Portage West Middle School Storage Barn - Construction Documents Summary
This document is a comprehensive set of construction drawings for a storage barn project at Portage West Middle School in Portage, Michigan, prepared for Portage Public Schools by Tower Pinkster Architecture/Engineering and H&S Engineering as the civil consultant. The project involves the construction of a 2,093 square-foot storage barn classified as Use Group S-1 (Moderate-hazard Storage) with Type VB construction, designed to comply with the 2015 Michigan Building Code and 2012 NFPA 101 Life Safety Code. The facility features a single-story structure with engineered wood trusses at 24-inch on-center spacing, a 6-inch concrete slab foundation with turned-down edges, steel siding (Fabral Grandrib 3), asphalt shingles, two overhead doors (10 feet wide), and one manual man door. The building contains calculated occupancy of 7 occupants with egress travel distances of 32 to 40 feet, complying with the 200-foot maximum permitted travel distance. The design includes storm water management with a 4-foot diameter leaching basin and 24-inch perforated HDPE pipe in stone trenches, providing 998 cubic feet of storage volume against the required 838 cubic feet.
Electrical infrastructure includes a new 60-amp Square D MPZ15S40F Powerzone panel fed from an existing 480-volt distribution panel, with an estimated total demand of 14 amps at 3,450 VA. The electrical system provides duplex receptacles (including GFCI-protected wet location outlets), industrial strip lighting fixtures, and connections for overhead door operation. Construction documents specify detailed foundation plans with 24-by-10-inch footings for typical columns and 36-by-12-inch footings at overhead door locations, site-specific grading notes, soil erosion and sedimentation control measures including temporary silt fencing, and permanent seeding requirements. The project is subject to Michigan Handicapped Accessibility Code and Americans with Disabilities Act compliance. All construction work must follow MDOT-MDEQ specifications and compliance requirements, with the general contractor responsible for obtaining all necessary permits, tap fees, meter deposits, and notifying utility locating services a minimum of 48 hours before excavation work commences.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN TEAM
ARCHITECT/ENGINEER
REFERENCED CODES
SITE ADDRESS
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig a n
-5
.3
.6
P H
O N
E
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
XPORTAGE - WEST MIDDLE SCHOOL -
STORAGE BARN
PORTAGE PUBLIC SCHOOLS
Portage, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-2
.0
G
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
DRAWING INDEX
CIVIL CONSULTANT
5725 VENTURE PARK DRIVE, SUITE A
KALAMAZOO, MI 49009
PHONE: 269.250.5991
PORTAGE PUBLIC SCHOOLS
7145 MOORSBRIDGE RD
PORTAGE, MI ZIP 49024
GENERAL
G 001 COVER SHEET
G 101 FIRST FLOOR CODE COMPLIANCE PLAN, TYPICAL SYMBOLS AND GENERAL
NOTES
CIVIL
C 100 SITE PLAN
ARCHITECTURAL
A 100 FOUNDATION AND FRAMING PLAN
A 101 FIRST FLOOR PLAN, ROOF FRAMING PLAN AND DOOR SCHEDULE
A 301 EXTERIOR ELEVATIONS, BUILDING SECTIONS, 3D VIEW AND WALL
SECTIONS
ELECTRICAL
E 101 FIRST FLOOR POWER PLAN
242 E. KALAMAZOO AVE, SUITE 100
KALAMAZOO, MICHIGAN 49007
PHONE: 269.343.6133
FAX: 269.343.6633
BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
ENERGY: 2015 MICHIGAN ENERGY CODE
PLUMBING: 2015 MICHIGAN PLUMBING CODE
MECHANICAL: 2015 MICHIGAN MECHANICAL CODE
FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1
USE GROUP: S-1
CONSTRUCTION TYPE: TYPE VB
AUTOMATIC SPRINKLERS: NON SPRINKLED
PROJECT AREA
TOTAL FINISHED PROJECT: 2,093 SQ. FT.
4 EAST FULTON STREET, SUITE 200
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.9944
FAX: 616.456.5936
ISSUED FOR DATE
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED
MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
CODE COMPLIANCE KEY
EGRESS SYMBOLS
EGRESS EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS PERMITTED
BY EGRESS WIDTH
ROOM OR SPACE EGRESS IS FROM
TRAVEL DISTANCE : 100'-0"
PERMITTED TRAVEL DISTANCE - 200'-0"
EXISTING TRAVEL DISTANCE
TO EGRESS DOOR
PERMITTED MAXIMUM TRAVEL
DISTANCE PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIRE-RATING KEY
DESIGNATION PARTITION RATING PRIORITY
3 HOUR 1
2 HOUR FIRE/SMOKE
2 HOUR
1 HOUR FIRE/SMOKE
1HOUR
SMOKE RESISTANT
EGRESS
Door #
EGRESS ROOM
A B C D E
STORAGE
EGRESS
4 OCC.
E G
R E
S S
O
C C
TR
A V E L
D
IS
TA
N C E
'-0
P E R M
IT
TE
D D
IS
TA
N C E
'-0
TRAVEL DISTANCE: 40'-0"
TRAVEL DISTANCE: 200'-0"
GENERAL NOTES - ARCHITECTURAL
1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR
TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO
THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6. WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT
ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS
NOTED OR DETAILED OTHERWISE. PROVIDE SQUARE OUTSIDE CORNERS AT ALL
LOCATIONS FINISHED WITH WALL TILE, REFER TO FINISH PLANS (A600 SHEETS)
FOR LOCATIONS.
7. TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8. TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK
LOCATIONS.
9. STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.
10. STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
11. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
12. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND
CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
14. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
15. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
16. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
17. PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL
ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED
WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.
18. ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING
TO MATCH EXISTING ADJACENT.
A101A
TYPICAL SYMBOLS & REFERENCES
NOTE:
ROOM NAMES AND NUMBERS ON PLANS ARE
FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
ROOM IDENTIFICATION TAG
ROOM NAME
ROOM NUMBER
DETAIL TITLE
1 DETAIL TITLE
1" = 0'-1"A101
DETAIL NUMBER
SHEET NUMBER
UNIT MATCHLINES
U N
IT
A
U N
IT
B
TYPICAL NOTATION SYMBOLS
CALLOUT REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION REFERENCE BUBBLE
A301
A
ELEVATION LETTER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE BUBBLE
4 A 652
ELEVATION NUMBER
SHEET NUMBER
DETAIL REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
BUILDING SECTION REFERENCE BUBBLE
A 311
DETAIL NUMBER
SHEET NUMBER
ELEVATION AND SECTION REFERENCE TOOLS
ELEVATION TAG - EXISTING
FINISH FLOOR
ELEVATION 100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
100'-0" ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
ELEVATION TAG - NEW
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
WORKING POINT LAYOUT TAG
100'-0" : 100'-0"
DISTANCE IN THE "Y" DIRECTION FROM THE
"X" BASE LINE
DISTANCE IN THE "X" DIRECTION FROM THE
"Y" BASE LINE
BORROWED LIGHT AND DOOR IDENTIFICATION
A 502
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
SYMBOLS
BARRIER-FREE
B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
CLASSROOM
A000A
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
C O
D E
C O
M P
L
IA
N C
E P
L A
N
T Y
P
IC
A L
S Y
M B
O L S
A N
D G
E N
E R
A L
N O
T E
S
-2
.0
G
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FIRST FLOOR CODE COMPLIANCE PLAN
Michigan Building Code – 2015 Edition
Section 311.2: The storage room to be classified as Moderate-hazard Storage Group
S-1. (Must comply with the maximum allowable quantities of hazardous materials listed in Table 307.1 (1).
Table 504.3: Allowable Height: Occupancy S-1, Type V-S: 40 feet
Table 504.4: Allowable Stories: Occupancy S-1, Type V-S: 1 Story
Section 506.2: Allowable Area: Occupancy S-1, Type V-NS: 9,000 sf
Section 506.3: A frontage increase is not required. The building area complies with the allowable area in Table 506.2.
Section 602.2: Table 601 – Construction Type V-B (Non-sprinklered – Single Story)
Construction in which structural elements, and exterior walls, and interior walls are of any materials permitted by this code.
Table 1004.1.2: Occupant Load Factors
Storage Areas: 300 gross
Calculated Occupancies
Storage (2,093 gross sq. ft.) – 7 Occupants
Section 1005.3: Egress Capacity Factors
1005.3.2 All others = 0.2 inches per Occupant
Table 1006.2.1: Maximum Common Path of Travel shall not exceed: Storage: 100 ft without sprinkler system and occupant load is less than 30 occupants
Section 1007.1.1 Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them.
Table 1017.2 Exit Access Travel Distance shall not exceed:
Storage: 200 feet
STM YD
RIM = 900.58
WATER PER CITY OF PORTAGE
AS-BUILT MAPS
APPROXIMATE LOCATION OF
WATER PER CITY OF PORTAGE
GIS MAPS
STM CB
E.G.
E.G.
E.G.
900.23
900.20
900.42
900.50 900.50
900.34
900.50
900.42
900.50
900.22
900.42
E.G.
900.12
E.G.
900.04
E.G.
899.93
900.34
900.42
900.34
900.42
900.42 900.42
900.41900.36
S H
E E
T
T
I T
L E
S H
E E
T
N
U M
B E
R
O W
N E
R P
R O
J E
C T
I T
L E
D A
T E
E a s t
K a l a m a z o o
A v e n u e
S u i t e
K a l a m a z o o
M i c h i g
P
H O
.3
.6
F
A X
T O
W E
R P
I N
K S
T E
R C
O M
A L
L
R
I G
H T
S
R
E S
E R
V E
D
E a s t
F u l t o n
S t r e e t
S u i t e
G r a n d
R a p i d s
M i c h i g a n
4 P
H O
N E
.4
.5
F
A X
S
T
A
O
F M
I C
H
I
G
A
N
L
C
S
D
P
R
O
F
E S S I
O
A
L
G
R
DANIEL LEWIS, P.E.
No. 52573
N 1 inch = ft.
10 2015
1. DIMENSIONS TAKE PRECEDENCE OVER SCALE. CONTRACTOR
TO VERIFY ALL DIMENSIONS IN FIELD.
2. IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS BECOME
APPARENT, THESE SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER PRIOR TO CONSTRUCTION OF
ANYTHING AFFECTED SO THAT CLARIFICATION OR REDESIGN
MAY OCCUR.
1. PROPERTY INFORMATION:
PARCEL #s: 00017-095-O
SITE AREA: 2875000 SF (66 AC)
OWNER: PORTAGE PUBLIC SCHOOLS
8107 MUSTANG DR
PORTAGE, MI 49002
2. ZONING:
R-1B RESIDENTIAL
ABUTTING PROPERTY CURRENTLY ZONED:
NORTH: R-1B RESIDENTIAL
SOUTH: PD RESIDENTIAL
EAST: R-1B RESIDENTIAL
WEST: PD RESIDENTIAL/RM-1 RESIDENTIAL
3. SETBACKS
FRONT = 0'
SIDES = 0' (25' IF ABUTS R DISTRICT)
REAR = 0' (25' IF ABUTS R DISTRICT)
4. PARKING: NOT APPLICABLE
5. STORM WATER RETENTION REQUIRED
TOTAL IMPERVIOUS AREA:
3,349 SQFT
REQUIRED STORM WATER VOLUMES
BASED ON 3" OVER IMPERVIOUS AREA:
REQUIRED STORAGE VOLUME: 838 CFT
PROVIDED VOLUME: 998 CFT
SITE DATA
GENERAL NOTES
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: H & S ENGINEERING
A. 6" CONCRETE PAVEMENT (SEE DETAIL THIS SHEET)
B. CONNECT ELECTRIC SERVICE AND METER, COORDINATE WITH UTILITY PROVIDER
C. 10' OVERHEAD DOOR
D. DOWNSPOUT
E. MAN DOOR
SITE PLAN NOTES
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS
IN FORCE AT TIME OF CONSTRUCTION.
2. ALL PLUMBING WORK SHALL BE PERFORMED BY A STATE OF MICHIGAN LICENSED PLUMBER
ACCORDING TO THE INTERNATIONAL PLUMBING CODE AS MODIFIED BY THE STATE OF MICHIGAN AND LOCAL HEALTH DEPARTMENT. FURNISH AND INSTALL ALL MATERIALS AND LABOR TO PROVIDE
A FULL WORKING SYSTEM.
3. ALL WORK SHALL CONFORM TO THE MICHIGAN HANDICAPPED ACCESSIBILITY CODE AND THE
AMERICANS WITH DISABILITIES ACT.
4. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT
COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER
FEES REQUIRED FOR PROPOSED WORK.
5. CONTACT "MISS DIG" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM
OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF
THE "MISS DIG" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A
MANNER AS TO ENSURE THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE
DISTURBED.
6. MANHOLE AND CATCH BASIN STRUCTURES SHALL BE PRECAST AND HAVE A MAXIMUM OF 2
ADJUSTING RINGS FOR FINISH GRADE ADJUSTMENT.
7. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
1. SOILS EXPOSED IN THE BASE OF ALL SATISFACTORY FOUNDATION EXCAVATIONS SHOULD BE
PROTECTED AGAINST ANY DETRIMENTAL CHANGES IN CONDITION SUCH AS FROM DISTURBANCE,
RAIN AND FREEZING. SURFACE RUN-OFF WATER SHOULD BE DRAINED AWAY FROM THE
EXCAVATION AND NOT ALLOWED TO POND. IF POSSIBLE, ALL FOOTING CONCRETE SHOULD BE
POURED THE SAME DAY THE EXCAVATION IS MADE. IF THIS IS NOT PRACTICAL, THE FOOTING
EXCAVATIONS SHOULD BE ADEQUATELY PROTECTED.
2. REMOVE ALL SUBGRADE GRADE MATERIAL THAT MAY BE SOFTENED BY RAINS, FREEZING, OR
CONSTRUCTION TRAFFIC, ETC. AND REPLACE WITH COMPACTED GRANULAR FILL.
3. THE CONTRACTOR SHALL INSTALL A PEDESTRIAN FENCE AROUND ALL EXCAVATIONS TO BE LEFT
OPEN OVERNIGHT AS REQUIRED.
4. EXTERIOR CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH OF 4000 PSI AND SHALL HAVE
LIMESTONE AGGREGATE AND SHALL HAVE 4 - 6 % AIR ENTRAINMENT WITH A BROOM FINISH.
5. EXPANSION JOINTS IN CONCRETE PAVEMENT AND WALLS SHALL BE 1/2" ASPHALT IMPREGNATED FULL DEPTH 40' O.C. MAXIMUM & AT SIDEWALK INTERSECTIONS. CRACK CONTROL SCORING AT
SIDEWALK WIDTH DIMENSION AND @ 10'-0" O.C. IN DRIVES.
SITE MATERIALS & CONSTRUCTION NOTES:
GENERAL CONSTRUCTION NOTES
POLE BARN
F.F. - 900.50
TOTAL SQFT: 2,048
5'
10'
5'
5'
64'
REMOVE OLD FENCE
(SEE FENCE REMOVALS
THIS SHEET)
SAWCUT CLEAN STRAIGHT EDGE FOR
NEW CONCRETE CONNECTION
A
B
C
C
LIMITS OF CONSTRUCTION
LEGEND
SAWCUT
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS IN
FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER FEES
REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE
REQUIRED BY THE CITY OF PORTAGE
3. CONTACT "811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48
HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF
THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "811" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT
THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. MATCH EXISTING GRADES AROUND PERIMETER WITH SLOPES AS SHOWN.
