Plans.pdf
PDF 9 MB Posted
- Attached to
- Project 13679. DOT EVSE. Contract 25-302571
- Solicitation number
- 0000038255
- Issued by
- Shasta County, Siskiyou County, California
About this file
This is a construction plans document for the California Department of Transportation (Caltrans) District 2 Electric Vehicle Supply Equipment (EVSE) project at the Mt. Shasta Maintenance Station, located at 1625 Mott Road, Mt. Shasta, California 96067. The project, identified as Contract 25-302571 and Project Number 13679, involves the installation and electrical connection of Level II EVSE infrastructure comprising four charging stations (distributed across two levels with zero existing spaces on each level and four new spaces on Level 2). The scope of work includes installation of wiring devices, conduit systems, panelboard infrastructure, disconnect switches, and all associated electrical components necessary for a complete and operational charging system. Additional work includes saw cutting, trenching, backfilling, finishing of affected lot surfaces, restoration to original condition, and potential installation of bollards. The project requires electrical work conforming to the 2022 California Building Code, California Electrical Code, California Fire Code, and Title 24 standards, with State Fire Marshal approval obtained on January 16, 2025. Plans were issued for various review stages between August 26, 2024, and January 16, 2025.
The project is restricted to Small Business and Micro Business contractors certified through the California Department of General Services, Office of Small Business and DVBE Services. A C-10 contractor license is required to bid. Contractors must submit valid Certificates of Reported Compliance (CRCs) for any fleet vehicles subject to California Air Resources Board In-Use Off-Road Diesel-Fueled Fleet Regulations prior to contract execution. The work includes infrastructure for four 208-volt, 100-ampere electrical vehicle charging stations with an estimated connected load of 66.56 kilovolt-amperes and estimated demand load of 83.2 kilowatt-amperes. Special inspections are required for concrete construction and post-installed mechanical or adhesive anchors in accordance with California Building Code Section 1705. Bids must be submitted electronically to Jannice.castro@dgs.ca.gov before 2:00 P.M. on the specified bid deadline, with project management and development oversight provided by the Department of General Services Architecture & Engineering Section.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ADVERTISEMENT_FOR_BID_13940.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS © 2024 TomTom
SITE MAP
VICINITY MAP
G0.0
NONE
CODES AND REFERENCES SHEET INDEX
SYMBOLS AND ABBREVIATIONS
TITLE 19 CCR PUBLIC SAFETY, DIVISION 1, STATE FIRE MARSHAL REGULATIONS
TITLE 24 CCR, PART 1 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
TITLE 24 CCR, PART 2 2022 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1 AND 2 (2021 IBC, AS AMENDED BY CA)
TITLE 24 CCR, PART 3 2022 CALIFORNIA ELECTRICAL CODE (CEC) (2020 NEC, AS AMENDED BY CA)
TITLE 24 CCR, PART 8 2022 CALIFORNIA HISTORICAL BUILDING CODE
TITLE 24 CCR, PART 9 2022 CALIFORNIA FIRE CODE (CFC) (2021 IFC, AS AMENDED BY CA)
TITLE 24 CCR, PART 10 2022 EXISTING BUILDING CODE
TITLE 24 CCR, PART 11 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CAL GREEN CODE)
TITLE 24 CCR, PART 12 2022 CALIFORNIA REFERENCED STANDARDS CODE (SEE ALSO TITLE 24 CCR-PART 2, CHAPTER 35 -
REFERENCE STANDARDS AND TITLE 24 CCR - PART 9, CHAPTER 47 - REFERENCED STANDARDS)
DRAWINGS
G0.0 TITLE SHEET
E0.0 ELECTRICAL NOTES
E1.0 SINGLE LINE DIAGRAM AND SCHEDULES
E2.0 ELECTRICAL SITE PLAN
E3.0 ELECTRICAL DETAILS
S1.0 GENERAL NOTES
S2.0 DETAILS
EVCS DESCRIPTION SCOPE OF WORK
EXISTING EVCS SPACES NEW EVCS SPACES
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(4) LEVEL 2
FLEET WORKPLACE WORKPLACEFLEET
DISCONNECT SWITCH, NON-FUSIBLE, SEE PLANS FOR RATING
EXISTING TO BE REMOVED AND SALVAGED
EXISTING TO BE DEMOLISHED
NEW PLANS-FINAL LOCATION OF RELOCATED EQUIPMENT.
DEMO PLANS-EXISTING TO BE RELOCATED.
EXISTING TO REMAIN
(RS)
(D)
(RL)
(E)
ENCLOSED CIRCUIT BREAKER
GROUND FAULT PROTECTION
GREEN
GREEN
WHITE
WHITE
BLUE
RED
RED
BLACK
BLACK
240V
240Y/120V
POWER WIRE COLOR CODE
SYSTEM
208Y/120V
480Y/277V
PHASE A
BLACK
YELLOW
PHASE B
RED
BROWN
PHASE C
BLUE
ORANGE
NEUTRAL
WHITE
GRAY
GROUND
GREEN
GREEN
ELECTRICAL ABBREVIATIONS
INCOMING ELECTRIC SERVICE
GROUND
DISCONNECT SWITCH, FUSIBLE, SEE PLANS FOR RATING
FUSE
SWITCH
2S, 2W = 2 SPEED, 2 WINDING
RV=REDUCED VOLTAGE STARTING
FULL-VOLTAGE NON-REVERSING UNLESS NOTED
MAGNETIC MOTOR STARTER, NEMA SIZE INDICATED
MCP INDICATES MOTOR CIRCUIT PROTECTOR
3 POLE UNLESS NOTED
CIRCUIT BREAKER,
METERING
Y, SHEET WHERE DETAIL IS DRAWN
DETAIL CALL-OUT: X, DETAIL IDENTIFIER;
WITH EQUIPMENT
CONTROLLER/STARTER FURNISHED
+ 48" UON
+ 18" UON
FLOOR GRADE TO CENTERLINE OF DEVICE
INDICATES HEIGHT FROM FINISHED
SHEET NOTE, SEE NOTE INDICATED
SURFACE MOUNTED PANELBOARD-NEW, EXISTING
POWER DISTRIBUTION SWITCHBOARD
CONDUIT STUB-OUT AND CAPPED
CONDUIT BENDS AWAY FROM OBSERVER
CONDUIT BENDS TOWARD OBSERVER
BELOW GRADE, #4/0 UON
GROUNDING CONDUCTOR 30"
CURVE LINE INDICATES GROUND WIRE
WIRE SIZE OTHER THAN #12
GROUND WIRE
QUANTITY #12 WIRE CURVE LINE INDICATES
CONDUIT EXPOSED 3/4"C-2#12, 1#12G, UON
3/4"C-2#12, 1#12G, UON
CONDUIT UNDER GROUND
CEILING 3/4"C-2#12, 1#12G, UON
CONDUIT CONCEALED IN WALLS OR
PULLBOX
HAND HOLE, 11"Hx17"Lx12"D, UON
ELECTRICAL SYMBOLS - ONE LINE DIAGRAMELECTRICAL SYMBOLS - PLANS
JUNCTION BOX
SINGLE RECEPTACLE 120V, 20A GFCI TYPE
DUPLEX RECEPTACLE
EXISTING AREA LIGHT AND POLE
(AIP)
1"C-2#12, 1#12G
(U)(V"C-W#X,Y#Z)
EXAMPLE: (2)(3/4"C-2#12-1#12G) INDICATES TWO 3/4"
CONDUITS EACH WITH 2#12 AND 1#12G CONDUCTORS
ELECTRICAL SYMBOLS COMMON
SINGLE RUN OF RACEWAY AND CIRCUIT CONDUCTORS.
