This document outlines the project specifications for a Portable Lithium Battery Storage Container, a state and local contract opportunity issued by Forrest County, Mississippi. The project requires a transportable container that complies with various industry standards, including UFC 3-520-05, NFPA 70, NFPA 1, and NAVSEA S9310-AQ-SAF-010, for battery room design requirements. The container must be operational 24/7, 365 days a year, and all maintenance and testing must be completed by a qualified vendor. The project requires approximately 200 square feet of interior space, with no specific interior storage system or door requirements. The battery capacity must be 8 or greater, with options for 5.4 kWh lithium-ion, 1 kWh, and 24V batteries. The project also requires permanent power onsite and at a backup site, including 125V, 250V, 110V, and 480V power pedestals.
The state and local contract opportunity, named 9280-24-R-IFBD-00032, is for the Portable Lithium Ion Battery Storage Container Building, and is issued by Forrest County, Mississippi. No additional details regarding pricing terms, set asides, incumbents, funding requirements, or other salient information are provided in the document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| PORTABLE LITHIUM BATTERY CONTAINER BID PACKET.docx | DOCX document | |
| 24-32 ADVERTISEMENT AD.docx | DOCX document | |
| download.docx | DOCX document | |
| download.pdf | ||
| 24-32 COVER SHEET.docx | DOCX document | |
| PORTABLE LITHIUM BATTERY STORAGE CONTAINER PROJECT SPECS 24-32.docx | DOCX document | |
| 24-32 ADVERTISEMENT AD.docx | DOCX document | |
| 24-32 COVER SHEET.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Portable Lithium Battery Storage Container Project Specs
1. Compliant with UFC 3-520-05
2. Comply with NFPA 70, National Electrical Code (NEC), NFPA 1, Fire Code, NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response, and NAVSEA S9310-AQ-SAF-010 for battery room design requirements.
a. Note that battery storage will not be inside a building, so the NFPA requirements may not apply.
b. Transportable on a public highway. The unit must be transportable on public roads as intermodal cargo. Any components that extend out past the CONEX footprint cannot preclude the unit from being loaded on a trailer and transported on public roads and highways. See DOT guidelines.
3. Battery Storage must be operational 24/7, 365 days a year. All maintenance and testing must be completed by a qualified vendor.
4. All maintenance should be in accordance with UFC 3-520-05, NFPA 70, NEC, and IEEE. The following maintenance is to be included but not limited to:
a. Duct cleaning and inspection
b. Mechanical system inspection and repair as necessary
c. Fire system inspection and repair as necessary
d. Lighting system inspection and repair v1.1 6 as necessary
5. Routinely functionally test all operating systems in the room or as required by the manufacturer. At a minimum, the following must be tested:
a. All alarms including, emergency exhaust button, fire alarm pull stations, emergency power shut off, and VOC sense signal
b. Mechanical systems including, exhaust, air conditioner, etc.
c. Fire systems including, fire dampers, pull stations, and switches
d. Battery charging stations
6. Roughly 200 SF of interior space is required - a 20’ CONEX will meet this requirement.
a. No specific interior storage system required
b. No specific door required; original CONEX door will work
7. Battery capacity must be 8+. Battery sizes or comparably sized batteries: The battery sits in a molded section on a custom plate made by the vehicle manufacturer. Batteries will be stored and charged in CONEX. There will be no other power load inside the CONEX
a. 5.4 kWh lithium-ion battery tray
b. 1 kWh battery tray
c. 24V battery for Drix DDS system
8. Permanent power onsite and at backup site:
a. Power pedestal with 125V and 250 V (50 amps)
b. Power pedestal with 110V (15 amps)
c. Power pedestal with 480V (100 amps)