Plans.pdf
PDF 5 MB Posted
- Attached to
- Project 13685. DOT D5 EVSE. Contract 25-284384
- Solicitation number
- 0000037223
- Issued by
- San Luis Obispo County, San Luis Obispo City, California
About this file
Summary
This is a 100% construction drawing document prepared for Caltrans District 5 for the Templeton Maintenance Station Electric Vehicle Supply Equipment (EVSE) installation project located at 640 N. Main Street, Templeton, California. The project scope consists of installing EVSE infrastructure to provide power to three electric vehicle charging station (EVCS) ports, including one new 75 kilovolt ampere (KVA) transformer, one new 200-ampere (A) panelboard, new feeders to EVCS port locations, and necessary structural and civil work. The project involves a dual-port pedestal-type EVCS with 19,200 volts-amperes (VA) per port and a single-port pedestal-type EVCS with 19,200 VA per port, both designated for fleet vehicle use only and not available to the general public. The EVCS equipment will be provided and installed by the State's current electric vehicle charging station vendor, with final terminations and splicing performed by the state vendor. All work must comply with the 2022 California Building Code, 2022 California Electrical Code, 2022 California Fire Code, and applicable national standards including NFPA codes. The project has been approved by the Office of the State Fire Marshal for fire and panic only as of December 30, 2024 (CSFM Application Number 24-S-4152-C; Project Number 000000000013685).
The construction documents include electrical, structural, and civil details with comprehensive specifications for conduit routing, grounding systems, equipment anchoring, underground utilities, and concrete foundations. Special inspections are required for concrete construction, structural steel welding and bolting, and post-installed anchors in hardened concrete. The project team includes GOSS Engineering, Inc. as civil engineer and electrical engineer (contact: Ed Burtch, 951-340-1977), Proactive Engineering Consultants as structural engineer (contact: Felix Gonzalez, 949-716-7460), and Solid Rock Structural Solutions as additional structural support (contact: Robert J. Fecarotta, 949-418-6722). The Office of Sustainability at the Department of General Services serves as project director (contact: Ann Watson, 279-782-3872). All electrical work requires third-party testing for new feeder conductors, arc-flash hazard assessments and warning labels per NFPA 70E standards, and compliance with seismic design criteria utilizing equivalent lateral force analysis with a Risk Category II importance factor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf | ||
| 15_-SL2-_ChargePoint_CP6000_Spec-Inst-SignOff.pdf | ||
| 13.1_13685_Structural_Calculations.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Caltrans District 5 - Templeton Maintenance Station
EVSE Installation
100% Construction Drawings
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (3) ELECTRIC VEHICLE
CHARGING STATION (EVCS) PORTS WITHIN THE TEMPLETON MAINTENANCE STATION.
SEE EVCS NOTE ON THIS SHEET.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (1) NEW 75KVA
TRANSFORMER, (1) NEW 200A PANELBOARD AS WELL AS NEW FEEDERS TO THE EVCS
PORTS LOCATIONS AS SHOWN ON THESE PLANS. PROJECT INCLUDES STRUCTURAL
AND CIVIL WORK EFFORT/S NECESSARY TO SUPPORT THIS PROJECT. SEE SHEET
E1.00 FOR A SUMMARY OF THE EVCS PORTS.
ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSTALLATION OF THE EVSE, SUCH WORK IS IN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 12 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 12 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 12 E1.00 SITE PLAN
4 OF 12 E2.00 POWER PLAN
5 OF 12 E4.00 ELECTRICAL DETAILS
6 OF 12 E4.01 ELECTRICAL DETAILS
7 OF 12 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
8 OF 12 C1 TITLE SHEET
9 OF 12 C2 SITE PLAN
10 OF 12 S0.01 GENERAL NOTES
11 OF 12 S0.02 SPECIAL INSPECTION TABLES, ABBREVIATIONS
AND SYMBOLS
12 OF 12 S1.01 PLANS AND DETAILS
PROJECT
LOCATION
BUILDING INFORMATION
CONSTRUCTION TYPE: WOOD TYPE, V-B
OCCUPANCY CLASSIFICATION: B
OCCUPANCY LOAD: 8
ACTUAL BUILDING HEIGHT: 9' 9" AT EVE, 10' 4" AT PEAK
BUILDING AREA (SQ. FT.) 1,250 SQ. FT.