FIRST NUMBER IS RACEWAY SIZE.
THE FOLLOWING NUMBERS ARE THE CONDUCTOR
QUANTITIES AND SIZES.
A AMPERES
AMPERES INTERRUPTING CAPACITY, SYMMETRICAL
AMERICAN WIRE GAUGE
BARE COPPER
CONDUIT, CONDUCTOR
AICS
AWG
BC
C
CB CIRCUIT BREAKER
CKT CIRCUIT
CNTL CONTROL
CO CONDUIT ONLY
CT CURRENT TRANSFORMER
DTL DETAIL
DWG DRAWING
E EXISTING
G, GND GROUND
GFCI GROUND-FAULT CIRCUIT INTERRUPTER
HH HANDHOLE
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LTG LIGHTING
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
N NEUTRAL
NIC NOT IN CONTRACT
NO. NUMBER
P POLE
PB PUSH BUTTON, PULL BOX
PC PHOTO CELL
PH, Ø PHASE
PVC POLYVINYL CHLORIDE
REQ'D REQUIRED
SMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT
SW SWITCH
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
W WATTS, WIRE
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
NTS NOT TO SCALE
FLUSH MOUNTED PANELBOARD
EXISTING TO BE REMOVED AND REPLACED WITH NEW(RP)
ABOVE FINISHED GRADEAFG
BOLLARD
NEW PLANS: EXISTING TO NEW
INTERCEPTION POINT:
EVCS ELECTRICAL VEHICLE CHARGING STATION
LB FITTING
TEE FITTING
A-1,3
G
#10
PB
J
X
Y
+18"
RV
MCP
30A
M
F
GFP
LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT
(#)# CONDUIT CALLOUT REFERENCE WITH NUMBER OF CONDUITS
SHOWN IN PARENTHESIS.
PROJECT
LOCATION
PROJECT
WORKING AREA
(4 EVCS SPACES)
ELECTRICAL VEHICLE CHARGING STATIONS (EVCS) INSTALLED ON THIS PROJECT WILL NOT BE AVAILABLE TO THE GENERAL PUBLIC, AND IS INTENDED FOR
USE BY A DESIGNATED VEHICLE OR EMPLOYEE. ELECTRIC VEHICLE CHARGER PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
INSTALL AND ELECTRICALLY CONNECT EVCS INFRASTRUCTURE FOR MAKE READY INSTALLATION AS
SHOWN. CONTRACTOR TO PROVIDE AND INSTALL THE WIRING DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND OPERATIONAL SYSTEM INCLUDING REQUIRED TESTING.
CONTRACTOR SHALL ALSO PROVIDE THE REQUIRED SAW CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE AND RESTORE TO ORIGINAL CONDITION. EVCS CHARGER
PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
(0) LEVEL 1
(0) LEVEL 2
POWER TRANSFORMER
FEEDER DESIGNATION SEE
CONDUIT/CONDUCTOR TABLE FOR SIZE
TITLE SHEET
HOMERUN TO PANEL A,
CIRCUIT 1 AND 3
ABANDON IN PLACE. (D) ABOVE GROUND CONDUITS &
CONNECTORS DOWN TO 3" BELOW GROUND LEVEL.
REMOVE AND (D) CONDUCTORS IN UG CONDUITS.
PLUG UG CONDUITS AND ABANDON IN PLACE.
MULTIPLE RUNS OF RACEWAY AND CIRCUIT CONDUCTORS
U = # OF PARALLEL RUNS
V = CONDUIT SIZE
W = # OF PHASE/NEUTRAL CONDUCTORS IN EA. CONDUIT
X = PHASE/NEUTRAL CONDUCTOR SIZE
Y = #OF GROUND CONDUCTORS IN EACH CONDUIT
Z = GROUND CONDUCTOR SIZE
V1
1625 MOTT ROAD,
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ann Watson Phone 279 782-3872 Fax 916 376-6216 ann.watson@dgs.ca.gov
08/26/24 ISSUED FOR CD90 CLIENT REVIEW0
JASWH SWH JSV
EVCS LEVEL II
DGS - CDOT DST2
MAINTENANCE STATION
DEPARTMENT OF
GENERAL SERVICES
10/14/24 ISSUED FOR CD95 CLIENT REVIEW1
PROJECT NUMBER:
000000000013679
2 10/28/24 100% WORKING SFM SUBMITTAL
SFM APPLICATION NUMBER: 24-N-4410
ISSUE DATE: 10/29/2024
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
DOT - Electric Vehicle Supply Equipment - Mt Shasta Maintenance Station
PROJECT NUMBER: 000000000013679; 3/2/26
E0.0
N/A
ELECTRICAL NOTES
SPECIAL INSPECTIONS REQUIRED
CONCRETE CONSTRUCTION:
STEEL CONSTRUCTION:
GENERAL NOTES:
V1
N/A
1625 MOTT ROAD,
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ann Watson Phone 279 782-3872 Fax 916 376-6216 ann.watson@dgs.ca.gov
08/26/24 ISSUED FOR CD90 CLIENT REVIEW0
JASWH SWH JSV
EVCS LEVEL II
DGS - CDOT DST2
MAINTENANCE STATION
DEPARTMENT OF
GENERAL SERVICES
10/14/24 ISSUED FOR CD95 CLIENT REVIEW1
PROJECT NUMBER:
000000000013679
2 10/28/24 100% WORKING SFM SUBMITTAL
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
E1.0
NONE
SINGLE LINE DIAGRAM
AND SCHEDULES
PB-EV
(E) MSB
SINGLE LINE DIAGRAM
1187 CA-36,
CHESTER, CA 96020
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JASWH SWH WP
EVCS LEVEL II
CA DOT DISTRICT 2
CHESTER MAINTENANCE STATION
DEPARTMENT OF
GENERAL SERVICES
Ann Watson Phone 279 782-3872 ann.watson@dgs.ca.gov
06/24/24 ISSUED FOR CD90 CLIENT REVIEW0
09/13/24 ISSUED FOR CD90 CLIENT REVIEW1
N/A
VOLTAGE DROP CALCULATION
NOTES:
PB-EV PANEL SHALL BE USED FOR ONLY 208V, 1Ø EVCS CHARGING STATIONS.
