Asbestos and Lead-Containing Paint Survey Report

This is a demolition survey report prepared by GLE Associates, Inc. for Gainesville Regional Utilities (GRU) documenting asbestos-containing materials (ACM) and lead-containing paint (LCP) identified in four downtown structures: the Waste Water Admin Building, Waste Water Warehouse, Field Services Building, and Electric Operations Offices and Warehouse located in Gainesville, Florida. The survey was conducted June 9-11, 2025, by EPA/AHERA accredited inspectors Mark L. Fohn and Dario D. Arazi in accordance with National Emission Standards for Hazardous Air Pollutants (NESHAP) requirements. A total of 207 bulk material samples were collected from 65 homogeneous areas and analyzed by Polarized Light Microscopy (PLM) at Arrowhead Technologies, LLC, an NVLAP-accredited laboratory. Additionally, 50 paint samples were tested by EMSL Analytical, Inc., an EPA-recognized National Lead Laboratory Accreditation Program (NLLAP) facility using EPA Method 3050B/7000B.

The survey identified multiple ACM requiring regulated removal and disposal. Friable and Category II non-friable RACM found include: white hard block pipe insulation containing 8% amosite and 2% chrysotile (800 linear feet) in the Electric Operations building; olive sheet vinyl backing containing 35% chrysotile (1,000 square feet) in the Field Services building; and grey cementitious panels containing 15% chrysotile (1,200 square feet) in the Electric Operations building. Category I non-friable materials include grey exterior caulk (420 linear feet) and mechanical equipment flashing aluminum coating (80 square feet) in the Waste Water Admin building, and grey interior and exterior caulk (440 linear feet combined) in the Waste Water Warehouse. Lead-containing paint was detected in 25 of 50 samples, with concentrations ranging from 0.0068% to 12.8% by weight, found on various substrates including metal surfaces, concrete, and structural components throughout all four buildings. The report recommends that licensed asbestos abatement contractors remove all identified RACM prior to demolition and that lead-containing materials be managed in accordance with OSHA Lead in Construction Standard 29 CFR 1926.62.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2610 NW 43rd Street, Suite 2A Gainesville, Florida 32606

352-335-6648 • Fax 352-335-6187

DEMOLITION

ASBESTOS AND LEAD-CONTAINING

PAINT SURVEY REPORT

Gainesville Regional Utilities – Downtown Structures Waste Water Admin, Waste Water Warehouse, Field

Services, and Electric Operations Offices and Warehouse

Gainesville, Florida 32601

GLE Project No.: 25000-31280

Prepared for:

Mr. Andrew Drummond Gainesville Regional Utilities - GRU Facilities

Manager 301 SE 4th Avenue

July 2025

Prepared by:

GLE Associates, Inc.

2610 NW 43rd Street, Suite 2A | Gainesville, Florida 32606 | 352-335-6648 | Fax: 352-335-6187

Tampa | Orlando | Ft. Lauderdale | Miami | Jacksonville | Atlanta | Nashville Architecture AR 0007729 • Engineer RY 5483 • Asbestos ZA 0000034 • Geology PG 1737

July 16, 2025

Mr. Andrew Drummond Sent via email: DrummondAG@gru.com Gainesville Regional Utilities - GRU Facilities Manager 301 SE 4th Avenue Gainesville, Florida 32601

RE: Demolition Asbestos and Lead-Containing Paint Survey Report

Gainesville Regional Utilities – Downtown Structures Waste Water Admin, Waste Water Warehouse, Field Services, and Electric Operations Offices and Warehouse

GLE Project No.: 25000-31280

Dear Mr. Drummond:

GLE Associates, Inc. (GLE) performed a demolition survey for asbestos-containing materials (ACM) and lead containing paint (LCP) on June 9-11, 2025, at the Waste Water Admin Building, the Waste Water Warehouse, the Field Services Building, and the Electric Operations Offices and Warehouse, located in Gainesville, Florida. The survey was performed by Mr. Mark L. Fohn and Mr. Dario D. Arazi with GLE. This report outlines the sampling and testing procedures, and presents the results along with our conclusions and recommendations.

GLE appreciates the opportunity to serve as your consultant on this project. If you should have any questions, or if we can be of further service, please do not hesitate to call.

Sincerely, GLE Associates, Inc.

Michael D. Harrell Robert B. Greene, PE, PG, CIH, LEED AP Gainesville Department Manager President

Florida LAC# EA 0000009

MDH/MLF/PSZ/RBG/mb

\\gvlsvr\sys\Work\Asbestos\'25\25000\31280 - GRU Four Downtown Structures ACM and Lead\Report\ACMPbSurveyReport.docx mailto:DrummondAG@gru.com

TABLE OF CONTENTS

1.0 INTRODUCTION 1

1.1 Introduction 1

1.2 Facility Description 1

2.0 ASBESTOS 3

2.1 Asbestos Survey Procedures 3

2.2 Identified Suspect Asbestos-Containing Materials 4

Table 2.2-1 — Summary of Homogeneous Sampling Areas - Waste Water Admin Table 2.2-2 — Summary of Homogeneous Sampling Areas - Waste Water Warehouse Table 2.2-3 — Summary of Homogeneous Sampling Areas - Field Services Table 2.2-4 — Summary of Homogeneous Sampling Areas - Electric Operations Offices and Warehouse

3.0 LEAD-CONTAINING PAINT 10

3.1 Lead-Containing Paint Survey Procedures 10

3.2 Identified Suspect Lead-Containing Paint 10

Table 3.2-1 — Summary of Suspect Lead-Containing Paint Analytical Results - Waste Water Admin Table 3.2-2 — Summary of Suspect Lead-Containing Paint Analytical Results - Waste Water Warehouse Table 3.2-3 — Summary of Suspect Lead-Containing Paint Analytical Results - Field Services Table 3.2-4 — Summary of Suspect Lead-Containing Paint Analytical Results - Electric Operations Offices and Warehouse