6. ALL SPOT ELEVATIONS ARE TOP OF PAVEMENT GRADES AT EDGE OF METAL (EOM) UNLESS
OTHERWISE NOTED.
7. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO MASS GRADING.
8. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS AND
GEOTECHNICAL REPORT.
9. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR TO
COMMENCEMENT OF WORK.
10. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO ADJACENT ROADWAYS.
CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
11. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST BE SEEDED TO
ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS TO BE SEEDED AND MULCH
BLANKETS APPLIED IMMEDIATELY TO PROVIDE A STABLE BASE AND AVOID EXCESSIVE EROSION.
GRADING NOTES
DENOTES PERMANENT SEEDING. ALL DISTURBED AREAS NOT PAVED OR GRAVELED SHALL
BE RESTORED. PLACE TOPSOIL SURFACE, SALV, 3 INCH, MDOT SEEDING, MIXTURE TUF
APPLIED AT A RATE OF 220 LB/ACRE, FERTILIZER, CHEMICAL NUTRIENT, CL A APPLIED AT A
RATE OF 228 LB/ACRE; MULCH AT A RATE OF 2 TON/ACRE AND MULCH ANCHORING.
(APPLIES TO ENTIRE PROJECT)
DENOTES TEMPORARY SILT FENCE. SILT FENCE SHALL BE INSTALLED AT CREEK
CROSSINGS, ADJACENT TO ALL WETLANDS AND SURFACE WATERS, AND OTHER
LOCATIONS AS DIRECTED BY THE ENGINEER. EACH SILT FENCE SHALL BE INSTALLED
GENERALLY ALONG THE SAME CONTOUR ELEVATION.
SOIL EROSION & SEDIMENTATION CONTROL NOTES
1 ALL CONSTRUCTION METHODS SHALL BE DONE IN COMPLIANCE WITH MDOT-MDEQ. THE OWNER SHALL BE RESPONSIBLE FOR OBTAINING A "SOIL EROSION PERMIT" FROM THE COUNTY AND A "PERMIT BY RULE/NOTICE OF COVERAGE" FROM MDEQ, IF APPLICABLE, PRIOR TO START OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL REQUIREMENTS OF THE COUNTY "SOIL EROSION PERMIT" AND FOR ALL CERTIFIED STORM WATER INSPECTION SERVICE REQUIRED BY THE "PERMIT BY RULE." EROSION CONTROL MEASURES SHOWN ON THE PLANS ARE THE MINIMUM REQUIREMENTS AND SHALL NOT RELIEVE THE CONTRACTOR'S
RESPONSIBILITY FOR PROVIDING ALL REQUIRED EROSION CONTROL MEASURES.
2. AVOID UNNECESSARY DISTURBING OR REMOVING OF EXISTING VEGETATED TOPSOIL OR EARTH COVER, THESE COVER
AREAS ACT AS SEDIMENT FILTERS.
3. ALL TEMPORARY SOIL EROSION PROTECTION SHALL REMAIN IN PLACE UNTIL REMOVAL IS REQUIRED FOR FINAL CLEAN
UP AND APPROVAL.
4. GEOTEXTILE SILT FENCE SHALL BE INSTALLED AS REQUIRED WHEN CROSSING CREEKS OR WHEN ADJACENT TO WETLANDS OR SURFACE WATER BODIES TO PREVENT SILTATION AND ELSEWHERE AS DIRECTED BY THE ENGINEER.
SEEDING AND/OR SODDING SHALL BE INSTALLED ON CREEK BANKS IMMEDIATELY AFTER CONSTRUCTION TO PREVENT
EROSION.
5. MAINTENANCE, CLEANING, AND REMOVAL OF THE VARIOUS SEDIMENT CONTROL MEASURES SHALL BE INCLUDED IN
THE VARIOUS EROSION CONTROL ITEMS.
NUMBER IN CIRCLE REFERS TO NUMBERED DETAILS ON MDOT STANDARD PLAN R-96-D, SOIL EROSION & SEDIMENTATION CONTROL MEASURES. "P" DENOTES PERMANENT MEASURE AND "T" DENOTES TEMPORARY MEASURE.
SOIL EROSION CONTROL PLANS DENOTE MINIMUM EROSION MEASURES REQUIRED AS DESCRIBED BELOW.
