- 36c25920q0229
About this file
This document provides product specifications and installation guidelines for emergency eyewash stations. It describes various eyewash fixture models from Bradley Corporation that comply with ANSI/ISEA Z358.1 standards for emergency eyewash and shower equipment. The fixtures include swing-activated eyewash stations, combination drench showers and eye/face wash units, self-contained eyewash stations, and enclosed safety shower stations. Specifications cover features such as valve operation, water supply requirements, placement guidelines, flow rates, temperature controls, and weekly testing procedures. Installation of these eyewash fixtures would help agencies like the Department of Veterans Affairs meet federal workplace safety standards for eye and body flush equipment in hazardous areas.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25920Q0229 0003.docx | DOCX document | |
| Description of Changes for Solicitation Amendment 200617.docx | DOCX document | |
| Drawings Rev 2_2 of 3.zip | ZIP file | |
| Product Data Rev 2.zip | ZIP file | |
| 554-21-101 Install RMR EyeWash Stations - Locations_Rev-3.xlsx | XLSX spreadsheet | |
| Drawings Rev 2_3 of 3.zip | ZIP file | |
| Drawings Rev 2_1 of 3.zip | ZIP file | |
| RFI Answers.docx | DOCX document | |
| 36C25920Q0229 0002.docx | DOCX document | |
| Cabinet Work Pictures.docx | DOCX document | |
| 55-21-101 Eyewash Specifications.pdf | ||
| Photos - Temp controlled room D2-213.zip | ZIP file | |
| Drawings 1.pdf | ||
| Product Data 2.pdf | ||
| Drawings 3.pdf | ||
| Drawings 2.pdf | ||
| 554-21-101 Install RMR EyeWash Stations - Locations_Rev-2.pdf | ||
| 36C25920Q0229_1.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ANSI/ISEA Z358.1-2014
Quick Compliance Guide
BRADLEYCORP.COM
2 3
Important Information About Compliance The U.S. Code of Federal Regulations 29CFR 1910.151 states:
“Where the eyes or body of any person may be exposed to injurious or corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.”
The American National Standards Institute (ANSI) establishes standards for minimum performance and use requirements for eyewash and shower equipment. The
ANSI/ISEA Z358.1-2014 for Emergency Eyewash and Shower
Equipment provides detailed guidelines to which the
Occupational Safety and Health Administration (OSHA), State OSHA and other regulatory agencies commonly refer.
The Joint Commission 2009 EC Standard for Hospitals requires: “The hospital takes action to minimize or eliminate identified safety and security risks in the physical environment.” Furthermore, hospitals are required to “Minimize risk associated with selecting, handling, storing, transporting, using, and disposing hazardous chemicals.” Surveyors commonly refer to OSHA requirements and the ANSI Standard for further guidance on best demonstrated practices.
Canadian Provincial authorities also typically refer to
ANSI standards when auditing for or advising proper requirements for emergency eyewash showers.
Safety Considerations
Personal Wash Unit
ANSI standards allow a personal wash unit (ie. Bottled
Eyewash) to be used as a supplement to the compliant
ANSI/ISEA Z358.1 fixtures outlined in this guide. While supplemental fixtures (single head drench hoses, bottle eyewash) serve an important function in highly toxic, hazardous environments, it is important to remember they do not provide the same protection as ANSI compliant drench showers, eye or eye/face washes. (Appendix A1)
First Aid Practices
Prior to the occurrence of an accident, consult with a physician or other professional for guidance in regards to common and specific work place hazards that may be present in your facility. Refer to Safety Data Sheets (SDS) for specific type of flush required (eyewash, eye/face or combination drench) given the hazards in the environment.
Provide access to a physician or other medical professional immediately after an accident occurs. (Appendix A2)
Waste Disposal
Few consider the ramifications of hundreds of gallons of pooling flushing fluid in the area surrounding drench showers and eyewashes. It’s important to have a plan in place for the disposal of the flushing fluid, whether one opts for the installation of drains in new construction facilities or dedicated waste containment systems. Pooling fluid creates slip hazards, and presents a safety risk to an impaired worker.
When planning for the disposal of flushing fluid, consult your local ordinances and governing authorities. (Appendix A3)
Personal Protective Equipment
Providing employees with personal protective equipment
(safety glasses, protective suits, etc), in accordance with
OSHA 1910.132(a), is required. It can be challenging to enforce the use of that protection equipment at all times.
