PORTABLE LITHIUM BATTERY STORAGE CONTAINER PROJECT SPECS 24-32.docx

DOCX document 16 KB Posted

Attached to
9280-24-R-IFBD-00032-V01
Solicitation number
3160006602
Issued by
Jasper County, Mississippi

About this file

This document contains the project specifications for a Portable Lithium Battery Storage Container for the State of Mississippi, Forrest County. The project requires a 20' CONEX container that is compliant with various safety and transportation regulations, including UFC 3-520-05, NFPA 70, NFPA 1, and NAVSEA S9310-AQ-SAF-010. The container must have a battery capacity of 8+ kWh, with specific battery size options listed, and be capable of operating 24/7, 365 days a year. Maintenance and testing requirements are detailed, including duct cleaning, mechanical system inspection, fire system inspection, and routine functional testing of all operating systems. The container requires permanent power onsite and at a backup site, with specific power pedestal configurations.

The related state and local contract opportunity is for the Portable Lithium Ion Battery Storage Container Building, with an ID of 9280-24-R-IFBD-00032. The contract is being issued by the State of Mississippi, Forrest County. No additional pricing terms, set asides, incumbents, funding requirements, or other salient information is provided in the document.

View the file

Other files

File Type Posted
PORTABLE LITHIUM BATTERY CONTAINER BID PACKET.docx DOCX document
24-32 ADVERTISEMENT AD.docx DOCX document
download.docx DOCX document
download.pdf PDF
24-32 COVER SHEET.docx DOCX document
24-32 ADVERTISEMENT AD.docx DOCX document
24-32 COVER SHEET.docx DOCX document
PORTABLE LITHIUM BATTERY STORAGE CONTAINER PROJECT SPECS 24-32.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Portable Lithium Battery Storage Container Project Specs

1. Compliant with UFC 3-520-05

2. Comply with NFPA 70, National Electrical Code (NEC), NFPA 1, Fire Code, NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response, and NAVSEA S9310-AQ-SAF-010 for battery room design requirements.

a. Note that battery storage will not be inside a building, so the NFPA requirements may not apply.

b. Transportable on a public highway. The unit must be transportable on public roads as intermodal cargo. Any components that extend out past the CONEX footprint cannot preclude the unit from being loaded on a trailer and transported on public roads and highways. See DOT guidelines.

3. Battery Storage must be operational 24/7, 365 days a year. All maintenance and testing must be completed by a qualified vendor.

4. All maintenance should be in accordance with UFC 3-520-05, NFPA 70, NEC, and IEEE. The following maintenance is to be included but not limited to:

a. Duct cleaning and inspection

b. Mechanical system inspection and repair as necessary

c. Fire system inspection and repair as necessary

d. Lighting system inspection and repair v1.1 6 as necessary

5. Routinely functionally test all operating systems in the room or as required by the manufacturer. At a minimum, the following must be tested:

a. All alarms including, emergency exhaust button, fire alarm pull stations, emergency power shut off, and VOC sense signal

b. Mechanical systems including, exhaust, air conditioner, etc.

c. Fire systems including, fire dampers, pull stations, and switches

d. Battery charging stations

6. Roughly 200 SF of interior space is required - a 20’ CONEX will meet this requirement.

a. No specific interior storage system required

b. No specific door required; original CONEX door will work

7. Battery capacity must be 8+. Battery sizes or comparably sized batteries: The battery sits in a molded section on a custom plate made by the vehicle manufacturer. Batteries will be stored and charged in CONEX. There will be no other power load inside the CONEX

a. 5.4 kWh lithium-ion battery tray

b. 1 kWh battery tray

c. 24V battery for Drix DDS system

8. Permanent power onsite and at backup site:

a. Power pedestal with 125V and 250 V (50 amps)

b. Power pedestal with 110V (15 amps)

c. Power pedestal with 480V (100 amps)

File details come from the government source that posted it. Updated .