3P
26T
3P
3P
3P
3P3P
SILT FENCE
E.G. EXISTING GRADE
26T
26T
PORTAGE WEST
MIDDLE SCHOOL
D
D
31 LF - CHAIN LINK FENCE CONNECTED TO BUILDING
15 LF - CHAIN LINK FENCE CONNECTED TO BUILDING
32'
D
4' DIA. LEACHING BASIN
BEEHIVE COVER
RIM: 899.50
24" HDPE W IE: 892.50
6" SDR 35 S IE: 896.23
BTM: 889.50
4' DIA. MANHOLE
BEEHIVE COVER
RIM: 900.20
24" HDPE E IE: 892.50
6" SDR 35 S IE: 896.23
BTM: 890.20
STORM WATER CLEANOUT
I.E. 897.00
77LF - 6" SDR
35 @ 1.00%
6"x6"x6" WYE
40' - 24" PERFORATED HDPE PIPE
IN STONE TRENCH @ 0.00% (SEE DETAIL THIS SHEET)
6"x6"x6" WYE
77LF - 6" SDR 35 @ 1.00%
ELECTRICAL SERVICE
FOR BUILING TO BE RUN
BY OTHERS PRIOR TO PROJECT.
CLEANOUT DETAIL
NOT TO SCALE
GROUND SURFACE EJIW 1410
3' M
A X
THREADED PLUG CAP
UNLESS OTHERWISE
SPECIFIED
SIZE OF PIPE AS
SHOWN ON PLANS GRAVEL FILL (WITHIN OPENING
AROUND PIPE END SECTION)
CONCRETE REINFORCED
FOOTING
GRADE 35S OR PRECAST
REINFORCED SECTION
UNLESS OTHERWISE
SPECIFIED
CONCRETE ADJUSTING
RING GRADE35S, CONC.
REINF. BATTER BLOCKS
AND MORTAR, OR
REINF. PRECAST
MANHOLE SECTION.
(2) 45° (1
8 BEND)
PIPE SECTION
E.J.I.W. #6517
(OR APPROVED EQUAL)
48" DIA.
1' 1'
1'
18" MIN., 24" MAX.
PRECAST REINFORCED
CONCRETE
BASE SECTION
COARSE AGGREGATE,
WASHED MDOT 6A
PRECAST PERFORATED
CONCRETE STRUCTURE
COARSE AGGREGATE,
WASHED MDOT 6A
NONWOVEN GEOTEXTILE
FABRIC, AMOCO 4553
OR EQUAL
NOTE:
INLET SHALL BE
CONSTRUCTED IN
ACCORDANCE WITH ASTM
SPECIFICATION C-478
LEACHING BASIN DETAIL
NOT TO SCALE
TRENCH BACKFILL
NO SCALE
2.5' EACH
SIDE
STONE TRENCH DETAIL
3'
1' VOLUMES PROVIDED BELOW ASSUME
40% VOIDS IN STONE
PIPE SIZE VOLUME/LFT
24" 18.68 CFT
ALL TRENCH SLOPES TO COMPLY WITH
APPLICABLE STATE AND FEDERAL
REGULATIONS.
GEOTEXTILE FABRIC COMPLETELY
SURROUNDING STONE. OVERLAP
FABRIC 1 FOOT
MDOT 6A WASHED STONE (40% VOIDS)
24" PERF. PIPE
STORM WATER CLEANOUT
I.E. 897.00
FENCE REMOVALS
1:40 SCALE
P O
LE
B
A R
N
R E
M O
V E
0L
F
FE
N C
E
D
29T29T
DENOTES INLET PROTECTION FABRIC DROP. SHALL BE INSTALLED AT EXISTING AND
PROPOSED STORM SEWER INLETS TO PROVIDE SETTLING AND FILTERING OF SILT LADEN
WATER PRIOR TO ENTRY INTO THE DRAINAGE SYSTEM.
29T
S I T
E
P
L A
N
C
M A
Y
P O
R T
A G
E
W
E S
T
M I D
D L
E
S
C H
O O
L
S T
O R
A G
E
B
A R
N
P o r t a g e
M i c h i g a n
P O
R T
A G
E
P
U B
L I C
S C
H O
O L
S
ISSUED FOR DATE
SILT FENCE
E
E
6"x6"x6" WYE
6"x6"x6" WYE
5'
N
6" MINIMUM COMPACTED (98%)
SAND SUB-BASE (MDOT CLASS II)
OR AS RECOMMENDED BY GEOTECHNICAL
ENGINEER
6"-4,000 P.S.I.
NON-REINFORCED
CONCRETE TOPSOIL
ACCEPTABLE COMPACTED
SUB-BASE (AS RECOMMENDED
BY GEOTECHNICAL ENGINEER)
1.0' MIN.
CONC. PAVEMENT SECTION
NOT TO SCALE
AutoCAD SHX Text DANIEL G. LEWIS ENGINEER No. 52573
A 301
A
A 301
B
A 301
C
A 301
D
A 301
A B C D E
A 301
32' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0"
24" X 10"
FOOTING
(TYP.) - U.N.O.
24" x 10" FOOTING AT
END WALL COLUMNS
(TYP.) - U.N.O.
36" x 12" FOOTING
AT OVERHEAD DOOR
(TYP.) - U.N.O.
24" x 10" FOOTING AT
END WALL COLUMNS
(TYP.) - U.N.O.
36" x 12" FOOTING
AT OVERHEAD DOOR
(TYP.) - U.N.O.
24" X 10"
FOOTING
(TYP.) - U.N.O.
3' - 9 1/2"
/2
14"Ø CONCRETE
PIERS WITH (6)
VERTICAL #5 BARS
AND 4# STIRRUPS
AT 12" O.C.