ANSI explicitly states that personal protective equipment does not replace the role of safety drench showers, eyewashes, and other safety flushing equipment. These fixtures are intended to treat injuries should PPE prove to be inadequate or fail. (Appendix A4)
Installation
Supply lines
Each manufacturer provides its own recommendations in regards to the supply size that’s adequate for each fixture. It’s important to note that by reducing the size of the supply, the shower’s ability to deliver the flushing fluid at the proper rate with the intended pattern is directly affected. (Appendix B1)
Water Capacity
Compliant safety showers and eyewashes are supplied with a minimum pressure of 30 psi (207 kPa). Typical facilities supply their fixtures with 45 psi (310 kPa) inlet supply pressure. Extra care should be taken with any pressure that exceeds 80 psi (552 kPa). Complicated site conditions often require the installation of fixtures a significant distance from the water supply. The owner and designer are responsible for ensuring that adequate pressure and flushing fluid will be delivered through the fixture even at low points of pressure. (Appendix B2)
Valve Operation
Valves that remain open are required in order to allow the injured individual to maximize the use of their hands to disrobe and flush their eyes. In limited circumstances, an inspector or other “enforcing authority” may allow a self-closing ball valve, in school-related laboratory environments, where the contaminant is “not a serious threat.” (Appendix B3)
Alarm Devices
Systems that provide visual, audible and an auxiliary connection serve as a great asset that discourages false activations, and allows medical personnel to locate where the accident occurred and respond rapidly. (Appendix B4)
Placement of Emergency Equipment
Safety drench showers, eye and eye/face washes must be within 10 seconds or 55 feet (16.8 meters) of the hazard.
Fixtures may not be blocked. A door is considered an obstruction. However, if the contaminant is not hazardous or corrosive, a single door may be present provided it opens in the same direction of travel. The door may not have a locking mechanism, which may prevent the person access to use the equipment during an emergency. (Appendix B5)
Delivered Flushing Fluid Temperature
Lukewarm (tepid) water is required for the full 15 minute flush, for a drench shower, eye or eye/face wash. To encourage injured personnel to continue to flush the entire
15 minutes or longer as needed, the ANSI/ISEA Z358.1-2014 standard indicates that tepid water is required. Tepid is defined as 60-100ºF (15.6-37.8ºC). Prolonged exposure to near freezing water has been proven to affect the body’s ability to maintain body temperature, increasing the risk of hypothermia. Whenever possible, consult a physician to determine the recommended temperature based on specific types hazardous chemicals or material. (Appendix B6)
Weekly Activation
Emergency Drench Showers, Eye and Eye/Face Washes must be activated one time per week. This activation ensures that nothing is blocking the flow of the flushing fluid and eliminates any chance of contamination from stagnant water. (Appendix B7)
This guide serves as a supplement to the ANSI/ISEA Z358.1-2014 standard.
Quick Compliance Guide
FREE Confidential Safety Evaluation • 800.BRADLEY • bradleysafety.com
4 5
Safety Drench Showers
• Valve mechanism opens in one second or less; it stays open until manually closed. (Section 4.2)
• Supply with flushing fluid ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…"). (Definitions, Sections 4.1.1, 4.4.1)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials. Locate on the same plane as hazard and free of obstructions. (Section 4.5.2, Appendix B5)
• Doors are an obstruction. (Appendix B5)
• Must resist corrosion in the presence of flushing fluid. (Section 4.1.5)
• Audible, visual and central control alarm systems deter vandals and notify personnel that an accident occurred. (Appendix B4)
• Environmental conditions often require freeze or scald protection equipment. (Section 4.5.5)
Top down view
Requires a 16" (406 mm) radius from the center of the drench shower spray pattern to be free of obstructions.
(Section 4.1.4)
15-minute Flush Tepid Water Third-Party
Certifications Weekly Activations: Annual Inspections
Compliant showers release a continuous flow of at least 20
GPM (76 L-MIN) of tepid flushing fluid for a period of at least 15 minutes.
