This document provides standard drawings and specifications for gabion retaining walls to be used in the repair of landslides along roadways in Anasco, Puerto Rico under Solicitation Number 693C73-23-B-000009. The project involves embankment stabilization, gabion and gravity retaining walls, drainage installation, pavement reconstruction, guardrails, signage, and other work. Bids from certified small businesses will be accepted with an estimated price range of $2,000,000 to $5,000,000. Bid documents can be found on www.sam.gov by searching for the solicitation number. Bids are due on the date specified in Block 13a of the SF1442 solicitation form. The annual representations and certifications must be completed on www.sam.gov and www.dol.gov/vets/vets4212.htm.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B (Base)
SEE SPECIAL NOTE 3
CASE 1. STEP-FRONT GABION WITH LIVE SURCHARGE AND 2:1 SLOPE
GABI 09
APRIL-28-2021
GABIONS STEP-FRONT
GRAVITY WALL
STANDARD DRAWING APPROVAL
RECOMMENDED BY: DATE: APPROVED BY:
INTERIM STANDARD DRAWING
3'-0"(OFFSET)
0.2M (8 IN) UNDERDRAIN PIPE
(SEE GENERAL NOTE 5)
T
BACKFILL OR EMBANKMENT
(SEE GENERAL NOTE 3)
SURCHARGE 260 PSF
GEOTEXTILE (SEE GENERAL NOTE 4)
EXISITNG SLOPE
2:1 MAX. SLOPE OR FLATTER
2:1 MAX. SLOPE
OR FLATTER
CENTER LINE OF ROAD
1.52M MIN. FOR STEP-FRONT WALL
IN SITE WHERE LEAN CONCRETE BASE ARE
DIFICULT OR NOT RECOMMENDED BY THE
ENGINEER (SEE GENERAL NOTE 7)
1.
4M
M
IN
WALL ANGLE= 6 DEGREES
EXCAVATION (SEE GENERAL NOTE 8)
LEAN CONCRETE (SEE GENERAL NOTE 6)
H (C
O U
R
SE
S)
*SPECIAL NOTES:
*1. THE DESIGN IS BASED ON THE DESIGN ASSUMPTIONS FOR MATERIAL
PROPERTIES, LOADING CONDITIONS, AND GEOMETRY. DIFFERENCES TO THESE
SHOULD BE EVALUATED TO THE IMPACT TO THE DESIGN.
*2. NOTE THAT THERE IS A DIFFERENT COHESION REQUIREMENT FOR THE
FOUNDATION SOILS FOR TALLER STRUCTURES. SEE: “GABION STANDARD
DRAWING WAS DEVELOPED UNDER THE FOLLOWING CONDITIONS OR
ASSUMPTIONS” NOTES 7C AND 7D
3. ROW LIMITS DEPENDS ON ROW PLANS, SLOPE CONDITIONS AND AS
INSTRUCTED BY THE ENGINEER.
B(BASE)
DESIGN REFERENCES
1. AASHTO LRFD 9th Ed. 2020– BRIDGE DESIGN SPECIFICATIONS
2. PUERTO RICO BUILDING CODE AS AMMENDEND 2018
3. INTERNATIONAL BUILDING CODE (IBC 2018) AND ASCE-7 16
GABION STANDARD DRAWING WAS DEVELOPED UNDER THE FOLLOWING CONDITIONS OR ASSUMPTIONS:
1. EARTHQUAKE – GENERAL MAX EXPECTED ROCK ACCELERATION BASED ON ASCE-7 16 FOR PUERTO RICO (OBTAIN USING ATC
HAZARDS BY LOCATION)
a. ASSUMED SITE LOCATION: PUERTO RICO, RISK CATEGORY II, SITE CLASS “D”
b. PGA= 0.501g (MCEG PEAK GROUND ACCELERATION)
c. FPGA = 1.2 (SITE AMPLIFICATION FACTOR)
d. AS PER AASHTO LRFD 3.10.4 AS = FPGA X PGA =1.2 x 0.501= 0.601g > 0.4g (SEISMIC ANALYSIS IS MANDATORY).
e. FOR MODULAR GRAVITY WALLS (GABION WALL) CAPABLE TO DEFORM, SHALL BE AS AASHTO LRFD C11.6.5.2.2, USE KH = 0.5KH0= 0.3g
2. VERIFY AT STRENGTH LIMIT STATES (FOR OVERALL STABILITY, BEARING, SLIDING ECCENTRICITY AND STRUCTURAL FAILURE)
3. VERIFY AT EXTREME EVENT LIMIT STATE (OVERALL STABILITY FAILURE, BEARING, SLIDING ECCENTRICITY AND STRUCTURAL
FAILURE)
4. FOR LIVE SURCHARGE A MINIMUM OF 260 PSF WAS USED FOR STRENGTH LIMIT STATES (IN CASES WHERE LIVE SURCHARGE IS EXPECTED. WHEN USED IN EXTREME EVENT LIMIT STATE COMBINATION AASHTO LRFD 3.4.1 ALLOWS A REDUCTION IN LIVE LOAD
OR 50% (�EQ = 0.5).