4.0 CONCLUSIONS AND RECOMMENDATIONS 17

4.1 Asbestos - General 17

4.1.1 Asbestos - Specific 18

4.2 Lead-Containing Paint 19

5.0 LIMITATIONS AND CONDITIONS 20

APPENDICES

Appendix A – Analytical Results and Chains of Custody Appendix B – Personnel and Laboratory Certifications

1.0 INTRODUCTION

1.1 INTRODUCTION

The purpose of this demolition survey was to identify accessible asbestos-containing materials (ACMs) and lead-containing paint (LCP) and their general locations within the Waste Water Admin Building, the Waste Water Warehouse, the Field Services Building, and the Electric Operations Offices and Warehouse, located in Gainesville, Florida. The asbestos survey was conducted pursuant to National Emission Standards for Hazardous Air Pollutants (NESHAP, 40 CFR 61) requirements, associated with the scheduled demolition plans. The survey was performed on June 9-11, 2025, by Mr. Mark L. Fohn and Mr. Dario D. Arazi , Environmental Protection Agency/Asbestos Hazard Emergency Response Act (EPA/AHERA) accredited inspectors. The scope of this survey did not include demolition of any building components, evaluation of architectural plans, or removal cost estimating.

1.2 FACILITY DESCRIPTION

A summary of the facility investigated is outlined in the table below.

Waste Water Admin

Facility Type: Administrative Construction Date: Unknown Number of Floors: One

Exterior Floor Support: Concrete Slab on Grade Wall Support: Concrete Block (CMU)

Exterior Finish: Paint, Stucco Roof System Type: Built Up (Modified Bitumen)

Interior Wall Substrate: Drywall and Joint Compound Wall Finishes: Paint, Texture, Cove Base Floor Finishes: Vinyl Floor Tile, Ceramic Tile, Carpet, Terrazzo Ceiling System: Drywall and Joint Compound, Suspended Ceiling System Ceiling Finishes: Paint, Texture, Suspended Ceiling Tiles

Waste Water Warehouse

Facility Type: Commercial Construction Date: Unknown Number of Floors: One

Exterior Floor Support: Concrete Slab on Grade Wall Support: Concrete Block (CMU)

Exterior Finish: Paint Roof System Type: Built Up (Modified Bitumen)

Interior Wall Substrate: Drywall and Joint Compound, CMU Wall Finishes: Paint, Cove Base Floor Finishes: Ceramic Tile Ceiling System: Suspended Ceiling System Ceiling Finishes: Suspended Ceiling Tiles

Field Services

Facility Type: Administrative Construction Date: Unknown Number of Floors: One

Exterior Floor Support: Concrete Slab on Grade Wall Support: Concrete Block (CMU)

Exterior Finish: Paint, Stucco, Wood Siding Roof System Type: Built Up (Modified Bitumen)

Interior Wall Substrate: Drywall and Joint Compound, Plaster Wall Finishes: Paint, Texture, Cove Base Floor Finishes: Vinyl Floor Tile, Carpet, Sheet Vinyl Flooring, Terrazzo Ceiling System: Drywall and Joint Compound, Suspended Ceiling System Ceiling Finishes: Paint, Suspended Ceiling Tiles

Electrical Operations Offices and Warehouse

Facility Type: Administrative, Warehouse Construction Date: Unknown Number of Floors: One

Exterior Floor Support: Concrete Slab on Grade Wall Support: Concrete Block (CMU), Wood Framing

Exterior Finish: Paint, Brick Roof System Type: Built Up (Modified Bitumen), Asphalt Shingles

Interior Wall Substrate: Drywall and Joint Compound, Plaster Wall Finishes: Paint, Texture, Wall Covering, Cove Base Floor Finishes: Vinyl Floor Tile, Ceramic Tile, Carpet, Terrazzo Ceiling System: Suspended Ceiling System Ceiling Finishes: Suspended Ceiling Tiles

2.0 ASBESTOS

2.1 ASBESTOS SURVEY PROCEDURES

The survey was performed by visually observing accessible areas within the scope of work.

EPA/AHERA accredited inspectors performed the visual observations (refer to Appendix B for personnel qualifications).

After the overall visual survey was completed, representative sampling areas were determined.

The surveyors delineated homogeneous areas of suspect materials and samples of each material were obtained, in general accordance with regulations as established by the Occupational Safety and Health Administration (OSHA) and NESHAP. The field surveyors determined sample locations based on previous experience. Both friable and non-friable materials were sampled. A friable material is one that can be crushed when dry by normal hand pressure. This survey did not include the demolition of building components to access suspect material.

After completion of the fieldwork, the samples were delivered to Arrowhead Technologies, LLC, a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory for analysis. The samples were analyzed by Polarized Light Microscopy (PLM) coupled with dispersion staining, in general accordance with EPA-600/R-93/116. Utilizing this procedure, the various asbestos minerals (chrysotile, amosite, crocidolite, actinolite, tremolite, and anthophyllite) can be determined. The percentages of asbestos minerals in the samples were visually determined by the microscopist. Please note that the EPA designates all materials containing greater than one percent asbestos as an “asbestos-containing material” (ACM).

Regulated Asbestos-Containing Material (RACM) is defined as (a) Friable asbestos materials,

(b) Category I non-friable ACM that has become friable, (c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this subpart.

Category I and Category II non-friable ACM, as defined by the EPA:

Category I non-friable ACM means asbestos-containing packings, gaskets, resilient floor covering, asphalt roofing products, and pliable sealants and mastics that are in good condition and not friable, containing more than one percent asbestos, as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM.