(Sections 4.1.2, 4.4.1, 4.5.5, 4.5.6)
(lukewarm) 60–100°F
(15.6–37.8°C) encourages full 15 minute flush or until medical personnel arrive. (Definitions, Sections 4.5.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Section 4.6.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Section 4.6.5)
69" (1752 mm) (Sections 4.2, 7)
60" (1524 mm) (Sections 4.1.4, 7)
Spray Pattern Diameter
20" (508 mm) (Section 4.1.4, 7)
82–96" (2083–2438 mm) (Sections 4.1.3, 7)
16" (406 mm) (Sections 4.1.4, 7)
Combination Drench Shower, Eye and Eye/Face Washes
• Valve mechanism opens in one second or less; it stays open until manually closed. (Sections 4.2, 5.2, 6.2, 7.1.1, 7.1.2, 7.1.3)
• Drench shower and eye or eye/face wash must operate simultaneously. (Section 7.4.4)
• Supply with flushing fluid ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”).
(Definitions, Sections 4.1.1, 4.4.1, 5.1.1, 6.1.1, 7.1.2, 7.1.3)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials. Locate on same plane as the hazard, free of obstructions.
(Sections 4.5.2, 5.4.2, 6.4.2, 7.1.1, 7.1.2, 7.1.3, 7.4.2, Appendix B5)
• Must resist corrosion in the presence of flushing fluid
(Sections 4.1.5, 5.1.5, 6.1.5, 7.1.1, 7.1.2, 7.1.3)
• Protect eye and eye/face wash heads from contaminants.
(Sections 5.1.3, 6.1.3, 7.1.2, 7.1.3)
• Flow Rates: Eyewash unit delivers a minimum of .4 GPM (1.5 L-MIN) for 15 minutes.
(Section 5.1.6) Eye/face wash unit delivers a minimum of 3.0 GPM (11 L-MIN) for 15 minutes. (Section 6.1.6)
• Use flow meter to check flow rate; use test gauge to test flow pattern.
(Sections 5.1.8, 5.3.1, 6.1.7, 6.3, 7.1.2, 7.1.3)
• Environmental conditions often require freeze or scald protection equipment.
(Sections 4.5.5, 5.4.5, 6.4.5, 7.1.1, 7.1.2, 7.1.3)
Top down view
Requires a 16" (406 mm) radius from the center of the drench shower spray pattern to be free of obstructions. (Sections 4.1.4, 7.1.1)
Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eye or eye/face wash sprayheads.
(Sections 5.4.4, 6.4.4, 7.1.2, 7.1.3)
Use a Bradley test gauge (Model 269-1444) to check flow pattern.
69" (1752 mm) (Sections 4.2, 7)
60" (1524 mm) (Sections 4.1.4, 7)
Spray Pattern Diameter
20" (508 mm) (Section 4.1.4, 7)
33–53" (838–1346 mm) (Sections 5.4.4, 6.4.4)
82–96" (2083–2438 mm) (Sections 4.1.3, 7)
6" (152 mm) (Sections
5.4.4, 6.4.4) 16"
(406 mm) (Sections 4.1.4, 7)
15-minute Flush Tepid Water Third-Party
Certifications Weekly
Activations:
Annual Inspections
Compliant showers release a continuous flow of at least 20 GPM
(76 L-MIN) of tepid flushing fluid for a period of at least 15 minutes. (Sections
4.1.4, 4.4.1, 4.5.5, 4.5.6, 7.1.1)
Compliant eye or eye/face wash fixture releases a continuous flow of flushing fluid for a minimum of 15 minutes.
(Sections 5.1.6, 5.4.5, 5.4.6, 6.1.6, 6.4.5, 6.4.6, 7.1.2, 7.1.3)
(lukewarm)
60–100°F
(15.6–37.8°C) encourages full
15-minute flush or until medical personnel arrive.
(Definitions, Sections 4.5.6, 5.4.6, 6.4.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 4.6.2, 5.5.2, 6.5.2, 7.5.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Section 7.5.5)
(Section 4.6.5)
6 7
Eye and Eye/Face Wash Fixtures
• Valve mechanism opens in one second or less; it stays open until manually closed. (Sections 5.2, 6.2)
• Supply with flushing fluid, ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”)
Definitions, Sections 5.1.1, 6.1.1)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials. Locate on the same plane as hazard and free of obstructions.
(Sections 5.4.2, 6.4.2, Appendix B5)
• Must resist corrosion in the presence of flushing fluid.
(Sections 5.1.5, 6.1.5)
• Protect eye and eye/face wash heads from contaminants.
(Sections 5.1.3, 6.1.3)
• Flow Rates: Eyewash unit delivers a minimum of .4 GPM (1.5 L-MIN) for
15 minutes. (Section 5.1.6) Eye/face wash unit delivers a minimum of 3.0
GPM (11 L-MIN) for 15 minutes. (Section 6.1.6)
• Use a flow meter to test flow rate; use a test gauge to test flow pattern.
