released.
Hose: 8’ reinforced PVC hose. 275 PSI maximum working pressure.
Mounting: Bracket with spring clips to hold unit on wall.
Clips position spray heads and handle to face forward at all times.
Backflow Preventer: In-line dual check backflow preventer installed on inlet of hose (G5026BP only). ASSE 1024 Listed.
Note: Check with code authority for compliance with local plumbing code.
Supply: 3/8" NPT male swivel-type inlet.
Sign: ANSI-compliant identification sign.
Quality Assurance: Unit is completely assembled and water tested prior to shipment.
Available Options F FSH 8 ft. flexible stainless steel hose in place of PVC hose.
F VB In-line vacuum breaker for installation between valve and spray head.
F G3600LF Thermostatic mixing valve precisely blends hot and cold water to deliver warm (tepid) water as required by ANSI Z358.1-2014. Refer to “Tempering Valves” section for complete technical and product selection information.
THIS SPACE FOR ARCHITECT/ENGINEER APPROVAL
Due to continuing product improvement, the information contained in this document is subject to change without notice. All dimensions are ± 1/4" (6mm).
Eyewash / Drench Hose Units
Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com
Listed 8116. Units have been tested to and comply with
ANSI Z358.1-2014 and the Uniform Plumbing Code.
Emergency Eyewash/Drench Hose
Sign Included
F G5026 Eyewash/Drench Hose Unit, Wall Mounted F G5026BP Eyewash/Drench Hose Unit, Wall Mounted, with Backflow Preventer
NOTES:
1. EACH GS-PLUS™ SPRAY HEAD HAS A "FLIP-TOP" DUST COVER,
INTERNAL FLOW CONTROL AND FILTER TO REMOVE IMPURITIES
FROM THE WATER FLOW.
2. HOSE SHOULD NOT BE USED IN APPLICATIONS WHERE WATER
PRESSURE EXCEEDS 90 PSI. HOSE SHOULD BE INSPECTED
PERIODICALLY FOR DETERIORATION.
4" (102mm)
2 3/4" (70mm)
3/8" NPT MALE
SWIVEL INLET
7/8" (22mm)
(4) Ø17/64"
DETAIL "A"
MOUNTING BRACKET
1 1/2" (38mm)
(7mm) HOLES
6 1/2" (165mm)
30°
9 3/4" (248mm)
2 1/4" (57mm)
(2) GS-PLUS™
SPRAY HEADS
CHROME PLATED BRASS
SQUEEZE VALVE WITH
REPLACEABLE STAINLESS
STEEL SEAT
LOCKING CLIP
NYLON HANDLE
8' HIGH PRESSURE
REINFORCED PVC HOSE
STAINLESS STEEL
SQUEEZE HANDLE
WITH PLASTIC COVER POWDER COATED
MOUNTING BRACKET
WITH SPRING CLIPS
(SEE DETAIL 'A')
rev. 022019
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
IMPORTANT: THESE SYSTEMS ARE DESIGNED TO PROVIDE MIXED WATER
FROM 60 TO 90°F (15 TO 32°C) FOR EMERGENCY EYE OR EYE/FACE WASH
APPLICATIONS ONLY IN ACCORDANCE WITH ASSE 1071.
Installation
1. Install valve in a location where it may be easily cleaned, adjusted or repaired.
2. Inlets are clearly marked on valve body casting. Connect hot water to inlet marked "HOT" and cold water to inlet marked
"COLD."
3. Included angle checkstops must be installed on both supply lines (see above).
4. Use solder or pipe cement sparingly. Flush supply pipes before connecting valve. Flush outlet pipe and valve once valve is connected.
Maximum operating pressure is 125 PSI (860 KPA) for hot and cold water. Maximum hot to cold water pressure differential is 5%.
Note: Should piping be exposed to excessive hot or cold conditions, it may be necessary to insulate piping to prevent freezing or scalding water.
Note: Please provide valve serial number (stamped on cover of valve) when ordering parts.
Thermometer
1/2" OD Copper Tube Inlets
Cold Water Inlet
Hot Water Inlet
G3600LF
Angle Checkstop
Angle Checkstop
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
Adjustment and Service Guardian Equipment thermostatic mixing valves may be easily cleaned, adjusted and repaired. Servicing may be possible without disconnecting valve.
Note: Thermostatic water mixing valves are regulating mechanisms which must be regularly maintained to provide best performance. Local water quality and usage conditions dictate cleaning frequency. (See Maintenance Guide and Record card included with valve shipment and reference ANSI Z358.1)
1. Remove handle, retaining ring, loosen set screw, and remove stop.
2. Activate emergency fixture.
3. Replace handle and adjust to reach desired maximum temperature.
Note: Temperatures above 90°F are not recommended. Consult a medical advisor for correct temperature settings.