AREA OF PROJECT (SQ. FT.) 9,000 SQ. FT.
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: 1,200 SQ. FT.
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: NO
FIRE ALARM: NO
OTHER FIRE PROTECTION SYSTEMS: NO
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1972
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: YES
PROJECT TEAM
PROJECT DIRECTOR
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(279) 782-3872
CONTACT: ANN WATSON
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON ST., SUITE 301,
CORONA, CA. 92879
(951) 340-1977
CONTACT: ED BURTCH
PROACTIVE ENGINEERING CONSULTANTS
27051 TOWNE CENTRE DRIVE, SUITE 270
FOOTHILL RANCH, CA 92610
(949) 716-7460
CONTACT: FELIX GONZALEZ
SOLID ROCK STRUCTURAL SOLUTIONS
1501 QUAIL STREET, SUITE 150
NEWPORT BEACH, CA 92660
(949) 418-6722
CONTACT: ROBERT J. FECAROTTA
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN ARC-FLASH
HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL CONTRACTOR, IN
COMPLIANCE TO THE REQUIREMENTS OF THE LATEST CEC 110.16.
AN ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE
LATEST NFPA 70E - 130.5, SHALL BE PERFORMED BY THE ELECTRICAL
CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD
WARNING LABEL/MARKING TEMPLATE/S SHALL BE SUBMITTED TO THE
EEOR FOR REVIEW AND APPROVAL.
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013685
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
N. MAIN ST.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
PROJECT NUMBER: 000000000013685; 11/07/25
http://www.gossengineering.com
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
T
TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 AMERICA WITH DISABILITIES ACT STANDARDS
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH STUDIES SHALL BE PROVIDED FOR LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THE STUDY SHALL INCLUDE ALL PORTIONS OF THE ELECTRICAL DISTRIBUTION SYSTEM (WITHIN THE PROJECT SCOPE OR AS DEFINED BY THE EEOR) SUPPLIED BY NORMAL AND ALTERNATE SOURCES OF POWER. THIS INCLUDES SWITCHGEAR, SWITCHBOARDS, PANEL BOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, GENERATORS AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THE ANALYSIS WILL INCLUDE CREATION OF ARC-FLASH HAZARD WARNING LABELS. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS. THE CONTRACTOR WILL SUBMIT TO THE EEOR FOR APPROVAL AND INSTALL THE LABELS. PROVIDE A CURRENT, UP-TO-DATE SHORT CIRCUIT CURRENT STUDY. IF ONE DOES NOT EXIST, THEN PERFORM A SHORT CIRCUIT STUDY IN ACCORDANCE WITH IEEE 399 STANDARD (BROWN BOOK), “IEEE RECOMMENDED PRACTICE FOR INDUSTRIAL AND COMMERCIAL POWER SYSTEM ANALYSIS,” BASED UPON THE POSITIVE AND ZERO SEQUENCE SOURCE IMPEDANCE SUPPLIED BY THE LOCAL ENERGY PROVIDER. ALL STUDIES SHALL BE SUBMITTED TO THE EEOR FOR REVIEW AND APPROVAL.
10. PERFORM AN ARC FLASH HAZARD ANALYSIS AFTER THE SHORT CIRCUIT AND PROTECTIVE DEVICE COORDINATION STUDIES HAVE BEEN COMPLETED BASED UPON IEEE 1584 STANDARD, “IEEE GUIDE FOR PERFORMING ARC FLASH HAZARD CALCULATIONS.” THE ANALYSIS SHALL BE CALCULATED BY MEANS OF THE
SKM POWER TOOLS FOR WINDOWS COMPUTER SOFTWARE PACKAGE. PERTINENT DATA, RATIONALE
EMPLOYED, AND ASSUMPTIONS IN DEVELOPING THE CALCULATIONS SHALL BE INCORPORATED IN THE INTRODUCTORY REMARKS OF THE STUDY. THE ANALYSIS SHALL BE IN ACCORDANCE WITH APPLICABLE NFPA 70E, OSHA 29-CFR, PART 1910 SUBPART S AND IEEE 1584 STANDARDS. INCIDENT ENERGIES AND HAZARD CATEGORIES MUST BE CALCULATED. THE USE OF THE NFPA “TABLE METHOD” IS UNACCEPTABLE. BASED ON THE RESULTS OF THE INCIDENT ENERGY STUDY, THE SELECTED VENDOR SHALL PRODUCE AND INSTALL A WARNING LABEL (ORANGE <40 CAL/CM2) OR DANGER LABEL (RED > 40 CAL/CM2) APPROXIMATELY 4” X 6” (BRADY MULTI-COLOR OR EQUIVALENT) FOR EVERY POINT IN THE SYSTEM AS SPECIFIED SYSTEM EQUIPMENT SHOWN ON THE ONE-LINE DIAGRAM. LABELS WILL BE IN ACCORDANCE WITH ANSI Z535.4-2002 LISTING ITEMS 1-8 ABOVE. ALSO, INCLUDE THE BUS NAME, SYSTEM OPERATING VOLTAGE, AND DATE OF ISSUE. THE LABEL MUST
BE READABLE IN BOTH INDOOR AND OUTDOOR ENVIRONMENTS FOR AT LEAST 3 YEARS.
a. DETERMINE THE FOLLOWING:
· ARC HAZARD BOUNDARY (INCHES)
· WORKING DISTANCE (INCHES)
· ARC FLASH INCIDENT ENERGY AT THE WORKING DISTANCE (CALORIES/CM2)
· PPE CATEGORY AND DESCRIPTION INCLUDING THE GLOVE RATING
· VOLTAGE RATING OF THE EQUIPMENT
· LIMITED APPROACH DISTANCE (INCHES)
· RESTRICTED APPROACH DISTANCE (INCHES)
· PROHIBITED APPROACH DISTANCE (INCHES)
b. PRODUCE ARC FLASH EVALUATION SUMMARY SHEETS LISTING THE FOLLOWING ADDITIONAL ITEMS.
· BUS NAME
· UPSTREAM PROTECTIVE DEVICE NAMES, TYPE AND SETTINGS
· BUS LINE-TO-LINE VOLTAGE
· BUS BOLTED FAULT
· PROTECTIVE DEVICE BOLTED FAULT CURRENT
· ARCING FAULT CURRENT
· PROTECTIVE DEVICE TRIP / DELAY TIME
· BREAKER OPENING TIME
· SOLIDLY GROUNDED COLUMN
· EQUIPMENT TYPE
· GAP
· ARC FLASH BOUNDARY
· WORKING DISTANCE
· INCIDENT ENERGY
· REQUIRED PROTECTIVE FIRE RATED CLOTHING TYPE AND CLASS
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
SCALE
SITE PLAN 1
1/32" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B
R L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
SITE PLAN
E1.00
E2.00
EVCS SUMMARY
LOCATION PARKING TYPE SHEET EXISTING EVCS SPACES NEW EVCS SPACES
PARKING LOT
*FLEET E2.00 (0) LEVEL 2 (3) LEVEL 2
TOTAL FLEET PORTS: (3) LEVEL 2
* NOTE:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH CBC
11B-228.3.2 ACCESS REQUIREMENTS.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
1"C - 2#2
& 1#8 GRD.
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
T
PANELBOARD 'EV'
PB
1 1/2"C - 4#2
& 1#6 GRD.
12 7
(E) TEMPORARY
GENERATOR
TRANSFER SWITCH
(E) DISCONNECT
(E) MAIN
SWITCHBOARD
'MSB'
J
11 12
EVCS-2 2 6
EVCS-1 1 6
(TYP.) 14
1"C - 2#2
& 1#8 GRD.
1 1/2"C - 4#2
& 1#6 GRD.
(E) GAS METER
TRANSFORMER 'TEV'12 8 7
SCALE
POWER PLAN 1
1/4"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
POWER PLAN
E2.00
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH
19,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (4#2 + 1#6 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. PROVIDE MULE TAPE ROUTED
THROUGH CONDUIT FROM THE PANELBOARD TO
EVCS STUB-UP. SEE DETAIL #1 ON SHEET E4.00.
SINGLE PORT PEDESTAL TYPE EVCS WITH
19,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (2#2 + 1#8 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION.PROVIDE MULE TAPE ROUTED
THROUGH CONDUIT FROM THE PANELBOARD TO
EVCS STUB-UP. SEE DETAIL #2 ON SHEET E4.00.
SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PROVIDE 13" X 24" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #6
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
RELOCATE EXISTING SHRUB TO NEW LOCATION.
VERIFY LOCATION WITH SITE REPRESENTATIVE.
SEE GENERAL NOTES 5 & 6 ON THIS SHEET.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #1 & #2 SHEET E4.01 FOR
TRANSFORMER GROUND ROD AND
GROUND-WELL DETAILS.
PENETRATION THROUGH WOOD FRAME WALL.
PROVIDE 24" X 24" X DEPTH AS REQUIRED
PULLBOX TO TRANSITION THROUGH WALL AND
ROUTE CONDUIT ALONG WALL. MOUNT PULLBOX
BELOW EXISTING DISCONNECT SWITCH.
ELECTRICAL EQUIPMENT CONCRETE PAD.
REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
PROVIDE 200A-3P DISCONNECT SWITCH WITH
WEATHERPROOF ENCLOSURE.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
SURFACE MOUNTED CONDUIT/S. PAINT TO
MATCH EXISTING SURFACE.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
DETAIL #8 ON SHEET E4.00 FOR MORE
INFORMATION.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND IRRIGATION IMPROVEMENTS
AFFECTED IN WORK.
PROPOSED EV CHARGERS
EVCS #
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
POWER SELECT
(FLA)
VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL 80 208V-1PH N/A FLEET
2 PEDESTAL SINGLE 80 208V-1PH N/A FLEET
NOTES:
· (1) DUAL PORT AND (1) SINGLE PORT EVCS SHALL SERVE (3) FLEET PARKING STALLS
· (FLA) STANDS FOR FULL LOAD AMPS
· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
1 2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
DUAL PORT PEDESTAL
EV CHARGING STATION
(19,200VA PER PORT)
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #4
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #7 ON THIS SHEET.
SCALE
SINGLE PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 2
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
SINGLE PORT PEDESTAL
EV CHARGING STATION
(19,200VA PER PORT)
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #4
ON THIS SHEET.
6"
MIN.
STEEL COUPLING WITH
THREADED PLUG
FINISH GRADE
PVC CONDUIT
TRANSITION
COUPLING
CONTINUOUS RIGID GALVANIZED
STEEL CONDUIT WRAPPED AROUND
WITH 40 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
CONTINUOUS RIGID
GALVANIZED STEEL
CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 5
N.T.S.
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 4
N.T.S.
1'-6"
MIN.
FINISH GRADE
PVC CONDUIT
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
PVC COUPLING WITH
THREADED PLUG
PVC CONDUIT
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 7
N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL 3
N.T.S.
3" CLEAN SAND
BEDDING
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NEW ASPHALT PAVEMENT EXISTING ASPHALT PAVEMENT
EXISTING BASE
CRUSHED AGGREGATE BASE
RECOMPACTED TO 95%
RLATIVE COMPACTION
ELECTRICAL
WARNING TAPE
NATIVE BACKFILL
95% COMPACTION
12"
GRADE LEVEL
24"
MIN.
ELECTRICAL
WARNING TAPE
3" CLEAN SAND
BEDDING
NOTE:
PER CEC 300.5 NO CONCRETE CASING IS
REQUIRED IF SCHEDULE 80 PVC IS USED
2'-0" BELOW GRADE LEVEL. SEE POWER
PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NATIVE BACKFILL
90% COMPACTION
ASPHALT PAVEMENT
APPLICATION
NATIVE SOIL APPLICATION
CONDUIT/S PER PLAN
CONDUIT/S PER PLAN
1'-0"
MIN.
2'-0"
MIN.
MATCH
EXISTING +1"
MATCH
EXISTING
+1"
SCALE
UNDERGROUND PULLBOX DETAIL 6
N.T.S.
GRAVEL
BASE
ELECTRICAL
CONDUIT(S)
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
COMPACTED
BACKFILL
(TYPICAL)
ELECTRICAL
CONDUIT(S)
(IN/OUT)
2'-0"
MIN.
NOTE:
REFER TO SHEET NOTES ON POWER
PLANS FOR SPECIFIC PULLBOX
DIMENSIONS.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #7 ON THIS SHEET.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
3. PROVIDE FISH TAPE FROM EVCS STUB-UP BACK TO THE NEW PANELBOARD.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. SINGLE PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
3. PROVIDE FISH TAPE FROM EVCS STUB-UP BACK TO THE NEW PANELBOARD.
SCALE
BOLLARD DETAIL 8
N.T.S.
4'-0"
CONCRETE CAP
FIELD PRIME STEEL BOLLARDS
WITH 2 COATS OF ZINC-RICH
PRIMER. PAINT BOLLARDS WITH 2
COATS OF INDUSTRIAL YELLOW
ENAMEL.
FOOTING AND STEEL
PIPE PER STRUCTURAL
DRAWINGS.
FINISH GRADE
1 1/2" PVC CONDUIT
4#2 & 1#6 GRD.
WITH MULE TAPE BACK
TO PANELBOARD
1" PVC CONDUIT
2#2 & 1#8 GRD.
WITH MULE TAPE BACK
TO PANELBOARD
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
GROUND-WELL DETAIL 2
N.T.S.
G R O U N D
COVER SHALL HAVE CAST
LETTERING "GROUND"
1 CUBIC FT.
MIN. 3/4" GRAVEL
3/4"Ø X 10'-0"L
COPPER GROUND
ROD
PRE-CAST CONCRETE
BOX 10"W x 17"L x 12"D
OPEN BOTTOM
#2 GROUNDING WIRE
CONNECTED TO
EQUIPMENT
GROUND ROD CLAMP
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
SCALE
GROUND RING DETAIL 1
N.T.S.
#2 BARE COPPER GROUND
WIRE FOR GROUND RING.
3/4"Ø X 10'-0"L
COPPER GROUND ROD
WELD TO COPPER
GROUND ROD BY
EXOTHERMIC PROCESS
SCALE
CONNECTION TO GROUND ROD DETAIL 3
N.T.S.
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
G R O U N D
G R O U N D
GROUND-WELL
(SEE DETAIL #8 ON THIS SHEET)
PAD MOUNTED
TRANSFORMER
GROUND-WELL
(SEE DETAIL #8 ON THIS SHEET)
REFER TO STRUCTURAL
DRAWINGS FOR EQUIPMENT
PAD INFORMATION
#2 BARE COPPER GROUND WIRE
FOR GROUND RING.
(TYP.)
PROVIDE EXOTHERMIC WELDING
FOR CONNECTIONS BELOW GRADE.
(TYP.)
NOTE:
1. THE GROUND RING SHALL BE INSTALLED NOT LESS THAN 30" BELOW FINISH SURFACE PER NEC 250.53.
EQUIPMENT GROUNDING
CONNECTION
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
ELECTRICAL
DETAILS
E4.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
SINGLE LINE DIAGRAM 1
N.T.S.
LEGEND:
EXISTING
NEW
SHEET NOTES:
PROVIDE NEW CIRCUIT BREAKER. SIZE AS
SHOWN. MATCH TO EXISTING MAKE, MODEL AND
AIC RATING.
100A 3P
400A BUS
40A 3P
30A 2P
(E)
(E F E E D
E R
(E) A.C.
CONDENSER
(E F E E D
E R
M
400A 3P
MAIN SWITCHBOARD "MSB"
400A, 240D/120V, 3Ø, 4W
NEMA-1, 42,000 AIC, HIGH LEG SYSTEM
(E) A.C.
CONDENSER
(E F E E D
E R
200A 3P
INCOMING SERVICE FROM
SOUTHERN CALIFORNIA
EDISON
200A 3P
(E)
PANEL
'A'
(E)
EQUIP.
STORAGE
BLDG.
(E F E E D
E R
225A 3P
(E)
MODULAR
BLDG.
(E
F E E D
E R
300A 3P
200A-3P
WP
IF=22,433A
PANEL
'EV'
TRANSFORMER 'TEV'
75KVA, 240V-208Y/120V
3Ø, 4W
%Z = BELOW 5.5%
NEMA-3R
(SQUARE-D POWER-STYLE SWITCHBOARD)
IF=3,306A
IF=2,807A
1"C-1#2 TO
GROUND ROD
3"C - 3#3/0
& 1#6 GRD.
L: ±37'-0" %V.D.: 0.36%
3"C - 4#3/0
& 1#2 GRD.