(Sections 5.1.8, 5.3.1, 6.1.7, 6.1.8, 6.3, 6.3.1)
• Audible, visual and central control alarm systems deter vandalism and alert safety personnel. (Appendix B4)
• Environmental conditions often require freeze or scald protection equipment. (Sections 5.4.5, 6.4.5)
Top down view
Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eye or eye/face wash sprayheads. (Sections 5.4.4, 6.4.4)
Use a Bradley test gauge (Model
269-1444) to check flow pattern.
33–53” (838–1346 mm)
(Sections 5.4.4, 6.4.4)
6" (152 mm) (Sections 5.4.4, 6.4.4)
15-minute Flush Tepid Water Third-Party
Certifications Weekly Activations: Annual Inspections
Compliant fixtures release a continuous flow of tepid flushing fluid for a minimum of 15 minutes.
(Sections 5.1.6, 5.4.5, 5.4.6, 6.1.6, 6.4.5, 6.4.6)
(lukewarm) 60–100°F
(15.6–37.8°C) encourages full 15 minute flush or until medical personnel arrive. (Definitions, Sections 5.4.6, 6.4.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 5.5.2, 6.5.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Sections 5.5.2, 5.5.5, 6.5.2, 6.5.5)
Dual Head Eye/Face Wash & Drench Hose
• Considered an eye/face wash if it complies with the installation and performance requirements of the eye/face wash standard. (Sections 6, 8.2.1)
• Single-head drench hoses complement the 15-minute flush provided by a primary ANSI/ISEA Z358.1 compliant eyewash fixture. (Section 8)
• Valve mechanism opens in one second or less; it stays open until manually closed.
(Sections 6.2, 8.2.1)
• Fixtures compliant as an eye/face wash must remain "on" once activated
(Sections 6.2, 8.2.1)
• Supply with flushing fluid ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”) (Definitions, Sections 6.1.1, 8.2.1)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials.
Locate on same plane as the hazard, free of obstructions.
(Section 6.4.2, Appendix B5)
• Protect unit heads from contaminants. (Sections 6.1.3, 8.2.1)
• Flow Rates: Eye/face wash unit delivers a minimum of 3.0 GPM
(11 L-MIN) for 15 minutes. (Section 6.1.6, 8.2.1)
• Use a flow meter to test flow rate; use a test gauge to test flow pattern.
(Sections 6.1.7, 6.3, 8.2.1)
Top down view
Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eye or eye/face wash sprayheads. (Sections 6.4.4, 8.2.1)
Use a Bradley test gauge (Model 269-1444) to check flow pattern.
Distance to floor 33–53” (838–1346 mm) (Sections 5.4.4, 6.4.4)
6" (152 mm) (Sections 6.4.4, 8.2.1)
15-minute Flush Tepid Water Third-Party
Certifications Weekly Activations: Annual Inspections
Compliant fixtures release a continuous flow of tepid flushing fluid for a minimum of 15 minutes.
(Sections 6.1.6, 6.4.5, 6.4.6, 8.2.1)
(lukewarm) 60–100°F
(15.6–37.8°C) encourages full 15 minute flush or until medical personnel arrive. (Definitions, Sections 6.4.6, 8.2.1, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 6.5.2, 8.2.1, 8.2.4.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Sections 6.5.5, 8.2.4.5)
8 9
Laboratory Eye & Eye/Face Wash Fixtures
• Valve mechanism opens in one second or less; it stays open until manually closed. (Sections 5.2, 6.2)
• Supply with flushing fluid, ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”) (Definitions, Sections 5.1.1, 6.1.1)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials.
• Locate on same plane as the hazard, free of obstructions.
(Sections 5.4.2, 6.4.2, Appendix B5)
• Protect unit heads from contaminants. (Sections 5.1.3, 6.1.3)
• Flow Rates: Eyewash unit delivers a minimum of .4 GPM for 15 minutes. (Section 5.1.6) Eye/face wash unit delivers a minimum of 3.0 GPM (11 L-MIN) for 15 minutes. (Section 6.1.6)
• Use a flow meter to test flow rate; use a test gauge to test flow pattern. (Sections 5.1.8, 5.3.1, 6.1.7, 6.3)
The Joint Commission 2009 EC Standard for Hospitals requires: “The hospital takes action to minimize or eliminate identified safety and security risks in the physical environment.” Furthermore, hospitals are required to “Minimize risk associated with selecting, handling, storing, transporting, using, and disposing hazardous chemicals.” Surveyors commonly refer to OSHA requirements and the ANSI Standard for further guidance on best demonstrated practices.
