POPLAR_04-124692_DWG_A.pdf

PDF 4 MB Posted

Attached to
ADA Path of Travel Upgrades at 11 Preschool Playgrounds
Solicitation number
25/26-0026i
Issued by
San Bernardino County, California

About this file

This is an architectural design document prepared by Lionakis for the Fontana Unified School District's Poplar Elementary School play equipment replacement project located at 9937 Poplar Avenue, Fontana, California 92335. The project scope encompasses the installation of new play equipment and play surfacing replacement with a focus on accessibility compliance. The design includes an overall site plan, an enlarged site plan showing surface slopes and transitions, and a play structure layout. A mandatory job walk is scheduled for November 12, 2025, at 9:00 am, with bid responses due November 20, 2025, at 2:00 pm and a tentative contract award date of December 8, 2025. The contract term is 60 calendar days. The project requires compliance with the 2022 California Building Code, California Fire Code, ADA Standards for Accessible Design, and ASTM standards for playground surfaces, with all construction documents reviewed and approved by the Division of the State Architect.

The estimated construction cost is $180,000 with a 10% Unidentified Conditions Allowance to be added to the base bid. Contractors must possess a valid Class B Contractor's License, register with the Department of Industrial Relations, comply with prevailing wage requirements, and provide performance and payment bonds each equal to 100% of the total contract amount. Comprehensive general liability insurance with specific coverage limits is required. The project is one of eleven elementary school sites across the Fontana Unified School District, including Cypress, Dorothy Grant, Hemlock, North Tamarind, Oak Park, Poplar, Randall Pepper, Redwood, Shadow Hills, Tokay, and Date Elementary Schools, all funded through public works contracting with payment based on a site-by-site total pricing model. The design emphasizes accessible path of travel requirements, including barrier-free access routes with controlled slopes, ground surface compliance per ASTM F 1951 and F 1292, and synthetic play surface installation with proper transitions to existing concrete walkways.

View the file

Other files

File Type Posted
ADA_Path_of_Travel_Upgrades_at_11_Preschool_Playgrounds_(Addendum_#1_Revision).pdf PDF
ADA_Path_of_Travel_Upgrades_at_11_Preschool_Playgrounds.pdf PDF
POPLAR_04-124692_DWG_A.pdf PDF
DOROTHY_GRANT_04-124684_DWG_A.pdf PDF
TOKAY_04-124690_DWG_A.pdf PDF
HEMLOCK_04-124685_DWG_A.pdf PDF
SHADOW_HILLS_04-124691_DWG_A.pdf PDF
CYPRESS_04-124686_DWG_A.pdf PDF
OAK_PARK_04-124687_DWG_A.pdf PDF
RANDALL_PEPPER_04-124681_DWG_A.pdf PDF
District_Specifications.pdf PDF
NORTH_TAMARIND_04-124695_DWG_A.pdf PDF
REDWOOD_04-124693_DWG_A.pdf PDF
DATE_04-124688_DWG_A.pdf PDF
DSA_Approval,_Poplar_04_124692_0.pdf PDF
DSA_Approval,_S_Hills_04_124691_0.pdf PDF
DSA_Approval,_O_Park_04_124687_0.pdf PDF
DSA_Approval,_R_Pepper_04_124681_0.pdf PDF
DSA_Approval,_Redwood_04_124693_0.pdf PDF
DSA_Approval,_Hemlock_04_124685_0.pdf PDF
DSA_Approval,_N_Tamarind_04_124695_0.pdf PDF
DSA_Approval,_Cypress_04_124686_0.pdf PDF
DSA_Approval,_T_Porter_04_124689_0.pdf PDF
DSA_Approval,_Live_Oak_04_124696_0.pdf PDF
BID_REQUEST_FORM_9-23-25.pdf PDF
DSA_Approval,_D._Grant_04_124684_0.pdf PDF
DSA_Approval,_Tokay_04_124689_0.pdf PDF
DSA_Approval,_Date_04_124688_0.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

VICINITY MAP

OWNER

FONTANT UNIFIED SCHOOL DISTRICT

9680 CITRUS AVENYE

FONTANT, CA 92335

CONTACT: FACILITIES PLANNING DESIGN AND CONSTRUCTION

CONTACT NAME: SAMER ALUZBAIDI, EXECUTIVE DIRECTOR

PHONE: 909.357.7528

ARCHITECT

LIONAKIS

2050 MAIN STREET, SUITE 400

IRVINE, CA

CONTACT: TONY PACHECO-TAYLOR

PHONE: 949.955.1919

EMAIL: TONYPACHECOTAYLOR@LIONAKIS.COM

PROJECT DIRECTORY

THIS PROJECT SCOPE INCLUDES THE FOLLOWING:

NEW PLAY EQUIPMENT AND PLAY SURFACING REPLACEMENT.