5. ASSUMED UNIT WEIGHT OF GABIONS = 110 PCF
6. �Qi > �Rn IN POUNDS PER SQUARE FEET (PSF) AS PER TABLE
7. ASUMED SOIL PROPERTIES AT WALL BASE, BACKFILL OR SUSTAIN SOIL
a. ASSUMED WEIGHT OF SOIL = 120 PCF
b. ANGLE OF INTERNAL FRICTION (�) = 280
c. COHESION, C= 150 PSF (FOR 1 TO 4 COURSES)
d. COHESION, C=600 PSF (FOR 5 TO 7 COURSES ONLY)
GENERAL NOTES:
1. GABIONS SHALL FOLLOW STANDARD SPECIFICATION 614- GABIONS
2. EMBANKMENT MATERIAL SHALL FOLLOW STANDARD SPECIFICATION 203 – EXCAVATION AND EMBANKMENT.
3. BACKFILL MATERIAL AS PER STANDARD SPECIFICATION 206
4. GEOTEXTILE SHALL FOLLOW STANDARD SPECIFICATION 712- MISCELLANEOUS MATERIALS
5. UNDERDRAIN PIPE SHALL FOLLOW STANDARD SPECIFICATION 605 – UNDERDRAINS
6. CONCRETE FOR WALL BASE (LEAN CONCRETE) SHALL FOLLOW STANDARD SPECIFICATION 305 – LEAN CONCRETE BASE
a. THE LEAN CONCRETE BASE NEED TO BE "ROUGH OR COARSE" TO IMPROVE FRICTION BETWEEN GABION WALL AND
CONCRETE
b. THICKNESS CONCRETE WALL BASE=0.15M, LENGTH=WALL LENGTH, WIDTH=WALL BASE (B FROM TABLE) +0.2M
7. IN SITE LOCATIONS WHERE LEAN CONCRETE BASE ARE DIFFICULT OR NOT RECOMMENDED BY THE ENGINEER AN ALTERNATIVE TO THE LEAN CONCRETE BASE SHALL BE USE T=0.3M OF "1 INCH CRUSH STONE", BUT SHALL BE A SUBSIDIARY OBLIGATION UNDER
STANDARD SPECIFICATION - 614 GABIONS
8. EXCAVATION SHALL FOLLOW STANDARD SPECIFICATION 206 – EXCAVATION FOR STRUCTURES
B (BASE)
1'-6" (OFFSET)
SEE SPECIAL NOTE 3
T
2:1 OR FLATTER
EXISITNG SLOPE
CASE 2. STEP-BACK GABION WITH LIVE SURCHARGE AND 2:1 SLOPE
BACKFILL OR EMBANKMENT
(SEE GENERAL NOTE 3)
(WHEN FAILURE IS AT ROAD EDGE)
EMBANKMENT MATERIAL (SEE GENERAL NOTE 2)
SURCHARGE 260 PSF
GEOTEXTILE (SEE GENERAL NOTE 4)
EXCAVATION (SEE GENERAL NOTE 8)
WALL ANGLE =6 DEGREES
GABI 10
APRIL-28-2021
GABIONS STEP-BACK
GRAVITY WALL
STANDARD DRAWING APPROVAL
RECOMMENDED BY: DATE: APPROVED BY:
INTERIM STANDARD DRAWING
CENTER LINE OF ROAD
IN SITE LOCATIONS WHERE LEAN CONCRETE BASE
ARE DIFFICULT OR NOT RECOMMENDED BY
THE ENGINEER (SEE GENERAL NOTE 7)
0.2M (8 IN) UNDERDRAIN PIPE (SEE GENERAL NOTE 5)
LEAN CONCRETE (SEE GENERAL NOTE 6)
H (C
O U
R S
ES
2:1 FLATTER
OR EXISTING CONDITION
1.
4M
M
IN
1.4M MIN.
*SPECIAL NOTES:
*1. THE DESIGN IS BASED ON THE DESIGN ASSUMPTIONS FOR MATERIAL
PROPERTIES, LOADING CONDITIONS, AND GEOMETRY. DIFFERENCES TO THESE
SHOULD BE EVALUATED TO THE IMPACT TO THE DESIGN.
*2. NOTE THAT THERE IS A DIFFERENT COHESION REQUIREMENT FOR THE
FOUNDATION SOILS FOR TALLER STRUCTURES. SEE: “GABION STANDARD
DRAWING WAS DEVELOPED UNDER THE FOLLOWING CONDITIONS OR
ASSUMPTIONS” NOTES 7C AND 7D
3. ROW LIMITS DEPENDS ON ROW PLANS, SLOPE CONDITIONS AND AS
INSTRUCTED BY THE ENGINEER.