Category II non-friable ACM means any material, excluding Category I non-friable ACM, containing more than 1 percent asbestos as determined using the methods specified in Appendix E, Subpart E, 40 CFR Part 763 Section 1, PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

2.2 IDENTIFIED SUSPECT ASBESTOS-CONTAINING MATERIALS

A total of two hundred seven (207) samples of suspect building materials were collected from the facility during the survey, representing sixty-five (65) different identified homogeneous areas. The results of the laboratory analyses are included in Appendix A.

A summary of the homogenous sampling areas of suspect ACM determined to be present is outlined in the following table.

ASBESTOS CONTENT

Expressed as percent

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-1: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

WASTE WATER ADMIN BUILDING

DW-01 Drywall/Joint Compound Walls Throughout, Restroom Ceilings NF ND 7 NIS NA M-01 Grey Particle Board SW Cubicle Area, North of Restroom F ND 3 NIS NA

M-02 12” x 12” Spline Tile (on Tack Board Walls) Various Walls Throughout F ND 3 NIS NA

M-03 White Interior Caulk Interior Doors and Windows Throughout NF ND 3 NIS NA

M-04 Grey Exterior Caulk Exterior Doors and Windows Throughout NF 3% C 3 420 LF CAT I

M-05 Grey Ceramic Tile Grout/Thin Set Men’s and Women’s Restrooms NF ND 3 NIS NA M-06 White Sink Undercoat Kitchen NF ND 3 NIS NA

MAS-01 Grey Duct Mastic Throughout NF ND 3 NIS NA PL-01 Grey Exterior Stucco Throughout NF ND 3 NIS NA

RBU-01 Built-Up Roofing (Stone/Tar/Felt) Roof NF ND 3 NIS NA RF-01 Built-Up Roof Flashing (Stone/Tar/Felt) Roof NF ND 3 NIS NA

RF-02 Mechanical Equipment Flashing Mechanical Equipment NF

Membrane ND;

Tar ND;

Felt ND;

Al. Coating 1%

3 80 SF CAT I

RF-03 Perimeter Roof Flashing Perimeter of Roof NF ND 3 NIS NA

S-01 Troweled Applied Surfacing Texture on Drywall Throughout NF ND 3 NIS NA

VB-01 4” Grey Cove Base/Beige Adhesive Throughout NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-2: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

WASTE WATER WAREHOUSE

CT-01 2’ x 2’ White Rough Design Ceiling Tiles Throughout F ND 3 NIS NA

DW-01 Drywall/Joint Compound Throughout NF ND 3 NIS NA

M-01 Grey Interior Caulk Interior Doors and Windows Throughout NF 2% C 3 220 LF CAT I

M-02 Grey Exterior Caulk Exterior Doors and Windows Throughout NF 2% C 3 220 LF CAT I

M-03 Grey Ceramic Tile Grout/Thin Set Throughout NF ND 3 NIS NA RBU-01 Built-Up Roofing (Stone/Tar/Felt) Roof NF ND 3 NIS NA RF-01 Built-Up Roof Flashing (Stone/Tar/Felt) Perimeter of Roof NF ND 3 NIS NA RF-02 Mechanical Flashing Mechanical Equipment NF ND 3 NIS NA

VB-01 4” Grey Cove Base/Beige Adhesive Throughout (Except Warehouse and Back Office) NF ND 3 NIS NA

VB-02 4” Pink Cove Base/Beige Adhesive Rear Office Storage NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-3: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

FIELD SERVICES BUILDING

CT-01 2’ x 4’ White Pinhole Ceiling Tiles Front of Building F ND 3 NIS NA

CT-02 2’ x 4’ White Directional Fissured Ceiling Tiles Back of Building F ND 3 NIS NA

DW-01 Drywall/Joint Compound Throughout NF ND 3 NIS NA

FT-01 12” x 12” Beige Floor Tile/Beige Adhesive

Restrooms/Outside of Restrooms, South Hallway NF ND 3 NIS NA

M-01 Black Sink Undercoating Back Restroom NF ND 3 NIS NA MAS-01 White Duct Mastic Throughout NF ND 3 NIS NA

PL-01 Grey Exterior Stucco Exterior NF ND 3 NIS NA

MSV-01 Olive Sheet Vinyl/Beige Adhesive South Entrance and South Office NF Sheet Vinyl ND;

Mastic ND;

Backing 35% C

3 1,000 SF

CAT II/

RACM

RBU-01 Built-Up Roofing (Stone/Tar/Felt) Roof NF ND 3 NIS NA RF-01 Built-Up Roof Flashing (Stone/Tar/Felt) Perimeter of Roof NF ND 3 NIS NA RF-02 Mechanical Flashing Mechanical Equipment NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-4: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

ELECTRIC OPERATIONS OFFICES AND WAREHOUSE

CT-01 2’ x 2’ White Rough Design Ceiling Tiles

NE Office Areas, Hallway and Offices F ND 3 NIS NA

CT-02 2’ x 2’ White Large Fissured Ceiling Tiles

NE Restroom Hallway Entrance and NE Section of Building F ND 3 NIS NA

CT-03 2’ x 2’ White Pinhole Ceiling Tiles North Entrance (Left) F ND 3 NIS NA

CT-04 2’ x 2’ White Directional Fissured Ceiling Tiles North Entrance Rooms to West F ND 3 NIS NA

CT-05 2’ x 2’ White Pinhole Ceiling Tiles SW Office Area F ND 3 NIS NA CT-06 12” x 12” White Spline Ceiling Tiles Mechanical Rooms F ND 3 NIS NA DW-01 Drywall/Joint Compound Throughout NF ND 7 NIS NA

FT-01 12” x 12” Tan-White Streak Floor Tile/Gold Adhesive NE Section of Building NF ND 3 NIS NA

FT-02 12” x 12” Dark Brown Wood Looking Floor Tile/White Adhesive Offices SE of Entrance NF ND 3 NIS NA

FT-03 12” x 12” White-Grey Streak Floor Tile/Beige Adhesive West Side Offices and Hallway NF ND 3 NIS NA