ELECTRICAL ION METER, SCHNEIDER IEM3000 SERIES OR APPROVED EQUAL.
INSTALL A NEW CIRCUIT BREAKER MATCHING THE EXISTING BREAKER MANUFACTURER,
AND KAIC RATING ON EXISTING MAIN SWITCHBOARD (MSB).
CABLES SIZED FOR MAXIMUM CAPACITY OF CHARGER. CONDUITS SIZED UP 1" FOR FUTURE
PROOFING.
AN ARC-FLASH ASSESSMENT STUDY SHALL BE PERFORMED AND ADHERE TO NFPA70E
130.5.3 CONTRACTOR IS TO PROVIDE ARC-FLASH WARNING LABELS IN COMPLIANCE WITH
CEC 110.16. ARC-FLASH ASSESSMENT STUDY AND ARC-FLASH WARNING LABELS SHALL BE
SUBMITTED TO THE ELECTRICAL ENGINEERING OF RECORD FOR REVIEW AND APPROVAL.
CONTRACTOR TO VERIFY AND MATCH AIC RATING TO EXISTING MSB.
FUSED DISCONNECT SWITCHES SHALL COMPLY WITH NEC 110.25.
CONDUIT/ CABLE SCHEDULE
PANEL SCHEDULE
SECTION POSITION DESCRIPTION
LOAD
HP kVA A
1 PANEL R MECHANICAL SHOP
2 PANEL H SUBFEED
3 PANEL G SUBFEED
4 PB-EV 66.56 184.75
ESTIMATED LOAD MSB
TOTAL NEW CONNECTED LOAD 66.6 184.8
TOTAL DEMAND LOAD 83.2 230.9
AØ BØ CØ
(1) MAXIMUM DEMAND (BASED ON 1 YEAR OF UTILITY DATA)
(kVA) 4.68 4.68 4.68
(A) 39.00 39.00 39.00
(2) NEW CONNECTED LOAD
(kVA) 24.96 24.96 16.64
(A) 208.00 208.00 208.00
(3) TOTAL PROSPECTIVE LOAD
SUM OF (1) AND (2)
(kVA) 29.64 29.64 21.32
(A) 247. 0 247.0 247.0
(4) FEEDER EVALUATION (NEC 220.87)
MAXIMUM DEMAND AT 125% PLUS NEW LOAD
(4)=1.25x(1+2)
(kVA) 37.1 37.1 26.7
(A) 308.8 308.8 308.8
(E) MAIN SWITCHBOARD 'MSB'
VERTICAL BUS BRACING
MAIN FUSE RATING
MAIN BREAKER INTR. RATING
MAX FAULT AT MAIN BREAKER
FEEDER SIZE
VERTICAL BUS RATING 400A
VOLTS 208Y/120V, 3Ø, 4W 60HZ
XFMR CONFIGURATION
XFMR RATING
XFMR PRIMARY
XFMR SECONDARY
XFMR TEMP. RISE
XFMR IMPEDANCE
XFMR VOLTAGE
TAG XFMR TAG
ENCLOSURE TYPE NEMA 3R XFMR ENCLOSURE TYPE
LOCATION PARKING LOT XFMR LOCATION
MSB
400A
PROPOSED EV CHARGERS
EXISTING PANEL LOAD SUMMARY
DS-EV-1A
100A 2P
100A 2P
DS-EV-1B
400A BUS, 208Y/120V, 3Ø, 4W, 60HZ
DS-EV-2A
100A 2P
100A 2P
DS-EV-2B
1303 1303
V1
1303 1303
1303 1303
2 10/29/24 100% WORKING SFM SUBMITTAL
PROJECT NUMBER:
000000000013679
V2
MAINTENANCE STATION
1625 MOTT ROAD,
MT SHASTA, CA 96067
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
E2.0
1/16"=1'-0"
ELECTRICAL SITE PLAN
DRAWING LIMITS
DRAWING LIMITS
D R A W
IN
G L
IM
IT
S
D R A W
IN
G L
IM
IT
S
X X
Know what's below.
before you dig.Call
1625 MOTT ROAD,
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ann Watson Phone 279 782-3872 Fax 916 376-6216 ann.watson@dgs.ca.gov
-BKMBKM-
EVSE LEVEL II
DGS - CDOT DST2
MAINTENANCE STATION
DEPARTMENT OF
GENERAL SERVICES
F F
V1
J J
V2V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
SCALE:
PERMANENT BOLLARD
NONE
N/A E3.0
N/A
ELECTRICAL DETAILS
V1
SAW CUT, THEN PATCH TO
MATCH (E) SURFACE FINISH
FINISH SURFACE, AC PAVING
CONCRETE, GRASS, ETC.
RED WARNING TAPE
(ELECTRICAL)
SELECT BACKFILL
90% COMPACTION
CONDUIT, NUMBER AND SIZES
PER PLANS
SAND FILL
M
IN
3"
M
IN
NOTES:
1. WIDTH OF TRENCH WILL BE DETERMINED BY
THE SIZE OF CONDUITS, NUMBER OF
CONDUITS, AND CONFIGURATION.
3"
M
IN
SCALE:
CONDUIT TRENCH
NONE
1187 CA-36,
CHESTER, CA 96020
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JASWH SWH WP
EVCS LEVEL II
CA DOT DISTRICT 2
CHESTER MAINTENANCE STATION
DEPARTMENT OF
GENERAL SERVICES
Ann Watson Phone 279 782-3872 ann.watson@dgs.ca.gov
06/24/24 ISSUED FOR CD90 CLIENT REVIEW0
09/13/24 ISSUED FOR CD90 CLIENT REVIEW1
10/29/2024 100% WORKING SFM SUBMITTAL
CROWN CONCRETE
4" DIA GALVANIZED STEEL
PIPE. PRIME AND PAINT
2 COATS INDUSTRIAL
YELLOW ENAMEL
(E) CONCRETE
4' -0
3/4" HOLE
1/2" STEEL BASEPLATE
EQUIPMENT ANCHOR
PER SPECIFICATION
SECTION
16012 (TYP.)
PANELBOARD SUPPORT
3" GALVANIZED PIPE
P-1000
UNISTRUT
PANELBOARD
FINISHED GRADEFINISHED GRADE
1' -0
(M
IN
A D
JU
S T T
O B
O
LT
H O
LE
S
O F P
A N E
LB
O A R D
PANELBOARD
6" WIDER THAN
PANELBOARD
1' -6
(M
IN
3" M
IN
18" (MIN.) CONCRETE
SCALE:
CROWN CONCRETE
4" DIA GALVANIZED STEEL
PIPE. PRIME AND PAINT
2 COATS INDUSTRIAL
YELLOW ENAMEL
SLOPE 1/2"
AGGREGATE BASE (TYP)
CONCRETE
4' -0
3' -0
3" M
IN
PERMANENT BOLLARD
NONE
1'-3"
PANELBOARD SUPPORT
3" GALVANIZED PIPE
P-1000
UNISTRUT
DISCONNECT
FINISHED GRADEFINISHED GRADE
1' -0
(M
IN
A D
JU
S T T
O B
O
LT
H O
LE
S
O F P
A N E
LB
O A R D
DISCONNECT
6" WIDER THAN
PANELBOARD
1' -6
(M
IN
3" M
IN
18" (MIN.) CONCRETE
V2
MAINTENANCE STATION
1625 MOTT ROAD,
MT SHASTA, CA 96067
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
X-X
VII. REINFORCING STEEL:
1. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60.
2. REINFORCING STEEL FOR CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS SHALL HAVE THE
FOLLOWING CONCRETE COVER, SEE ACI 117 FOR TOLERANCES.
A. CONCRETE EXPOSED TO EARTH OR IN CONTACT WITH GROUND:
a. CAST AGAINST AND PERMANENTLY IN CONTACT WITH EARTH 3"
b. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#5 AND SMALLER) 1-1/2"
c. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#6 AND LARGER) 2"
B. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. SLABS, JOISTS AND WALLS (#11 AND SMALLER) 3/4"
b. SLABS, JOISTS AND WALLS (#14 AND LARGER) 1-1/2"
c. BEAMS, COLUMNS AND PEDESTALS 1-1/2"
3. BAR SPLICES MAY BE DELETED AND CONTINUOUS REINFORCING USED AT CONTRACTORS OPTION. BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN FRAMED BEAMS AND SLABS SPLICE TOP
BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS.
4. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH ACI 318 AND THE
'MANUAL OF STANDARD PRACTICE' BY CRSI AS MODIFIED BY THE CONTRACT DOCUMENTS.
5. FIELD BENDING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT SEOR APPROVAL. ALL
REINFORCING BENDS SHALL BE MADE COLD.
IV. REINFORCED CONCRETE:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318 AND ACI 301 WITH MODIFICATIONS AS NOTED
ON THE CONTRACT DOCUMENTS.
2. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND BEAR THE WET SEAL OF A CIVIL ENGINEER LICENSED IN THE STATE OF THE PROJECT AND BE PROVIDED TO THE SEOR FOR REVIEW. EACH MIX DESIGN SHALL BEAR THE NAME OF THE PROJECT AND THE SPECIFIC USE.
3. CONCRETE MODULUS OF ELASTICITY SHALL MEET THE MINIMUM PROVIDED IN ACI 318 SECTION 19.2.2 FOR THE 28-DAY STRENGTH SPECIFIED BELOW. TEST SHALL BE IN ACCORDANCE WITH ASTM C469.
4. CONCRETE SHALL HAVE THE FOLLOWING ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS.
LOCATION STRENGTH, f'c CONCRETE TYPE
A. FOUNDATIONS 4,000 PSI* NORMAL WEIGHT
* INDICATES FOOTING DESIGNED FOR F'c = 2,500 PSI THEREFORE SPECIAL INSPECTIONS NOT
REQUIRED
1. PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR II. CONCRETE EXPOSED TO SOILS
CONTAINING CORROSIVE ELEMENTS (SULFATES) SHALL COMPLY WITH CBC 1904.1.
2. FLY ASH MAY BE USED AS A SUBSTITUTE FOR PORTLAND CEMENT. WEIGHT OF FLY ASH SHALL NOT EXCEED 15% OF CEMENT WEIGHT. FLY ASH SHALL CONFORM TO ASTM C618 CLASS F AND LOSS OF
IGNITION SHALL BE LIMITED TO 2%.
3. MIXING OPERATIONS SHALL CONFORM TO ASTM C94.
4. ALL CONCRETE NOT IN CONTACT WITH EARTH TO HAVE FINISH AS SPECIFIED BY ARCHITECT OR AS
COVERED IN PROJECT SPECIFICATIONS. UNLESS OTHERWISE NOTED, NON-ARCHITECTURAL
CONCRETE COLUMNS AND WALLS SHALL HAVE 3/4”CHAMFERED CORNERS.
5. AGGREGATE FOR NORMALWEIGHT CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS
OF ASTM C33 AND PROJECT SPECIFICATIONS.
6. ALL CONCRETE SHALL BE REINFORCED. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT AS REQUIRED BY ACI-318 IN ELEMENTS WHERE NO REINFORCEMENT IS INDICATED ON THE DRAWINGS.
7. DRY PACK OR GROUT UNDER BASE PLATES AND SILL PLATES SHALL BE 7000 PSI MIN AT 28 DAYS.
8. CONCRETE PLACEMENT SHALL CONFORM TO ACI 304 AND PROJECT SPECIFICATIONS. SANDBLAST ALL
CONCRETE SURFACES WHICH NEW CONCRETE WILL BE PLACED AGAINST.
9. TWO HOURS MUST ELAPSE BETWEEN END OF COLUMN OR WALL POURS AND THE BEGINNING OF
FLOOR POURS.
10. ALL REINFORCEMENT, ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SECURELY HELD IN PLACE WHILE CONCRETE IS POURED. ADDITIONAL BARS TO BE PROVIDED BY THE CONTRACTOR FOR
SUPPORT AS NEEDED.
11. MECHANICAL, ELECTRICAL AND PLUMBING OPENINGS AND SLEEVES ARE SHOWN INDICATIVELY AND
SMALL OPENINGS AND SLEEVES ARE NOT SHOWN. SEE SLAB EDGE, MECHANICAL, ELECTRICAL,
PLUMBING AND OTHER TRADES FOR SIZE AND LOCATION OF ALL SLAB AND WALL OPENINGS AND SLEEVES. CONTRACTOR TO DEVELOP AND SUBMIT A SINGLE COORDINATION DRAWING COMBINING ALL TRADES INDICATING ALL SLAB OPENINGS AND SLEEVES PRIOR TO POURING CONCRETE FOR REVIEW
BY STRUCTURAL ENGINEER.
12. ALL PIPE AND CONDUIT OPENINGS SHALL BE SLEEVED AND CAST IN PLACE UNLESS OTHERWISE
NOTED. DO NOT SAWCUT, CORE OR CORE DRILL STRUCTURAL CONCRETE WITHOUT EXPLICIT
DIRECTION FROM THE STRUCTURAL ENGINEER. DRILL BITS THAT CAN CUT OR DAMAGE REINFORCING
ARE NOT PERMITTED TO BE USED ON STRUCTURAL CONCRETE.
13. CONDUITS AND PIPES SHALL NOT BE PERMITTED IN STRUCTURAL CONCRETE ELEMENTS UNLESS SPECIFICALLY REVIEWED BY THE STRUCTURAL ENGINEER. ALL CONDUITS TO BE EMBEDDED IN THE
STRUCTURAL CONCRETE SHALL BE SUBMITTED FOR STRUCTURAL REVIEW ON A SINGLE
COORDINATED CONDUIT DRAWING COMBINING ALL TRADES DEVELOPED AND COORDINATED BY THE
CONTRACTOR. COORDINATED CONDUITS/PIPES MUST BE PLACED IN ONE LAYER AVOIDING
CROSSOVER AND SPACED AT THE GREATER OF 3" OR 3 DIAMETERS. DRAWINGS SHALL SHOW STUB-UP LOCATIONS, BEND RADIUS AND DETAILS OF CONDUIT/PIPE INSTALLATION. ALL CONDUITS AND PIPES
SHALL BE INSTALLED PER THE REQUIREMENTS OF ACI 318 SECTIONS 20.7 AND 26.8.2.
A. ELECTRICAL CONDUIT SHALL BE RIGID STEEL CONDUIT OR FLEXIBLE PLASTIC CONDUIT. ALUMINUM
CONDUIT IS PROHIBITED. CONDUIT OUTSIDE DIAMETER SHALL NOT EXCEED 2" OR 1/6 SLAB
THICKNESS, WHICHEVER IS LESSER. CONDUIT SHALL BE FIRMLY CHAIRED AND TIED TO PREVENT
DISPLACEMENT DURING POURING.
II. DESIGN LOADS:
1. DEAD LOAD: EQUIPMENT SELF WEIGHT.
2. WIND LOAD
A. ULTIMATE DESIGN BASIC WIND SPEED V(ult) = 95 MPH
B. WIND IMPORTANCE FACTOR = 1.00
C. WIND EXPOSURE CATEGORY = C
3. SEISMIC LOAD
A. SITE CLASS = D (DEFAULT)
B. RISK CATEGORY = II
C. SEISMIC IMPORTANCE FACTOR = 1.00
D. MAPPED SPECTRAL RESPONSE
a. SHORT PERIOD SS = 0.65 g
b. 1-SECOND PERIOD S1 = 0.33 g
E. DESIGN SPECTRAL RESPONSE (5% DAMPED)
a. SHORT PERIOD SDS = 0.56 g
I. GENERAL NOTES:
1. ALL STRUCTURAL WORK SHALL CONFORM TO THE DRAWINGS, THE PROJECT SPECIFICATIONS, ALL
DRAWING NOTES, AND THE 2022 CALIFORNIA BUILDING CODE (CBC).
2. ALL APPLICABLE REFERENCE STANDARDS, AS MODIFIED BY THE BUILDING CODE, INCLUDE:
A. ASCE/SEI 7-16: MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
B. ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
C. AISC 360-16: SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
D. ACI 117-10: STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIAL
E. AISI SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS, 2016
3. THE SCOPE OF WORK IS NOT SOLELY DEFINED BY THESE DOCUMENTS.
4. TYPICAL DETAILS APPLY THROUGHOUT THE PROJECT, EVEN IF NOT SPECIFICALLY REFERENCED IN PLANS OR DETAILS. DETAILS OF CONSTRUCTION NOT FULLY SHOWN OR NOTED ON THE DRAWINGS NOR CALLED OUT IN THE SPECIFICATIONS SHALL BE OF THE SAME SIZE AND CHARACTER AS FOR
SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.
5. ALL FORCES INDICATED IN THE STRUCTURAL DRAWINGS ARE SERVICE LOADS AS DEFINED BY ASCE-7, UNLESS NOTED OTHERWISE.
6. DO NOT USE SCALED DIMENSIONS; USE ONLY WRITTEN DIMENSIONS. WHERE NO DIMENSION IS
PROVIDED, CONSULT THE ARCHITECT FOR CLARIFICATIONS BEFORE PROCEEDING WITH WORK.
7. SEE ARCHITECTURAL DRAWINGS FOR SITE POSITIONING AND PROJECT DATUM, REFERENCE IS (0'-0")
AS SHOWN ON ARCHITECTURAL DRAWINGS.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONDITIONS OF THE JOB SITE
INCLUDING SAFETY OF PERSONS AND PROPERTY AND THE MEANS AND METHODS OF CONSTRUCTION.
9. STRUCTURAL ELEMENTS SHALL BE CENTERED ABOUT GRIDLINES OR DIMENSION LINES, UNLESS
OTHERWISE NOTED.
10. THE CONTRACTOR SHALL PROVIDE ENGINEERED DESIGNS OF TEMPORARY SHORING AND BRACING AND MAKE SAFE ALL FLOORS, ROOFS, WALLS, EXCAVATIONS AND ADJACENT PROPERTY AS PROJECT
CONDITIONS AND LOCAL BUILDING CODE REQUIRE.
11. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC. REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT
SHOWN ON PLAN. DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE ARCHITECT
IMMEDIATELY.
12. OPENINGS SHALL NOT BE MADE IN ANY STRUCTURAL MEMBER UNLESS SPECIFICALLY SHOWN ON THE
STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.
13. DEFICIENT WORK AND WORK NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AS IDENTIFIED
BY THE ARCHITECT OR INSPECTOR SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE.
CONTRACTOR SHALL COMPENSATE OWNER FOR SERVICES ARISING FROM DEFICIENT WORK.
14. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY REQUIRED DEWATERING OF THE SITE
DURING CONSTRUCTION.
15. THE CONTRACTOR SHALL PREPARE ENGINEERED DESIGN AND SHALL BE RESPONSIBLE FOR
CONFIRMING ADEQUACY OF AS BUILT STRUCTURE FOR ALL SURCHARGE LOADS RESULTING FROM
COMPACTION AS WELL AS CRANES TRUCKS, BULLDOZERS OR ANY OTHER CONSTRUCTION
EQUIPMENT. ENGINEERED DESIGNS SHALL BE PREPARED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION AND SUBMITTED TO ENGINEER OF RECORD FOR REVIEW.
16. THE STRUCTURAL COMPONENTS BY THEMSELVES ARE A NON-SELF-SUPPORTING STRUCTURE.
LATERAL FORCES DUE TO WIND, EARTHQUAKE, OR SOIL ARE CARRIED BY THE ROOF AND FLOOR DIAPHRAGMS TO THE LATERAL SYSTEM. CERTAIN ELEMENTS SHOWN ON THE STRUCTURAL DRAWINGS
(SUCH AS BRACING, ROOF AND FLOOR SLABS, AND CONCRETE IN COMPOSITE COLUMNS) ARE
REQUIRED FOR OVERALL OR LOCAL STABILITY OF OTHER ELEMENTS (SUCH AS BEAMS, COLUMNS, AND WALLS). IF DUE TO SEQUENCING OF CONSTRUCTION, THESE STABILITY ELEMENTS ARE NOT IN PLACE, THE CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION WHERE THE PROJECT IS LOCATED, WHO SHALL INVESTIGATE WHERE TEMPORARY
SHORING/BRACING IS REQUIRED AND SHALL DESIGN THIS TEMPORARY SHORING/BRACING. THE
CONTRACTOR SHALL PROVIDE THIS SHORING/BRACING UNTIL THE REQUIRED STRUCTURAL ELEMENTS AND THEIR CONNECTIONS HAVE BEEN INSTALLED AND REACH THEIR FINAL DESIGN STRENGTHS.
17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT WHEN PLACED ON FRAMED FLOORS OR ROOFS.
THE CONSTRUCTION MATERIAL LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING WHERE STRUCTURE IS NOT COMPLETE OR HAS
NOT ATTAINED DESIGN STRENGTH.
18. BUILDING TOLERANCES: STANDARD TOLERANCES SHALL BE BASED ON THE REQUIREMENTS OF THE AISC CODE OF STANDARD PRACTICE AND ACI 117, STANDARD SPECIFICATIONS FOR TOLERANCES FOR
CONCRETE CONSTRUCTION AND MATERIALS.
III. FOUNDATIONS:
1. FOUNDATION DESIGN CRITERIA ARE BASED ON CODE MINIMUM VALUES AS SPECIFIED IN CHAPTER 18
"SOILS AND FOUNDATIONS" OF THE 2021 CALIFORNIA BUILDING CODE (CBC).
2. FOOTINGS ARE DESIGNED BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 1,500 PSF.
3. LATERAL BEARING PRESSURE FOR FOOTING DESIGN IS 100 PSF.
4. SOIL PREPARATION OF THE SITE SHALL FOLLOW THE RECOMMENDATIONS DESCRIBED IN CHAPTER 18 OF 2021 CBC. THIS INCLUDES REMOVAL OF EXISTING STRUCTURES/UTILITIES, REMOVAL OF EXISTING FILL WHERE DEEMED NECESSARY, PREPARATION OF THE SUBGRADE & COMPACTION, EXCAVATIONS
FOR NEW FOUNDATIONS & SLABS, AND BACKFILLING TO RETAINING WALLS.
5. FOUNDATIONS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED FILL MATERIAL 12 INHES IN DEPTH WITH THE IN-PLACE DRY DENSITY NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT
OPTIMUM MOISTURE CONTENT DETERMINED IN ACCORDANCE WITH ASTM D1557.
6. LOCATION OF ALL UNDERGROUND UTILITIES SHALL BE VERIFIED PRIOR TO CONSTRUCTION OF FOUNDATION TO AVOID ANY INTERFERENCE. CONTRACTOR SHALL EXPOSE EXISTING UTILITY LINES IN THE IMMEDIATE AREA TO DETERMINE THEIR EXACT INVERT ELEVATION, SIZE AND LOCATION RELATIVE TO THE FOUNDATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY INTERFERENCE WITH PILES, FOOTINGS OR FOUNDATION WALLS.
7. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER, AND SEEPAGE. WATER SHALL NOT BE ALLOWED TO STAND IN TRENCHES OR FORMS BEFORE OR AFTER CONCRETE IS PLACED, AND SHALL BE PUMPED OUT. IF BOTTOMS OF TRENCHES
BECOME SOFTENED DUE TO RAIN OR OTHER WATER BEFORE FOUNDATIONS ARE CAST, THE
CONTRACTOR SHALL, AT THEIR OWN EXPENSE, EXCAVATE THE SOFTENED MATERIAL AND REPLACE
WITH CONCRETE.
8. CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED TO SAFELY AND ADEQUATELY RETAIN THE EARTH BANKS AND ANY EXISTING
STRUCTURE.
9. EXCAVATIONS FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO
PLACING OF CONCRETE AND REINFORCING. CONTRACTOR SHALL NOTIFY THE GEOTECHNICAL
ENGINEER WHEN THE EXCAVATIONS ARE READY FOR INSPECTION. THE GEOTECHNICAL ENGINEER
SHALL SUBMIT A LETTER OF COMPLIANCE TO THE OWNER.
10. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING
WALLS BEFORE CONCRETE OR MASONRY HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR
SHALL BRACE OR PROTECT ALL BUILDING WALLS BELOW GRADE FROM LATERAL LOADS UNTIL
ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL DESIGN STRENGTH.
CONTRACTOR SHALL PROVIDE FOR DESIGNS, PERMITS AND INSTALLATION OF BRACING AND
PROTECTION.
VIII. ANCHOR RODS:
1. ANCHOR RODS SHALL BE ASTM F1554 GRADE 36 WITH CLASS 1A THREADS, UNLESS NOTED
OTHERWISE. FURNISH ANCHOR RODS PREFABRICATED WITH MATCHING DOUBLE HEAVY HEX NUTS
JAMMED AT THE END EMBEDDED IN CONCRETE. FURNISH HARDENED PLATE WASHERS, LOCK
WASHERS, AND MATCHING HEAVY HEX NUTS FOR SECURING THE BASE PLATE TO THE ANCHOR RODS.
A RIGID STEEL TEMPLATE SHALL BE USED TO LOCATE ANCHOR RODS WHILE PLACING CONCRETE.
2. HOOKED ANCHOR RODS SHALL NOT BE USED EXCEPT WHERE NOTED.
3. ANCHOR RODS SHALL HAVE SUFFICIENT LENGTH TO PROVIDE THE MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, MEASURED FROM THE FACE OF THE CONCRETE TO THE NEAR FACE OF THE DOUBLE NUT, WITH ADEQUATE EXTENSION AS REQUIRED TO RECEIVE THE BASE PLATE WITH FULL THREAD
PROJECTION FOR NUT INSTALLATION.
4. ANCHOR ROD INSTALLATION SHALL BE COORDINATED WITH REINFORCING AND FRAMEWORK.
5. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER EVALUATION BY THE CONTRACTOR'S ERECTION
ENGINEER.
6. AFTER BASE INSTALLATION, ANCHOR ROD NUTS SHALL BE INSTALLED TO A SNUG-TIGHT CONDITION.
7. NO HEATING OR BENDING OF THE ANCHOR RODS IS PERMITTED. HOLES IN THE BASE
MATERIAL SHALL NOT BE ENLARGED BY BURNING.
VI. MECHANICAL AND ADHESIVE ANCHORS:
1. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE:
A. "SET-XP”BY SIMPSON STRONG TIE (ICC ESR-2508)
B. "HIT-RE 500-SD" BY HILTI, INC. (ICC ESR-3814) EQUIPMENT ANCHORAGE UON
C. "PURE110+BY DEWALT (ICC ESR-3298)
2. EXPANSION ANCHORS INSTALLED INTO CONCRETE:
A. "STRONG-BOLT 2" BY SIMPSON STRONG-TIE (ICC ESR-3037)
B. "KWIK BOLT TZ2 (KB-TZ2)”BY HILTI, INC. (ICC ESR-4266)
C. "POWER-STUD+SD2" BY DEWALT (ICC ESR-2502)
3. ADHESIVE ANCHORS: ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS AND ANSI B18.22.1
TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS ASTM A193 GRADE B7
THREADED RODS TO USE ASTM A 563 GRADE DH HEAVY HEX NUTS AND ASTM F 436 WASHERS.
4. ADHESIVE DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
5. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC-ES REPORT AND MANUFACTURERS
RECOMMENDATIONS.
6. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS PER ICC-ES REPORT &
MANUFACTURERS RECOMMENDATIONS.
7. CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL
ASSEMBLIES ATTACHED WITH MECHANICAL OR ADHESIVE ANCHORS.
8. PRIOR TO ALL DRILLING OR CORING, THE CONTRACTOR SHALL (1) VERIFY THE EXISTING CONCRETE OR MASONRY THICKNESS TO PREVENT DAMAGE TO THE OPPOSITE FACE OF CONCRETE AND MAINTAIN 1 -1 /2 ”CLEAR COVER U.N.O., AND (2) IDENTIFY EXISTING REINFORCING LOCATIONS BY PACHOMETER, PROBING, CHIPPING, ETC. TO AVOID DAMAGE EXISTING REINFORCING.
9. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH, WHICHEVER IS
LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE
ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS
NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION.
10. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION TO SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER
(AAI) CERTIFIED THROUGH ACI/CRSI OR EQUIVALENT (ACI 318-14 17.8.2.2).
11. ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-14 17.1.2).
SETTING INFORMATION SYM. UNITS
NOMINAL ANCHOR DIAMTER (IN.)
INSTALLATION TORQUE
CARBON STEEL
INSTALLATION TORQUE
STAINLESS STEEL
TINST
TINST
FT-LB
(Nm)
FT-LB
(Nm)
1/4 3/8 1/2 5/8 3/4
(5)
(41)
(68)
(54)
(149)
(8)
(41)
(54)
(81)
(169)
SLAB STEP/ DEPRESSION
SLOPE UP
SLOPE DOWN
RIDGE
VALLEY
REVISION NUMBER
ELEVATION
SECTION MARK
ELEVATION MARK
GRID BUBBLE
S301
S201
SLAB THICKNESS
CHANGE
DETAIL MARK
S501
THE INSPECTOR SHALL OBSERVE THESE FUNCTIONS ON A RANDOM BASIS.
OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS.
OBSERVE
THESE INSPECTIONS SHALL BE PERFORMED FOR EACH CONNECTION OR MEMBER,
AND COMPLETED PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.
PERFORM
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT CONTINUOUSLY
WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED
CONTINUOUS
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT
WHERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF
WORK.
PERIODIC
A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN APPROVED AGENCY AND
APPROVED BY THE BUILDING OFFICIAL AS HAVING THE COMPETENCE NECESSARY TO
INSPECT A PARTICULAR TYPE OF CONSTRUCTION REQUIRING SPECIAL INSPECTION.
SPECIAL
INSPECTOR
INSPECTION OF CONSTRUCTION REQUIRING THE EXPERTISE OF AN APPROVED
SPECIAL INSPECTOR IN ORDER TO ENSURE COMPLIANCE WITH THE BUILDING CODE
AND THE APPROVED CONSTRUCTION DOCUMENTS.
SPECIAL
INSPECTION
DEFINITIONS
REFERENCES
CODES/STANDARDS
SPECIAL INSPECTION AND TEST REQUIREMENTS
TYPE REQUIRED INSPECTIONS AND/OR TESTSFREQUENCY
INDICATES SPECIAL INSPECTION OF ITEM IS REQUIRED FOR THE WORK DEFINED IN
THE CONSTRUCTION DOCUMENTS FOR THIS PROJECT.
INSPECTION AND TESTING REQUIREMENTS ON THIS SHEET ARE IN ACCORDANCE
WITH SECTION 1705 OF THE 2021 CALIFORNIA BUILDING CODE (CBC). AND HAVE BEEN
IDENTIFIED AS A STATEMENT OF SPECIAL INSPECTIONS AS REQUIRED BY CBC
SECTION 1704.3. THE OWNER OR THE OWNER'S AUTHORIZED AGENT, OTHER THAN
THE CONTRACTOR, SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO
PROVIDE THE SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION AS
REQUIRED BY CBC SECTION 1705 AND IDENTIFY THE APPROVED AGENCIES TO THE
BUILDING OFFICIAL. THESE SPECIAL INSPECTIONS AND TESTS ARE IN ADDITION TO
THE INSPECTIONS BY THE BUILDING OFFICIAL THAT ARE IDENTIFIED IN CBC SECTION
110. SPECIAL INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE WITH CBC SECTION
1704.2.1, AND ALL OTHER APPLICABLE SECTIONS AND STANDARDS.
SPECIAL INSPECTIONS AND TESTS INDICATED ON THIS SHEET ARE FOR THE
STRUCTURAL WORK, SEE OTHER DISCIPLINES DRAWINGS AND SPECIFICATIONS FOR
REQUIRED NONSTRUCTURAL SPECIAL INSPECTIONS AND TESTS.
STATEMENT OF SPECIAL INSPECTIONS
CONCRETE CBC 1705.3
4. ANCHORS POST-INSTALLED
IN HARDENED CONCRETE
MEMBERS
INSPECT ALL OTHER MECHANICAL OR ADHESIVE ANCHORS THAT ARE NOT ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS - SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI318: 17.8.2 OR OTHER QUALIFICATION PROCEDURES.
PERIODIC ACI 318: 17.8.2
GENERAL NOTES ABBREVIATIONS
Ann Watson Phone 279 782-3872 Fax 916 376-6216 ann.watson@dgs.ca.gov
Issue
DateNo. Description
Project
Drawn
File Date
Supervisor
Sheet Title
Designed
Work Order
Sheet Number
Sheet ScaleReference North
DSA Building Number
Vault File Number
Checked
Client Agency
Address
X
C A D
F
IL
E
R Q P O N M L K J I H G F E D C B A
Stantec Consulting Services Inc.
801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775
DEPARTMENT OF
GENERAL SERVICES
IS DK AD
GENERAL NOTES
1403 Furneaux Road, Olivehurst, CA 95961
S1.0
# POUND
& AND
@ AT
AB ANCHOR BOLT
ACS ALL COMMON SIDES
ADDL ADDITIONAL
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
ALT ALTERNATE
ARCH,
ARCH'L
ARCHITECT, ARCHITECTURAL
BL BRICKLEDGE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAILING
BO BOTTOM OF
BOB BOTTOM OF BEAM
BOD BOTTOM OF DECK
BOS BOTTOM OF STEEL
BOT, BOTT BOTTOM
BP BASE PLATE
BRBF BUCKLING RESTRAINED BRACED
FRAME
BRG BEARING
BTWN BETWEEN
C CHANNEL
CB CONCRETE BEAM
CC CARRIED COLUMN
CEN CENTER
CFMF COLD-FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT, CONNECTION
CONT CONTINUOUS
CTR CENTERED
CWI CERTIFIED WELDING INSPECTOR
D, DIA DIAMETER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEF DEFORMED, DEFINITION
DEFL DEFLECTION
DET, DTL DETAIL
DIAG DIAGONAL
DN DOWN
DWG DRAWING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
EMB EMBED
EN EDGE NAILING
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQ SPA EQUAL SPACE
ES EACH SIDE
EW EACH WAY
EXIST, (E) EXISTING
EXT EXTERIOR
FD FLOOR DRAIN
FDN, FNDN FOUNDATION
FF EL FINISH FLOOR ELEVATION
FN FIELD NAILING
FOA FACE OF ANGLE
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FT FEET
FTG FOOTING
Fy YIELD STRESS
GA GAGE, GUAGE
GALV GALVANIZED
GB GRADE BEAM
GLB GLUED-LAMINATED BEAM
GT GIRDER TRUSS
H, HORIZ HORIZONTAL
HC HOLLOW CORE
HI HIGH
HK HOOK
HSS HOLLOW STRUCTURAL STEEL
IN INCHES
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIPS
KB KNEE BRACE
L ANGLE
LB POUND
LF LINEAR FOOT
LG LENGTH
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOW
LT WT LIGHTWEIGHT
LVL LEVEL
MAX MAXIMUM
MC MOMENT CONNECTION
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEZZ MEZZANINE
MFR,
MANUF
MANUFACTURER
MID MIDDLE
MIL MILLIMETER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
N NORTH
NA NOT APPLICABLE
NDT NON-DESTRUCTIVE TESTING
NEW, (N) NEW
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
REF REFER, REFERENCE
REINF REINFORCED, REINFORCEMENT
REM REMAINDER
REQ'D REQUIRED
REQ'MTS,
REQMTS
REQUIREMENTS
REV REVISION
SAD SEE ARCHITECTURAL DRAWINGS
SC SLIP CRITICAL
SCHED SCHEDULE
SCJ SAWN CONTROL JOINT
SECT SECTION
SF SQUARE FEET
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SOG SLAB ON GRADE
SPA SPACES, SPACING
SQ SQUARE
SSH SHORT SLOTTED HOLE
STD STANDARD
STL STEEL
STRUCT STRUCTURE, STRUCTURAL
SUPP SUPPORT
T&B TOP AND BOTTOM
TEMP TEMPORARY
THK THICK
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOSC TOP OF STRUCTURAL CONCRETE
TOSL TOP OF SLAB
TOT TOTAL
TOW TOP OF WALL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V, VERT VERTICAL
VIF VERIFY IN FIELD
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WB WIND BRACE
WBBP WIND BRACE BASEPLATE
WHSS WELDED HEADED STEEL STUD
WP WORKING POINT, WORK POINT
WRT WITH RESPECT TO
WT WEIGHT
WWR WELDED-WIRE REINFORCEMENT
YD YARD
SYMBOLS
EVSE LEVEL II
CHP SHASTA OFFICE
09-30-622426
9-24-24
10/14/24 ISSUED FOR CD95 CLIENT REVIEW0
PROJECT NUMBER:
000000000013679
1 10/28/24 100% WORKING SFM SUBMITTAL
V1V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
A A
UNISTRUT P1001 TYPUNISTRUT P1000 TYP
(E) TAPPERED Wx
8' 0"
ELEVATION
SECTION A-A
1' 2/ 5"
P E R M
FR
EQUIP BY OTHERS
USE MOUNTING
HOLES PROVIDED
BY MFR (4) TOT
BB
SECTION B-B
G A G E
1/2" DIA BOLT W/
P1010 SPRING NUT &
WASHER TYP
11 1/8"
UNISTRUT P2346 W/
(2) 1/2" DIA THROUGH
BOLTS TYP
150 LBS
EQ EQ
P E R M
FR
1' 7"
M
IN
4" SQ BP TYP
1/2" DIA BOLT W/
P1010 SPRING NUT &
WASHER TYP (4) TOTAL @
EQUIP
(E) TAPPERED Wx COL
EQ EQ
(E) SLOPED FLANGE
4" LONG x 12 GA BENT PL W/
1/2" DIA THROUGH BOLT TYP
STRUT TYP
TYP
24" MAX
6" M
IN
TYP
4'-0" MAX
BENT PL TYP
TYP
6" MIN
C
LR3"
TYP
3" CLR
2' 0"
ELEVATIONSUBGRADE PER
GENERAL NOTES
(2) #5 EA WAY TOP
AND BOTTOM
FINISHED GRADE
DUAL PEDESTAL
CHARGER
WT = 111 LBS
PLAN
ANCHOR POINT
PER MFP TYP
(4) TOT
EQUIPMENT BASE
BY OTHERS
4"
3/ 4"2 1/4"7"
11 1/2"
1/ 2"
5/8" DIA HILTI KB-TZ2
W/ 4" EMBED MIN TYP
3' 2"
4' 9"
6" MIN
2' 0"
2' - 0" Ann Watson Phone 279 782-3872 Fax 916 376-6216 ann.watson@dgs.ca.gov
Issue
DateNo. Description
Project
Drawn
File Date
Supervisor
Sheet Title
Designed
Work Order
Sheet Number
Sheet ScaleReference North
DSA Building Number
Vault File Number
Checked
Client Agency
Address
X
C A D
F
IL
E
Stantec Consulting Services Inc.
801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775
DEPARTMENT OF
GENERAL SERVICES
IS DK AD
DETAILS
1403 Furneaux Road, Olivehurst, CA 95961
S2.0
EVSE LEVEL II
CHP SHASTA OFFICE
NTS S002
8 DUAL PEDESTAL CHARGER ANCHORAGE PLAN
NTSS002
6 DUAL PEDESTAL CHARGER ANCHORAGE PLAN
09-30-622426
9-24-24
10/14/24 ISSUED FOR CD95 CLIENT REVIEW0
PROJECT NUMBER:
000000000013679
1 10/28/24 100% WORKING SFM SUBMITTAL
V1
WALL MOUNTED
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/16/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4410
| 0001 G0.0 TITLE SHEET |
| 0002 E0.0 ELECTRICAL NOTES |
| 0003 E1.0 SINGLE LINE DIAGRAM AND SCHEDULES |
| 0004 E2.0 ELECTRICAL SITE PLAN |
| 0005 E3.0 ELECTRICAL DETAILS |
| 0006 S-001 GENERAL NOTES |
| 0007 S-002 DETAILS |