4. Replace stop such that it rests against the web on the left side of the cover.
5. Tighten set screw and reassemble. Hold a thermometer under water flow to verify maximum temperature has been set appropriately.
Then set desired operating temperature.
Troubleshooting
To Reset Adjustable High Temperature Limit Stop:
If installed on a circulated hot water system, verify the valve is piped according to Required Piping Method on page 3.
See page 5 for complete parts breakdown and parts kits.
WARNING: THIS THERMOSTATIC
MIXING VALVE HAS AN ADJUSTABLE
HIGH TEMPERATURE LIMIT STOP
WHICH MUST BE CHECKED. IF
TEMPERATURE IS TOO HIGH, THE
INSTALLER MUST RESET THIS STOP
IMMEDIATELY. ALWAYS CHECK
THE TEMPERATURE OF THE MIXED
WATER WHEN THE LEVER HANDLE
IS TURNED TO FULL HOT. EXCESSIVE
HOT WATER TEMPERATURE IS
DANGEROUS AND MAY CAUSE
SCALDING.
THE HIGH TEMPERATURE LIMIT STOP
IS FACTORY SET AT APPROXIMATELY
90°F (32°C) WITH AN INCOMING HOT
WATER SUPPLY TEMPERATURE OF
135°F (57°C). IF THE INCOMING HOT
WATER TEMPERATURE IS HIGHER
THAN 135°F (57°C), THE VALVE
(WHEN TURNED TO FULL HOT) WILL
DELIVER WATER IN EXCESS OF 90°F
(32°C) AND THE HIGH TEMPERATURE
LIMIT STOP MUST BE RESET.
Symptom Component Type Part No. Description Leak between valve cover and body. Packings and Gaskets 6806 Cover Gasket
Leak at lockable dial. Packings and Gaskets MU-5A O-Ring
Valve outlet temperature cannot be adjusted or will not mix consistently.
Port Sleeve Assembly TAG-1M or
RK3600A
Port Sleeve Assembly or Repair Kit
After cleaning or replacing port sleeve assembly, valve will not hold temperature.
Thermostat Group 6810 or
RK3600A
Thermostat Group or Repair Kit
Hot water bypass into cold line. Checkstops
RK3600B Checkstop KitSupplies cannot be shut off completely. Checkstops
Leak at checkstop bonnet. Checkstops
Handle Set Screw
Stop
Retaining Ring
Web
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
Hot Supply
Cold Supply
To Hot Water Source
Thermometer
Angle Checkstop
1/2” OD Copper Tube Inlets
Angle Checkstop
Hot Inlet Cold Inlet
Required when hot water must be circulated to a thermostatic mixing valve that is a substantial distance from the hot water source. Recommended hot water inlet temperature is 135°F (57°C).
This unit must be cycled each time the emergency equipment is inspected (See ANSI Z358.1, Maintenance and Training section).
1. Set the thermostatic mixing valve to full hot.
2. Activate eye or eye/face wash and verify outlet temperature does not exceed 90°F (32°C).
3. Turn thermostatic valve to full cold and wait ten seconds.
4. Turn thermostatic valve to full hot and wait ten seconds.
5. Verify outlet temperature does not exceed 90°F (32°C).
6. Turn thermostatic mixing valve to full cold and wait ten seconds.
7. If necessary, adjust high temperature limit stop (see page 2).
Then set mixing valve to desired operating temperature and deactivate emergency equipment.
Required Piping Method
G3600LF
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
To Dismantle Valve:
Turn off hot and cold water supplies to valve. Remove four cover screws and remove cover and thermostat group. (Figure
1) After replacing parts, lockable dial must be reset to obtain correct temperature range from Cold to Hot. (see "To Reset Adjustable High Temperature Limit Stop" on page 2).
To Clean Port Sleeve Assembly:
Remove base stud (Figure 2). Twist port sleeve nut into valve body, slide port sleeve assembly toward port sleeve nut, and lift from valve body to clean. Clean with non-corrosive agent and soft cloth. DO NOT USE ABRASIVES. Wash parts thoroughly after cleaning and reassemble. Reinstall port sleeve assembly with long slot end nearest port sleeve nut. Tighten port sleeve nut to complete reassembly. DO NOT OVERTIGHTEN.
To Clean Thermostat Group:
Loosen set screw and remove handle (Figure 1). Remove retaining ring and stop. Push rod through cover to remove thermostat group. DO NOT PULL COILS OUT OF SHAPE. Use brush and cleaning solution (non-corrosive and grit-free) to remove any depost build-up from thermostat coil. Wash thoroughly before reassembly.