FT-04 12” x 12” Dark Grey Floor Tile/Yellow Glue SW Room NF ND 3 NIS NA

M-01 White Sink Undercoating NE Kitchen NF ND 3 NIS NA M-02 Grey Ceramic Tile Grout/Thin Set NE Restrooms NF ND 3 NIS NA M-03 White Ceramic Tile Grout/Thin Set NW Restroom NF ND 3 NIS NA M-04 Grey Sink Undercoating SW Room NF ND 3 NIS NA M-05 Black Sink Undercoating NW Room Outside of Restroom NF 5% C 3 8 SF CAT II M-06 Grey Exterior Stucco Sporadic Throughout North Side NF ND 3 NIS NA M-07 White Exterior Door Caulk Exterior Doors, West Side NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-4: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

ELECTRIC OPERATIONS OFFICES AND WAREHOUSE

M-08 Grey Exterior Aluminum Window Caulk Aluminum Windows Throughout NF ND 3 NIS NA M-09 Grey Exterior Sill Caulk Aluminum Windows Throughout NF ND 3 NIS NA M-10 Black Tar/Felt Over NE Mezzanine NF ND 3 NIS NA

MAS-01 White Duct Mastic Throughout NF ND 3 NIS NA MCP-01 Grey Cementitious Panels North Side of Building NF 15% C 3 1,200 SF CAT II

PL-01 White Smooth Coat over Grey Rough Coat Plaster Throughout NF ND 3 NIS NA

S-01 Sandy Troweled Applied Wall Texture NE Offices Outside of Restrooms NF ND 3 NIS NA

TSI-01 White Hard Block Pipe Insulation NE Restroom Chase F 8% A;

2% C

3 800 LF RACM

RF-01 White Rolled Roofing/Tar/Felt Flashing Lower Roof NF ND 3 NIS NA RR-01 White Rolled Roofing/Tar/Felt Lower Roof NF ND 3 NIS NA RS-01 White Roof Shingles/Tar/Felt Upper Roof NF ND 3 NIS NA

3.0 LEAD-CONTAINING PAINT

3.1 LEAD-CONTAINING PAINT SURVEY PROCEDURES

The lead-containing paint survey was performed by visually observing accessible painted component surfaces associated with the scope of work. The protocol used in this lead paint survey is a modified version of the survey methodology established by HUD. The protocol was modified to conform to the specific parameters of this project.

During the walk through of the facility, each area was observed and an inventory of painted surfaces was developed. The surveyor then subdivided the areas into homogeneous areas of apparent similar paint history.

Testing of the painted surfaces was performed by collecting representative paint chips. All samples were submitted to EMSL Analytical, Inc., an accredited laboratory recognized under EPA’s National Lead Laboratory Accreditation Program (NLLAP). These samples were analyzed by EPA Method 3050B/7000B and the results are reported in percentage of lead by weight of the paint sample (% Wt). Please note that any detectable concentration of lead in the paint is designated by OSHA as “lead-containing.”

3.2 IDENTIFIED SUSPECT LEAD-CONTAINING PAINT

The identified suspect lead-containing coatings are described in the following table:

1 BOLD result indicates lead-containing paint.

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-1: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

WASTE WATER ADMIN BUILDING

Pb-1 Waste Water Admin Interior Throughout Wood Doors/Frames White < 0.0064 Pb-2 Waste Water Admin Interior Doors to Exterior Metal Doors/Frames White < 0.0064 Pb-3 Waste Water Admin Interior Doors to Exterior Metal Doors/Frames Dark Brown 0.554 Pb-4 Waste Water Admin Exterior Throughout Stucco Walls Beige < 0.0064 Pb-5 Waste Water Admin Exterior Soffit Stucco Soffit White < 0.0064

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-2: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

WASTE WATER WAREHOUSE

Pb-1 Waste Water Warehouse Interior Throughout Drywall Walls White < 0.0064 Pb-2 Waste Water Warehouse Interior Sporadic Throughout Metal Doors/Frames White < 0.0064 Pb-3 Waste Water Warehouse Interior Throughout CMU Walls White < 0.0064 Pb-4 Waste Water Warehouse Interior Sporadic Throughout Metal Doors/Frames Brown < 0.0064 Pb-5 Waste Water Warehouse Interior Sporadic Throughout Metal Doors/Frames Grey < 0.0064 Pb-6 Waste Water Warehouse Exterior Throughout CMU Walls Beige < 0.0064 Pb-7 Waste Water Warehouse Exterior Throughout Concrete Curbing Yellow 3.53

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-3: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

FIELD SERVICES BUILDING

Pb-1 Field Services Interior Throughout Wood Doors/Frames White < 0.0064 Pb-2 Field Services Interior Throughout CMU Walls Off-White < 0.0064 Pb-3 Field Services Interior Throughout (Also Under Pb-2) CMU Walls Green < 0.0083 Pb-4 Field Services Exterior Throughout Wood Siding Beige < 0.0064 Pb-5 Field Services Exterior Throughout CMU Walls Beige < 0.0064 Pb-6 Field Services Exterior Throughout Metal Doors/Frames Brown 0.0600 Pb-7 Field Services Interior Throughout Drywall Walls White < 0.0064

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-4: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

ELECTRICAL OPERATIONS OFFICES AND WAREHOUSE

Pb-1 Electrical Operations Offices/Warehouse Interior NE Area of Building Drywall Walls Beige 0.106

Pb-2 Electrical Operations Offices/Warehouse Interior NE Area Offices Wood Doors/Frames/Trim White < 0.0064

Pb-3 Electrical Operations Offices/Warehouse Interior HVAC Room Plaster Walls/Ceiling Grey 0.0170

Pb-4 Electrical Operations Offices/Warehouse Interior NW Section of Building Plaster Walls/Ceiling Beige 0.232