DESIGN REFERENCES
1. AASHTO LRFD 9th Ed. 2020– BRIDGE DESIGN SPECIFICATIONS
2. PUERTO RICO BUILDING CODE AS AMMENDEND 2018
3. INTERNATIONAL BUILDING CODE (IBC 2018) AND ASCE-7 16
GABION STANDARD DRAWING WAS DEVELOPED UNDER THE FOLLOWING CONDITIONS OR ASSUMPTIONS:
1. EARTHQUAKE – GENERAL MAX EXPECTED ROCK ACCELERATION BASED ON ASCE-7 16 FOR PUERTO RICO (OBTAIN USING ATC
HAZARDS BY LOCATION)
a. ASSUMED SITE LOCATION: PUERTO RICO, RISK CATEGORY II, SITE CLASS “D”
b. PGA= 0.501g (MCEG PEAK GROUND ACCELERATION)
c. FPGA = 1.2 (SITE AMPLIFICATION FACTOR)
d. AS PER AASHTO LRFD 3.10.4 AS = FPGA X PGA =1.2 x 0.501= 0.601g > 0.4g (SEISMIC ANALYSIS IS MANDATORY).
e. FOR MODULAR GRAVITY WALLS (GABION WALL) CAPABLE TO DEFORM, SHALL BE AS AASHTO LRFD C11.6.5.2.2, USE KH = 0.5KH0= 0.3g
2. VERIFY AT STRENGTH LIMIT STATES (FOR OVERALL STABILITY, BEARING, SLIDING ECCENTRICITY AND STRUCTURAL FAILURE)
3. VERIFY AT EXTREME EVENT LIMIT STATE (OVERALL STABILITY FAILURE, BEARING, SLIDING ECCENTRICITY AND STRUCTURAL FAILURE)
4. FOR LIVE SURCHARGE A MINIMUM OF 260 PSF WAS USED FOR STRENGTH LIMIT STATES (IN CASES WHERE LIVE SURCHARGE IS EXPECTED. WHEN USED IN EXTREME EVENT LIMIT STATE COMBINATION AASHTO LRFD 3.4.1 ALLOWS A REDUCTION IN LIVE LOAD OR
50% (�EQ = 0.5).
5. ASSUMED UNIT WEIGHT OF GABIONS = 110 PCF
6. �Qi > �Rn IN POUNDS PER SQUARE FEET (PSF) AS PER TABLE
7. ASUMED SOIL PROPERTIES AT WALL BASE, BACKFILL OR SUSTAIN SOIL
a. ASSUMED WEIGHT OF SOIL = 120 PCF
b. ANGLE OF INTERNAL FRICTION (�) = 280
c. COHESION, C= 150 PSF (FOR 1 TO 4 COURSES)
d. COHESION, C=600 PSF (FOR 5 TO 7 COURSES ONLY)
GENERAL NOTES:
1. GABIONS SHALL FOLLOW STANDARD SPECIFICATION 614- GABIONS
2. EMBANKMENT MATERIAL SHALL FOLLOW STANDARD SPECIFICATION 203 – EXCAVATION AND EMBANKMENT.
3. BACKFILL MATERIAL AS PER STANDARD SPECIFICATION 206
4. GEOTEXTILE SHALL FOLLOW STANDARD SPECIFICATION 712- MISCELLANEOUS MATERIALS
5. UNDERDRAIN PIPE SHALL FOLLOW STANDARD SPECIFICATION 605 – UNDERDRAINS
6. CONCRETE FOR WALL BASE (LEAN CONCRETE) SHALL FOLLOW STANDARD SPECIFICATION 305 – LEAN CONCRETE BASE
a. THE LEAN CONCRETE BASE NEED TO BE "ROUGH OR COARSE" TO IMPROVE FRICTION BETWEEN GABION WALL AND
CONCRETE
b. THICKNESS CONCRETE WALL BASE=0.15M, LENGTH=WALL LENGTH, WIDTH=WALL BASE (B FROM TABLE) +0.2M
7. IN SITE LOCATIONS WHERE LEAN CONCRETE BASE ARE DIFFICULT OR NOT RECOMMENDED BY THE ENGINEER AN ALTERNATIVE TO THE LEAN CONCRETE BASE SHALL BE USE T=0.3M OF "1 INCH CRUSH STONE", BUT SHALL BE A SUBSIDIARY OBLIGATION UNDER STANDARD
SPECIFICATION - 614 GABIONS
8. EXCAVATION SHALL FOLLOW STANDARD SPECIFICATION 206 – EXCAVATION FOR STRUCTURES