PPCC DQ 16-779 Art Classroom Ventilation Question Answer .pdf

PDF 149 KB Posted

Attached to
PPCC DQ 16-779 CON 1573 & CON 1574
Solicitation number
DQ1 GJJA 2016000367 2
Issued by
El Paso County, Colorado

About this file

This is a Question and Answer document related to a state and local contract opportunity for art classroom ventilation work at Pikes Peak Community College (PPCC) in Colorado, specifically for projects designated as DQ 16-779, CON 1573, and CON 1574. The document addresses technical specifications and design clarifications for ventilation system installation at PPCC's Centennial Campus. Key project details include exhaust fan placement restrictions, ductwork routing requirements, and conflict resolution between new and existing mechanical systems. The document references Addendum #1, which contains maps, drawings, letters, and supporting documentation available through PPCC's upload portal, providing bidders with detailed design guidance and spatial constraints for the proposed work.

The Q&A responses establish specific technical parameters for the ventilation installation, including that the exhaust fan location at Centennial Campus cannot be repositioned to the north due to structural coordination constraints, with the fan set back 10 feet from the low parapet. Regarding ductwork placement, contractors are instructed to position new ductwork as high as possible in the space while avoiding direct contact with structural elements to minimize vibration transmission. Where conflicts with existing ductwork occur, the new 20x10 ductwork (or equivalent) should be routed to the south of existing systems to avoid interference. These technical clarifications in the addendum serve to guide bidders in preparing accurate proposals and ensuring compliance with PPCC's engineering and operational requirements.

View the file

Other files

File Type Posted
PPCC DQ 16-779, Art Classroom HVAC CC & DTS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Art Classroom Ventilation CC & DTS

PPCC DQ 16-779

Question/Answer

1. Addendum #1 Map/Drawings, Letter, and Cover are located at https://apps.ppcc.edu/upload-purchasing/?key=1c70c5322cf293f702aa5afa444333c2.

2. Is there any leeway for the exhaust fan location at the Centennial Campus?

a. There is no leeway to the north, the fan is set back 10’-0” from the low parapet and location has been coordinated with structural engineer.

3. What is the height of the ductwork at Centennial campus?

a. Where exposed, keep new ductwork as high in the space as possible, however, we do not want ductwork resting against structure to minimize vibration transmission.

4. Crossing existing ductwork will not fit?

a. New 20x10 or equivalent ductwork can route to the south of the existing ductwork to avoid the noted conflict. Refer to attached addendum #1 documents.