Pb-5 Electrical Operations Offices/Warehouse Interior NW Section of Building Metal Ducts Beige 0.250

Pb-6 Electrical Operations Offices/Warehouse Interior Warehouse Metal Barn Door Brown 0.129

Pb-7 Electrical Operations Offices/Warehouse Interior Warehouse CMU Walls Mint Green 0.0182

Pb-8 Electrical Operations Offices/Warehouse Interior Warehouse Concrete Floor Yellow 8.76

Pb-9 Electrical Operations Offices/Warehouse Interior Warehouse Metal Doors/Frames Dark Brown 0.140

Pb-10 Electrical Operations Offices/Warehouse Interior Warehouse Wood Window Frames Dark Brown < 0.0064

Pb-11 Electrical Operations Offices/Warehouse Interior Warehouse Metal Handrails Orange 6.85

Pb-12 Electrical Operations Offices/Warehouse Interior Warehouse Metal I-Beams Grey 0.427

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-4: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

ELECTRICAL OPERATIONS OFFICES AND WAREHOUSE

Pb-13 Electrical Operations Offices/Warehouse Interior Warehouse CMU Walls White 0.0068

Pb-14 Electrical Operations Offices/Warehouse Interior Warehouse Drywall Walls Mint Green < 0.0064

Pb-15 Electrical Operations Offices/Warehouse Interior Warehouse Metal Stairs/Handrail Yellow 6.71

Pb-16 Electrical Operations Offices/Warehouse Interior NW Conference Room Drywall Walls White < 0.0064

Pb-17 Electrical Operations Offices/Warehouse Exterior South Metal Doors/Frames Grown 0.0500

Pb-18 Electrical Operations Offices/Warehouse Exterior East/West on South Side Concrete Wall Beige 0.176

Pb-19 Electrical Operations Offices/Warehouse Exterior Warehouse Metal Barn Door Brown 0.949

Pb-20 Electrical Operations Offices/Warehouse Exterior Warehouse, New Door Next to Barn Door Metal Door Grey < 0.0081

Pb-21 Electrical Operations Offices/Warehouse Exterior NE Mechanical Room (Old Door) Metal Door Grey 0.260

Pb-22 Electrical Operations Offices/Warehouse Exterior Throughout Metal

Gutter/Pipes/Beams Beige 0.0348

Pb-23 Electrical Operations Offices/Warehouse Exterior Around Exterior Stucco Walls Pink < 0.0064

Pb-24 Electrical Operations Offices/Warehouse Exterior Around Exterior CMU Walls Beige < 0.0064

2 The requirements of the OSHA Lead in Construction Standard 29CFR 1926.62 are invoked if any amount of lead is present in the sample;

there is no minimum concentration.

TABLE 3.2-4: SUMMARY OF SUSPECT LEAD-CONTAINING PAINT ANALYTICAL RESULTS

GAINESVILLE REGIONAL UTILITIES – DOWNTOWN STRUCTURES

WASTE WATER ADMIN, WASTE WATER WAREHOUSE, FIELD SERVICES, AND ELECTRIC OPERATIONS OFFICES AND WAREHOUSE – GAINESVILLE, FLORIDA

SAMPLE

# BUILDING INTERIOR OR

EXTERIOR LOCATION COMPONENT COLOR

LEAD

CONCENTRATION

(% BY WEIGHT)

ELECTRICAL OPERATIONS OFFICES AND WAREHOUSE

Pb-25 Electrical Operations Offices/Warehouse Exterior NE Metal Gate Beige 1.87

Pb-26 Electrical Operations Offices/Warehouse Exterior SW Metal I-Beam to

Overhang White < 0.0064

Pb-27 Electrical Operations Offices/Warehouse Exterior SW Metal Bollards Yellow 6.46

Pb-28 Electrical Operations Offices/Warehouse Exterior Handicap Parking Tarmac Blue < 0.0064

Pb-29 Electrical Operations Offices/Warehouse Exterior SW Corner of Building Signage Metal Sign Blue 6.42

Pb-30 Electrical Operations Offices/Warehouse Exterior SW Corner of Building Moveable Steps Metal Handrail/Steps Orange 12.8

Pb-31 Electrical Operations Offices/Warehouse Exterior SW Corner of Building Moveable Steps Metal Steps Green 0.183

4.0 CONCLUSIONS AND RECOMMENDATIONS

4.1 ASBESTOS – GENERAL

Asbestos-containing materials (ACMs) were identified in the scope of this survey. General and specific conclusions and recommendations are provided below.

The EPA, OSHA and the State of Florida have promulgated regulations dealing with asbestos.

For commercial building owners, the EPA NESHAP (40 CFR 61) regulations require removal of RACM, prior to conducting activities which might disturb the material. They also deal with notification, handling and disposal of asbestos.

The EPA recommends that an Operations and Maintenance (O&M) Program be developed for any facilities with ACM, and this Program should address all ACM (known and/or assumed) present. The O&M Program establishes notification and training requirements along with special procedures for working around the ACM. The O&M Program would remain in effect until all asbestos is removed.

Category I and Category II non-friable materials, as defined by the EPA, may remain within a facility during demolition with no potential cessation of work, provided they remain non-friable and the appropriate engineering controls (i.e., wet methods) are utilized, with the resulting waste disposed of as asbestos-containing waste. However, there is no guarantee that these materials will remain non-friable. If the materials become friable, then they are classified as RACM.

RACM, as defined by the EPA, must be removed prior to renovation or demolition activities that may disturb the materials.

The OSHA regulations deal with employee exposure to airborne asbestos fibers. The regulations restrict employee exposure, and require special monitoring, training and handling procedures when dealing with asbestos. Additionally, OSHA has regulations that may supersede the EPA regulations. In order to protect the worker, OSHA has established a permissible exposure limit (PEL), which limits employee exposure to airborne fiber concentrations. OSHA requires objective evidence that the PEL will not be exceeded, as justification that personal air monitoring and engineering controls will not be required. OSHA has also established rules requiring the containerization and labeling of asbestos waste.