SCOPE OF PROJECT

SHEET INDEX

N/A

DEFERRED SUBMITTALS

BUILDING IDENTIFIER - WHERE OCCURS

DISCIPLINE DESIGNATOR - LEVEL 1

DISCIPLINE DESIGNATOR - LEVEL 2

REPLACE DASH WHERE OCCURS

SHEET TYPE SUBSET DESIGNATOR

LEVEL/SEQUENCE DESIGNATOR

AREA IDENTIFIER - WHERE OCCURS

SHEET TYPE DESIGNATOR

C.A-123AB

UNIQUE PORTION IDENTIFIER - WHERE OCCURS

SHEET TYPE DESIGNATORS

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - LARGE SCALE VIEWS

5 - DETAILS

6 - SCHEDULES & DIAGRAMS

7 - USER DEFINED

8 - USER DEFINED

9 - 3D REPRESENTATIONS

DISCIPLINE DESIGNATORS - LEVEL 1

G GENERAL

H HAZARDOUS MATERIALS

V SURVEY/MAPPING

B GEOTECHNICAL

C CIVIL

L LANDSCAPE

S STRUCTURAL

A ARCHITECTURAL

I INTERIORS

Q EQUIPMENT

F FIRE PROTECTION

P PLUMBING

D PROCESS

M MECHANICAL

E ELECTRICAL

W DISTRIBUTED ENERGY

T TELECOMMUNICATIONS

R RESOURCE

X OTHER DISCIPLINES

Z CONTRACTOR/SHOP DRAWINGS

O OPERATIONS

SHEET IDENTIFICATION LEGEND

ARCHITECTURAL SYMBOLS LEGEND

B3 A-501

B3 A-501

A4 A-201

D2 A-512

TOC 98'-8"

B3 A-301

A2 A-303

A2 A-303

ROOM NAME

NORTH

PLAN

MATCH LINE

SEE XX / X-XXX

A

A-202 A2

A1

A2A4

A3

A-202

LEVEL 1

100'-0"

D2 A-512

D2 A-512

DETAIL INDICATOR - REFERENCE &

DETAIL INDICATOR - ITEM

DETAIL INDICATOR - SECTION & DETAIL

INDICATOR - SECTION ITEM

SECTION INDICATOR - PARTIAL

BUILDING/WALL &

DETAIL INDICATOR - AREA

SECTION INDICATOR - BUILDING

ELEVATION INDICATOR - EXTERIOR

ELEVATION INDICATOR - INTERIOR,

SINGLE & MULTIPLE VIEW

MATCH LINE INDICATOR

REFERENCE GRID WITH REFERENCE GRID LINES

REVISION INDICATOR & REVISION CLOUD

ROOM IDENTIFIER WITH ROOM NAME & NUMBER

ELEVATION INDICATOR - LEVEL & SPOT

WINDOW OR LOUVER IDENTIFIER

KEYNOTE INDICATOR

PLAN NORTH & TRUE NORTH INDICATOR

PROJECT LOCATION

LOCATION MAP

1 2 3 4 5

D

C

B

A

SHEET

TITLE

MANAGEMENT

ISSUED

PROJECT

SEAL

CONSULTANT

CLIENT PROJECT NO:

COPYRIGHT:

LIONAKIS PROJECT NO:

LIONAKIS 2017

IF

T

HI

S

SH

EE

T

IS

N

OT

"x

IT

IS

A R

ED

UC

ED

P

RI

NT

SC

AL

E

AC

CO

RD

IN

GL

Y

1/4

1/2

1"

2"

CLIENT

6/2 7/2

5 5

:26 :40

P M

Au tod es k D oc s:/

/02

.16

P op lar E lem en tar y/0

4.1 6_

AR

CH

MS

TR

_R

_C

EN

TR

AL

.rv t

G-001

COVER SHEET

9937 POPLAR AVE

FONTANA, CA 92335

OTC PACKAGE

025154.16 ?00.00.00?

FONTANA UNIFIED

POPLAR ELEMENTARY SCHOOL

JUNE 2025

POPLAR ELEMENTARY PLAY EQUIPMENT REPLACEMENT

FONTANA UNIFIED

POPLAR ELEMENTARY PLAY

EQUIPMENT REPLACEMENT

9937 POPLAR AVE

FONTANA, CA 92335

9680 CITRUS AVENUE FONTANA, CA 92335

SEE UNITED STATES NATIONAL

CAD STANDARD FOR ANY

ABBREVIATIONS NOT LISTED

BELOW.