A 301
A
A 301
B
A 301
C
A 301
D
A 301
A B C D E
A 301
(2) 1 3/4" x 9 1/2"
LVL CARRIERS ON
EACH SIDE AT
OVERHEAD DOORS
(TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
(2) 1 3/4" x 9 1/2"
LVL CARRIERS ON
EACH SIDE AT
OVERHEAD
DOORS (TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F O
U N
D A
T
IO
N A
N D
F R
A M
IN
G
P L A
N
-2
.0
A
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FOUNDATION PLAN
1/8" = 1'-0"
FRAMING PLAN
GENERAL NOTES
1. REFER TO CODE COMPLIANCE PLAN FOR WALL RATING LINES.
2. REFER TO FLOOR FINISH PLANS FOR INTERIOR ELEVATION CALLOUTS.
3. REFER TO SHEET A 501 FOR WALL AND CEILING ACCESS PANEL INFORMATION.
A 301
A
A 301
B
A 301
C
A 301
D
A 301
A B C D E
101D
101C
101B
101A
/2
32' - 10 1/2"
8' - 0" 8' - 0" 8' - 0" 8' - 0"
A 301
/4
/4
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
STORAGE
3' - 4" 2 3/4"
/4 "1
OHSF
SEE SCHED.
S E E S
C H E D U
LE
SEE SCHEDULE
S E E S
C H E D U
LE
2" TYP. SEE SCHED. 2" TYP.
S E E S
C H E D U
LE
T Y P
A 301
A
A 301
B
A 301
C
A 301
D
A 301
A B C D E
A 301
/1
P
IT
C H E
N G
IN
E E R E D
T R U S S E S
A T
O
.C
/2
LINE OF BUILDING BELOW LINE OF BUILDING BELOW
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
P L A
N
R O
O F
F R
A M
IN
G
P L A
N A
N D
D O
O R
S C
H E
D U
L E
-2
.0
A
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FIRST FLOOR PLAN
DOOR SCHEDULE - FIRST FLOOR
NUMBER
ROOM
NAME
FIRE RATING DOOR SIZE FRAME DETAILS
GLASS
ACCESS CONTROLS
HDWR.
SET
REMARKS
DOOR ROOM DOOR FRAME TYPE MAT FIN WIDTH HEIGHT ELEV MAT FIN HEAD JAMB SILL
A-PHO
NE
BARRIER-
FREE
CARD
READER
ELEC. LOCK
HDWR.
MAG
HOLD
101A 101 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No 1.0 -
101B 101 STORAGE - - OHS STL FACTORY FINISH 12' - 0" 10' - 0" - STL - 5 / A 301 - - - No No No No No 2.0 -
101C 101 STORAGE - - OHS STL FACTORY FINISH 10' - 0" 10' - 0" - STL - 5 / A 301 - - - No No No No No 2.0 -
101D 101 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No 1.0 -
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
FRAME ELEVATION
1/8" = 1'-0"
ROOF FRAMING PLAN
FIRST FLOOR
100' - 0"
ABCDE
TRUSS BEARING
112' - 0"
A 301
FOOTING
96' - 6"
4" 12"
4"
12"
STEEL SIDING -
FABRAL GRANDRIB 3
OR EQUAL
STEEL SIDING
OUTSIDE CORNER
GUTTER
FIRST FLOOR
100' - 0"
A 301
1 2 3 4 5 6 7 8 9
TRUSS BEARING
112' - 0"
FOOTING
96' - 6"
STEEL SIDING -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDNG
OUTSIDE CORNER
GUTTER
STEEL DOWNSPOUT
RIDGE VENT
FIRST FLOOR
100' - 0"
A B C D E
TRUSS BEARING
112' - 0"
A 301
FOOTING
96' - 6"
4"
12" 4"
12"
STEEL SIDING -
FABRAL GRANDRIB
3 OR EQUAL
STEEL SIDING
OUTSIDE CORNER
FIRST FLOOR
100' - 0"
A 301
123456789
TRUSS BEARING
112' - 0"
FOOTING
96' - 6"
STEEL SIDING -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDING
OUTSIDE CORNER
STEEL DOWNSPOUT
GUTTER
RIDGE VENT
FIRST FLOOR
100' - 0"
A B C D E
TRUSS BEARING
112' - 0"
A 301
FOOTING
96' - 6"
4"
12" 4"
12"
A 301
A 301
FIRST FLOOR
100' - 0"
A 301
1 2 3 4 5 6 7 8 9
TRUSS BEARING
112' - 0"
FOOTING
96' - 6"
SHINGLES, COLOR:
EXTERIOR ELEVATION KEY
METAL SIDING, COLOR:
FIRST FLOOR
100' - 0"
A
TRUSS BEARING
112' - 0"
ENGINEERED WOOD
TRUSSES AT 2' O.C.
1/2" OSB SHEATHING
METAL GUTTERS
METAL FASCIA
2X6 SUB FASCIA
VENTED SOFFIT PANELS
2X4 GIRTS AT 24" O.C.