Top down view
Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eye or eye/face wash sprayheads. (Sections 5.4.4,6.4.4)
Use a Bradley test gauge (Model 269-
1444) to check flow pattern.
6" (152 mm) (Sections 6.4.4, 8.2.1)
15-minute Flush Tepid Water Third-Party
Certifications Weekly Activations: Annual Inspections
Compliant fixtures release a continuous flow of tepid flushing fluid for a minimum of
15 minutes. (Sections
5.1.6, 5.4.5, 5.4.6, 6.1.6, 6.4.5, 6.4.6)
(lukewarm) 60–100°F
(15.6–37.8°C) encourages full 15 minute flush or until medical personnel arrive. (Definitions, Sections 5.4.6, 6.4.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 5.5.2, 6.5.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Sections 5.5.5, 6.5.5)
(Sections 5.4.4, 6.4.4)
Self-Contained Eyewash Fixtures
• Eyewash unit delivers a minimum of .4 GPM for 15 minutes.
(Section 5.3.2)
• Valve mechanism opens in one second or less; it stays open until manually closed. (Section 5.3.2)
• Supply with flushing fluid, ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”) (Definitions, Section 5.1.1)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials. Locate on same plane as the hazard, free of obstructions. (Sections 5.4.2, Appendix B5)
• Use a flow meter to test flow rate; use a test gauge to test flow pattern. (Section 5.4.7)
• Frigid conditions require the installation of freeze protection equipment. (Section 5.4.5)
Top down view
Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eyewash sprayheads. (Sections 5.4.4)
Use a Bradley test gauge (Model
269-1444) to check flow pattern.
6" (15.2 cm) (Sections 6.4.4, 8.2.1)
15-minute Flush Tepid Water Third-Party
Certifications Weekly Activations: Annual Inspections
Compliant fixtures release a continuous flow of tepid flushing fluid for a minimum of
15 minutes. (Sections
5.1.6, 5.4.5, 5.4.6)
(lukewarm) 60–100°F
(15.6–37.8°C) encourages full 15 minute flush or until medical personnel arrive. (Definitions, Sections 5.4.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 5.5.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair. (Sections 5.5.5)
(Sections 5.4.4, 6.4.4)
Front View
10 11
Enclosed Safety Showers
• Colder ambient temperature may require an enclosure for added protection. (Section B6)
• Valve mechanism opens in one second or less; it stays open until manually closed. (Sections 4.2, 5.2, 6.2, 7.1.1, 7.1.2, 7.1.3)
• Drench shower and eye or eye/face wash must operate simultaneously. (Section 7.4.4)
• Supply with flushing fluid ("potable water, preserved water, preserved buffered saline solution or other medically acceptable solution…”). (Definitions, Sections 4.1.1, 4.4.1, 5.1.1, 6.1.1, 7.1.2, 7.1.3)
• Locate 10 seconds or 55' (16.8 m) from contaminants or hazardous materials. Locate on same plane as the hazard, free of obstructions.
(Sections 4.5.2, 5.4.2, 6.4.2, 7.1.1, 7.1.2, 7.1.3, 7.4.2, Appendix B5)
• Must resist corrosion in the presence of flushing fluid
(Sections 4.1.5, 5.1.5, 6.1.5, 7.1.1, 7.1.2, 7.1.3)
• Protect eye and eye/face wash heads from contaminants.
(Sections 5.1.3, 6.1.3, 7.1.2, 7.1.3)
• Requires a 16" (406 mm) radius from the center of the drench shower spray pattern to be free of obstructions. (Sections 4.1.4, 7.1.1)
• Required to be free of obstructions a minimum of 6" (152 mm) from the outside of the eye or eye/face wash sprayheads.