The State regulations require that anyone involved in asbestos consulting activities be a licensed asbestos consultant and that anyone involved in asbestos abatement, with the exception of roofing materials, be a licensed asbestos abatement contractor.

4.1.1 ASBESTOS – SPECIFIC

MSV-01: Backing Associated with Olive Sheet Vinyl (Field Services Building) TSI-01: White Hard Block Pipe Insulation (Electric Operations Offices and Warehouse)

These materials are defined by the EPA as RACM. The backing associated with sheet vinyl in the field services building was observed to be in good condition, and did not appear to present a significant issue, as observed, at the time of the survey. The hard block pipe insulation in the electric operations offices and warehouse building was observed to be in significantly damaged condition, and presents a significant issue, as observed, at the time of the survey. We recommend that a licensed asbestos abatement contractor properly remove and dispose of the identified RACM prior to conducting demolition activities that might disturb the ACM.

M-04: Grey Exterior Caulk (Waste Water Admin Building) RF-02: Aluminum Coating on Mechanical Equipment Flashing (Waste Water Admin Building) M-01: Grey Interior Caulk (Waste Water Admin Warehouse) M-02: Grey Exterior Caulk (Waste Water Admin Warehouse)

These materials are defined by the EPA as a Category I non-friable materials. These materials may remain within a facility during demolition with no potential stoppage of work provided they remain non-friable. However, there is no guarantee that it will remain non-friable. If a material becomes friable, then it is classified as RACM. RACM, as defined by the EPA, must be removed prior to renovation or demolition activities that may disturb the materials. Also, OSHA has additional requirements that may supersede the EPA rules. These materials do not appear to present a significant issue, as observed, at the time of the survey. We recommend that the identified Category I material be maintained as part of an O&M Program and periodically monitored for any changes in condition prior to demolition. As discussed above, in order to protect the worker, OSHA has established a PEL which limits airborne fiber concentrations. Objective evidence that the PEL will not be exceeded is required by OSHA as justification that personal air monitoring and engineering controls will not be required. OSHA has also established rules requiring the containerization and labeling of asbestos waste.

Should prior abatement be desired, the work must be performed in accordance with Federal, State, and local regulations. In lieu of abatement, demolition utilizing the wet method is acceptable by a demolition contractor properly trained and certified to conduct Class II asbestos work, along with proper disposal and transport of the demolished materials to an approved landfill as asbestos-containing waste.

M-05: Black Sink Undercoat (Electric Operations Offices and Warehouse) MCP-01: Grey Cementitious Panels (Electric Operations Offices and Warehouse)

These materials are defined by the EPA as Category II non-friable materials. These materials have a high probability of becoming friable by the forces expected to act on the material in the course of demolition operations. Therefore, it will be classified as RACM.

The identified RACM does not appear to present a significant issue, as observed, at the time of the survey. We recommend that the identified RACM be maintained as part of an O&M Program and periodically monitored for any changes in condition prior to demolition. Additionally, we recommend that a licensed asbestos abatement contractor properly remove and dispose of the RACM prior to conducting demolition activities that might disturb the ACM.

4.2 LEAD-CONTAINING PAINT

Lead-containing paint (LCP) was identified in twenty-five (25) of the fifty (50) samples.

Under the present OSHA lead construction standard, all identified lead-containing paint affected by construction activities falls under the requirements of 29 CFR 1926. There are no current government guidelines defining a lead paint concentration that creates a hazardous atmosphere when disturbed. Based on current OSHA guidelines, for those employees who will be disturbing lead-containing paint, their employer must make an initial determination by monitoring employee exposure if any employee is exposed to lead at or above the established Permissible Exposure Limit (PEL) of 30 µg/m3 (8-hour TWA).

The employer must implement OSHA prescribed protective measures until they can demonstrate that the employee exposure is not in excess of the PEL. Due to the planned demolition or renovations for these facilities, GLE’s recommendations are as follows:

For all identified lead painted materials where abrasive blasting, welding, cutting and/or torch burning are planned, removal of lead paint is to be completed by a properly trained lead removal contractor.

For all identified lead painted materials where manual demolition (e.g. drywall), manual scraping, manual sanding and heat gun applications are planned: provide workers with interim protection as outlined in the OSHA Lead in Construction Standard until the employee exposure monitoring indicates that that all tasks being performed are not exposing employees above the

PEL.

The interim employee protection measures include but are not limited to the following:

appropriate respiratory protection; appropriate personal protective clothing and equipment;

change areas; hand washing facilities; biological monitoring; and training.

All waste generated during the lead paint removal and during subsequent manual demolition or renovation activities should be characterized by Toxicity Characteristic Leaching Procedure testing for lead for waste disposal purposes.

5.0 LIMITATIONS AND CONDITIONS

As a result of previous renovations, there may be hidden materials, such as floor tile, sheet vinyl flooring, insulation, etc. These materials may be found in various areas hidden under existing flooring materials or in wall cavities. Any materials or coatings found during construction activities, either not addressed in this survey report, or similar to the ACM or LCP identified in this survey report should be assumed to be ACM or LCP until sampling and analysis documents otherwise.

Because of the hidden nature of many building components (i.e. within mechanical chases), it may be impossible to determine if all of the suspect building materials have been located and subsequently tested. Destructive testing in some instances is not a viable option. We cannot, therefore, guarantee that all potential ACM or LCP has been located. For the same reasons, estimates of quantities and/or conditions are subject to readily apparent situations, and our findings reflect this condition. We do warrant, however, that the investigations and methodology reflect our best efforts based upon the prevailing standard of care in the environmental industry.

