Pre-Fabricated_Site_Shelter_Spec.pdf
PDF 129 KB Posted
- Attached to
- Pettis Park Pavilion State and local contract opportunity
- Solicitation number
- 19-25-CIP
- Issued by
- Volusia County, Florida
About this file
This document is a technical specification section (Section 10 73 46) for pre-fabricated site shelters for the Pettis Park Pavillion project in New Smyrna Beach, Florida. The specification details the procurement of a 16' x 24' rectangular gable-style pavilion with a 3:12 roof pitch and 7'-6" eave height, to be manufactured by RCP Shelters, Inc. The project involves a single pre-engineered shelter constructed with Southern Yellow Pine glue laminated wood, structural steel columns, and a Galvalume metal roof system with exposed fasteners. The shelter will be factory-finished with Sherwin Williams semi-transparent wood stain and powder-coated steel components, with the final color to be selected by the owner.
The technical specification includes comprehensive requirements for structural components, manufacturing standards, and installation procedures. Manufacturer qualifications include a minimum of five years of experience in designing pre-fabricated glued laminated wood shelters, AISC and AITC memberships, and AWS-certified welding standards. The project requires digitally certified shop drawings with a professional engineer's state stamp, and the manufacturer must provide a minimum ten-year warranty against defects. The shelter will be shipped knocked down to minimize shipping charges, with specific packaging and protection requirements to ensure the integrity of the materials during transit and storage. Additional specifications cover steel finishing processes, wood species and treatments, and installation guidelines to ensure compliance with federal, state, and local building and safety codes.
View the file
Other files for this state and local contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pettis Park Pavillion New Smyrna Beach, FL SECTION 10 73 46 - 1 8/22/2025
SECTION 10 73 46
PRE-FABRICATED SITE SHELTERS
PART 1 GENERAL
1.1 SUMMARY
A. Design, fabrication, finishing, and delivery of pre-engineered, glue laminated wood, factory-fabricated site shelter.
B. Site work related to installation, by Contractor or Owner, including:
1. Unloading and temporary storage, if any.
2. Soil testing, if necessary.
3. Site preparation.
4. Column foundations, rebar, anchor bolts, and anchor embedment.
5. Concrete slab and embedment.
6. Erection.
7. Field touch up painting of factory finishes, if necessary.
C. Site access for delivery vehicles shall be provided by Owner.
1.2 SYSTEM DESCRIPTION
A. Design shall meet or exceed applicable building code.
B. Pre-Engineered, pre-fabricated packages shall include laminated wood beams, structural steel columns, T&G wood roof deck, wood fascia, and column to beam connection fasteners.
C. Pre-engineered, pre-fabricated package shall be designed as a fixed base, heavy timber construction structure. Superstructure components (columns, beams, & connection) shall be factory pre-cut and pre-drilled. Roof deck shall be delivered in specified lengths such that joints occur over beams for minimal cutting, Fascia and nailer shall be delivered in industry standard lengths and field cut by installer.
D. Field labor required to install the pre-fabricated parts. Structure is shipped knocked down. Onsite welding shall not be required or permitted.
1.3 REFERENCES
A. American National Standard for Wood Products – Structural Glued Laminated Timber (ANSI A- 190.1)
B. American Institute of Timber Construction (AITC)
C. American Plywood Association (APA)
D. Engineered Wood Association (EWA)
New Smyrna Beach, FL SECTION 10 73 46 - 2 8/22/2025
E. American Society of Testing Material (ASTM)
1. ASTM A500 - Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
2. ASTM A572 - Standard Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel
3. ASTM F1554 – Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
F. American Institute of Steel Construction (AISC)
G. American Welding Society (AWS)
H. Steel Structures Painting Council (SSPC); SSPC-SP10 - Near-White Blast Cleaning
I. Leadership in Energy and Environmental Design (LEED)
J. OSHA Standards 29 CFR, Part 1926, Subpart R (Steel Erection), Standard Number 1926.755:
Compliance requires a minimum of four anchor bolts per column.
1.4 QUALITY ASSURANCE
A. Designer Qualifications: Design under direct supervision of a Professional Engineer experienced in design of this type of work and licensed in the State where the Project is located.
B. Manufacturer Qualifications: Company experienced in design and manufacture of shelters of the type specified, and having the following:
1. Minimum five years of experience in design and fabrication of pre-fabricated glued laminated wood shelters.
2. Three references of similar shelters completed within the past two years within a 100 mile radius of project.
3. Fabricator membership in American Institute of Steel Construction (AISC), requiring quality control documentation and procedures. Provide current AISC shop certification upon request.
4. All welding shall be performed to AWS standards by AWS certified welders. Provide welding certification upon request.
5. Fabricator membership in AITC and APA/EWS. Members shall be marked (in an unseen finish product location) with an AITC or APA/EWS Quality Mark. Additionally, a Certificate of Conformance shall be provided, indicating conformance with ANSI/AITC A190.1-2002.
C. Perform the work in accordance with applicable federal, State, and local building and safety codes and regulations.
1.5 SUBMITTALS
A. Set of digitally certified shop drawings, showing all details of construction, including foundation sizes, reinforcement, and locations.
1. Provide the licensed professional engineer’s state stamp or seal on the shop drawings.
New Smyrna Beach, FL SECTION 10 73 46 - 3 8/22/2025
2. Provide the licensed professional engineer’s state stamp or seal on the structural calculations.
B. Selection Samples: For each finish product specified, color charts representing manufacturer's full range of available colors.