(Sections 5.4.4, 6.4.4, 7.1.2, 7.1.3)
• Flushing fluid height 33–53" (838-1346 mm) from standing surface. (Sections 5.4.4, 6.4.4, 7)
• Flow Rates: An eyewash delivers a minimum of .4 GPM for 15 minutes (Sections 5.1.6, 7.1.2). An eye/face wash delivers a minimum of 3.0 GPM (11 L-MIN) for 15 minutes. (Sections 6.1.6, 7.1.3)
• Use flow meter to check flow rate; use test gauge to test flow pattern. (Sections 5.1.8, 5.3.1, 6.1.7, 6.3, 7.1.2, 7.1.3)
• Use a Bradley test gauge (Model 269-1444) to check flow pattern.
• Environmental conditions often require freeze or scald protection equipment. (Sections 4.5.5, 5.4.5, 6.4.5, 7.1.1, 7.1.2, 7.1.3)
Top down view
6" (152 mm) (Sections
5.4.4, 6.4.4)
16" (406 mm) (Sections 4.1.4, 7)
15-minute Flush Tepid Water Third-Party
Certifications Weekly
Activations:
Annual Inspections
Compliant showers release a continuous flow of at least 20 GPM
(76 L-MIN) of tepid flushing fluid for a period of at least 15 minutes.
(Sections 4.1.4, 4.4.1, 4.5.5, 4.5.6, 7.1.1)
Compliant eye or eye/face wash fixture releases a continuous flow of flushing fluid for a minimum of 15 minutes. (Sections 5.1.6, 5.4.5, 5.4.6, 6.1.6, 6.4.5, 6.4.6, 7.1.2, 7.1.3)
(lukewarm)
60–100°F
(15.6–37.8°C) encourages full
15-minute flush or until medical personnel arrive.
(Definitions, Sections 4.5.6, 5.4.6, 6.4.6, Appendix B6)
Manufacturers may have their safety fixtures independently evaluated by a third-party testing organization. Look for certification when selecting a compliant fixture. (Definitions)
Flush lines and test by activating weekly.
Inspection tags are often included with fixtures to document testing and to satisfy a safety audit.
(Sections 4.6.2, 5.5.2, 6.5.2, 7.5.2)
ANSI recommends a comprehensive annual inspection of the facility to evaluate modified work space, assess new hazards introduced into the area, and to identify fixtures needing replacement or repair.
(Section 7.5.5)
(Section 4.6.5)
69" (1752 mm)
(Sections 4.2, 7)
60" (1524 mm)
(Sections 4.1.4, 7)
Spray Pattern
Diameter 20" (508 mm)
(Section 4.1.4, 7)
82–96" (2083–2438 mm) (Sections 4.1.3, 7)
262 251 6000 800 BRADLEY bradleycorp.com W142 N9101 Fountain Boulevard
Menomonee Falls, WI 53051 4055-2.5-0815
FREE Confidential Safety Evaluation • 800.BRADLEY • bradleysafety.com
© 2019 Bradley P.O. Box 309, Menomonee Falls, WI 53052-0309
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Page 1 of 3 6/26/2019 This information is subject to change without notice.
Bradley_TMV_Emergency_EFX8
Engineer's Approval
• Exceeds ANSI Z358.1
• ASSE 1071 Certified
• Reliable Liquid-Filled Thermostat with 10-Year Warranty
• Checkstops on Inlets
• Adjustable Set Point within Temperature Range
• Accurate Temperature Control to within ±3° F
• Built-in Cold Water Bypass, Assuring Cold Flow
• Positive Shutoff of Hot Supply When Cold Supply is Lost
• Easy Installation and Serviceability
• Dirt and Lime Resistant
• Dial Thermometer
• Factory Assembled and Tested
• Universal Mounting Capability
• Cabinet Features:
— 18 Gauge Body & Door
— Left-Hand Hinge
— Cylinder Lock
— Inlet/Outlet Knock-Out Holes for Mounting Flexibility
— Stainless Steel or Baked White Enamel Finishes
— Surface-Mounted or Recessed Style with Flange
Valve Specifications Maximum Operating Pressure 125 PSI (860 kPA)
Maximum Inlet Temperature 180° F (82° C)
Recommended Inlet Temperature 120° F (49° C) – 140° F (60° C)
Temperature Range Set Point Std. 65° F (18° C) to 90° F (32° C) 85° F (29° C)
Flow Capacities – GPM
Model Min.
Flow
Pressure Drop – PSI 5 10 15 20 30 45 60
S19-2000 1.5 3.0 4.0 5.0 6.0 7.3 9.0 10.5
Cold Bypass Only 2.3 3.2 4.0 4.6 5.6 6.8 7.7
Flow Capacities – L/Min
Model Min.
Flow
Pressure Drop – Bar .5 1.0 1.5 2.0 2.5 3.0 4.0
S19-2000 5.5 13.5 19.0 23.5 27.0 30.5 33.5 38.5
Cold Bypass Only 10.5 14.5 18.0 21.0 23.5 25.5 29.5
S19-2000
Valve Model Model Description
| ¨ | S19-2000 |
| ¨ | S19-2000EFX |
Emergency Fixture Thermostatic Mixing Valve Emergency Fixture Thermostatic Mixing Valve for S19294JB & S19294JBT Only
Configurable Valve Model (select one) Model Description
| ¨ | EFX8 |
| ¨ | CAB-EFX8 |
EFX8 Thermostatic Mixing Valve with Options EFX8 Thermostatic Mixing Valve Cabinet Only
Optional Valve Selections Finish
| ¨ | R |
| ¨ | C |
Rough Brass (standard) Chrome Plated
Bracket
| ¨ | B |
| ¨ | 0 |
Wall Mounting Bracket None
Optional Cabinet Selections Cabinets (includes bracket)
| ¨ | SS |
| ¨ | RS |
| ¨ | SE |
| ¨ | RE |
| ¨ | 0 |
Surface Mount Stainless Steel Recessed Stainless Steel Surface Mount White Enamel Recessed White Enamel None
Window
| ¨ | W |
| ¨ | 0 |
Plexi-Glass Window in Door None
Application Eye or Eye/Face Wash
Complies with ANSI/ISEA Z358.1
S19-2000 (EFX8), S19-2000EFX
Emergency Fixture Thermostatic Mixing Valves
This plumbing fixture is not intended to dispense water for human consumption through drinking or for preparation of food or beverages.
Product Compliance Listed by IAPMO R&T to
• ASSE 1071
• Uniform Plumbing Code (UPC)
• National Plumbing Code of Canada
• International Plumbing Code (IPC)
Listed by ASSE International to
• ASSE 1071
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Page 2 of 3 6/26/2019 This information is subject to change without notice.
Bradley_TMV_Emergency_EFX8
Dimensions
Front View
3-1/8" (79)
6-1/4" (159)
8-3/8" (213)
1-5/8" (41)3" (76)
5" (127)
Side View
14-1/2" (368)
9-3/4" (248) Door
11-1/4" (286) Door
5-3/8" (137)
5" (127)
3" (76)
Flange
11" (279) Box
13" (330) 1/2" NPT Inlets
2-1/2" (64)
1/2" NPT
Outlet
2-1/4" (57)
6-1/2" (165)
.28" Dia. Holes 4 Each Side
8 Total
7-1/2" (191)
12-1/2" (318)
2-1/2" (64)
2" (51)
2" (51)
Side View
1/2" NPT
4-3/4" (121)
3" (76)
1-3/4" (44)
5-1/2" (140)
1/2" NPT
(mm)
Front View
Dimensions — S19-2000 Recessed Cabinet
S19-2000 (EFX8), S19-2000EFX
Emergency Fixture Thermostatic Mixing Valves
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Page 3 of 3 6/26/2019 This information is subject to change without notice.
Bradley_TMV_Emergency_EFX8
Bottom View
Side View
2-1/2" (64)
12-1/2" (318)
2-1/4" (57)
1/2" NPT Outlet 2"
(51)
6-1/2" (165)1/2" NPT Inlets
Front View
3" (76)
11-1/4" (286) Door
11" (279) Box
9-3/4" (248) Door
5" (127)
5-1/2" (140)
Back View
2" (51)
3-1/4" (83)
7" (178)
5-1/2" (140)
3/4" (19)2" (51)
.31" Dia. Holes 8 Each Side
– 6 Total
8-1/2" (216)
Recessed View
11" (279) Surface-Mounted & Recessed
Bottom View Is the Same for Both Surface-Mounted and Recessed Dimensions.
(mm)Dimensions — S19-2000 Surface-Mounted Cabinet
S19-2000 (EFX8), S19-2000EFX
Emergency Fixture Thermostatic Mixing Valves
S19-270C, S19-270E Swing-Activated Eye and Eye/Face Wash
© 2014 Bradley P.O. Box 309, Menomonee Falls, WI 53052-0309
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Page 1 of 2 12/17/2012 This information is subject to change without notice.