Reassemble by reinstalling base stud, then place thermostat group 6810 on base stud. PORT SLEEVE ASSEMBLY DRIVING
BALL MUST BE INSERTED INTO HOLE ON LOWER COIL
BRACKET(Figure 3). Verify thermostat moves back and forth.
Replace cover and screws and turn hot and cold water supplies
on. See page 2 "To Reset Adjustable High Temperature Limit Stop."
Note: After installation, adjustment, and cleaning, always verify valve temperature with thermometer when turned to full hot. If necessary, adjust temperature of hot water source. EXCESSIVE
HOT WATER TEMPERATURE (OVER 90°F) IS DANGEROUS AND
MAY CAUSE SCALDING.
Figure 1
Figure 2
Figure 3
Base Stud
Long Slots
Port Sleeve Nut
Port Sleeve Nut
Port Sleeve Assembly
Port Sleeve Assembly
Driving Ball Coil Bracket
Cover Screws
Base Stud
HandleStop Thermostat Group
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
11 12 13 1514 16
RK3600B
Repair Kit*
RK3600A
Repair Kit
Notes:
1. After installing new parts, the adjustable high temperature limit stop must be reset (see page 2).
2. G3600LF valves are furnished with lockable dials.
* Includes parts to repair both hot and cold checkstops
Set Screw
Thermostatic Mixing Valve Parts
Item Part Number Description 1 TA-5 Base Stud 2 MU-2C Cover Screw 3 6810 Thermostat Group 4 6820 Stop 5 68240 Handle 6 MU-5A Stem O-Ring 7 3009 Cover O-Ring 8 TAG-1M Port Sleeve Assembly
Item Part Number Description 9 6806 Cover Gasket
10 3402 Port Sleeve Nut 11 LVC-8A Check Bonnet Packing 12 MU-6A Lower Stem with Packing 13 MU-9A Check Spring 14 MU-5A O-Ring 15 MU-4A Upper Check Stem 16 192700 Check Bonnet
1 97
10 2 4 53 6
7 6 9108
Checkstop Parts Thermostat Group
Lockable Dial
Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile gesafety.com rev. 1215 / © 2015 Guardian Equipment
Installation, Operation and Maintenance Guide G3600LF Series Thermostatic Mixing Valves
Flow Capacities
Sy st em P re ss ur e
D ro p (P
SI
12.5
37.5
Flow Rate (GPM)
1 2 3 4 5 6 7 8 9 10
Limited Warranty Guardian Equipment warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions, and when properly installed and maintained according to manufacturer's instructions for a period of two years from date of shipment. During the warranty period, Guardian Equipment will (at its discretion) repair or replace any product or part thereof, which shall be returned, freight prepaid to Guardian's factory and determined by the manufacturer to be defective in materials or workmanship. There are no warranties, expressed or implied, which extend beyond verbiage contained herein. There are no implied warranties of merchantability or fitness for a particular purpose. Guardian Equipment will not be held liable for labor, incidental or consequential damages. Any alteration or improper installation or improper use of the product will void this limited warranty.
MODEL IN OUT
MINIMUM
FLOW
(GPM)
INTERNAL
COLD WATER
BYPASS
MINIMUM
SYSTEM PRESSURE DROP
5 10 15 20 25 30 35 40 45 PSI
L/MIN 0.3 0.7 1.0 1.4 1.7 2.1 2.4 2.8 3.1 BAR
G3600LF 1/2" 1/2"
2 4 2.0 2.7 3.5 4.5 5.5 6.5 7.5 8.5 9.0 GPM
7.6 15 7.6 10 13 17 21 25 28 32 34 L/MIN
MAXIMUM FLOW CAPACITY
G3600LF HAS 1/2" NOMINAL SWEAT CONNECTIONS.
G3600LF
CAUTION: ALL THERMOSTATIC MIXING VALVES HAVE
LIMITATIONS. THEY WILL NOT PROVIDE THE DESIRED
ACCURACY OUTSIDE OF THEIR FLOW CAPACITY
RANGE. CONSULT CAPACITY CHART AND DO NOT
OVERSIZE. MINIMUM FLOW MUST BE NO LESS THAN
SHOWN ABOVE.
IMPORTANT: THESE SYSTEMS ARE DESIGNED TO
PROVIDE MIXED WATER FROM 60 TO 90°F (15 TO
32°C) FOR EYE OR EYE/FACE WASH APPLICATIONS
ONLY IN ACCORDANCE WITH ASSE 1071.