C. Warranty
1. Provide minimum ten-year warranty against manufacturer defects.
2. Provide roofing manufacturer’s limited warranty.
1.6 DELIVERY, STORAGE, AND PROTECTION
A. Individually wrap factory-finished structural components in fiber reinforced paper to protect the finish during transit.
B. Wood roof deck shall be load wrapped and banded together in bundles that do not exceed 2,000 lbs.
C. Shipped knocked down for minimal shipping charges.
D. Deliver products to project site in manufacturer's protective packaging.
E. Follow shelter manufacturer's recommendations and instructions, including those printed on the shop drawings. To minimize damage during unloading, use only padded forks or non-marring slings.
F. Prefinished materials not being immediately installed must be protected from sunlight.
G. Store products in manufacturer's unopened packaging well off the ground and covered out of weather until ready for installation.
PART 2 PRODUCTS
2.1 GENERAL
A. Model: LW-G1624-03 as manufactured by RCP Shelters, Inc.
B. Size and dimensions
1. Shape: rectangle
2. Dimensions: 16’ x 24’
3. Roof Style: gable
4. Roof Pitch: 3:12
5. Eave Height: 7’-6”
6. Quantity: 1
C. Approved Manufacturer: RCP Shelters, Inc. (Or Approved Equal)
1. 2100 SE Rays Way, Stuart, FL 34994.
2. Toll Free: 800-525-0207
New Smyrna Beach, FL SECTION 10 73 46 - 4 8/22/2025
3. Direct Line: (772) 288-3600
4. Fax: 772-288-0207
5. Website: www.rcpshelters.com
6. Email: info@rcpshelters.com
2.2 STRUCTURAL COMPONENTS
A. Steel
1. Columns: ASTM A500 Grade C structural steel tube. The following shapes are prohibited: I-beams, wide-flange beams, C-channels, Z-shapes.
2. Plates: ASTM A572 Grade 50
3. Finish: Powder Coat
a. Pre-blast inspection to catch and remove oil, grease, and other coatings impeding contaminants
b. Steel grit blasted to near white condition in accordance with SSPC-SP10, removing all oil residue, mil scale, weld spatter, and slag
c. Five stage phosphate wash (includes detergent, phosphate, rust protectant sealant)
d. Epoxy powder coat primer
e. Topcoat of TGIC polyester powder coat; color to be selected from manufacturer’s standard color chart by Owner.
f. All materials inspected to meet 100% coating, proper cure, film thickness, and impact resistance
g. Wet-coat alternatives shall not be acceptable.
4. Fasteners: 4 gauge hot-dipped galvanized annular ring nails
5. Column Anchors: ASTM F1554 Grade 36, provided by Contractor or Owner, attached to top of foundation, recessed below slab on grade.
B. Glued Laminated Wood
1. Species: Southern Yellow Pine
2. Appearance Grade: Architectural
3. Lamination Thickness: 2” Nominal
4. Adhesive: Resorcinol
5. Stress Combination: 24F-V3
6. Preservation Treatment: None
7. Size: Per engineered drawings
8. Stain: factory applied Sherwin Williams semi-transparent wood stain.
C. Structural Wood Roof Deck
1. Species: #1 grade Southern Yellow Pine, kiln dried
2. Treatment: none
3. Size: nominal 2” x 8”
4. Pattern: center matched, tongue and groove, with veed edges 1 side (EV1S)
5. Stain: factory applied Sherwin Williams semi-transparent wood stain.
http://www.rcpshelters.com/ mailto:info@rcpshelters.com
New Smyrna Beach, FL SECTION 10 73 46 - 5 8/22/2025
D. Fascia
1. Species: #1 grade Alaskan Yellow Cedar
2. Size: nominal 2” x 6”
3. Stain: factory applied Sherwin Williams semi-transparent wood stain.
E. Metal Roof System: Galvalume® metal roof panels with exposed fasteners.
1. Profile: 5V
2. Panel Gauge: minimum 26-gauge
3. Panel Width: 3'-0"
4. Panel Length: Precut to the length from the eave to the ridge
5. Panel Orientation: Ribs shall run with the pitch of the roof for proper drainage
6. Trim: Matching roof trim and fasteners
7. Finish: Factory pre-finished with Kynar 500® paint system; color to be selected by Owner from standard color chart
8. Underlayment: HydraShell MAX
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that site earthwork has been performed as required for satisfactory installation.
3.2 PREPARATION
A. Install footings and column anchors of size, design, and location as specified by shelter manufacturer on approved shop drawings.
3.3 INSTALLATION
A. Perform installation in accordance with applicable federal, State, and local building and safety codes.
B. Structural special inspections, if required, are shall be arranged and paid for by the Contractor or
Owner.
C. Install shelter in accordance with manufacturer's approved shop drawing and good construction practices.
D. Install slab in accordance with shelter manufacturer's shop drawings. Slab perimeter dimensions determined by Owner.
3.4 CLEANING AND PROTECTION
A. Clean installed work to like-new condition.
B. Protect installed products until completion of project.
https://marcoindustries.com/products/underlayment/hydrashell-max/
New Smyrna Beach, FL SECTION 10 73 46 - 6 8/22/2025
C. Touch-up, repair, or replace damaged finishes before Substantial Completion. Touch up paint provided by manufacturer.
END OF SECTION