Bradley_EyeFaceWash_S19-270C_E
| • | Exceeds | American | National | Standard | Z358.1 | Specifications | ||
| • | Durable, | Ceramic | Valve | |||||
| • | Precise | 20° | Side-Swing | Activation | ||||
| • | Durable | Anti-Rotational | Deck | Mount | ||||
| • | Universal | Right | or | Left | Hand | Mounting | Options | |
| • | Chrome-Plated | Brass | on | Exposed | Piping | and | Fittings | |
| • | Universal | Identification | Sign | and | Inspection | Tag | Included |
Specifications
| Unit | design | saves | space | and | fits | easily | into | any | work | environment. | Eye | and | eye/face | wash |
| units | operate | quickly | by | pulling | swing | arm | 90° | over | sink. | The | unit | is | pre-assembled | for |
| right-hand | mounting, | but | if | desired, | there | is | the | option | to | assemble | for | left-hand | mounting. | |
| New | vandal | resistant | ceramic | valve | limits | wear | and | tear | on | moving | parts, | provides | ||
| dependability | and | long | lasting | performance. | Safe, | steady | water | flow | under | varying | water | |||
| supply | conditions | from | 30-90 | PSI | is | assured | by | integral | flow | control. | Eye/face | wash | ||
| sprayheads | contain | an | antimicrobial | agent | to | protect | the | sprayheads | (S19-270E | only). | ||||
| NOTE: The | ANSI | Z358.1 | standard | requires | an | uninterruptible | supply | of | flushing | fluid. | ||||
| Bradley | plumbed | emergency | fixtures | require | a | minimum | of | 30 | PSI | flowing | pressure. |
This plumbing fixture is not intended to dispense water for human consumption through drinking or for preparation of food or beverages.
Standard Equipment Standard Sprayhead Assembly
| Chrome-plated | brass | sprayhead | assembly | with | twin | soft-flow | eyewash | heads | and | ||
| protective | sprayhead | covers. | The | integral | flow | control | assures | safe, | steady | flow | under |
| varying | water | supply | conditions | from | 30–90 | PSI. | (S19-270C). |
Eye/Face Wash Sprayhead Assembly
| Twin | perforated | disc | eye/face | wash | heads | with | protective | sprayhead | covers. | The | integral | |
| flow | control | assures | safe, | steady | flow | under | varying | water | supply | conditions | from | 30–90 |
| PSI. | (S19-270E). |
Valve
| Ceramic | ½" | NPT | stay-open | valve. | The | ceramic | discs | provide | a | precise | 20° | activation | and |
| deactivation | angle, | minimizing | excessive | splashing | when | the | unit | is | activated. |
Pipe and Fittings Chrome-plated brass.
Water Supply
½" NPT.
S19-270C
S19-270E
| Satisfies | ANSI | Z358.1 |
| tepid | water | requirements. |
Recommended Option:
Navigator S19-2000 EFX8
Emergency Thermostatic Mixing Valve
Model Number Description
S19-270C Swing-Activated Eyewash – Universal Mount
S19-270E Swing-Activated Eye/Face Wash – Universal Mount
S19-2000 Navigator EFX8 - Emergency Thermostatic
S19-270C, S19-270E Swing-Activated Eye and Eye/Face Wash
© 2014 Bradley P.O. Box 309, Menomonee Falls, WI 53052-0309
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Page 2 of 2 12/17/2012 This information is subject to change without notice.
Bradley_EyeFaceWash_S19-270C_E
S19-270E
S19-270C
4-1/8" (105mm)
5-3/4" (146mm)
Ø 2-3/8" (60mm)
Ø 2-3/8" (60mm)
OFF
ON
2-3/8" (60mm)
2-3/8" (60mm)
Top of Sink Deck
Top of Sink Deck
3-1/8" (79mm)
3-1/8" (79mm)
11-3/8" (289mm)
11-5/8" (295mm)
28-7/8" to 40-7/8" (733mm to 1038mm) to finished floor 1-3/8" (35mm) maximum
1-3/8" (35mm) maximum
27-1/4" to 39-1/4" (692mm to 997mm) to finished floor
Ø 7/8" (22mm)
Ø 7/8" (22mm)
Mounting Pattern
Ø 3/16" (5mm)
2" (51mm)
Ø 1-1/8" (29mm)
| 4055_EFX_Quick-Compliance-Guide-Booklet |
| Bradley S19-2000_Emergency_Mixing_Valve |
| Bradley_EyeFaceWash_S19-270C_E |