STEEL SIDING -
FABRAL GRANDRIB
6X6 TREATED POST
(2) ROWS OF TREATED
2X6 T&G SKIRT BOARDS
6" CONCRETE SLAB WITH
TURNED DOWN EDGE
ASPHALT SHINGLES ON
15# FELT WITH ONE
ROW OF ICE SHIELD
4" COMPACT SAND
'F' CHANNEL
(2) 2x10 CONTINUOUS
CARRIERS ON EACH
SIDE OF POSTS
E
TRUSS BEARING
112' - 0"
ASPHALT SHINGLES ON
15# FELT WITH ONE
ROW OF ICE SHIELD
1/2" OSB SHEATHING
STEEL GUTTERS
2X6 SUB FASCIA
METAL FASCIA
VENTED SOFFIT PANELS
(2) 1 3/4" X 9 1/2"
LVL - BOTH SIDES
STEEL SIDING -
FABRAL GRANDRIB
F CHANNEL
J CHANNEL
2X6 NAILERS
STEEL TRIM BY SIDING MANUF.
ENGINEERED WOOD
TRUSSES AT 24" O.C.
6X6 TREATED POST
OVERHEAD DOOR
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
E X
T E
R
IO
R E
L E
V A
T
IO
N S
B
U
IL
D
IN
G S
E C
T
IO
N S
D V
IE
W
A N
D W
A L
L S
E C
T
IO
N S
-2
.0
A
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"A 301
A NORTH ELEVATION
1/8" = 1'-0"A 301
B WEST ELEVATION
1/8" = 1'-0"A 301
C SOUTH ELEVATION
1/8" = 1'-0"A 301
D EAST ELEVATION
1/8" = 1'-0"A 301
1 BUILDING SECTION
1/8" = 1'-0"A 301
2 BUILDING SECTION
3D View
1/2" = 1'-0"A 301
4 WALL SECTION
1 1/2" = 1'-0"A 301
5 WALL DETAIL
.6
9.64
143.39 1
.4
9.34
51.90
. 0
(OVERHEAD DOOR (TYP))
A B C D E
A A A
A A A
AAA
A A ARPSB- 4 , 40"
RPSB- 2 , 40"
RPSB- 2 , 40" , GFCI
RPSB- 3 , 40"
RPSB- 3 , 40"
RPSB- 4 , 40"
RPSB
RPSB- 4 , 40" , GFCI
RPSB- 3 , 40" , GFCI
B
RPSB- 1
B
RPSB- 1
RPSB- 4
, WP , GFCI
RPSB- 3
, WP , GFCI
MOUNT 10'-6"
(TYP TYPE B)
RPSB- 5
, OVERHEAD DOOR
RPSB- 6
, OVERHEAD DOOR
A1
A1
RPSB
EXSITNG POWER PANEL I
IN SHOP MEZZANINE
NEW UNDERGROUND
FEEDER
HH
SYMBOL DESCRIPTION MOUNTING HEIGHTS
RECEPTACLE SYMBOLS
POWER SYMBOLS
LIGHTING SYMBOLS
ST
ELECTRICAL SYMBOLS
DISTRIBUTION PANELBOARD
PANELBOARD
CIRCUIT BREAKER
72" TO TOP
72" TO TOP
DUPLEX RECEPTACLE - WITH GFI
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - WET LOCATION ENCLOSURE WITH GFIWP
GFI
24"
DUPLEX RECEPTACLE 16"
TIMER SWITCH - SENSOR SWITCH: PTS-720 OR EQUAL
FLUSH IN-GRADE HAND HOLE
40"
RECEPTACLES VARIATIONS - HEIGHT PER ABOVE UNLESS INDICATED ON DRAWINGS:
INDUSTRIAL LIGHT FIXTURE
NOTES:
MOUNT DEVICES AT HEIGHTS INDICATED UNLESS INDICATED
OTHERWISE ON PLANS. HEIGHTS ARE TO BOTTOM OF DEVICE.
WALL MTD. LIGHT FIXTURE
PUSH-BUTTON STATION - 3 HOLE
EXISTING POWER PANEL I
600 AMPS 480/277V 3Ø, 4W
/2
R2B
PANEL
DEMAND:
14A
2 #6, 1 #8 G 1" CONDUIT
PROVIDE EMT IN BUILDING,
PROVIDE PVC IN GRADE
PROVIDE NEW BREAKER
IN EXISTING SQUARE D
PANEL
GROUND
BUS
10' SPACING (TYP)
#3/0 Cu GND (TYP)
10'-0"
GROUND ROD
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
P O
W E
R P
L A
N
-2
.0
E
M A
Y
P O
R T
A G
E
W E
S T
M
ID
D L
E S
C H
O O
L
S T
O R
A G
E B
A R
N
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
GENERAL ELECTRICAL NOTES
ELECTRICAL KEYED NOTES
1 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING
AND PATCHING REQUIRED FOR NEW WORK OR WHERE DEVICES ARE
REMOVED AND NOT REPLACED.
2 ELECTRICAL CONTRACTOR SHALL COORDINATE WITH G SERIES SHEETS
DEVICE COORDINATION DETAIL. DEVICES ARE TO ALIGN VERTICALLY
AND HORIZONTALLY AND FOLLOW THE RULES OF THIS DETAIL
CONSISTENTLY. A PRE-INSTALL DEVICE COORDINATION MEETING FOR
DEVICE FINISHES AND LAYOUT MAY BE REQUIRED IN THE
SPECIFICATION FOR THIS PROJECT.