& AND

@ AT

(E) EXISTING

' FOOT, FEET

" INCH(ES)

# NUMBER

ALUM ALUMINUM

ARCH ARCHITECTURAL

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT / ENGINEER

AB ANCHOR BOLT

AC ASPHALTIC CONCRETE

ACC ACCESSIBLE

ACS DR ACCESS DOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

AD AREA DRAIN

ADC AUTOMATIC DOOR CLOSER

ADO AUTOMATIC DOOR OPERATOR

ADDL ADDITIONAL

ADJ SHV ADJUSTABLE SHELVING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AGGR AGGREGATE

AHU AIR HANDLING UNIT

ASSY ASSEMBLY

BD BOARD

BKG BACKING

BLDG BUILDING

BM BEAM

BM BENCHMARK

BOT BOTTOM

BTWN BETWEEN

BUR BUILT-UP ROOFING

BW BOTH WAYS

C CHANNEL

CAB CABINET

CB CATCH BASIN

CBC CALIFORNIA BUILDING CODE

CEM CEMENT

CEM PLAS CEM PLASTER

CFLG COUNTERFLASHING

CFMF COLD-FORMED METAL FRAMING

CG CORNER GUARD

CI CAST IRON

CJ CONSTRUCTION JOINT /

CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

CO CLEANOUT

COL COLUMN

CONC CONCRETE

CONSTR CONSTRUCTION

CONT CONTINUE / CONTINUOUS

COTG CLEANOUT TO GRADE

CP CONTROL PANEL

CPT CARPET

CRS COLD ROLLED STEEL

CSK COUNTER SUNK

CSWK CASEWORK

CT CERAMIC TILE

CTR CENTER

DBL DOUBLE

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

LIST OF ARCHITECTURAL ABBREVIATIONS GENERAL NOTES

GENERAL

G-001 COVER SHEET

ARCHITECTURAL

AS101 OVERALL SITE PLAN

AS102 ENLARGED SITE PLAN

AS103 PLAY STRUCTURE LAYOUT

DHM DETENTION HOLLOW METAL

DIA DIAMETER

DIM DIMENSION

DS DOWNSPOUT

DSP DRY STANDPIPE

DWG DRAWING

DWR DRAWER

EA EACH

EGSB EXTERIOR GYPSUM SHEATHING

BOARD

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC / ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