SPEAKMAN
400 ANCHOR MILL ROAD
NEW CASTLE, DE 19720
800-537-2107 800-977-2747
WWW.SPEAKMAN.COM
JULY 2017
Architect/Engineer Approval Space: P:
F:
W:
R: 555
SEF-9000
EYEWASH FEATURES:
• Eyewash is connected to Speakman SC-5811-RCP service sink faucet’s cold water integral stop port supply
• 6 ft. stainless steel supply hose
• Activated by squeeze valve with automatic stay open device
• (2) yellow plastic spray heads with flip top dust caps
• 3.06 gpm @ 30 psi performance (eyewash only)
• 2.66 gpm @ 30 psi (with sink on)
• Integral vacuum breaker and check valve
FAUCET FEATURES:
• ½ in. NPT female inlets supply
• Vandal resistant four-arm handles with color coded indexes
• Perfect® valves with ¼ turn ceramic cartridges
• 4 gpm (min) @ 20 psi
• Cast brass nozzle with ¾ in. hose thread, pail hook and top brace outlet
• Integral vacuum breaker
COMPLIANCE:
• ASME A112.18.1/CSA B125 certified (service sink faucet)
• ANSI/ISEA Z358.1 certified (eyewash)
• ASSE -1001 certified (service sink & faucet)
OPTIONS: Add suffix to model #
• 4 in. wrist blade handles for service sink ❑ -4WH
• 5 ft. hose with hook for service sink ❑ -5H
• Check valves in swivel assembly for service sink ❑ -CK
• Addition of SE-370 thermostatic mixing valve for eyewash ❑ -TW
WARRANTY:
• 3 year limited
Eyesaver® Service Sink Faucet with Eyewash/Drench Hose
NEW CASTLE, DE 19720
800-537-2107 800-977-2747
WWW.SPEAKMAN.COM
JULY 2017
Architect/Engineer Approval Space: P:
F:
W:
R:556
DIMENSIONS:
NOTE: 1. Inlets are 1/2˝ NPT female. 2. All dimensions are in inches (millimeters) unless otherwise specified and are subject to change without notice. 3. The SEF-9200 EyesaverTM service sink unit and the SC-5811-RCP service sink fitting can be purchased together as a SEF-9000 EyesaverTM service sink fitting.
NEW CASTLE, DE 19720
800-537-2107 800-977-2747
WWW.SPEAKMAN.COM
JULY 2017
Architect/Engineer Approval Space: P:
F:
W:
R: 557
SEF-9000-FM
EYEWASH FEATURES:
• Eyewash is connected to Speakman SC-5811-RCP service sink faucet’s cold water integral stop port with stainless steel supply hose
• 6 ft. stainless steel supply hose
• Activated by squeeze valve with automatic stay open device
• (2) yellow plastic spray heads with flip top dust caps
• 3.06 gpm @ 30 psi performance (eyewash only)
• 2.66 gpm @ 30 psi (with sink on)
• Integral check valve
• Eyewash is permanently attached to wall mounting bracket
FAUCET FEATURES:
• ½ in. NPT female inlets supply
• Vandal resistant four-arm handles with color coded indexes
• Perfect® valves with ¼ turn ceramic cartridges
• 4 gpm (min) @ 20 psi
• Cast brass nozzle with ¾ in. hose thread, pail hook and top brace outlet
• Integral vacuum breaker
COMPLIANCE:
• ASME A112.18.1/CSA B125 certified (service sink faucet)
• ANSI/ISEA Z358.1 certified (eyewash)
• ASSE -1001 certified (service sink & faucet)
OPTIONS: Add suffix to model #
• 4 in. wrist blade handles for service sink ❑ -4WH
• 5 ft. hose with hook for service sink ❑ -5H
• Check valves in swivel assembly for service sink ❑ -CK
• Addition of SE-370 thermostatic mixing valve for eyewash ❑ -TW
WARRANTY:
Eyesaver® Service Sink Faucet with Fixed Mount Eyewash
NEW CASTLE, DE 19720
800-537-2107 800-977-2747
WWW.SPEAKMAN.COM
JULY 2017
Architect/Engineer Approval Space: P:
F:
W:
R:558
DIMENSIONS:
NOTE: 1. Inlets are 1/2˝ NPT female. 2. All dimensions are in inches (millimeters) unless otherwise specified and are subject to change without notice. 3. The SEF-9200 EyesaverTM service sink unit and the SC-5811-RCP service sink fitting can be purchased together as a SEF-9000 EyesaverTM service sink fitting.
NEW CASTLE, DE 19720
800-537-2107 800-977-2747
WWW.SPEAKMAN.COM
JULY 2017
Architect/Engineer Approval Space: P:
F:
W:
R: 559
SEF-9200
EYEWASH FEATURES:
• Connects to Speakman SC-5811-RCP service sink faucet’s cold water integral stop port supply
• 6 ft. stainless steel supply hose
• Activated by squeeze valve with automatic stay open device
• (2) yellow plastic spray heads
• 3.06 gpm @ 30 psi performance (eyewash only)
• 2.66 gpm @ 30 psi (with sink on)
• Integral vacuum breaker and…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .