PLC Boiler Replacement CD set.pdf
PDF 1 MB Posted
- Solicitation number
- RFP KSD 260000002129 1
- Issued by
- Kent County, Grand Rapids City, Michigan
About this file
This is a comprehensive set of construction drawings and project documentation for the Pine Grove Learning Center Boiler Replacement project in Wyoming, Michigan, prepared for Kent ISD. The project involves the replacement of domestic water heaters and the installation of two new condensing boilers (2500 MBH capacity each) to serve the facility's hot water heating system. The work is designated as Alternate P-1 and includes related mechanical, plumbing, electrical, and architectural modifications. The project is located at 2101 52nd St SW, Wyoming, Michigan, with construction documents dated 05.06.2026 and released for bids and construction. The scope encompasses demolition of existing equipment, installation of new boilers with integrated controls, condensate neutralization systems, side-stream filtration, expansion tanks, circulating pumps, and associated piping and ductwork. All work must comply with the 2021 Michigan Building Code, 2021 Michigan Mechanical Code, 2021 Michigan Plumbing Code, 2023 NFPA 70 (NEC), NFPA 13, and NFPA 101 Life Safety Code requirements.
The project design was completed by GMB (Architect/Engineer) located in Grand Rapids, with Owen-Ames-Kimball serving as the Construction Manager. The construction documents include detailed floor plans, mechanical schematics, plumbing layouts, electrical coordination diagrams, and specifications for all installed equipment, including boiler schedules, pump specifications, expansion tank requirements, and control system specifications. The existing building is Type II-B construction (non-combustible) with occupancy classification E (educational). Work includes provisions for maintaining 1-hour fire barriers, accessibility compliance per ADA standards, proper firestopping of penetrations, and coordination with existing building systems. The project requires contractor investigation of existing conditions, proper sequencing of demolition and new construction, temporary shoring and bracing, and coordination among all trades including mechanical, plumbing, electrical, and structural work to ensure successful completion and integration with the existing facility infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| COMBINED SET.pdf | ||
| 03._-_Advertisement_to_Bid_Notice - Revised.pdf | ||
| Addendum 1.pdf | ||
| CM Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1: WATER HEATER REPLACEMENT
OWNER
KENT ISD
2930 KNAPP STREET NE
GRAND RAPIDS, MI 49525
616.364.1333
WWW.KENTISD.ORG
CONSTRUCTION MANAGER
OWEN-AMES-KIMBALL
126 OTTAWA AVE NW STE 600
GRAND RAPIDS, MI 49503
616.456.1521
WWW.OWEN-AMES-KIMBALL.COM
EXISTING BUILDING CONSTRUCTION: 2021 MICHIGAN REHABILITATION CODE OF EXISTING BUILDINGS
NEW BUILDING CONSTRUCTION: 2021 MICHIGAN BUILDING CODE
SCHOOL BUILDING LIFE SAFETY: 2012 NFPA 101 LIFE SAFETY CODE AS AMENDED BY THE MICHIGAN SCHOOL RULE S
ELECTRICAL: 2023 NFPA 70 (NEC) AS AMENDED BY MICHIGAN RULES PART 8
MECHANICAL: 2021 MICHIGAN MECHANICAL CODE
PLUMBING: 2021 MICHIGAN PLUMBING CODE
FIRE ALARM SYSTEM: NFPA 70 & 72
FIRE EXTINGUISHERS: NFPA 10
FIRE SPRINKLERS: NFPA 13
CODES APPLIED
ARCHITECTURAL
A2.0.01 PLANS AND DETAILS
MECHANICAL
M0.0.01 MECHANICAL GENERAL INFORMATION
M2.1.01 ENLARGED BOILER ROOM MECHANICAL DEMOLITION PLAN
M2.2.01 ENLARGED BOILER ROOM MECHANICAL PLANS
M2.4.1A UNIT 'A' FIRST FLOOR GAS PIPING PLAN
M3.1.01 MECHANICAL & CONTROL DIAGRAMS
M5.1.01 MECHANICAL SCHEDULES & DETAILS
PLUMBING
P0.0.01 PLUMBING GENERAL INFORMATION
P2.3.1A UNIT 'A' FIRST FLOOR PLUMBING PLAN
P6.1.01 PLUMBING DETAILS & SCHEDULES
ELECTRICAL
E0.0.01 ELECTRICAL SYMBOL LEGENDS, GENERAL NOTES, & SCHEDULES
E2.2.01 ENLARGED ELECTRICAL PLANS
GENERAL INFORMATION
G0.0.01 GENERAL NOTES DIMENSIONS AND LEGENDS
GMB PROJECT #
VICINITY MAP
MAP BY GOOGLE
ALTERNATE SUMMARY, SEE SPECIFICATION SECTION 01 23 00 FOR FULL DESCRIPTIONS
ARCHITECT + ENGINEER
GMB
555 FOURTH STREET NW
GRAND RAPIDS, MI 49504
616.796.0200
WWW.GMB.COM
CODE REFERENCES
ALTERNATES
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8A
N
EW
.rv t
PINE GROVE LEARNING CENTER BOILER
REPLACEMENT
KENT ISD
WYOMING, MICHIGAN
100168
2101 52ND ST SW
05.06.2026
BIDS & CONSTRUCTION
WALL AND
BASE CABINET
MOP STRIP
AND SHELF
FIRE VALVE
CABINET
FIRE EXTINGUISHER
& WALL BRACKET
SANITARY
NAPKIN
RECEPTACLE
FULL LENGTH
MIRROR AND
B.F. MIRRORS
TOILET
PARTITION
DOOR
LA
TC
H
SI
DE
HI
NG
E
SI
DESWITCH
OUTLET
OUTLET
SHELFFE
* TO CENTERLINE OF OPERATION.
ALARM
3/8" = 1'-0"
NOTE:
MOUNT FLUSH
VALVE / HANDLE
ON WIDE SIDE
HAIR
DRYER
FIRE
EXTINGUISHER
SANITARY
NAPKIN
DISPENSER
TOWEL AND
WASTE
COMBINATION
PAPER
TOWEL
WASTE
RECEPTACLE
HAND
DRYER
CLOTHES
HOOKS
TO
C
EN
TE
RL
IN
E
OF
O
PE
RA
TI
ON
VERTICAL BABY
CHANGING
STATION
5' - 0" MIN.
HOSE
LENGTH 24"x 36"
MIRROR
MIRROR -
FULL WIDTH
OF COUNTER
SHELVING
MIRROR
SIZE AS
SPECIFIED
OR NOTED
BACKSPLASH
B.F. WATER CLOSET STALLS
B.F. ROOM SIGNAGE
B.F. CONTROLS AND ACCESSORIES
2ND B.F. WATER CLOSET STALL
IF (6) OR MORE WATER CLOSET STALLS ARE PROVIDED.
STANDARD WATER CLOSET STALLS B.F. TRANSFER SHOWER PLANB.F. TRANSFER SHOWER EL.STANDARD URINALB.F. URINAL B.F. & STANDARD LAVATORYB.F. & STAND. SINK W/ COUNTER
DOOR ACTUATOR POWER
OPERATOR BOLLARD
B.F. DRINKING FOUNTAINS/COOLERS STANDARD DRINKING FOUNTAINS
URINAL SCREEN
3'
- 0
2'
- 4
1'
- 5
3' - 0" 6"
CLEAR
3' - 6" 1' - 6"
2'
- 4
8"
1'
- 5
2'
- 4
3'
- 0
3'
- 4
1'
- 6
3' - 4"
1' - 0" 3' - 6"
5' - 0" CLEAR 4' - 0"
TOILET
PARTITION
TOILET
PARTITION
3' - 0" 5' - 0" 4' - 0"
1' - 0" 3' - 6"
3' - 4"
3'
- 4
1'
- 6
3'
- 0
2'
- 4
1'
- 5
"3'
- 0
2'
- 4
1' - 6" 1' - 6"
MAX.
2' - 6"
MIN.
2' - 6"
2' - 6" 5' - 0" 3' - 0"
2' - 6"
MAX.
2' - 6"
MIN.
2' - 6" 3' - 0"
1'
- 3
" 2'
- 4
2'
- 4
" 6'
- 0
" M
IN
IM
UM
4'
- 0
" M
AX
3' - 0"
"-1
9" 3'
- 0
3'
- 4
1'
- 6
CO
NT
RO
L A
RE
A
3'
- 2
" M
IN
MAX.
2 1/2"
MA
X.
1 1 /2"
MA
X
"-1
5"
23" MAX.
22" MIN.
CL OF RAIL
1'-6".
36".
2'- 6"
M
IN
6'
- 2
TO
L
IP
O
F S
IN
K
2'
- 1
0" M
AX
MIN.
2' - 6"
1' - 3" 1' - 3"
RE
FL
EC
TI
NG
" M
AX
. T O
MI
RR
OR
3'
- 0
BOWL
3" INSIDE
9"
2'
- 3
"8"
TO
L
IP
O
F S
IN
K
2'
- 1
0" M
AX
6" 1' - 4" 4' - 0" CLEAR
6'
- 2
2'
- 1
0" M
AX
MIN.
2' - 6"
1' - 3" 1' - 3"
3'
- 2
MI
RR
OR
3'
- 0
6" 1' - 0" 4' - 0" CLEAR
9"
8"
2'
- 3
TO
LI
P O
F S
IN
K
2'
- 1
0" M
AX
6" 1' - 0" 4' - 0" CLEAR
1' - 6"
MAX.
4" PROJECTION
9"
8"
MI
N.
2'
- 3
TO
S
PO
UT
3'
- 0
" M
AX
ALCOVE
2' - 6"
1' - 3" 1' - 3"
TO
S
PO
UT
3'
- 0
" M
AX
1' - 3" VARIES 1' - 3"
TO
S
PO
UT
3'
- 0
" M
AX
TO
S
PO
UT
3'
- 6
" M
AX
3'
- 6
3'
- 8
MA
X.
1'
- 1
0"
MIN.
2' - 6"
MIN.
2' - 8"
1' - 4" 1' - 4"
MA
X.
1'
- 5
1' - 3" 1' - 3"
MA
X.
1'
- 0
4'
- 0
1' - 9"
3'
- 1
0"
3'
- 6
1'
- 6
" 3'
- 2
W
OR
K
SU
RF
AC
E 2'
- 1 0"
T O
4'- 0"
A .D
.A
B.
F.
(M
AX
6'- 0"
ME
N' S
ST
AN
DA
RD
5'- 4"
W
OM
EN
'S
S
TA
ND
AR
D
6'
- 0
(M
AX
2'-
" B
.F
2'- 0"
B .F
ST
D.
3'
- 0
ST
D.
1'
- 1 0"
2'
- 6
5'
- 0
3'
- 4
MA
X.
1'
- 6
" B F
6'
- 0
" B .F
. M
AX
6" MIN.
" M
IN
CH
ILD
9"
M
IN
AD
UL
T)
" M
IN
CH
ILD
9"
M
IN
AD
UL
T)
" M
IN
CH
ILD
9"
M
IN
AD
UL
T)
FIRE BARRIER WALL SIGNAGE
FIRE BARRIER PROTECT
ALL OPENINGS
MINIMUM 3"
HIGH
LETTERING
CONCEALED SPACE
SIGN OR
STENCILING AT
MAXIMUM 30 FT.
INTERVALS AND AT
15 FT. FROM END
WALLS
FLOOR OR
ROOF DECK
CEILING
7" - 9" 7" - 9"
*DESIGN SHOWN FOR
SINGLE ROLL DISPENSER
7" - 9"
*DESIGN SHOWN FOR
SINGLE ROLL DISPENSER
HORIZONTAL BABY
CHANGING
STATION
TO
C
EN
TE
RL
IN
E
OF
O
PE
RA
TI
ON
SU
RF
AC
E3"
M
AX
CL
O
F
RA
IL
4"
M
AX
TO WALL
15" -16"
48".
CL OF SWR
1' - 3" MAX.
OPENING SIDE
OF SHOWER
HOLD 36" FINISH
TO FINISH
CLEARANCE,
TRADES TO
COORDINATE
5'
- 0
BO
TT
OM
O
F
BR
AI
LL
E 4'
- 0
MI
N.
T O
NOTE: OPPOSITE SIDE
GRAB BARS SIMILAR
LAYOUT
BOTTLE FILLERS WHERE
PROVIDED TO BE ON
ACCESSABLE HEIGHT
FIXTURE
X
2'
- 3
X ≥ 6
8"
4" MAX.
MA
X.
2'
- 3
X
6'
- 8
MIN.
1' - 6"MI
N.
5'
- 0
FRONT APPROACH, PULL SIDE
MIN.
* 1' - 0"MI
N.
4'
- 4
* IF BOTH CLOSER AND LATCH ARE PROVIDED
MIN.
3' - 0"MI
N.
5'
- 0
HINGE APPROACH, PULL SIDE
* 4
0" M
IN
3'
- 6
" M
IN
MIN.
* 1' - 0"
MIN.
1' - 10"
* 4
6" M
IN
4'
- 0
" M
IN
LATCH APPROACH, PULL SIDE
MIN.
2' - 0"
* 4
0" M
IN
3'
- 6
" M
IN
LATCH APPROACH, PUSH SIDE
MIN.
2' - 0"
MIN.
5' - 0"
MI
N.
4'
- 8
MIN.
2' - 6"
MI
N.
4'
- 4
MA
X.
2'
- 0
MI
N.
4'
- 4
MA
X.
2'
- 0
MIN.
2' - 8"
MIN.
3' - 0"
NOTE:
INFORMATION SHOWN IS TAKEN FROM THE
AMERICAN NATIONAL STANDARD INSTITUTE
(ANSI) AND IS FOR REFERENCE ONLY AS
DESCRIBED IN ANSI ICC A117.1-2017
MA
X.
MA
X.
MA
X.
MA
X.
1/4
1/2
1/2
1/4
3'
- 0
" C
LE
AR
MI
N.
3'
- 0
3' - 0" CLEAR
MIN.
4' - 4"
SEAT
WALL
BACK
WALL
MI
N.
2'
- 6
2'
- 6 " C
LE
AR
5' - 0" CLEAR
MA
X.
1'
- 3
MIN.
1' - 4"
MAX.
2' - 3"
CONTROLS TO
BE 38" MIN. TO
48" MAX. ABOVE
FLOOR
CONTROLS TO
BE ABOVE
GRAB BAR TO
48" MAX.
ABOVE FLOOR
6" M
AX
FRONT APPROACH, PUSH SIDE
MIN.
3' - 6"MI
N.
4'
- 6
HINGE APPROACH, PULL SIDE
* IF BOTH CLOSER AND LATCH ARE PROVIDED
HINGE APPROACH, PUSH SIDE
* IF CLOSER IS PROVIDED
* IF CLOSER IS PROVIDED
CHANGES IN LEVEL
PROTRUDING OBJECTS REDUCED VERTICAL CLEARANCE ACCESSIBLE ROUTE
CLEAR WIDTH
WATER CLOSET AND LAVATORY CLEARANCE
2'
- 1
" M
AX
1'
- 5 " M
IN
TRANSFER SHOWER CLEARANCE
CL
CL
CONTROL
WALL
SIDE
WALL
CL
SIDE
WALL
SEAT
(IF APPLICABLE)
CL BACK
WALL
STANDARD ROLL-IN SHOWER CLEARANCE
MIN.
5' - 0"
6" MAX.
ø 5'
- 7"
FIGURE 404.2.3.2
FIGURE 303.3
FIGURE 404.2.3.2
FIGURE 404.2.3.2
FIGURE 404.2.3.2
FIGURE 404.2.3.2
FIGURE 404.2.3.2
FIGURE 404.2.3.2
FIGURE 307.2 FIGURE 307.4
FIGURE 403.5
CHAPTER 6 CHAPTER 6 CHAPTER 6
GENERAL PROJECT NOTES: CODE NOTES:
ACCESSIBILITY NOTES:
STRUCTURAL NOTES:
FLOOR DRAIN
FIRE EXTINGUISHER
HAND DRYER
MARKER BOARD
BEARINGBRG.
F.D.
F.E.
F.E.C.
H.D.
M.B.
FIRE EXTINGUISHER CABINET
(SURFACE MOUNTED)
ABBREVIATIONS
CEILINGCLG.
DIMENSIONDIM.
ISOCYANURATEISO.
= ABOVE FINISHED FLOORA.F.F.
EQUALEQ.
ALTERNATEALT. =
HORIZONTALHORIZ. =
FLR. FLOOR=
FIN. FINISHED=
GYP. GYPSUM BOARD=
GALV. GALVANIZED=
CONTINUOUSCONT. =
BARRIER FREEB.F. =
CONCRETECONC. =
BATTEN INSULATIONBATT. =
CORRIDORCORR. =
CONFERENCECONF. =
= AMERICANS WITH DISABILITY ACTA.D.A.1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
FINISH FLOOR ELEVATION = EXISTING = 100'-0"
DRAWINGS ARE NOT TO BE SCALED WHEN A DIMENSION IS IN QUESTION, VERIFY W/ ARCHITECT.
DETAILS SHOWN BUT NOT CALLED OUT STILL APPLY, UNLESS OTHERWISE NOTED.
GENERAL TRADES CONTRACTOR SHALL COORDINATE ALL TRADES INCLUDING OWNER FURNISHED EQUIPMENT, INCLUDING DIMENSIONS OF SUCH AS THEY RELATE TO HIS/HER OWN WORK.
ALL EXPOSED SURFACES SHALL BE FINISHED. CONTACT ARCHITECT FOR DIRECTION IF FINISH IS NOT LISTED.
NO UTILITIES INCLUDING BUT NOT LIMITED TO, PIPING AND CONDUIT SHALL BE EXPOSED UNLESS APPROVED BY
ARCHITECT.
GYPSUM BOARD WALLS AND BULKHEADS SHALL HAVE CONTROL JOINTS AT A 30'-0" O.C. MAXIMUM AND AS SHOWN ON
DRAWINGS.
ANY CONTRACTOR IS TO STOP WORK IMMEDIATELY IN AREA IF ABATEMENT MATERIAL(S) ARE ENCOUNTERED. NOTIFY GENERAL CONTRACTOR OF SUSPECTED AREA SO PROPER ABATEMENT CAN BE DONE. (UNDER A SEPARATE
ABATEMENT CONTRACT AS NEGOTIATED BY OWNER.)
AT ALL AREAS OF WORK WHERE EXISTING MASONRY BLOCK AND BRICK WALLS ARE BEING MODIFIED OR CONNECTED
TO NEW MASONRY AND/OR BRICK MUST BE TOOTHED, UNLESS NOTED OTHERWISE ON DRAWINGS.
CONTRACTOR SHALL VERIFY LOCATIONS OF UTILITIES PRIOR TO EXCAVATION, TRENCHING, ETC. AND SHALL REPAIR
OR REPLACE ANY DAMAGED UTILITIES AS A RESULT OF CONSTRUCTION.
ALL TRADES ARE TO COORDINATE ANY DEMOLITION, CAPPING OR ABANDONMENT OF EXISTING MECHANICAL, ELECTRICAL, PLUMBING OR ARCHITECTURAL ITEMS.
ANY DEMOLITION OR CONSTRUCTION WHICH DAMAGES ADJACENT SURFACES IS TO BE REPAIRED TO MATCH THE EXISTING SURFACE DAMAGED (MATERIALS & FINISHES) AND ALL REPAIR WORK IS TO BE COORDINATED WITH NEW
CONSTRUCTION.
CONTRACTOR IS TO PROVIDE TEMPORARY SHORING AND BRACING FOR EXISTING ROOF/FLOOR STRUCTURE AS
REQUIRED UNTIL PERMANENT WALLS & LINTELS ARE INSTALLED.
SITE SECURITY AND SAFETY ARE THE CONTRACTOR'S RESPONSIBILITY. SITE SHALL BE SECURED (FENCED IF
REQUIRED) BY CONTRACTOR.
ALL ITEMS TO BE SAVED AND/OR RELOCATED ARE TO BE STORED IN A PROPER MANNER SO NO DAMAGE WILL OCCUR
TO THESE ITEMS DURING THEIR STORAGE PERIOD.
ALL CONSTRUCTION AND MATERIALS ARE TO BE INSTALLED BY THE MANUFACTURER'S SPECIFICATIONS AND/OR
RECOMMENDATIONS UNLESS DIRECTED OTHERWISE BY ARCHITECT.
SEE SPECIFICATIONS FOR STEEL LINTEL SIZES FOR WALL OPENINGS NOT DETAILED (e.g. HVAC DUCTS, ETC.).
REFER TO GENERAL INFORMATION SHEET G0.01 FOR TYPICAL BARRIER FREE AND ACCESSIBLE DIMENSIONS.
SEE FLOOR PLANS FOR WALL REINFORCING REQUIRED. (SEE WALL REINFORCING SCHEDULE)
FURNISH & INSTALL 2x12 HORIZONTAL WOOD BLOCKING BETWEEN STUDS WHERE REQUIRED FOR MOUNTING OF
UPPER CABINETS, GRAB BARS OR OTHER EQUIPMENT AS REQUIRED FOR PROPER SUPPORT.
COORDINATE ALL CONSTRUCTION PRACTICE TOLERANCES WITH OTHER TRADES WHOSE WORK MAY BE AFFECTED, DIRECTLY OR INDIRECTLY, WITH YOUR SPECIFIC TRADE. IN ALL CASES, THE MOST STRINGENT TOLERANCE SHALL APPLY AND SHALL BE COORDINATED THRU THE GENERAL CONTRACTOR, JOB SUPERINTENDENT AND/OR
CONSTRUCTION MANAGER AND FIELD OBSERVATION PERSON AS APPLICABLE.
REFER TO FLOOR PLANS, SCHEDULES AND EXTERIOR ELEVATIONS FOR WINDOW FRAME TYPES.
REFER TO FLOOR PLANS, SCHEDULES AND INTERIOR ELEVATIONS FOR BORROWED LITE FRAME TYPES.
AT MASONRY CAVITY WALL LOCATION, PROVIDE APPROPRIATE SEPARATION IN REGARDS TO INTERIOR AIR EXFILTRATION AND EXTERIOR AIR AND WATER INFILTRATION THRU WALL. PROVIDE NECESSARY AIR AND WATER
BARRIERS REQUIRED, INCLUDING DAMS, TO PREVENT WALL LEAKAGE.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
FIRE DEPARTMENT ACCESS AND WATER SUPPLY SHALL BE IN PLACE PRIOR TO COMMENCEMENT OF VERTICAL
CONSTRUCTION.
FIRE STOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND CONCEALED WALL SPACES
AT THE CEILING, FLOOR, AND ROOF LEVELS.
INSTALL SOLID BLOCK BEHIND ALL RECESSED WALL UNITS AS REQUIRED TO MAINTAIN FIRE RATINGS.
ALL FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS, AND SMOKE PARTITIONS SHALL BE IDENTIFIED WITH STENCILING AT INTERVALS NOT TO EXCEED 30'. REFER TO CODE PLAN FOR WALLS REQUIRED TO
BE PROTECTED.
ALL PENETRATIONS AT SMOKE AND FIRE RATED WALLS, FLOORS, CEILINGS, ETC. SHALL BE PROTECTED, SEALED OR DAMPERED USING ONLY U.L. AND / OR I.C.B.O. APPROVED METHODS, MATERIALS AND INSTALLATION.
SEE REFLECTED CEILING PLANS AND LIGHTING PLANS FOR EXIT SIGNAGE LOCATIONS.
ALL EXITS TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF KEY OR SPECIAL KNOWLEDGE.
PANIC HARDWARE TO BE PROVIDED AT EACH EXIT DOOR FROM ROOMS WITH AN OCCUPANT LOAD 50 OR MORE
INCLUDING MAIN CORRIDOR EXIT DOORS.
ALL ELEVATORS SHALL COMPLY WITH A.D.A., A.D.A.G.G. AND A.N.S.I. REQUIREMENTS.
SPECIAL STRUCTURAL INSPECTIONS ARE REQUIRED. REVIEW GENERAL STRUCTURAL NOTES AND SPECIFICATIONS
FOR REQUIREMENTS.
FIRE SPRINKLERS AND FIRE ALARM SYSTEM SHALL BE PROVIDED PER NFPA NO. 13, 70 & 72. SUBMIT ALL REQUIRED DRAWING AND INFORMATION TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO COMMENCEMENT OF ANY RELATED WORK. OBTAIN APPROVAL OF COMPLETED SYSTEMS PRIOR TO FINAL ACCEPTANCE.
1.
2.
3.
4.
5.
6.
7.
8.
PUBLIC ENTRANCES: AT LEAST 60% SHALL BE ACCESSIBLE.
ACCESSIBLE ENTRANCES TO THE BUILDING SHALL BE IDENTIFIED BY THE INTERNATIONAL SIGN OF ACCESSIBILITY.
AN ACCESSIBLE ROUTE OF NOT LESS THAN 3 FT. WIDE MUST BE PROVIDED TO ALL PORTIONS OF THE BUILDING AND BETWEEN THE BUILDING AND THE PUBLIC WAY. ACCESSIBLE ROUTES SHALL HAVE A MAXIMUM SLOPE OF 1:20 AND A
MAXIMUM CROSS SLOPE OF 1:50.
ACCESSIBLE ROUTE SHALL BE WITHOUT STEPS OR CHANGES IN LEVEL GREATER THAN 1/2" WITHOUT AN APPROVED
RAMP.
ACCESSIBLE RAMPS THAT ARE REQUIRED BY ANSI A 117.1 SHALL NOT HAVE A SLOPE THAT EXCEEDS 1FT. IN 12 FEET.
RAMPS AND GROUND SURFACES SHALL BE OF A SLIP RESISTANT SURFACE.
THRESHOLDS MUST BE 1/2" OR LESS IN HEIGHT.
ALL ACCESSIBLE PARKING SPACES MUST HAVE A SIGN THAT INCLUDES THE INTERNATIONAL SIGN OF ACCESSIBILITY.
PARKING SPACE WILL BE OUTLINED IN A CONTRASTING COLOR WITH THE INTERNATIONAL SIGN OF ACCESSIBILITY
PAINTED IN THE CENTER.
ALL ALARMS TO MEET ACCESSIBILITY REQUIREMENTS.
1.
2.
CONSTRUCTION AND/OR CONTROL JOINTS IN CONCRETE SHALL BE ON A 12'-0" SQUARE GRID (MAX.) UNLESS OTHERWISE NOTED. ALL CONSTRUCTION JOINTS SHALL BE DOWELED W/ 1/2" SMOOTH DOWELS AT 24" O.C. SEE DETAILS.
PROVIDE CONTINUOUS U-BLOCK BOND BEAMS AT THE LOCATIONS INDICATED ON WALL SECTIONS OR DETAILS. FILL U- BLOCKS WITH CONCRETE AND REINFORCE WITH (2) #5 BARS CONTINUOUS UNLESS NOTED OTHERWISE ON DRAWINGS.
BOARDBD. =
DISHWASHERDW. =
EXISTINGEX. =
MAXIMUMMAX. =
DOWNDN. =
DOWNSPOUTDS. =
DRINKING FOUNTAIND.F. =
TACK BOARD
UNLESS NOTED OTHERWISE
T.B.
U.N.O.
SIMILAR TOSIM.
OPPOSITEOPP.
ON CENTERO.C.
MISCELLANEOUSMISC.
TOILETT.
NOT IN CONTRACTN.I.C.
MECHANICALMECH.
STORAGESTOR.
VESTIBULEVEST.
WITHW/
TYPICALTYP.
MINIMUMMIN.
MASONRY JOINTM.J. =
PLASTIC LAMINATEP.LAM =
TONGUE AND GROOVET&G =
STANDARDSTD. =
NOMINALNOM. =
WELDED WIRE FABRICW.W.F. =
VERTICALVERT. =
TOP OF MASONRYT.O.M. =
SPECIFICATIONSPEC. =
REQUIREDREQ. =
METALMTL. =
MICHIGAN BUILDING CODEM.B.C. =
TOP OF WALLT.O.W. =
TOP OF FOOTINGT.O.F. =
REINFORCINGREINF. =
ROOF DRAINR.D. =
ELEVATIONEL. =
VERIFY IN FIELDV.I.F. =
ALUMINUMALUM. =
BOTTOM OFB.O. =
DIAMETERDIA. =
EXPANSIONEXP. =
HOLLOW STRUCTURAL SECTIONH.S.S. =
MANUFACTURERMFR. =
INSULATIONINSUL. =
PRESERVATIVE TREATEDP.T. =
STAINLESS STEELS.S. =
CONTROL JOINTC.J. =
MASONRY OPENINGM.O. =
FIRE EXT. RECESSED CABINETF.E.R.C.
F.E.S.C. FIRE EXT. SEMI-RECESSED CABINET
GA. GAUGE=
EXTERIOREXT. =
F.R.T. FIRE RETARDANT TREATED=
20 1 1/4" 250S125-30 BULKHEADS & MISC. FRAMING
20 1 1/4" 362S125-30 INTERIOR WALLS & BULKHEADS
20 1 5/8" 600S162-33
16 1 5/8" 600S162-54 EXTERIOR WALLS
20 1 1/4" 250T125-30 BULKHEADS & MISC. FRAMING
20 1 1/4" 362T125-30 INTERIOR WALLS & BULKHEADS
20 1 1/4" 600T125-33
INTERIOR WALLS & BULKHEADS
16 1 1/2" 600T150-54 EXTERIOR WALLS
20 087F125-33
20 150F125-33
N/A
N/A
WHERE NOTED
WHERE NOTED
20 362T250-33 DEFLECTION TRACK2 1/2"
COLD-FORMED METAL FRAMING SCHEDULE
DEPTH GAUGE
(33 KSI)
FLANGE
WIDTH
2 1/2"
LOCATION / USEIDENTIFICATION
AISI S100/S200
3 5/8" 6"
6"
ST
UD
S
JO
IS
TS
TR
AC
K
2 1/2"
3 5/8"
6"
6"
7/8"
1 1/2"
FU
RR
IN
G
(H
AT
3 5/8"
NOTE: ALL MEMBERS IN THIS SCHEDULE ARE SIZED FOR MAXIMUM 15' TALL WALLS, NOTE THAT 6"
INTERIOR STUDS CAN SPAN A MAXIMUM HEIGHT OF 28'
SEE COLD-FORMED METAL HEADER SCHEDULE FOR SPECIFIC JAMB & HEADER REQUIREMENT
NON-LOAD BEARING
20 1 5/8" 362S162-33 INTERIOR JAMBS
20 1 5/8" 600S162-33
3 5/8" 6"
18 1 5/8" 600S162-436"
18 1 5/8" 600S162-436"
18 1 1/4" 600T125-436"
6" 20 GA. MAX HEIGHT 22'
6" 18 GA. 22' - 28'
6" 20 GA. MAX HEIGHT 22'
6" 18 GA. 22' - 28'
6" 20 GA. MAX HEIGHT 22'
6" 18 GA. 22' - 28'
GENERAL FLOOR PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
DIMENSIONS GIVEN ARE TO THE FACE OF MASONRY UNITS OR TO THE FINISHED FACE OF METAL STUD PARTITION WALLS.
REFERENCE MECHANICAL, PLUMBING AND ELECTRICAL FOR ITEMS NOT SHOWN. COORDINATE AS REQUIRED INCLUDING
NECESSARY FRAMING, BLOCKING, ETC.
FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF ANY CABINETRY, FRAMES, STRUCTURAL ITEMS, ETC.
PROVIDE PAINTED ACCESS PANELS IN WALLS AND CEILINGS TO PROVIDE ACCESS TO CONCEALED ITEMS INCLUDING BUT NOT LIMITED TO VALVES, CONTROLS, MECH. EQUIPMENT, ETC. ACCESS PANELS MAY NOT ALWAYS BE SHOWN ON PLANS. IT IS THE SUB CONTRACTOR RESPONSIBILITY TO DETERMINE LOCATIONS. COORDINATE LOCATIONS WITH OTHER GENERAL
CONTRACTOR / SITE SUPERVISOR.
PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER DETAILS. SEE G0.01 FOR REQUIREMENTS.
CONTRACTOR TO MAINTAIN / REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED BY DEMOLITION / NEW
CONSTRUCTION. TYPICAL THROUGHOUT.
SEAL ALL PENETRATIONS IN FIRE RATED FLOORS AND WALLS WITH APPROVED FIRESTOPPING.
WALLS TO BE PATCHED WITH LIKE MATERIALS WHERE EXISTING WALLS HAVE BEEN COMPROMISED FROM DEMOLITION. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO REMOVAL AND REINSTALLATION OF CASEWORK AND WALL MOUNTED EQUIPMENT IN ORDER TO ACHIEVE SAID PATCH. IN AREAS WHERE BLOCK OR BRICK HAVE BEEN USED, NEW MASONRY TO BE TOOTHED IN AND MATCH EXISTING. AREAS AND FINISHES IN QUESTION SHALL BE COORDINATED WITH
ARCHITECT.
COLD-FORMED METAL HEADER SCHEDULE
ROUGH
OPENING
MATERIAL HEADER
SHAPE
6'-0"
MAX.
HEADER: (2) 362S162-33 JOISTS
(2) 362T125-33 TRACKS
JAMBS: (1) 362S162-33 STUD EACH END
(1) 362T125-33 TRACK
ALL HEADERS IN THIS SCHEDULE ARE SIZED FOR INTERIOR, NON-LOAD BEARING WALLS ONLY
BASED ON 12' WALL HEIGHT / 5 psf INTERNAL LOAD / 50 plf VERTICAL DEAD LOAD
12'-0"
MAX.
HEADER: (2) 1000S162-43 JOISTS
(1) 362S162-33 HORIZONTAL
(3) 362T125-33 TRACKS
JAMBS: (2) 362S162-33 STUDS EACH END
(1) 362T125-33 TRACK
T J
T
J
T T H
10'-0"
MAX.
HEADER: (2) 600S162-33 JOISTS
(2) 362T125-33 TRACKS
JAMBS: (2) 362S162-33 STUDS EACH END
(1) 362T125-33 TRACK
T J
T
T
INTERIOR, NON-LOAD BEARING
A7.01
1 VIEW NAME
1/8" = 1'-0"
A101
SIM
A1.01
SIM
1/8" = 1'-0"
VIEW NAME
1i
B106A
A1.01
SIM
NORTH ARROW, FLOOR PLAN CALLOUT
VIEW CALLOUT
DETAIL CALLOUT (SECTION OR PLAN)
BUILDING SECTION
WALL OR PARTIAL SECTION
(PLAN VIEW & ELEVATIONS)
A1.01
SIM
ROOM LABEL
ELEVATION LABEL
WINDOW / BORROWED LITE
DOOR TAG
ELEVATION TAG
GENERAL ANNOTATION LEGEND
AA
A6.01
AA
A6.01
A6.10
A7.01 A101
SIM
A7.01
W01 1iBL01
ROOM NUMBER
UNIT LETTER
DOOR SUFFIX LETTER
ROOM LABEL
FIRST FLOOR
100'-0"
HEIGHT ABOVE
FINISHED FLOOR
LEVEL NAME
ELEVATION HEIGHT
PLAN NORTH
VIEW NUMBER
SHEET NUMBER
SECTION DETAIL PLAN DETAIL
WINDOW TAG
BORROWED LITE TAG
ROOM LABEL W/ FINISHES
10' - 2"
ROOM NAME
A121
ROOM NAME
A121
Wall Finish
Base Finish Floor Finish
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8A
N
EW
.rv t
5/ 6/
2:
:2
PM
G0.0.01
100168
GENERAL NOTES
DIMENSIONS AND LEGENDS
JTD
SNG
P
IN
E G
R O
V E
L E
A R
N
IN
G C
E N
T E
R B
O
IL
E R
R E
P
LA
C E
M E
N T
K E
N T
IS
D
W Y
O M
IN
G
M
IC
H
IG
A
N
1/4" = 1'-0"
BARRIER FREE ADA DIMENSIONS
1/4" = 1'-0"
ACCESSIBLE BUILDING LEGEND
05.06.2026 BIDS &
CONSTRUCTION
T
AT
S
AT
S
T
GENERAL FLOOR PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
DIMENSIONS GIVEN ARE TO THE FACE OF MASONRY UNITS OR TO THE FINISHED FACE OF METAL STUD PARTITION WALLS.
REFERENCE MECHANICAL, PLUMBING AND ELECTRICAL FOR ITEMS NOT SHOWN. COORDINATE AS REQUIRED INCLUDING
NECESSARY FRAMING, BLOCKING, ETC.
FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF ANY CABINETRY, FRAMES, STRUCTURAL ITEMS, ETC.
PROVIDE PAINTED ACCESS PANELS IN WALLS AND CEILINGS TO PROVIDE ACCESS TO CONCEALED ITEMS INCLUDING BUT NOT LIMITED TO VALVES, CONTROLS, MECH. EQUIPMENT, ETC. ACCESS PANELS MAY NOT ALWAYS BE SHOWN ON PLANS. IT IS THE SUB CONTRACTOR RESPONSIBILITY TO DETERMINE LOCATIONS. COORDINATE LOCATIONS WITH OTHER GENERAL
CONTRACTOR / SITE SUPERVISOR.
PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER DETAILS. SEE G0.01 FOR REQUIREMENTS.
CONTRACTOR TO MAINTAIN / REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED BY DEMOLITION / NEW
CONSTRUCTION. TYPICAL THROUGHOUT.
SEAL ALL PENETRATIONS IN FIRE RATED FLOORS AND WALLS WITH APPROVED FIRESTOPPING.
WALLS TO BE PATCHED WITH LIKE MATERIALS WHERE EXISTING WALLS HAVE BEEN COMPROMISED FROM DEMOLITION. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO REMOVAL AND REINSTALLATION OF CASEWORK AND WALL MOUNTED EQUIPMENT IN ORDER TO ACHIEVE SAID PATCH. IN AREAS WHERE BLOCK OR BRICK HAVE BEEN USED, NEW MASONRY TO BE TOOTHED IN AND MATCH EXISTING. AREAS AND FINISHES IN QUESTION SHALL BE COORDINATED WITH
ARCHITECT.
WALL LEGEND
EXISTING CMU WALL
-DIMENSIONS GIVEN ARE TO THE FINISHED FACE OF CMU OR
GYPSUM WALL BOARD UNLESS NOTED OTHERWISE
EXISTING BRICK AND BLOCK WALL
SE
E
PL
AN
SE
E
PL
AN
BOILER
A160
2' - 4"
3'
- 6
1' - 11"
3'
- 6
A2.0.01
A2.0.01
BUILDING:
ALLOWABLE AREA: EXISTING
ACTUAL AREA: EXISTING
CONSTRUCTION TYPE: II-B MBC; II(000) NFPA 220
OCCUPANCY: E
REHABILITATION CODE: LEVEL 1 ALTERATIONS
BUILDING AREA UNCHANGED, NO NEW CONSTRUCTION
AUTOMATIC FIRE SUPPRESSION SYSTEM
FIRE ALARM - REFER TO ELECTRICAL FOR ADDITIONAL
INFORMATION
EMERGENCY LIGHTING - REFER TO ELECTRICAL FOR
ADDITIONAL INFORMATION
1-HR FB
ALTERNATE P-1
ALTERNATE P-1
DEMOLITION LEGEND
EXISTING WALL TO BE DEMOLISHED
PORTION OF EXISTING WALL TO BE DEMOLISHED
EXISTING OBJECT TO BE DEMOLISHED
EXISTING WALLS TO REMAIN
EXISTING OBJECTS TO REMAIN
XX DEMOLITION TAG: SEE DEMOLITION NOTES
AREA OF FLOOR CUTTING
ROOM NAME
CEILING FINISH
FLOOR FINISH
EXISTING ROOM FINISH INFORMATION:
ROOM NAME, FLOORING TYPE, CEILING TYPE
AREA OF CEILING REMOVAL AND REINSTALL
DEMOLITION NOTES
06 SEE MECHANICAL DEMOLITION NOTES FOR REMOVAL OF EXIST. PLUMBING/MECHANICAL (i.e. LAVATORIES, SINKS, WATER CLOSETS, URINALS, FIN TUBE, MECH. DUCTWORK, UNIT VENTS, ETC.)
DEMOLITION CONTRACTOR IS TO STOP WORK IMMEDIATELY IN AREA IF ASBESTOS IS ENCOUNTERED.
NOTIFY CONSTRUCTION MANAGER OF SUSPECTED AREA SO PROPER ABATEMENT CAN BE DONE.
(UNDER A SEPARATE ASBESTOS ABATEMENT CONTRACT AS NEGOTIATED BY OWNER.)
ALL MASONRY BLOCK AND BRICK WALLS TO BE REMOVED MUST BE TOOTHED TO RECEIVE NEW
MASONRY, UNLESS NOTED OTHERWISE ON DRAWINGS.
DEMOLITION CONTRACTOR IS TO PROVIDE TEMPORARY SHORING AND BRACING FOR EXISTING
ROOF/FLOOR STRUCTURE AS REQUIRED UNTIL PERMANENT WALLS & LINTELS ARE INSTALLED.
REFER TO STRUCTURAL & ARCHITECTURAL DRAWINGS FOR BEARING CONDITIONS.
ALL TRADES ARE TO COORDINATE ANY DEMOLITION, CAPPING OR ABANDONMENT OF EXISTING
MECHANICAL, ELECTRICAL, PLUMBING OR ARCHITECTURAL ITEMS.
ALL ITEMS TO BE SAVED AND/OR RELOCATED ARE TO BE STORED IN A PROPER MANNER SO NO
DAMAGE WILL OCCUR TO THESE ITEMS DURING THEIR STORAGE PERIOD.
ALL DEMOLITION WHICH DAMAGES ADJACENT SURFACES IS TO BE REPAIRED TO MATCH THE
EXISTING SURFACE DAMAGED (MATERIALS & FINISHES) AND ALL REPAIR WORK IS TO BE
COORDINATED WITH NEW CONSTRUCTION. FOR NEW OPENINGS IN EXISTING WALLS, COORDINATE
NEW LINTELS W/ MASONRY CONTRACTOR.
PATCH WALLS & ROOF TO MATCH EXISTING CONSTRUCTION BEHIND REMOVAL OF WALL LOUVERS, EXHAUST FANS, INTAKE HOODS & CABINET HEATERS. VERIFY SEQUENCE OF REMOVAL W/
CONSTRUCTION MANAGER. SEE MECHANICAL AND ELECTRICAL DEMOLITION SHEETS FOR WALL,
ROOF & FLOOR OPENINGS TO BE PATCHED.
ALL TRADES ARE TO COORDINATE THE REMOVAL OF EXISTING LOOSE EQUIPMENT WITH ARCHITECT AND/OR OWNER. ADDITIONAL EQUIPMENT FOUND THAT IS NOT NOTED ON DEMOLITION PLAN SHALL BE REMOVED AS PART OF GENERAL DEMOLITION AFTER VERIFICATION WITH ARCHITECT/OWNER.
GENERAL NOTES
DESIGN CRITERIA
1.
2.
3.
4.
5.
6.
7.
ROOF DETAILS - LOCATED ON SHEET A2.0.01
ROOF DRAIN
ROOF OVERFLOW DRAIN
FASTENING ENHANCEMENT AT CORNER - SEE SPEC AND DETAIL
PLUMBING VENT
STACK FLASHING
METAL COPING SPLICE DETAIL
ROOF CURB DETAIL
RE-ROOFING EXISTING NAILERS / BLOCKING TO REMAIN:
CONTRACTOR TO FIELD VERIFY THE EXISTING NAILERS / BLOCKING
WILL COMPLY TO MEET THE WIND UP LIFT CRITERIA. REMOVE ALL
DAMAGED NAILERS / BLOCKING AND / OR INSTALL ADDITIONAL
FASTENER AS REQUIRED TO COMPLY.
REFER TO PLUMBING DRAWINGS FOR LOCATION AND NUMBER OF
PLUMBING VENTS THRU ROOF.
REFER TO MECHANICAL DRAWINGS TO COORDINATE ALL ROOF
PENETRATIONS & LOCATIONS.
PROVIDE 1/2" PER FOOT TAPERED CRICKETS AT ALL ROOF HATCHES
AND MECHANICAL ROOF PENETRATIONS UNLESS OTHERWISE
NOTED. TAPER SHALL PROVIDE DRAINAGE AROUND HATCH AND
EQUIPMENT.
CONTRACTOR RESPONSIBLE TO FIELD VERIFY ALL SQUARE
FOOTAGE VALUES NOTED ON PLANS
STANDARD ROOF ABBREVIATIONS
RD = ROOF DRAIN
ORD = OVERFLOW ROOF DRAIN
EF = EXHAUST FAN
IV = INTAKE VENT
RTU = ROOF TOP UNIT
RV = RELIEF VENT
ULTIMATE WIND SPEED (3 SEC. GUST) 114 mph
WIND EXPOSURE C
INTERNAL PRESSURE COEFFICIENT (Gcpi) 0.18
COMPONENTS & CLADDING PRESSURE (asd):
FLAT ROOFS (BASED ON 20 SF)
UPLIFT WITHIN 9' OF CORNER 48 psf
UPLIFT WITHIN 9' OF EDGE 33 psf UPLIFT INTERIOR 16 psf
COMPONENTS & CLADDING PRESSURE (ult):
FLAT ROOFS (BASED ON 20 SF)
UPLIFT WITHIN 9' OF CORNER 80 psf
UPLIFT WITHIN 9' OF EDGE 55 psf UPLIFT INTERIOR 26 psf
FLASH IN NEW VENTS/STACKS INTO
EXISTING ROOF AS REQUIRED TO
MAINTAIN ALL ROOF MANUFACTURERS
WARRANTIES
NOTE: PATCH AND REPAIR ALL
ABANDONED ROOF OPENINGS TO
MATCH EXISTING ADJACENT
INSULATION AND MEMBRANE. ALL
WORK MUST MAINTAIN ROOF
MANUFACTURERS WARRANTIES
(E ) 2
2K
(E ) 2
2K
(E ) 2
2K
(E ) 2
2K
VIF
+/- 5' - 6"
VIF
+/- 5' - 6"
VIF
+/- 5' - 2"
L5X3X1/4 ROOF
FRAME, SEE
DETAIL, TYP
A2.0.01
TYP
A2.0.01
TYP
PROVIDE NEW FRAME IF NO
FRAME EXISTISTS
S.S. CLAMPING RING
FLASHING AS REQUIRED
ROOF LAP SEALANT CONT. (TYPICAL)
PRE-MOLDED FLASHING & METAL COLLAR
ROOF LAP SEALANT CONT. (TYPICAL)
VENT PIPE SEE PLUMBING DRAWINGS
MI
N.
1'
- 0
EXISTING ROOF SYSTEM AND
DECK TO REMAIN
EXISTING ROOF DECK
FLASH INTO EXISTING ROOF AS
REQUIRED TO MAINTAIN ALL ROOF
MANUFACTURER WARRANTIES
TEMPERATURE APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
UMBRELLA TO STACK
UMBRELLA
STORM COLLAR
EXISTING ROOF DECK
STACK PIPE SEE MECHANICAL
MIN.
4"
EXISTING ROOF SYSTEM
AND DECK TO REMAIN
MODIFY EXISTING
OPENING AS REQUIRE TO
MAINTAIN 1" AIR GAP TO
PIPE (TYP.)
MI
N.
1'
- 6
1"
FLASH INTO EXISTING ROOF AS
REQUIRED TO MAINTAIN ALL
ROOF MANUFACTURER
WARRANTIES
4"
4" M
IN
DRILL & EPOXY SET #4 DOWEL
AT ALL CORNERS OF NEW
PAD-EMBED 2 1/2" INTO BOTH
EXISTING SLAB AND NEW PAD
SCARIFY EXISTING SLAB
SURFACE UNDER NEW PAD
AND COAT WITH BONDING
AGENT
CONCRETE PAD WITH 6x6- W1.4xW1.4 WWM (FLAT
SHEETS)
3/4" CHAMFER- ALL
EDGES (TYP.)
EXISTING CONCRETE
SLAB
16 GA PLATE AT OPENINGS UP TO 12" WIDE;
12 GA PLATE AT OPENINGS UP TO 18" WIDE -
SCREW DOWN TO EX ROOF ON ALL SIDES
EXISTING ROOF DECK
EXISTING ROOF OPENING
NOTE: PLATE TO BE MIN 8" LARGER THAN OPENING
(EG - IF OPENING IS 18"ø, PROVIDE 26" X 26" X 12 GA PLATE)
BOILER
CONCRETE
EXPOSED
LEGEND - CODE COMPLIANCE PLAN
1-HR FIRE BARRIER (IBC SECTION 707 / NFPA 101 - 8.3)
FIRE BARRIER (1-HOUR FIRE RESISTANCE RATING REQUIRED). INSTALL FROM FLOOR
SLAB TO UNDERSIDE OF ROOF DECK ABOVE. OPENING SHALL BE LESS THAN 25% OF
THE WALL. OPENING PROTECTIVES DEPEND ON TYPE OF ASSEMBLY PER TABLE
716.1(2) (IBC) AND TABLE 8.3.4.2 (NFPA 101).
1-HR FB
GENERAL CODE NOTES
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
FIRE DEPARTMENT ACCESS AND WATER SUPPLY SHALL BE IN PLACE PRIOR TO COMMENCEMENT OF VERTICAL
CONSTRUCTION.
FIRE STOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND CONCEALED WALL SPACES AT
THE CEILING, FLOOR, AND ROOF LEVELS.
ALL OPENINGS AROUND MECHANICAL, PLUMBING, ELECTRICAL, AND STRUCTURAL PENETRATIONS THRU A FIRE RESISTIVE RATED ASSEMBLY (INCLUDING FLOORS) SHALL BE SEALED WITH FIRE RATED FIRESTOPPING IN COMPLIANCE WITH ASTM E814 AND EQUIVALENT TO FIRE RATING REQUIRED. PENETRATIONS THRU SMOKE RESISTIVE NON-FIRE
RATED ROOM, WALLS SHALL BE SEALED SMOKE TIGHT.
INSTALL SOLID BLOCK BEHIND ALL RECESSED WALL UNITS AS REQUIRED TO MAINTAIN FIRE RATINGS.
ALL FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS, AND SMOKE PARTITIONS SHALL BE IDENTIFIED WITH STENCILING AT INTERVALS NOT TO EXCEED 30'. REFER TO CODE PLAN FOR WALLS REQUIRED TO BE PROTECTED.
ALL PENETRATIONS AT SMOKE AND FIRE RATED WALLS, FLOORS, CEILINGS, ETC. SHALL BE PROTECTED, SEALED OR DAMPERED USING ONLY U.L. AND / OR I.C.B.O. APPROVED METHODS, MATERIALS AND INSTALLATION.
SEE REFLECTED CEILING PLANS AND LIGHTING PLANS FOR EXIT SIGNAGE LOCATIONS.
ALL EXITS TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF KEY OR SPECIAL KNOWLEDGE.
ALL ELEVATORS SHALL COMPLY WITH A.D.A., A.D.A.G.G. AND A.N.S.I. REQUIREMENTS.
SPECIAL STRUCTURAL INSPECTIONS ARE REQUIRED. REVIEW GENERAL STRUCTURAL NOTES AND SPECIFICATIONS FOR
REQUIREMENTS.
FIRE SPRINKLERS AND FIRE ALARM SYSTEM SHALL BE PROVIDED PER NFPA NO. 13, 70 & 72. SUBMIT ALL REQUIRED DRAWING AND INFORMATION TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO COMMENCEMENT OF ANY RELATED WORK. OBTAIN APPROVAL OF COMPLETED SYSTEMS PRIOR TO FINAL ACCEPTANCE.
TELOSCOPING BLEACHER SYSTEM SHALL BE PROVIDED PER 2021 MICHIGAN BUILDING CODE, A.D.A, A.D.A.G.G. AND A.N.S.I. REQUIREMENTS. SUBMITAL ALL REQUIRED DRAWINGS AND INFORMATION TO THE AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF ANY RELATED WORK. OBTAIN APPROVAL OF
COMPLETED INSTALLATION PRIOR TO FINAL ACCEPTANCE.
EXISTING BUILDING CONSTRUCTION: 2021 MICHIGAN REHABILITATION CODE OF EXISTING BUILDINGS
NEW BUILDING CONSTRUCTION: 2021 MICHIGAN BUILDING CODE
SCHOOL BUILDING LIFE SAFETY: 2012 NFPA 101 LIFE SAFETY CODE AS AMENDED BY THE MICHIGAN SCHOOL RULE S
ELECTRICAL: 2023 NFPA 70 (NEC) AS AMENDED BY MICHIGAN RULES PART 8
MECHANICAL: 2021 MICHIGAN MECHANICAL CODE
PLUMBING: 2021 MICHIGAN PLUMBING CODE
FIRE ALARM SYSTEM: NFPA 70 & 72
FIRE EXTINGUISHERS: NFPA 10
FIRE SPRINKLERS: NFPA 13
CODES APPLIED
L5X3X1/4 x 8" LONG (TYP)
OR FIELD WELD L5X5X1/4
DIRECTLY TO JOIST TOP
CHORD
L5X3X1/4
FIELD VERIFY LENGTH
LENGTHFIELD VERIFY
LENGTH
FIELD VERIFY
NOTE:
-UNLESS OTHERWISE NOTED TYPICAL FRAMING LAYOUT AND SIZE SHOWN FOR TYPICAL ROOF
EQUIPMENT OPENINGS. SEE FRAMING PLAN (& COORD W/ ARCH & MECH PLANS) FOR LOCATIONS.
-AT LARGE OPENINGS, SEE FRAMING PLANS FOR FRAME MEMBER SIZES
8"
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
KEYPLAN
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8A
N
EW
.rv t
5/ 6/
2:
:1
PM
A2.0.01
100168
PLANS AND DETAILS
JTD
SNG
P
IN
E G
R O
V E
L E
A R
N
IN
G C
E N
T E
R B
O
IL
E R
R E
P
LA
C E
M E
N T
K E
N T
IS
D
W Y
O M
IN
G
M
IC
H
IG
A
N
AREA OF WORK
1/4" = 1'-0"
PARTIAL FLOOR PLAN
1/4" = 1'-0"
PARTIAL DEMOLITION PLAN 1/4" = 1'-0"
PARTIAL ROOF PLAN
A2.0.01 1 1/2" = 1'-0"
4 TYPICAL PLUMBING VENT DETAIL - ALTERNATE P-1
A2.0.01 1 1/2" = 1'-0"
2 STACK FLASHING DETAIL
A2.0.01 1" = 1'-0"
1 EQUIPMENT PAD DETAIL
A2.0.01 3/4" = 1'-0"
3 ROOF INFILL - SMALL OPENING
A2.0.01 1/2" = 1'-0"
5 TYPICAL ROOF FRAME DETAIL
S
PI
FS
PS
TW
F
PT
1.
2.
3.
REFER TO PROJECT SPECIFICATIONS MANUAL FOR ADDITIONAL REQUIREMENTS.
INSTALL PLUMBING EQUIPMENT, TRIM, FITTINGS, AND OTHER COMPONENTS IN
ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS.
INSTALL PLUMBING EQUIPMENT ON CONCRETE BASE WHERE INDICATED.
GENERAL PLUMBING EQUIPMENT INSTALLATION NOTES :GENERAL PLUMBING PIPING INSTALLATION NOTES :
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
REFER TO PROJECT SPECIFICATIONS MANUAL FOR ADDITIONAL REQUIREMENTS.
DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL LOCATION AND
ARRANGEMENT OF PIPING SYSTEMS. INDICATED LOCATIONS AND ARRANGEMENTS
WERE USED TO SIZE PIPE AND OTHER DESIGN CONSIDERATIONS. INSTALL PIPING AS
INDICATED UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON COORDINATION
DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL PIPE SLEEVES
THROUGH FOUNDATION WALLS WITH OTHER TRADES.
INSTALL CLEANOUTS AT THE BASE OF ALL DRAIN PIPE STACKS WITH THE CENTER OF
THE PLUG LOCATED AT A MINIMUM OF 12 INCHES ABOVE THE FINISH FLOOR, UNLESS
NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER BUILDING ELEMENTS TO
ENSURE ACCESS.
INSTALL PIPING IN CONCEALED LOCATIONS UNLESS INDICATED OTHERWISE OR WHERE
LOCATED IN EQUIPMENT ROOMS AND SERVICE AREAS. INSTALL PIPING INDICATED TO
BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES
OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS
SPECIFICALLY INDICATED OTHERWISE.
ROUTE PIPING IN WALLS TO FIXTURE AND EQUIPMENT AT PROPER ELEVATION.
INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR
CEILING TILE REMOVAL.
INSTALL PIPING TO PERMIT VALVE SERVICING, FREE OF SAGS AND BENDS, AT
INDICATED SLOPES, INSTALL FITTINGS FOR CHANGES OF DIRECTION AND BRANCH
CONNECTIONS, AND TO ALLOW THE APPLICATION OF INSULATION.
UNLESS NOTED OTHERWISE ON THE PLUMBING PLANS, INSTALL DRAIN PIPING 2" AND
SMALLER SLOPED AT 1/4" PER FOOT (MINIMUM), AND DRAIN PIPING 3" AND LARGER
SLOPED AT 1/8" PER FOOT (MINIMUM).
INSTALL SANITARY VENT PIPING SLOPED (GRADED) BACK TO THE DRAINAGE SYSTEM.
HORIZONTAL DRAIN PIPING 4" AND LARGER SHALL HAVE RIGID BRACING OR RIGID
SUPPORT AT CHANGES OF DIRECTION OF 45 DEGREES OR GREATER TO RESIST THE
MOVEMENT OF THE UPSTREAM PIPING IN THE DIRECTION OF FLOW.
INSTALL OVERSIZED PIPE HANGERS ON ALL PIPING SYSTEMS WITH A CONTINUOUS
VAPOR BARRIER. REFER TO SPECIFICATION SECTION 22 07 19.
PIPE HANGERS SHALL NOT BE ATTACHED TO THE ROOF DECK UNLESS INDICATED
OTHERWISE.
COORDINATE ROUTING OF PLUMBING PIPING WITH ALL TRADES. ALL SANITARY PIPING
TO BE INSTALLED AND VENTED PER PLANS AND ALL APPLICABLE STATE AND LOCAL
CODES.
INSTALL PIPING SLOPED BACK T OTHE WATER SERVICE ENTRANCE IN ALL SEASONAL
BUILDINGS TO ACCOMMODATE DRAINAGE FOR SEASONAL FREEZE PROTECTION.
INSTALL TEE WITH LOCKABLE BALL VALVE AND THREADED CAP IMMEDIATELY
DOWNSTREAM OF MAIN SHUT OFF VALVE. FURNISH AND INSTALL HEAT TRACING
AROUND MAIN SHUT OFF VALVE TO BELOW FROST DEPTH.
GENERAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
ALL EXISTING PLUMBING FIXTURES, EQUIPMENT, AND ASSOCIATED PIPING SHOWN AS
DASHED (HEAVY/BOLD) SHALL BE REMOVED. PROTECT EXISTING WORK WHICH IS TO
REMAIN IN PLACE FOR REUSE WITH TEMPORARY COVERS, SHORING, BRACING, AND
SUPPORTS. EXISTING DOMESTIC COLD, HOT, HOT WATER RETURN, AND NATURAL GAS
PIPING LOCATED IN TUNNELS SHALL BE CAPPED AND ABANDONED IN PLACE.
THE OWNER RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIP OF ANY
EQUIPMENT AND MATERIALS TO BE REMOVED FROM THE BUILDING SITE. ALL
EQUIPMENT TO BE REMOVED AND NOT REUSED SHALL BECOME THE PROPERTY OF THE
CONTRACTOR AND SHALL BE REMOVED FROM THE OWNERS PROPERTY.
INVESTIGATION OF EXISTING PLUMBING SYSTEMS WILL BE REQUIRED BY THE
CONTRACTOR AS PART OF HIS BID PRICE, SO THAT THE EXACT EXTENT OF DEMOLITION
CAN BE ACCURATELY DETERMINED. THE CONTRACTOR'S BID PRICE SHALL ALSO COVER
REMOVAL OF SOME PORTIONS OF PLUMBING SYSTEMS NOT EXPLICITLY SHOWN ON THE
DEMOLITION DRAWINGS, BUT DISCOVERED DURING THE INVESTIGATION PROCESS. THE
CONTRACTOR SHALL WORK WITH THE ARCHITECT/ENGINEER AND THE OWNER TO
DETERMINE WHICH PORTIONS OF EXISTING SYSTEMS MUST REMAIN ACTIVE AND WHICH
PORTIONS MUST BE DEMOLISHED. REMOVE ALL INACTIVE PIPING TO THE NEAREST
ACTIVE MAINS AND CAP. ABANDONED PIPING SYSTEMS BENEATH THE BUILDING SHALL
BE CAPPED AT BOTH ENDS.
DEMOLITION OF AN ITEM SHALL INCLUDE REMOVAL OF ALL RELATED HANGERS,
SUPPORTS, PIPING, AND ACCESSORIES. REMOVAL OF POWER WIRING SHALL BE BY
OTHERS UNLESS INDICATED OTHERWISE.
CONTRACTOR SHALL PROTECT ALL WALLS, CEILINGS, FLOORS, LIGHTS AND OTHER
FINISHED SURFACES WHICH ARE NOT SCHEDULED FOR IMMEDIATE REMOVAL. IF
SURFACES OR LIGHTS ARE DAMAGED, CONTRACTOR SHALL REPAIR OR REPLACE TO
MATCH ORIGINAL CONDITIONS.
CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR ALL FLOOR, WALL, AND
ROOF REPAIR WORK LEFT BY REMOVED ITEMS.
PLUMBING ABBREVIATIONS
AAV AIR ADMITTANCE VALVE
AFF ABOVE FINISH FLOOR
AVTR ACID VENT THROUGH ROOF
BFP BACKFLOW PREVENTER
BT BATHTUB
CBV CALIBRATED BALANCING VALVE
CLG CEILING
CO CLEANOUT
CONN CONNECTION
CONT CONTINUATION
CONTR CONTRACTOR
COORD COORDINATE
DF DRINKING FOUNTAIN
DFU DRAINAGE FIXTURE UNITS
DN DOWN
DPB DOMESTIC WATER PRESSURE BOOSTER
DSN DOWNSPOUT NOZZLE
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EX / EXIST EXISTING
FD FLOOR DRAIN
FLR FLOOR
HB HOSE BIBB
HSS HOLLOW STRUCTURAL SECTION
HWFU HOT WATER FIXTURE UNITS
IE INVERT ELEVATION
IOB ICE MAKER OUTLET BOX
L / LAV LAVATORY
FCO FLOOR CLEANOUT
AHU AIR HANDING UNIT
H&C DOMESTIC HOT AND DOMESTIC COLD WATER
AV ACID VENT
AW ACID WASTE
CA COMPRESSED AIR
COND CONDENSATE
CW DOMESTIC COLD WATER
HW DOMESTIC HOT WATER
HWR DOMESTIC HOT WATER RETURN
G NATURAL GAS
GSAN GREASE LADEN SANITARY
GI GREASE INTERCEPTOR
CWFU COLD WATER FIXTURE UNITS
FSET FOOD SERVICE EQUIPMENT TRADES
LOC LOCATION
LT LAUNDRY TUB
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MFR MANUFACTURER
MSB MOP SERVICE BASIN
MIN MINIMUM
MV MIXING VALVE
OA OUTSIDE AIR
OC ON CENTER
OD OVERFLOW ROOF DRAIN
PSI POUNDS PER SQUARE INCH
RD ROOF DRAIN
RFCBV RESTRICTED FLOW CALIBRATED BALANCING VALVE
RH ROOF HYDRANT
RPZBFP REDUCED PRESSURE ZONE BACKFLOW PREVENTER
OSAN OIL LADEN SANITARY
OI OIL INTERCEPTOR
NOTE:
NOT ALL ABBREVIATIONS MAY BE PRESENT IN CONSTRUCTION DOCUMENTS.
SH SHOWER
TD TRENCH DRAIN
TYP TYPICAL
U / UR URINAL
USGS UNITED STATES GEOLOGICAL SURVEY
VTR VENT THROUGH ROOF
W WASTE
SAN SANITARY
SAN(FM) SANITARY FORCED MAIN
SCW SOFTENED DOMESTIC COLD WATER
ST STORM
ST(O) STORM OVERFLOW
V SANITARY VENT
U/G UNDERGROUND
UNO UNLESS NOTED OTHERWISE
WH WALL HYDRANT
WMB WASHING MACHINE OUTLET BOX
WSFU WATER SUPPLY FIXTURE UNITS
WC WATER CLOSET OR WATER COLUMN
WCO WALL CLEANOUT
WF WASH FOUNTAIN
S / SK SINK
LS LAB SINK
PLUMBING LINE SERVICE DESIGNATIONS
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER RETURN PIPING
SANITARY DRAIN PIPING UNDERGROUND
STORM DRAIN PIPING UNDERGROUND
SANITARY DRAIN PIPING ABOVE GROUND
STORM DRAIN PIPING ABOVE GROUNDST
SAN
SANITARY VENT PIPINGV
OVERFLOW STORM DRAIN PIPINGST(O)
HW
CW
HWR
SAN
ST
CONDENSATE PIPINGCOND
COMPRESSED AIR PIPINGCA
ACID WASTE PIPING UNDERGROUNDAW
ACID WASTE PIPING ABOVE GROUNDAW
ACID VENT PIPINGAV
NATURAL GAS PIPINGG
GREASE LADEN SANITARY DRAIN PIPINGGSAN
OIL LADEN SANITARY DRAIN PIPINGOSAN
SANITARY FORCED MAIN DRAIN PIPINGSAN (FM)
SOFTENED DOMESTIC COLD WATER PIPINGSCW
MATCHLINE
DIRECTION OF FLOW
NOTE:
NOT ALL PIPE SERVICES MAY BE PRESENT IN CONSTRUCTION DOCUMENTS.
PLUMBING SYMBOLS LEGEND
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
PLUG VALVE
ANGLE VALVE
PRESSURE REDUCING VALVE, SELF-CONTAINED
EXT. PRESSURE REDUCING VALVE
CHECK VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
HOSE BIBB / WALL HYDRANT
CALIBRATED BALANCING VALVE
BACKFLOW PREVENTER
WITH DRIP PAN
CONNECT TO EXISTING
CONCENTRIC REDUCER
UNION
CAP
"Y" STRAINER W/BLOWDOWN
COMPRESSED AIR
COMB. FILTER, REG. & OILER
FLOW SWITCH
PRESSURE SWITCH
PRESSURE TAP
THERMOWELL
FLEXIBLE CONNECTOR
PRESSURE GAUGE & SHUT OFF
THERMOMETER
PIPE RISER DOWN
PIPE RISER UP
NOTE:
NOT ALL SYMBOLS MAY BE PRESENT IN CONSTRUCTION DOCUMENTS.
FIXTURE
MINIMUM SIZE CONNECTION
CW HW SAN VENT
WATER CLOSET
(FLUSH VALVE)
URINAL (FLUSH VALVE)
LAVATORY
SINK
SHOWER
MOP SERVICE BASIN
WASHING MACHINE OUTLET
BOX (WITH STANDPIPE)
ICE MAKER OUTLET BOX
WALL HYDRANT / HOSE BIBB
ELECTRIC WATER COOLER
DRINKING FOUNTAIN
FLOOR DRAIN / FLOOR SINK
FLOOR DRAIN / FLOOR SINK
(MECHANICAL ROOM)
1 1/4" ---- 4" 2"
3/4" ---- 2" 1 1/2"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/2"
2"4"--------
1/2" 1/2" 1 1/4"
1/2" 1/2" 1 1/2"
2"1/2" 1/2"
3/4" 3/4" 3"
3/4" 3/4" 3" (TRAP)
1/2" --------
3/4" --------
1/2" ----
1/2" ----
1 1/4"
1 1/4"
3"--------
NOTE:
NOT ALL PLUMBING FIXTURES MAY BE PRESENT IN CONSTRUCTION DOCUMENTS.
FIXTURE
FIXTURE UNIT VALUES
DFU HWFU CWFU TOTAL
WATER CLOSET
(FLUSH VALVE)
URINAL (FLUSH VALVE)
LAVATORY
SINK
SHOWER
MOP SERVICE BASIN
WASHING MACHINE OUTLET
BOX (WITH STANDPIPE)
WALL HYDRANT / HOSE BIBB
ELECTRIC WATER COOLER /
DRINKING FOUNTAIN
FLOOR DRAIN / FLOOR
SINK (2" TRAP)
0.5
DRAINAGE
(NOTE 1)
SUPPLY
(NOTE 2)
1.5
2.25
2.25
1.5
2.25
2.25
0.25
1.4
0.25
FLOOR DRAIN / FLOOR
SINK (3" TRAP) 5 --- --- ---
FLOOR DRAIN / FLOOR
SINK (4" TRAP) 6 --- --- ---
1.
2.
3.
NOTES:
DRAINAGE FIXTURE UNIT VALUES (DFU) TAKEN FROM MICHIGAN PLUMBING CODE / 2021,
CHAPTER 7, TABLE 709.1.
SUPPLY FIXTURE UNIT VALUES TAKEN FROM MICHIGAN PLUMBING CODE/2021, APPENDIX
E TABLE E103.3(2). (PRINTED IN CODE FOR REFERENCE ONLY.)
NOT ALL PLUMBING FIXTURES MAY BE PRESENT IN CONSTRUCTION DOCUMENTS.
--- --- --- ---FLOOR DRAIN / FLOOR
SINK (EMERGENCY)
WATER CLOSET
(FLUSH TANK) 4 2 2
SYMBOL
WATER HAMMER ARRESTOR LEGEND
PDI RATING FIXTURE UNIT CAP
A 1-11
12-32
33-60
61-113
114-154
B
C
D
E
F 155-330
NOTE:
PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER
PLACEMENT OF WATER HAMMER ARRESTORS. REFER TO SPECIFICATION
SECTION 22 10 06 AND MANUFACTURERS RECOMMENDATIONS.
A
B
D
C
E
F
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8P
N
EW
.rv t
5/ 6/
2:
:2
PM
P0.0.01
100168
PLUMBING GENERAL
INFORMATION
LFT
JRT
P
IN
E G
R O
V E
L E
A R
N
IN
G C
E N
T E
R B
O
IL
E R
R E
P
LA
C E
M E
N T
K E
N T
IS
D
W Y
O M
IN
G
M
IC
H
IG
A
N
RECEIVING
A159 BOILER
A160
EX. 3" CW
EX. 1 1/2" HW
EX. 3/4" HWR
EX. 4" CW EX. 4" CW
EX. 4" CW EX. 3" CW
EX. 4" CW
EX. 3/4" CW
EX. 3/4" HWR
EX. 1 1/2" HW
EX. 3" CW
EX. 3" CW
WORK ASSOCIATED WITH DOMESTIC
WATER HEATERS AND RELATED
PIPING IS ALTERNATE P-1
D04
D04
D04
D01
D01
D02D03
D03 D03
D03
D03
D03 D03
D03
D03
D03
P6.1.01
P6.1.01
RECEIVING
A159 BOILER
A160
EX. 3/4" HWR
EX. 1 1/2" HW
EX. 3" CW
EX. 3" CW
EX. 3" CW
EX. 1 1/2" HW
EX. 3/4" HWR
EX. 4" CW
EX. 4" CW
EX. 4" CWEX. 4" CW
EX. 3" CW
EX. 3/4" CW
WORK ASSOCIATED WITH DOMESTIC
WATER HEATERS AND RELATED
PIPING IS ALTERNATE P-1
B-26.2
2500 MBH
B-26.1
2500 MBH
01 02
01 02
DWH-26.1
DWH-26.2
PP-26.1
PP-26.2
PP-26.3
P6.1.01
REUSE EXISTING ROOF
OPENINGS FOR VENT
AND COMBUSTION AIR
INTAKE DUCT, TYP. OF 2
2" HW
3/4" HWR
1 1/2" HW
1 1/2" HW
3/4" HWR
1" HWR
2" CW
PET-26.1
EX. 1 1/2" CW
EX. 1 1/2" CW
0.5 GPM
0.5 GPM
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8P
N
EW
.rv t
5/ 6/
2:
:3
PM
P2.3.1A
100168
UNIT 'A' FIRST FLOOR
PLUMBING PLAN
LFT
JRT
P
IN
E G
R O
V E
L E
A R
N
IN
G C
E N
T E
R B
O
IL
E R
R E
P
LA
C E
M E
N T
K E
N T
IS
D
W Y
O M
IN
G
M
IC
H
IG
A
N
1/2" = 1'-0"
UNIT 'A' PLUMBING DEMOLITION PLAN
1/2" = 1'-0"
UNIT 'A' PLUMBING PLAN
PLUMBING DEMO KEYNOTE LEGEND
D01 REMOVE EXISTING DOMESTIC WATER HEATER INCLUDING WATER AND GAS PIPING,
VALVES, VENT & COMBUSTION AIR INTAKE DUCT, EXPANSION TANK, RECIRCULATION PUMP
AND ANY RELATED ACCESSORIES.
D02 REMOVE EXISTING DOMESTIC HOT WATER STORAGE TANK SUPPORTS, PIPING, VALVES,
INSULATION, AND ANY RELATED ACCESSORIES.
D03 REMOVE EXISTING DOMESTIC WATER PIPING INCLUDING VALVES, INSULATION, AND
SUPPORTS. MODIFY PIPING TO REMAIN FOR CONNECTION TO NEW PIPING. REFER TO
PLANS FOR PIPING SYSTEM DESIGNATIONS AND PIPE SIZES.
D04 REFER TO HVAC, HYDRONIC, & NATURAL GAS PIPING PLANS FOR ADDITIONAL BOILER
DEMOLITION INFORMATION & DETAILS.
PLUMBING KEYNOTE LEGEND
01 CONNECT NEW HOT WATER TO EXISTING HOT WATER. REFER TO PLAN FOR PIPE SIZES.
02 CONNECT NEW HOT WATER RETURN TO EXISTING HOT WATER RETURN. REFER TO PLAN
FOR PIPE SIZES.
03 CONNECT NEW COLD WATER TO EXISTING COLD WATER. REFER TO PLAN FOR PIPE SIZES.
04 CAP EXISTING DOMESTIC COLD WATER PIPING AT MAIN. REFER TO PLAN FOR PIPE SIZES.
05 REFER TO HVAC, HYDRONIC, & NATURAL GAS PIPING PLANS FOR ADDITIONAL BOILER
INFORMATION & DETAILS.
PI
PI 3" COMBUSTION AIR INTAKE.
REFER TO PLUMBING PLANS
FOR CONT, TYP 2 PLACES
3" DIRECT VENT. REFER
TO PLUMBING PLANS FOR
CONT, TYP 2 PLACES
NOTES:
REFER TO SPECIFICATION SECTION
22 30 00 FOR POLYPROPYLENE
VENTING SYSTEM.
1.
2"
PRESSURE
GAUGE, TYP
RELIEF VALVE, PIPE
DISCHARGE TO 4"
AFF, TYP
2"
THERMOMETER, TYP
DWH-26.2DWH-26.1
EX. ST
PET-26.1
FS
1" HWR
2" HW
2" CW
X.X" CALIBRATED
BALANCING
VALVE (X.X GPM)
CHECK VALVE, TYP
BALL VALVE, TYP
RELIEF VALVE, PIPE
DISCHARGE TO 4" AFF,
TYP
CHECK VALVE, TYP
BALL VALVE, TYP
ROUTE 3/4" COND FROM
TRAP (BY WATER HEATER
MFR) TO FD, TYP 2 PLACES
FLOW SWITCH (BY
WATER HEATER
MFR), TYP 2 PLACES
CIRCULATING PUMP
(BY WATER HEATER
MFR), TYP 2 PLACES
DIRT
LEG, TYP
FINISH FLOOR
CONCRETE PAD
DRAIN VALVE, TYP
UNION, TYP
2"
1 1/2"
HW HW
HWR
CW
WATER HEATER MANUFACTURER'S
CONDENSATE NEUTRALIZER.
TS
TEMPERATURE
SENSOR
FS
1 1/2"
PP-26.3
WATTS MODEL
LFN36-M1 VACUUM
RELIEF VALVE
PP-26.2PP-26.1
REUSE EXISTING 250 GALLON
DOMESTIC WATER HOT
STORAGE TANK
2"
3/4"
EX. ST
257 GALLON
TO BE REUSED
EX. PET
HW
CW
HWR
EX. RECIRC PUMP
EX. DWH
250 MBH
FS
1 1/2"
EX. PUMP
EX. 3/4" HWR
EX. 2" HW
EX. 2" CW
D03
D03
D01 D01
D01
D03 D03
D01
D03
EX. ST
200 GALLON
EX. PET
HW
CW
HWR
EX. RECIRC PUMP
EX. DWH
199 MBH
FS
1 1/2"
EX. PUMP
EX. 3/4" HWR
EX. 2" HW
EX. 2" CWD01
D02
D03
D03
D01
D03 D01
D03
D01
D03
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//1
Ke nt
IS
D P in e
G ro ve L ea rn in g
C en te r B oi le r R ep la ce m en t/1
8P
N
EW
.rv t
5/ 6/
2:
:3
PM
P6.1.01
100168
PLUMBING DETAILS &
SCHEDULES
LFT
JRT
P
IN
E G
R O
V E
L E
A R
N
IN
G C
E N
T E
R B
O
IL
E R
R E
P
LA
C E
M E
N T
K E
N T
IS
D
W Y
O M
IN
G
M
IC
H
IG
A
N
NOT TO SCALEP6.1.01
1 WATER HEATER DETAIL (DUAL W/ TANK)
FUEL FIRED DOMESTIC WATER HEATER SCHEDULE
MARK MANUFACTURER MODEL TYPE RECOVERY RATE BURNER MIN INPUT GAS
PRESSURE (WC)
MAX INPUT GAS
PRESSURE (WC) EFFICIENCY % GAS CONNECTION
SIZE (INCHES)
FLUE SIZE
(INCHES)
COMBUSTION AIR
SIZE (INCHES)
STORAGE
(GALLONS)
MAX WORKING
PRESS (PSIG)
WATER CONNECTIONS
SIZE (INCHES)
ELECTRICAL WEIGHT (LBS) NOTESGPH ∆T °F MODULATION RATE INPUT (MBH) VOLT PH
DWH-26.1 LOCHINVAR AWN201PM CONDENSING 234 100 5:1 201 4" 14" 96 1/2" 3" 3" 1.8 160.0 1-1/4" 120 1 181 1, 2 DWH-26.2 LOCHINVAR AWN201PM CONDENSING 234 100 5:1 201 4" 14" 96 1/2" 3" 3" 1.8 160.0 1-1/4" 120 1 181 1, 2
PUMP SCHEDULE
MARK SERVICE MANUFACTURER MODEL TYPE GPM HEAD
(FT)
SIZE
(X" x X") DRIVE (Y/N) RPM ELECTRICAL OPER. WEIGHT (LB) NOTESMOTOR HP VOLT PH PP-26.1 DWH-26.1 LOCHINVAR 100287809 INLINE 28 38 1-1/4" FLNG NO N/A 3/4 120 1 N/A PP-26.2 DWH-26.2 LOCHINVAR 100287809 INLINE 28 38 1-1/4" FLNG NO N/A 3/4 120 1 N/A
PP-26.3 HWR BELL & GOSSETT SERIES PL30 INLINE 4 20 1" NPT NO 3300 1/6 120 1 13.1
EXPANSION TANK SCHEDULE
MARK SERVICE MANUFACTURER MODEL TYPE MOUNTING TANK VOLUME (GAL) ACCEPT. VOLUME (GAL) DIAMETER (IN) HEIGHT (IN) WEIGHT WHEN FULL (LB) PRE-CHARGE PRESSURE (PSI) MAX WORK PRESS (PSI) NOTES
PET-26.1 DWH-26.1 & DWH-26.2 AMTROL ST-30VC BLADDER FLOOR 14 11.3 15" 24" 119.24 50 150 1, 2
05.06.2026 BIDS &
CONSTRUCTION
NOT TO SCALEP6.1.01
2 WATER HEATER DEMOLITION DETAIL (250 MBH SYSTEM)
NOT TO SCALEP6.1.01
3 WATER HEATER DEMOLITION DETAIL (199 MBH SYSTEM)
PLUMBING DEMO KEYNOTE LEGEND
D01 REMOVE EXISTING DOMESTIC WATER HEATER INCLUDING
WATER AND GAS PIPING, VALVES, VENT & COMBUSTION AIR
INTAKE DUCT, EXPANSION TANK, RECIRCULATION PUMP AND
ANY RELATED ACCESSORIES.
D02 REMOVE EXISTING DOMESTIC HOT WATER STORAGE TANK
SUPPORTS, PIPING, VALVES, INSULATION, AND ANY RELATED
ACCESSORIES.
D03 REMOVE EXISTING DOMESTIC WATER PIPING INCLUDING
VALVES, INSULATION, AND SUPPORTS. MODIFY PIPING TO
REMAIN FOR CONNECTION TO NEW PIPING. REFER TO PLANS
FOR PIPING SYSTEM DESIGNATIONS AND PIPE SIZES.
NOTES:
1. PROVIDE RELIEF VALVE & BLOWDOWN / DRAIN VALVE.
2. PROVIDE MANUFACTURER'S NEUTRALIZATION KIT.
NOTES:
1. ASME RATED.
2. FIELD ADJUST TANK FACTORY PRE-CHARGE PRESSURE TO MATCH SYSTEM STATIC PRESSURE.
SD
SD
F/S
F/S
SD
M
H
T S
T R
CO2
S
PI
SD
FS
PS
PI
TW
F
TI
PT
T
T
T
C
C
FI
LT
ER
HVAC SYMBOLS
THERMOSTAT / SENSOR
RADIANT FLOOR THERMOSTAT
HUMIDISTAT
CARBON DIOXIDE SENSOR
OPPOSED BLADE DAMPER
MOTOR OPERATED DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)
FIRE DAMPER (THRU WALL)
SMOKE DAMPER (THRU FLOOR)
SMOKE DAMPER (THRU WALL)
PARALLEL BLADE DAMPER
COMBINATION FIRE/SMOKE DAMPER
(THRU FLOOR)
DUCT SMOKE DETECTOR
COMBINATION FIRE/SMOKE DAMPER
(THRU WALL)
CONNECT TO EXISTING
VALVE SYMBOLS
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
TRIPLE-DUTY VALVE
PLUG VALVE
DIAPHRAGM VALVE
NEEDLE VALVE
ANGLE VALVE
PRESSURE REDUCING VALVE, SELF-
CONTAINED
EXT. PRESSURE REDUCING VALVE
CHECK VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
HOSE BIBB
CALIBRATED BALANCING VALVE
TEMPERATURE CONTROL VALVE
CONTROL VALVE, 3-WAY
BACKFLOW PREVENTER
WITH DRIP PAN
INDICATES VALVE IS FLANGED (TYP)
CONNECT TO EXISTING
AUTOMATIC FLOW CONTROL VALVE
AFF
BOD
BOG
BOS
BOP
CUH
CONV
CO
EA
EF
OA
RA
SA
TOD
TOG
TOP
VD
VTR
UNO
ABOVE FINISHED FLOOR
BOTTOM OF DUCT
BOTTOM OF GRILLE
BOTTOM OF PIPE
BOTTOM OF STRUCTURE
CABINET UNIT HEATER
CONVECTOR
CLEAN-OUT
EXHAUST AIR
EXHAUST FAN
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
TOP OF DUCT
TOP OF GRILLE
TOP OF PIPE
VOLUME DAMPER
VENT THRU ROOF
UNLESS NOTED OTHERWISE
TOS TOP OF STRUCTURE
CLG CEILING
CONN CONNECTION
CONT CONTINUATION
DN DOWN
DWG DRAWING
ETR EXISTING TO REMAIN
EX. EXISTING
FLR FLOOR
TYP TYPICAL
MAU MAKE-UP AIR UNIT
AHU AIR HANDLING UNIT
ERU ENERGY RECOVERY UNIT
MECHANICAL ABBREVIATIONS
SPECS. SPECIFICATIONS
UH UNIT HEATER
MAX MAXIMUM
MIN MINIMUM
MFR MANUFACTURER
ET EXPANSION TANK
RTU ROOF TOP UNIT
DW DOUBLE WALL
BCU BLOWER COIL UNIT
FCU FAN COIL UNIT
ECM ELECTRONICALLY COMMUTATED MOTOR
MECHANICAL LINE SERVICE DESIGNATIONS
BFW
CTWS
CTWR
HPCR
HPS
LPS
LPCR
MPS
MPCR
PCR
SPWR
SPWS
SMR
SMS
BOILER FEED WATER
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
CHILLED GLYCOL RETURN
CHILLED GLYCOL SUPPLY
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM
LOW PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
SWIMMING POOL WATER RETURN
SWIMMING POOL WATER SUPPLY
SNOWMELT RETURN
SNOWMELT SUPPLY
CHGS
CHGR
PUMPED CONDENSATE RETURN
CDGR
CDGS CONDENSER GLYCOL SUPPLY
CONDENSER GLYCOL RETURN
CHWR
CHWS CHILLED WATER SUPPLY
CHILLED WATER RETURN
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
GEOTHERMAL WATER SUPPLY
GEOTHERMAL WATER RETURNGTWR
GTWS
G
HWR
HWS
RWR
RWS
V
NATURAL GAS
HOT WATER RETURN (HEATING)
HOT WATER SUPPLY (HEATING)
RADIANT WATER RETURN
VENT
RADIANT WATER SUPPLY
HGR
HGS
HOT GLYCOL RETURN
HOT GLYCOL SUPPLY
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND ARE INTENDED TO SHOW
THE GENERAL LAYOUT OF SYSTEMS AND EQUIPMENT. THE EXACT LOCATIONS
OF EQUIPMENT AND THE FINAL DUCTWORK LAYOUTS ARE THE
RESPONSIBILITY OF THE CONTRACTOR, AND SHALL BE FIELD-DETERMINED.
COORDINATE WITH THE BUILDING ARCHITECTURE AND STRUCTURE, AND
WITH NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS. WHERE
THE LAYOUT DIFFERS SIGNIFICANTLY FROM DESIGN, COORDINATE WITH THE
ARCHITECT/ENGINEER. RECORD ALL DIFFERENCES ON RECORD DRAWINGS.
COORDINATE LOCATIONS OF REGISTERS, DIFFUSERS AND GRILLES WITH THE
REFLECTED CEILING PLANS. COORDINATE ANY DISCREPANCIES WITH THE
ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
INSTALL ALL THERMOSTATS/SPACE TEMPERATURE SENSORS AT 48 INCHES
ABOVE FINISHED FLOOR (TO TOP OF SENSOR). WHERE APPLICABLE, ALIGN
WITH LIGHT SWITCHES.
ALL THERMOSTATS AND SENSORS LOCATED ON EXTERIOR WALLS SHALL
HAVE INSULATED BACKPLATES.
WHERE INTERNALLY LINED OR DOUBLE-WALL DUCTWORK IS SHOWN, THE
DIMENSIONS SHOWN INDICATE THE REQUIRED INSIDE FREE AREA
DIMENSIONS.
THE CONTRACTOR SHALL EXAMINE THE CONDITION OF ALL EQUIPMENT PRIOR
TO INSTALLATION. DO NOT INSTALL DAMAGED EQUIPMENT.
WHERE CONNECTING NEW DUCTWORK TO EXISTING, SEAL JOINTS AIRTIGHT
AND REPAIR DAMAGED INSULATION TO MATCH NEW.
WHERE DUCTWORK IS EXPOSED, ROUTE AS HIGH AS PRACTICAL IN THE
SPACE UNLESS INDICATED OTHERWISE.
REFER TO ARCHITECTURAL CODE COMPLIANCE PLANS FOR THE LOCATIONS
OF FIRE/SMOKE RATED ASSEMBLIES.
PAINT VISIBLE INTERIOR SURFACES OF DUCTS AT REGISTERS, GRILLES,
DIFFUSERS AND LOUVERS FLAT BLACK.
WHERE POSSIBLE, INSTALL EQUIPMENT AND DEVICES REQUIRING SERVICE
OR MAINTENANCE IN ACCESSIBLE LOCATIONS. WHERE NOT POSSIBLE,
PROVIDE ACCESS DOORS, SIZED SUITABLY FOR THE…