EPB ELECTRICAL PANEL BOARD

EQ EQUAL

EQUIP EQUIPMENT

EW EACH WAY

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXST EXISTING

EXP EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FB FLAT BAR

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FIN FINISH

FLG FLOORING

FLL FLOW LINE

FLR FLOOR

FOC FACE OF CONCRETE/CURB

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FOW FACE OF WALL

FP FIREPROOF

FRP FIBERGLASS REINFORCED

PLASTIC

FT FEET / FOOT

FTG FOOTING

FURG FURRING

FUT FUTURE

G GROUND; NATURAL GAS

GA GAGE

GALV GALVANIZED

GB GRAB BAR

GI GALVANIZED IRON

GLU LAM GLUED LAMINATED WOOD

GYP GYPSUM

HB HOSE BIB

HC HOLLOW CORE

HDBD HARDBOARD

HDW HARDWARE

HDWD HARDWOOD

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

JAN JANITOR

KIT KITCHEN

L ANGLE

LAB LABORATORY

LAV LAVATORY

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MR MOISTURE RESISTANT

MTD MOUNTED

MTL METAL

MULL MULLION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O/ OVER

OC ON CENTER

OD OUTSIDE DIAMETER

OF/CI OWNER FURNISHED /

CONTRACTOR INSTALLED

OFF OFFICE

OGL OBSCURE GLASS

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

PAF POWER ACTUATED FASTENER

PL PROPERTY LINE; PLATE

PLAM PLASTIC LAMINATE

PLB PLUMB

PLBG PLUMBING

PLYWD PLYWOOD

PNL PANEL

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT; PAINT

PTN PARTITION

PV PHOTOVOLTAIC

QT QUARRY TILE

R RADIUS; RISER

RD ROOF DRAIN

REBAR REINFORCING STEEL BAR

REF REFERENCE

REF REFRIGERATOR

REINF REINFORCE / REINFORCING

REQD REQUIRED

RESIL RESILIENT

RM ROOM

RO ROUGH OPENING

RWD REDWOOD

RWL RAIN WATER LEADER

SAD SEE ARCHITECTURAL

DRAWINGS

SATC SUSPENDED ACOUSTICAL TILE

CEILING

SB SPLASH BLOCK

SC SOLID CORE

SCHED SCHEDULE

SD STORM DRAIN

SDST SELF DRIVING, SELF TAPPING

SHT SHEET

SHTHG SHEATHING

SHV SHELVING

SIM SIMILAR

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SS SANITARY SEWER; SERVICE

SINK

SST STAINLESS STEEL

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SYMM SYMMETRICAL

SYS SYSTEM

T TREAD

T&G TONGUE & GROOVE

TEL TELEPHONE

THK THICKNESS

TMH TOP OF MANHOLE

TMPD TEMPERED

TO TOP OF

TOC TOP OF CURB

TOF TOP OF FRAME

TOJ TOP OF JOIST

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOPO TOPOGRAPHY

TOS TOP OF STEEL

TOW TOP OF WALL

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER/CABINET

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

UR URINAL

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VWC VINYL WALL COVERING

VWF VINYL WALL FABRIC

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WH WATER HEATER

WO WHERE OCCURS

WP WORKING POINT

WPM WATERPROOF MEMBRANE

WSCT WAINSCOT

WT WEIGHT

WTR WATER

WWR WELDED WIRE

REINFORCEMENT

2050 Main Street, Suite 400 Irvine, CA 92614 P 949.955.1919 F 949.955.9175 www.lionakis.com

C35462

LI

CE

NS

ED A

T

RCHITEC

R 7EN. 0 -30- 2

S AT

AT E

OF CA L I

FO

RN

I

D.Y

OH

PAC

TN

A

N -O

CEH

T A Y L O R

1. SPECIAL REQUIREMENTS:

-ACCESSIBLE PATH OF TRAVEL PER SHEET AS101

2. CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS,

INCLUDING BUT NOT LIMITED TO:

TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHALL REGULATIONS

TITLE 24 CCR, PART 1 - 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE

TITLE 24 CCR, PART 2 - 2022 CALIFORNIA BUILDING CODE, VOL.1 & 2 (CBC)

TITLE 24 CCR, PART 3 - 2022 CALIFORNIA ELECTRICAL CODE (CEC)

TITLE 24 CCR, PART 4 - 2022 CALIFORNIA MECHANICAL CODE (CMC)

TITLE 24 CCR, PART 5 - 2022 CALIFORNIA PLUMBING CODE (CPC)

TITLE 24 CCR, PART 6 - 2022 CALIFORNIA ENERGY CODE

TITLE 24 CCR, PART 9 - 2022 CALIFORNIA FIRE CODE (CFC)

TITLE 24 CCR, PART 11 - 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE

TITLE 24 CCR, PART 12 - 2022 CALIFORNIA REFERENCED STANDARDS

2022 NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS (CA AMENDED)

2019 NFPA 14, INSTALLATION OF STANDPIPE AND HOSE SYSTEMS

2021 NFPA 17, DRY CHEMICAL EXTINGUISHING SYSTEMS

2021 NFPA 17A, WET CHEMICAL EXTINGUISHING SYSTEMS

2022 NFPA 20, INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION

2018 NFPA 22, WATER TANKS FOR PRIVATE FIRE PROTECTION

2022 NFPA 24, INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES

2013 NFPA 25, INSPECTION, TESTING, MAINTENANCE OF WATER-BASED FIRE PROTECTION

SYSTEMS (CA AMENDED)

2022 NFPA 72, NATIONAL FIRE ALARM CODE (CA AMENDED)

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

3. CHANGES TO THE APPROVED DRAWINGS OR SPECIFICATIONS SHALL BE MADE BY ADDENDA OR

CONSTRUCTION CHANGE DOCUMENTS (CCD) APPROVED BY THE DIVISION OF THE STATE

ARCHITECT, AS REQUIRED BY THE SECTION 4-338 OF CALIFORNIA CODE OF REGULATIONS,

TITLE 24, PART I. (CAC 4-338) SUBSTITUTIONS OF PRODUCTS OR PROCESSES WHICH AFFECT STRUCTURAL SAFETY, FIRE AND LIFE-SAFETY, OR ACCESSIBILITY SHALL BE SUBMITTED AS AN

ADDDENDUM OR CONSTRUCTION CHANGE DOCUMENT TO DSA FOR REVIEW AND APPROVAL.

MARK DATE DESCRIPTION

OTC PACKAGE

TEST MARK (For DSA Use Only) Prior to adding document to the Session the Plan Reviewer shall place this test mark off the top edge of the first sheet and change status to "INCORPORATE". If Back-check menu does not show or the color does not change to green, the Plan Reviewer shall fix the back-check menu. For guidance on how to fix the back-check menu, refer to "_DSA EPR Support > Help Desk > Fixing Back Check Menu"

TOTAL SHEETS: 4

APP. INC:

REVIEWED FOR

SS FLS ACS

DATE:

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

04-124692

06/30/2025 x xx x x x x x x x x xx x x x x x x x x x x x x x x x x x

GENERAL NOTES

SITE LEGEND

1.

2.

3.

CONTRACTOR TO FIELD VERIFY SPOT ELEVATION PRIOR TO SETTING FINAL GRADES.

THE GROUND AROUND ANY BUILDING SHALL BE SLOPE A MINIMUM OF 5% AWAY FROM THE

BUILDING FOR AT LEAST 10 FEET FROM THE FACE OF THE WALL PER CBC, AND IMPERVIOUS

SURFACES SHALL BE SLOPED AT A MINIMUM OF 2% AWAY FROM THE BUILDING.

ACCESS TO A PUBLIC WAY: THE EXIT DISCHARGE SHALL PROVIDE A DIRECT AND

(CBC 1028.5) UNOBSTRUCTED ACCESS TO PUBLIC WAY.

EXISTING BUILDING WITH NO SCOPE OF WORK

EXISTING FIRE TRUCK ACCESS ROAD (MINIMUM

20'-0" CLEAR WIDTH)

EXISTING PATH OF TRAVEL (SEE SHEET AS102

FOR SLOPE INFORMATION)

"DESIGN PROFESSIONAL IN GENERAL

RESPONSIBLE CHARGE STATEMENT : THE POT

IDENTIFIED IN THESE CONSTRUCTION

DOCUMENTS IS COMPLIANT WITH THE CURRENT

APPLICABLE CALIFORNIA BUILDING CODE

ACCESSIBILITY PROVISIONS FOR PATH OF

TRAVEL REQUIREMENTS FOR ALTERATIONS,

ADDITIONS AND STRUCTURAL REPAIRS. AS

PART OF THE DESIGN OF THIS PROJECT, THE

POT WAS EXAMINED AND ANY ELEMENTS,

COMPONENTS OR PORTIONS OF THE POT THAT

WERE DETERMINED TO BE NONCOMPLIANT 1)

HAS BEEN IDENTIFIED AND 2) THE DETAILS,

DRAWINGS AND SPECIFICATIONS

INCORPORATED INTO THESE CONSTRUCTION

DOCUMENTS. ANY NONCOMPLIANT ELEMENTS,

COMPONENTS OR PORTIONS OF THE POT THAT

WILL NOT BE CORRECTED BY THIS PROJECT

BASED ON VALUATION THRESHOLD LIMITATIONS

OR A FINDING OF UNREASONABLE HARDSHIP

ARE SO INDICATED IN THESE CONSTRUCTION

DOCUMENTS.

DURING CONSTRUCTION, IF POT ITEMS WITHIN

THE SCOPE OF THE PROJECT REPRESENTED AS

CODE COMPLIANT ARE FOUND TO BE

NONCONFORMING BEYOND REASONABLE

CONSTRUCTION TOLERANCES, THEY SHALL BE

BOUGHT INTO COMPLIANCE WITH THE CBC AS A

PART OF THIS PROJECT BY MEANS OF

CONSTRUCTION CHANGE DOCUMENT.

"ACCESSIBLE PATH OF TRAVEL AS INDICATED

ON PLAN IS A BARRIER-FREE ACCESS ROUTE

WITHOUT ABRUPT LEVEL CHANGES EXCEEDING

½" IF BEVELED AT 1:2 MAXIMUM SLOPE OR

VERTICAL LEVEL CHANGES NOT EXCEEDING ¼"

MAXIMUM AND AT LEAST 48" IN WIDTH.

SURFACE IS STABLE, FIRM, AND SLIP-

RESISTANT. CROSS-SLOPE SHALL NOT BE

STEEPER THAN 1:48 AND SLOPE IN THE

DIRECTION OF TRAVEL SHALL NOT BE STEEPER

THAN 1:20. ACCESSIBLE PATH OF TRAVEL

SHALL BE MAINTAINED FREE OF OVERHANGING

OBSTRUCTIONS TO 80" MINIMUM AND FREE OF

OBJECTS PROTRUDING MORE THAN 4" FROM

THE WALL, ABOVE 27" AND LESS THAN 80"

ABOVE THE FLOOR. ARCHITECT SHALL VERIFY

THAT THERE ARE NO BARRIERS IN THE PATH OF

TRAVEL."