The information contained in this report was prepared based upon specific parameters and regulations in force at the time of this report. The information herein is only for the specific use of the client and GLE. GLE accepts no responsibility for the use, interpretation, or reliance by other parties on the information contained herein, unless prior written authorization has been obtained from GLE.

APPENDIX A

Analytical Results and Chains of Custody

PLM REPORT SUMMARY

3151 San Bernadino St.

Clearwater, Florida 33759

NVLAP Lab Code 200703-0813-679-0720 / mhall005@tampabay.rr.com

Client : GLE Associates Lab Set No. : 014858

Project : GRU-Electric Operations Offices and Warehouse 25-14858AT Job No. :

25000-31280Client Project No.: Report Date : 6/19/2025

Identification : Asbestos, Bulk Sample Analysis Sample Date : 6/11/2025

Test Method : Polarized Light Microscopy / Dispersion Staining (PLM/DS) Page 1 of 11App E to Sub E of 40 CFR Part 763 and EPA Method 600/R-93/116

On 6/13/2025, ninety-one (91) bulk material samples were submitted by Mark Fohn for asbestos analysis by PLM/DS.

Copies of Bulk Sample Analysis sheets are attached; additional information may be found therein. The results are summarized below:

Asbestos ContentSample Description / LocationLab Sample No.

None Detected-White Ceiling Tile2x2 White Rough Ceiling TIles CT-01 A014858-001

None Detected-White Ceiling Tile2x2 White Rough Ceiling TIles CT-01 B014858-002

None Detected-White Ceiling Tile2x2 White Rough Ceiling TIles CT-01 C014858-003

None Detected-White Ceiling Tile2x2 White Large Fissure Ceiling Tiles CT-02 A014858-004

None Detected-White Ceiling Tile2x2 White Large Fissure Ceiling Tiles CT-02 B014858-005

None Detected-White Ceiling Tile2x2 White Large Fissure Ceiling Tiles CT-02 C014858-006

None Detected-White Ceiling Tile2x2 White Pinhole Ceiling Tiles CT-03 A014858-007

None Detected-White Ceiling Tile2x2 White Pinhole Ceiling Tiles CT-03 B014858-008

None Detected-White Ceiling Tile2x2 White Pinhole Ceiling Tiles CT-03 C014858-009

None Detected-White Ceiling Tile2x2 White Directional Fissure Ceiling Tiles CT-04 A014858-010

None Detected-White Ceiling Tile2x2 White Directional Fissure Ceiling Tiles CT-04 B014858-011

None Detected-White Ceiling Tile2x2 White Directional Fissure Ceiling Tiles CT-04 C014858-012

These samples were analyzed by layers. Specific layer or component asbestos content is indicated when relevant. The EPA considers a material to be asbestos containing only if it contains more than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing Materials (RACM) -- materials which are friable or may become friable -- be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. Arrowhead utilizes CVAE on a routine basis and does not include point counting unless specifically requested.

The results may not be reproduced except in full.

PLM Report Summary - Revision 4 - 08/04/2022- Issuing Authority: Monte Hall, PG mailto:mhall005@tampabay.rr

Clearwater, Florida 33759

NVLAP Lab Code 200703-0813-679-0720 / mhall005@tampabay.rr.com

Client : GLE Associates Lab Set No. : 014858

Project : GRU-Electric Operations Offices and Warehouse 25-14858AT Job No. :

25000-31280Client Project No.: Report Date : 6/19/2025

Identification : Asbestos, Bulk Sample Analysis Sample Date : 6/11/2025

Test Method : Polarized Light Microscopy / Dispersion Staining (PLM/DS) Page 2 of 11App E to Sub E of 40 CFR Part 763 and EPA Method 600/R-93/116

On 6/13/2025, ninety-one (91) bulk material samples were submitted by Mark Fohn for asbestos analysis by PLM/DS.

Copies of Bulk Sample Analysis sheets are attached; additional information may be found therein. The results are summarized below:

Asbestos ContentSample Description / LocationLab Sample No.

None Detected-White Ceiling Tile2x4 White Pinhole Ceiling Tiles CT-05 A014858-013

None Detected-White Ceiling Tile2x4 White Pinhole Ceiling Tiles CT-05 B014858-014

None Detected-White Ceiling Tile2x4 White Pinhole Ceiling Tiles CT-05 C014858-015

None Detected-Wht/Tan Ceiling Panel12x12 White Spline Ceiling Tiles CT-06 A014858-016

None Detected-Wht/Tan Ceiling Panel12x12 White Spline Ceiling Tiles CT-06 B014858-017

None Detected-Wht/Tan Ceiling Panel12x12 White Spline Ceiling Tiles CT-06 C014858-018

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 A014858-019 None Detected-White Drywall Material

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 B014858-020 None Detected-White Drywall Material

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 C014858-021 None Detected-White Drywall Material

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 D014858-022 None Detected-White Drywall Material

These samples were analyzed by layers. Specific layer or component asbestos content is indicated when relevant. The EPA considers a material to be asbestos containing only if it contains more than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing Materials (RACM) -- materials which are friable or may become friable -- be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. Arrowhead utilizes CVAE on a routine basis and does not include point counting unless specifically requested.

The results may not be reproduced except in full.

Clearwater, Florida 33759

NVLAP Lab Code 200703-0813-679-0720 / mhall005@tampabay.rr.com

Client : GLE Associates Lab Set No. : 014858

Project : GRU-Electric Operations Offices and Warehouse 25-14858AT Job No. :

25000-31280Client Project No.: Report Date : 6/19/2025

Identification : Asbestos, Bulk Sample Analysis Sample Date : 6/11/2025

Test Method : Polarized Light Microscopy / Dispersion Staining (PLM/DS) Page 3 of 11App E to Sub E of 40 CFR Part 763 and EPA Method 600/R-93/116

On 6/13/2025, ninety-one (91) bulk material samples were submitted by Mark Fohn for asbestos analysis by PLM/DS.