3 PATCH ALL PENETRATIONS AS REQUIRED TO MAINTAIN FIRE RATING.
4 ALL CONDUITS SHALL RUN AS NEAR TO DECK AS PERMITTED BY CODE.
SOME CONDUITS WILL BE EXPOSED AND SHALL BE RUN IN A NEAT
MANNER. MAINTAIN THE SAME SPACING WHEN CONDUITS ARE RUN
TOGETHER.
5 REMOVE CEILINGS AND GRID AS REQUIRED. REPLACE ANY DAMAGED
CEILINGS.
6 ALL CONDUITS SHALL ENTER/EXIT THE BUILDING BELOW GRADE.
PROVIDE TRENCHING AND DIRECTIONAL BORING AS REQUIRED. CUT
AND PATCH AS REQUIRED. NO EXPOSED CONDUIT SHALL BE ALLOWED
ON EXTERIOR OF BUILDING.
7 PROVIDE FINAL CONNECTION TO ALL OWNER/CONTRACTOR PROVIDED
EQUIPMENT. COORDINATE RECEPTACLE SIZES AND TYPE WITH
EQUIPMENT, ADJUST CIRCUIT SIZE AS REQUIRED.
1 CONNECT RECEPTACLE TO LOAD SIDE OF UPSTREAM GFCI
RECEPTACLE.
2 PROVIDE SQAURE D: MPZ15S40F POWERZONE PANEL WITH 60 AMP
MAIN BREAKER. PROVIDE PLYWOOD BACKER BOARD TO MOUNT
PANEL TO.
3 PROVIDE 18"X24" HANDHOLE IN GRADE NEXT TO SIDEWALK. PROVIDE
CONDUIT FOR NEW PANEL RPSB, REFER TO ONE-LINE DIAGRAM.
PROVIED (1) 2" SPARE CONDUIT TO HAND HOLE WITH PULL STRING.
COORDINTE PARKING LOT TRENCHING WITH WATER PIPING PROJECT.
4 PROVIDE NEW 40/2 BREAKER IN IN EXISTING SQAURE D 480 VOLT
DISTRIBUTION PANEL TO FEED NEW PANEL RPSB.
A1 BASE BID: CONNECT OVERHEAD DOOR TO CIRCUIT SHOWN.
COORDINATE FINAL POWER CONNECTION WITH DOOR PROVIDER.
MOUNT AND WIRE DOOR SWITCH AND ELECTRIC EYE(S) AT BOTTOM OF
DOOR. IF ALTERNATE #1 IS ACCEPTED OMIT POWERED OVERHEAD
DOOR WORK, DOOR WILL BE MANUAL.
1/8" = 1'-0"
FIRST FLOOR POWER PLAN
1" = 20'-0"
ELECTRICAL SITE PLAN
NOTES:
TOTAL ESTIMATED DEMAND... 14 A
TOTAL CONNECTED LOAD (A): 14 A
TOTAL ESTIMATED DEMAND: 3450 VA
RECEPTACLE - 2800 VA 100.00% 2800 VA TOTAL CONNECTED LOAD: 3450 VA
LIGHTING - 650 VA 100.00% 650 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 17 A 12 A
ADDITIONAL FEED THRU LUGS LOAD (IF APPLICABLE): 0 VA 0 VA
TOTAL LOAD: 2010 VA 1440 VA
23 24
21 22
19 20
17 18
15 SPARE 20 1 0 0 1 20 SPARE 16
13 SPARE 20 1 0 0 1 20 SPARE 14
11 SPARE 20 1 0 0 1 20 SPARE 12
9 SPARE 20 1 0 0 1 20 SPARE 10
7 SPARE 20 1 0 0 1 20 SPARE 8
5 RECEPTACLE - STORAGE 20 1 500 500 1 20 RECEPTACLE - STORAGE 6
3 RECEPTACLE - STORAGE 20 1 720 720 1 20 RECEPTACLE - STORAGE 4
1 LIGHTING 20 1 650 360 1 20 RECEPTACLE - STORAGE 2
CIRCUIT DESCRIPTION TRIP (A) POLES A B POLES TRIP (A) CIRCUIT DESCRIPTION
ADDED ACCESSORIES: FEED-THRU LUGS... No I.C. RATING: 18 KAIC
LOCATION: STORAGE / FIRST FLOOR AMPS: 60 A MB , ULSE RATED FED FROM:
PANEL: RPSB MOUNTING: SURFACE VOLTAGE: 120/240V, 1PH, 3W
PANELBOARD " RPSB" LOAD SCHEDULE
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING WATTS MANUFACTURER
A INDUSTRIAL STRIP CHAIN 50 VA LITHONIA: # CLX-L48-SEF-WDL-WD-MVOLT-GZ10-40K-80CRI-WH-HC36
B LED WALL PACK WALL 25 VA LITHONIA: # WST-LED-P2-40K-VF-MVOLT-PIH-COLOR
SCALE: NONE
PARTIAL ONE-LINE DIAGRAM
EXIST. POWER PANEL I