(E) STORAGE CONTAINER

A#51087A#51087A#49017A#49017A#59669

A#64102 A#64102 A#65565 A#65565 A#100261

(E ) F

IR

E

LA

N E

A#14250

A#14250

A#14250

A#14250

A#14250 A#64102

A#14250

A#14885 A#14885

(E) FIRE LANE

(E) ACCESSIBLE PARKING

A#102261

(E) D.P. ACCESSIBLE

TOILETS A#67600

(E) D.P. ACCESSIBLE

TOILETS A#67600

(E) D.P. ACCESSIBLE

TOILETS A#67600

(E) DRINKING

FOUNTAIN

(E) D.P. ACCESSIBLE

TOILETS A#67600

(E) ACCESSIBLE

HI-LOW D.F. PER

A#67600

(E) D.P. ACCESSIBLE

TOILETS A#67600

(E) GRASS

AREA

(E) GRASS

(E) GRASS

AS102

(E) GRASS

AREA

(E) A/C

PAVING

(E) A/C

PAVING

1 2 3 4 5

D

C

B

A

SHEET

TITLE

MANAGEMENT

ISSUED

PROJECT

SEAL

CONSULTANT

CLIENT PROJECT NO:

COPYRIGHT:

LIONAKIS PROJECT NO:

LIONAKIS 2017

IF

T

HI

S

SH

EE

T

IS

N

OT

"x

IT

IS

A R

ED

UC

ED

P

RI

NT

SC

AL

E

AC

CO

RD

IN

GL

Y

1/4

1/2

7/2

5 5

:26 :41

P M

Au tod es k D oc s:/

/02

.16

P op lar E lem en tar y/0

4.1 6_

AR

CH

MS

TR

_R

_C

EN

TR

AL

.rv t

AS101

OVERALL SITE PLAN

025154.16 ?00.00.00?

FONTANA UNIFIED

POPLAR ELEMENTARY PLAY

EQUIPMENT REPLACEMENT

9937 POPLAR AVE

FONTANA, CA 92335

9680 CITRUS AVENUE FONTANA, CA 92335

2050 Main Street, Suite 400 Irvine, CA 92614 P 949.955.1919 F 949.955.9175 www.lionakis.com

C35462

LI

CE

NS

ED A

T

RCHITEC

R 7EN. 0 -30- 2

S AT

AT E

OF CA L I

FO

RN

I

D.Y

OH

PAC

TN

A

N -O

CEH

T A Y L O R

SCALE 1" = 30'-0"1 SITE PLAN - OVERALL

NORTH

MARK DATE DESCRIPTION

OTC PACKAGE

APP. INC:

REVIEWED FOR

SS FLS ACS

DATE:

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

04-124692 x xx x x x x x x x x x x x x x x x x x x x x x x x x x x x

A#14885

1.4%

.2

(E) CONCRETE

ACCESS RAMP

2.0%

.8

0.1%

.9

(E) GRASS

(E) AC PAVING

GROUND SURFACE OF PLAY AREAS:

GROUND SURFACES ON ACCESSIBLE ROUTES, CLEAR FLOOR

OR GROUND SPACES, AND TURNING SPACE FOR PLAY AREA

SHALL COMPLY WITH CBC SECTION 11B-1008.2.6 AS FOLLOWS:

• GROUND SURFACES SHALL BE INSPECTED AND MAINTAINS

REGULARLY AND FREQUENTLY TO ENSURE CONTINUED

COMPLIANCE WITH ASTM F 1951.

• GROUND SURFACES LOCATED WITHIN USE ZONES SHALL

COMPLY WITH ASTM F 1292 (1999 EDITION OR 2004 EDITION).