Copies of Bulk Sample Analysis sheets are attached; additional information may be found therein. The results are summarized below:

Asbestos ContentSample Description / LocationLab Sample No.

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 E014858-023 None Detected-White Drywall Material

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 F014858-024 None Detected-White Drywall Material

None Detected-White Joint CompoundDrywall / Joint Compound DW-01 G014858-025 None Detected-White Drywall Material

None Detected-Tan Floor Tile12x12 Tan/White Floor Tile w/ Gold Adhesive FT-01 A014858-026 None Detected-Gold Mastic

None Detected-Tan Floor Tile12x12 Tan/White Floor Tile w/ Gold Adhesive FT-01 B014858-027 None Detected-Gold Mastic

None Detected-Tan Floor Tile12x12 Tan/White Floor Tile w/ Gold Adhesive FT-01 C014858-028 None Detected-Gold Mastic

None Detected-Brown Floor Tile12x12 Dk. Brown Floor Tile w/ White Adhesive FT-02 A014858-029 None Detected-White Mastic

None Detected-Brown Floor Tile12x12 Dk. Brown Floor Tile w/ White Adhesive FT-02 B014858-030 None Detected-White Mastic

These samples were analyzed by layers. Specific layer or component asbestos content is indicated when relevant. The EPA considers a material to be asbestos containing only if it contains more than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing Materials (RACM) -- materials which are friable or may become friable -- be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. Arrowhead utilizes CVAE on a routine basis and does not include point counting unless specifically requested.

The results may not be reproduced except in full.

Clearwater, Florida 33759

NVLAP Lab Code 200703-0813-679-0720 / mhall005@tampabay.rr.com

Client : GLE Associates Lab Set No. : 014858

Project : GRU-Electric Operations Offices and Warehouse 25-14858AT Job No. :

25000-31280Client Project No.: Report Date : 6/19/2025

Identification : Asbestos, Bulk Sample Analysis Sample Date : 6/11/2025

Test Method : Polarized Light Microscopy / Dispersion Staining (PLM/DS) Page 4 of 11App E to Sub E of 40 CFR Part 763 and EPA Method 600/R-93/116

On 6/13/2025, ninety-one (91) bulk material samples were submitted by Mark Fohn for asbestos analysis by PLM/DS.

Copies of Bulk Sample Analysis sheets are attached; additional information may be found therein. The results are summarized below:

Asbestos ContentSample Description / LocationLab Sample No.

None Detected-Brown Floor Tile12x12 Dk. Brown Floor Tile w/ White Adhesive FT-02 C014858-031 None Detected-White Mastic

None Detected-White / Gray Floor Tile12x12 White/Gray Floor Tile w/ Beige Adhesive FT-03 A014858-032 None Detected-Beige Mastic

None Detected-White / Gray Floor Tile12x12 White/Gray Floor Tile w/ Beige Adhesive FT-03 B014858-033 None Detected-Beige Mastic

None Detected-White / Gray Floor Tile12x12 White/Gray Floor Tile w/ Beige Adhesive FT-03 C014858-034 None Detected-Beige Mastic

None Detected-Gray Floor Tile12x12 Dk. Gray Floor Tile w/ Yellow Glue FT-04 A014858-035 None Detected-Yellow Mastic

None Detected-Gray Floor Tile12x12 Dk. Gray Floor Tile w/ Yellow Glue FT-04 B014858-036 None Detected-Yellow Mastic

None Detected-Gray Floor Tile12x12 Dk. Gray Floor Tile w/ Yellow Glue FT-04 C014858-037 None Detected-Yellow Mastic

None Detected-White Sink MasticWhite Sink Undercoating M-01 A014858-038

None Detected-White Sink MasticWhite Sink Undercoating M-01 B014858-039

These samples were analyzed by layers. Specific layer or component asbestos content is indicated when relevant. The EPA considers a material to be asbestos containing only if it contains more than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing Materials (RACM) -- materials which are friable or may become friable -- be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. Arrowhead utilizes CVAE on a routine basis and does not include point counting unless specifically requested.

The results may not be reproduced except in full.

Clearwater, Florida 33759

NVLAP Lab Code 200703-0813-679-0720 / mhall005@tampabay.rr.com

Client : GLE Associates Lab Set No. : 014858

Project : GRU-Electric Operations Offices and Warehouse 25-14858AT Job No. :

25000-31280Client Project No.: Report Date : 6/19/2025

Identification : Asbestos, Bulk Sample Analysis Sample Date : 6/11/2025

Test Method : Polarized Light Microscopy / Dispersion Staining (PLM/DS) Page 5 of 11App E to Sub E of 40 CFR Part 763 and EPA Method 600/R-93/116

On 6/13/2025, ninety-one (91) bulk material samples were submitted by Mark Fohn for asbestos analysis by PLM/DS.

Copies of Bulk Sample Analysis sheets are attached; additional information may be found therein. The results are summarized below:

Asbestos ContentSample Description / LocationLab Sample No.

None Detected-White Sink MasticWhite Sink Undercoating M-01 C014858-040

None Detected-Gray Ceramic Tile GroutGray Ceramic Tile Grout & Thin Set M-02 A014858-041 None Detected-White Ceramic Tile Mortar

None Detected-Gray Ceramic Tile GroutGray Ceramic Tile Grout & Thin Set M-02 B014858-042 None Detected-White Ceramic Tile Mortar

None Detected-Gray Ceramic Tile GroutGray Ceramic Tile Grout & Thin Set M-02 C014858-043 None Detected-White Ceramic Tile Mortar

None Detected-White Ceramic Tile GroutWhite Ceramic Tile Grout & Thin Set M-03 A014858-044 None Detected-White Ceramic Tile Grout

None Detected-White Ceramic Tile GroutWhite Ceramic Tile Grout & Thin Set…