.1%

.1%

NEW PLAY STRUCTURE & ACCESSIBLE

PLAYGROUND TURF SURFACE. (SEE

SUPPORTING DOCUMENTS FOR

ADDITIONAL INFORMATION)

AS102

REPLACE EXISTING

CONCRETE WITH

NEW CONCRETE OR

AC PAVING (MATCH

EXISTING)

2%

MAX

M

A X

(E) AC PAVING

.2%

.1%

.4%

.8% .5%

1.7%

1.6%

.4%

2%

MAX

X

2%

MAX

X

BASE MATERIAL

BELOW TURF- PER

MANUFACTURER'S

SPECIFICATIONS

(E)

CONC

WALK

CONCRETE WALK - TURF

FLUSH TRANSITION

ACCESSIBLE

PLAYGROUND TURF

FACE

THE TRANSITION FROM CONCRETE SURFACE TO NEW SYNTHETIC PLAY

SURFACE SHALL COMPLY WITH CBC 11B-303.1

GENERAL NOTES

SITE LEGEND

1. CONTRACTOR TO FIELD VERIFY SPOT ELEVATION PRIOR TO SETTING FINAL GRADES.

2. THE GROUND AROUND ANY BUILDING SHALL BE SLOPE A MINIMUM OF 5% AWAY FROM THE

BUILDING FOR AT LEAST 10 FEET FROM THE FACE OF THE WALL PER CBC, AND IMPERVIOUS

SURFACES SHALL BE SLOPED AT A MINIMUM OF 2% AWAY FROM THE BUILDING.

3. ACCESS TO A PUBLIC WAY: THE EXIT DISCHARGE SHALL PROVIDE A DIRECT AND

(CBC 1028.5) UNOBSTRUCTED ACCESS TO PUBLIC WAY.

EXISTING BUILDING WITH NO SCOPE OF WORK

EXISTING FIRE TRUCK ACCESS ROAD (MINIMUM

20'-0" CLEAR WIDTH)

EXISTING PATH OF TRAVEL (SEE SHEET AS102

FOR SLOPE INFORMATION)

"DESIGN PROFESSIONAL IN GENERAL

RESPONSIBLE CHARGE STATEMENT: THE POT

IDENTIFIED IN THESE CONSTRUCTION

DOCUMENTS IS COMPLIANT WITH THE CURRENT

APPLICABLE CALIFORNIA BUILDING CODE

ACCESSIBILITY PROVISIONS FOR PATH OF

TRAVEL REQUIREMENTS FOR ALTERATIONS,

ADDITIONS AND STRUCTURAL REPAIRS. AS

PART OF THE DESIGN OF THIS PROJECT, THE

POT WAS EXAMINED AND ANY ELEMENTS,

COMPONENTS OR PORTIONS OF THE POT THAT

WERE DETERMINED TO BE NONCOMPLIANT 1)

HAS BEEN IDENTIFIED AND 2) THE DETAILS,

DRAWINGS AND SPECIFICATIONS

INCORPORATED INTO THESE CONSTRUCTION

DOCUMENTS. ANY NONCOMPLIANT ELEMENTS,

COMPONENTS OR PORTIONS OF THE POT THAT

WILL NOT BE CORRECTED BY THIS PROJECT

BASED ON VALUATION THRESHOLD LIMITATIONS

OR A FINDING OF UNREASONABLE HARDSHIP

ARE SO INDICATED IN THESE CONSTRUCTION

DOCUMENTS.

DURING CONSTRUCTION, IF POT ITEMS WITHIN

THE SCOPE OF THE PROJECT REPRESENTED AS

CODE COMPLIANT ARE FOUND TO BE

NONCONFORMING BEYOND REASONABLE

CONSTRUCTION TOLERANCES, THEY SHALL BE

BOUGHT INTO COMPLIANCE WITH THE CBC AS A

PART OF THIS PROJECT BY MEANS OF

CONSTRUCTION CHANGE DOCUMENT.

"ACCESSIBLE PATH OF TRAVEL AS INDICATED

ON PLAN IS A BARRIER-FREE ACCESS ROUTE

WITHOUT ABRUPT LEVEL CHANGES EXCEEDING

½" IF BEVELED AT 1:2 MAXIMUM SLOPE OR

VERTICAL LEVEL CHANGES NOT EXCEEDING ¼"

MAXIMUM AND AT LEAST 48" IN WIDTH.

SURFACE IS STABLE, FIRM, AND SLIP-

RESISTANT. CROSS-SLOPE SHALL NOT BE

STEEPER THAN 1:48 AND SLOPE IN THE

DIRECTION OF TRAVEL SHALL NOT BE STEEPER

THAN 1:20. ACCESSIBLE PATH OF TRAVEL

SHALL BE MAINTAINED FREE OF OVERHANGING

OBSTRUCTIONS TO 80" MINIMUM AND FREE OF

OBJECTS PROTRUDING MORE THAN 4" FROM

THE WALL, ABOVE 27" AND LESS THAN 80"

ABOVE THE FLOOR. ARCHITECT SHALL VERIFY

THAT THERE ARE NO BARRIERS IN THE PATH OF

TRAVEL."

AC PAVING / CONCRETE (MATCH EXISTING)

1 2 3 4 5

D

C

B

A

SHEET

TITLE

MANAGEMENT

ISSUED

PROJECT

SEAL

CONSULTANT

CLIENT PROJECT NO:

COPYRIGHT:

LIONAKIS PROJECT NO:

LIONAKIS 2017

IF

T

H

IS

S H

E E

T

IS

N O

T

0" x4

2" , I

T

IS

R E

D U

C E

D P

R

IN

T

S C

A

LE

A C

C O

R D

IN

G

LY

1/

4"

1/

6/

/2

3:

:5

P

M A ut od es k

D oc s:

//0

4.

P op la r

E le m en ta ry

/0

4.

_A

R C

H M

S T

R _R

_C

E N

T R

A L.

rv t

AS102

ENLARGED SITE PLAN

025154.16

?00.00.00?

FONTANA UNIFIED

POPLAR ELEMENTARY PLAY

EQUIPMENT REPLACEMENT

9937 POPLAR AVE

FONTANA, CA 92335

9680 CITRUS AVENUE FONTANA, CA 92335

2050 Main Street, Suite 400 Irvine, CA 92614 P 949.955.1919 F 949.955.9175 www.lionakis.com

C35462

L

IC

ENSED A

T

RCHITEC

R 7EN. 0 -30- 2

S

AT

A

T E

OF C A L I FO

R N

I

D.

Y O

H

PAC

T N

A N

OCEH

T A Y L O

R

SCALE 1/8" = 1'-0"1

ENLARGED SITE PLAN

NORTH

MARK DATE DESCRIPTION

OTC PACKAGE

1 1/2" = 1'-0"2

APP. INC:

REVIEWED FOR

SS FLS ACS

DATE:

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

04-124692

GROUND SURFACE OF PLAY AREAS:

GROUND SURFACES ON ACCESSIBLE ROUTES, CLEAR FLOOR

OR GROUND SPACES, AND TURNING SPACE FOR PLAY AREA

SHALL COMPLY WITH CBC SECTION 11B-1008.2.6 AS FOLLOWS:

• GROUND SURFACES SHALL BE INSPECTED AND MAINTAINS

REGULARLY AND FREQUENTLY TO ENSURE CONTINUED

COMPLIANCE WITH ASTM F 1951.

• GROUND SURFACES LOCATED WITHIN USE ZONES SHALL

COMPLY WITH ASTM F 1292 (1999 EDITION OR 2004 EDITION).

GENERAL NOTE

SEE SHEET AS102 FOR ADDITIONAL

SURFACE INFORMATION

1 2 3 4 5

D

C

B

A

SHEET

TITLE

MANAGEMENT

ISSUED

PROJECT

SEAL

CONSULTANT

CLIENT PROJECT NO:

COPYRIGHT:

LIONAKIS PROJECT NO:

LIONAKIS 2017

IF

T

HI

S

SH

EE

T

IS

N

OT

"x

IT

IS

A R

ED

UC

ED

P

RI

NT

SC

AL

E

AC

CO

RD

IN

GL

Y

1/4

1/2

7/2

5 5

:26 :45

P M

Au tod es k D oc s:/

/02

.16

P op lar E lem en tar y/0

4.1 6_

AR

CH

MS

TR

_R

_C

EN

TR

AL

.rv t

AS103

PLAY STRUCTURE

LAYOUT

025154.16 ?00.00.00?

FONTANA UNIFIED

POPLAR ELEMENTARY PLAY

EQUIPMENT REPLACEMENT

9937 POPLAR AVE

FONTANA, CA 92335

9680 CITRUS AVENUE FONTANA, CA 92335

2050 Main Street, Suite 400 Irvine, CA 92614 P 949.955.1919 F 949.955.9175 www.lionakis.com

C35462

LI

CE

NS

ED A

T

RCHITEC

R 7EN. 0 -30- 2

S AT

AT E

OF CA L I

FO

RN

I

D.Y

OH

PAC

TN

A

N -O

CEH

T A Y L O R

SCALE 1/4" = 1'-0"1 PLAY STRUCTURE LAYOUT

MARK DATE DESCRIPTION

OTC PACKAGE

APP. INC:

REVIEWED FOR

SS FLS ACS

DATE:

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

04-124692

GENERAL
G-001 - COVER SHEET
ARCHITECTURAL
AS101 - OVERALL SITE PLAN
AS102 - ENLARGED SITE PLAN
AS103 - PLAY STRUCTURE LAYOUT

File details come from the government source that posted it. Updated .