L: ±83'-0" %V.D.: 1.06%
(E) TEMPORARY GENERATOR
TRANSFER SWITCH
(E) FEEDER(E) TEMPORARY
GENERATOR
RECEPTACLE
(E) FEEDER
PULLBOX
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
124-01-02.50
10/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalEB6/12/2024 1
100% CD SubmittalEB10/25/20242
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
E V
F L E E T
O N
L Y
E V
F L E E T
O N
L Y
E V
F L E E T
O N
L Y
T
PB
J
TITLE SHEET
C1
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
AM
OM/FG
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
24-2560
10/21/2024
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalFG6/12/2024 1
100% CD SubmittalFG10/21/20242
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
T
PB
J
EV
FLEET
ONLY
SITE PLAN
C2
R
CALL 811 BEFORE YOU DIG.
CONSTRUCTION NOTES
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
N
M a in
S tr e e t, T e m p le to n C A
AM
OM/FG
As Noted
C a lt ra n s D is tr ic t
T e m p le to n M a in te n a n c e S ta ti o n
E V S E I n s ta lla ti o n
24-2560
10/21/2024
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4152-C
95% CD SubmittalFG6/12/2024 1
100% CD SubmittalFG10/21/20242
AUTHORIZED
ELECTRIC
FLEET
VEHICLES
ONLY
2"
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4152
DOT D5 - Electric Vehicle Supply Equipment - Templeton MS
1. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE AND LATEST REVISIONS
REFERRED TO HERE AS "THE CODE", AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL
SAFETY, AND THOSE CODES & STANDARDS LISTED IN THESE NOTES AND SPECIFICATIONS.
2. SEISMIC ANALYSIS PER CHAPTER 16 OF THE CODE UTILIZING THE FOLLOWING PROCEDURE:
- THE EQUIVALENT LATERAL FORCE ANALYSIS
RISK CATEGORY = II
IMPORTANCE FACTOR = 1.0
SS = 1.093
S1 = 0.401
SITE CLASS = D (DEFAULT)
SDS = 0.874
GROUND MOTION USED:
- CODE DESIGN RESPONSE SPECTRUM
SEISMIC DESIGN LOAD (NON-STRUCTURAL COMPONENT)
FP (HORIZONTAL FORCE)
FV (VERTICAL FORCE)
EV = 0.2 SDS WP
WP = COMPONENT WEIGHT
h = AVERAGE ROOF HEIGHT, FEET z = HEIGHT OF COMPONENT ATTACHMENT POINT, FEET
SDS = DESIGN SPECTRAL ACCELERATION
IP = COMPONENT IMPORTANCE FACTOR, PER ASCE 7-16 SECTION 13.1.3 = 1.0
ap = AMPLIFICATION FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1
RP = COMPONENT RESPONSE FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1
3. WIND ANALYSIS PER CHAPTER 16 OF THE CODE
RISK CATEGORY = II
BASIC WIND SPEED = 92 mph
WIND EXPOSURE = C
DESIGN CRITERIA
Fp = 0.4ap SDS
Rp
Ip{ } { 1 + 2 Wp z h } Fp MIN = 0.3 SDS IP WP
Fp MAX = 1.6 SDS IP WP
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. THE ARCHITECT
SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE
ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE
REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO
EXPENSE TO THE OWNER OR ARCHITECT.
3. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
4. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.
SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS.
SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.
SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN.
FLOOR AND ROOF FINISHES.
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
5. SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC., EXCEPT AS SHOWN OR
NOTED. ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES.
SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR MOTOR MOUNTS.
6. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE.
THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL
INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE
INSPECTION OF THE ABOVE ITEMS.
7. OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE SLABS, DECKS, WALLS, UNLESS SPECIALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER WHEN
DRAWINGS BY OTHERS SHOW OPENINGS, POCKETS, ETC., LARGER THAN 6" NOT SHOWN ON THE
STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED IN STRUCTURAL MEMBERS. FOR ANY FURTHER
RESTRICTIONS ON OPENINGS IN STRUCTURAL ELEMENTS, SEE APPLICABLE SECTIONS BELOW.
8. ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE OF THE LATEST REVISION.
9. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY
SUCH STRUCTURES ARE FOUND, STRUCTURAL ENGINEER SHALL BE NOTIFIED IMMEDIATELY.
10. CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR FLOOR. LOAD SHALL
NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE ADEQUATE SHORING AND/OR
BRACING WHERE STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH.
11. THE LOCATION OF EXISTING UNDERGROUND UTILITIES SHOWN ON THE DRAWINGS, IF ANY, ARE APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING UNDERGROUND UTILITIES AND COORDINATING WITH THE REQUIREMENTS OF THIS PROJECT. THE CONTRACTOR SHALL EXERCISE
EXTREME CAUTION IN EXCAVATING AND TRENCHING ON THE SITE. THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ARCHITECT IF ANY CONDITIONS ARE DISCOVERED THAT REQUIRES FURTHER
COORDINATION.
THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE THAT OCCURS DUE TO NOT FULLY LOCATING
EXISTING UTILITIES.
12. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS BASED ON AVAILABLE KNOWLEDGE OF EXISTING STRUCTURE. CONTRACTOR SHALL VERIFY IN FIELD ALL EXISTING CONDITIONS RELATIVE TO THE SCOPE OF THIS PROJECT. WHERE ACTUAL CONDITIONS ARE NOT IN ACCORDANCE WITH THE DRAWINGS PROVIDED, THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY.
CONTRACTOR SHALL ALIGN FOR SUFFICIENT BUDGET AND SCHEDULE CONTINGENCY TO ADDRESS
EXISTING HIDDEN CONDITIONS.
13. ALL DEMOLITION SHALL BE PERFORMED IN SUCH A WAY AS NOT TO DAMAGE THE EXISTING STRUCTURAL ELEMENTS THAT ARE TO REMAIN IN THE FINISHED STRUCTURE. ANY PORTIONS OF STRUCTURE TO REMAIN THAT ARE DAMAGED DURING DEMOLITION SHALL BE REPLACED AT NO ADDITIONAL COST. EXISTING STRUCTURAL ELEMENTS SHALL BE PROTECTED TO THE FULLEST EXTENT POSSIBLE, IN ORDER TO MITIGATE DAMAGE. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF ALL EXISTING STRUCTURAL
ELEMENTS THAT ARE NECESSARY FOR THE COMPLETION OF ALL NEW WORK.
GENERAL
1. FOUNDATION DESIGN BASED ON 2022 CBC CODE MINIMUM VALUES.
2. FOOTINGS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION:
W = FOOTING WIDTH
D = FOOTING DEPTH BELOW ADJACENT GRADE
ALLOWABLE BEARING *
WALL FTGS = 1500 PSF (MAX)
ISOLATED FTGS = 1500 PSF (MAX)
PASSIVE EARTH PRESSURE **
PASSIVE EARTH PRESSURE = 100 PCF (EFP) , 1500 PSF (MAX)
FOOTINGS SHALL BEAR ON FIRM NATURAL SOILS. MINIMUM DEPTH OF FOOTINGS BELOW LOWEST
ADJACENT FINAL GRADE SHALL BE 1'-0". MINIMUM WIDTH OF FOOTING SHALL BE 1'-0".
* VALUES MAY BE INCREASED BY 1/3 FOR WIND OR SEISMIC LOAD CASES
** PASSIVE PRESSURE AND FRICTION MAY BE COMBINED WITHOUT A REDUCTION
3. CONTRACTOR TO PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM EITHER SURFACE WATER, GROUND WATER OR SEEPAGE, IF REQUIRED.
4. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION PROCEDURES INCLUDING LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES IN
ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL SAFETY ORDINANCES.
5. EXCAVATION FOR FOOTINGS SHALL BE APPROVED BY THE INSPECTOR OR SOILS ENGINEER PRIOR TO
PLACING THE CONCRETE AND REINFORCING. CONTRACTOR TO NOTIFY THE INSPECTOR WHEN
INSPECTION OF EXCAVATION IS READY. INSPECTOR TO SUBMIT LETTER OF COMPLIANCE.
6. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING WALLS BEFORE CONCRETE OR GROUT HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL STRENGTH. CONTRACTOR SHALL PROVIDE FOR
DESIGN, PERMITS, AND INSTALLATION OF SUCH BRACING.
7. FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON DRAWINGS.
SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE APPROVED BY THE INSPECTOR OR SOILS
ENGINEER, FOUNDATION ELEVATIONS WILL BE ALTERED BY CHANGE ORDER.
8. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS REPORT AND APPROVED BY THE SOILS ENGINEER. FLOODING WILL NOT BE PERMITTED. ALL FILLS USED TO SUPPORT FOUNDATIONS SHALL BE INSPECTED BY THE SOILS ENGINEER REPRESENTATIVE PER CODE SECTION 1705.6 AND TABLE 1705.6.
9. ALL ABANDONED FOOTINGS, UTILITIES, ETC., SHALL BE REMOVED UNLESS NOTED OTHERWISE. NEW
FOOTINGS MUST EXTEND INTO UNDISTURBED SOILS.
10. SLABS ON GRADE SHALL BE SUPPORTED ON NATURAL GRADE OR COMPACTED FILL AS PER THE
RECOMMENDATIONS OF THE SOILS REPORT.
FOUNDATION
1. REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 & 21 OF THE CODE, ASTM
A615, GRADE 60 UNO.
2. BARS SHALL BE CLEAN OF RUST, GREASE, OR OTHER MATERIALS LIKELY TO IMPAIR BOND. ALL
REINFORCING BAR BENDS SHALL BE MADE COLD.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. WWF SHALL BE SUPPORTED ON APPROVED
CHAIRS.
4. REINFORCING BAR SPLICES SHALL BE MADE AS INDICATED ON THE DRAWINGS. LAP ALL HORIZONTAL BARS AT CORNERS AND INTERSECTIONS. STAGGER ALL SPLICES UNLESS NOTED OTHERWISE ON PLANS.
5. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL IN-PLACE
INSPECTION IS MADE.
6. WHERE WELDING OF REINFORCING IS APPROVED BY THE STRUCTURAL ENGINEER, IT SHALL BE DONE BY
AWS CERTIFIED WELDERS USING FILLER MATERIAL TO MATCH MATERIAL STRENGTHS. WELDING
PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF STRUCTURAL WELDING CODE- REINFORCING STEEL", AWS-D1.4, LATEST REVISION. REINFORCING BARS TO BE WELDED SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A706.
7. BARS IN SLABS SHALL BE SECURELY SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR APPROVED METAL
CHAIRS, PRIOR TO PLACING CONCRETE.
8. REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE "A.C.I. MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", LATEST EDITION.
9. COMPLETE AND DETAILED REINFORCING PLACEMENT DRAWINGS SHALL BE PREPARED AND SUBMITTED TO THE ARCHITECT FOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO FABRICATION IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE CODES. THESE DRAWINGS SHALL BE AVAILABLE ON THE JOB
SITE PRIOR TO PLACING OF CONCRETE.
10. MILL TEST REPORTS FOR GRADE 60 BARS SHALL BE SUBMITTED PRIOR TO PLACEMENT OF CONCRETE.
11. PROVIDE INSPECTION OF CONCRETE PER SPECIAL INSPECTION NOTES SECTION. INSPECTION SHALL BE SCHEDULED SO THAT PLACEMENT OF REINFORCING STEEL, CONDUIT, SLEEVES, AND EMBEDDED ITEMS
MAY BE CORRECTED PRIOR TO PLACEMENT OF OVERLYING GRIDS OR REINFORCING STEEL.
12. ALL GRADE 60 REINFORCING STEEL SHALL BE CLEARLY MARKED TO DIFFERENTIATE THEM FROM GRADE 40
REINFORCING STEEL IF CONCURRENTLY ON SITE.
13. CONCRETE PROTECTION FOR REINFORCEMENT:
No. 6 THROUGH No. 18 BARS
1-1/2
NOT EXPOSED
TO WEATHER
OR IN CONTACT
WITH GROUND
SLABS, JOISTS
AND WALLS
BEAMS,
COLUMNS,
PEDESTALS, AND
TENSION TIES
PRIMARY
REINFORCEMENT,
STIRRUPS, TIES,
SPIRALS, AND
HOOPS
ALL No. 5 BAR, W31 OR
D31 WIRE, AND
SMALLER
1-1/2 No. 14 AND No. 18
BARS
3/4 No. 11 BAR AND
SMALLER
CONCRETE
EXPOSURE
MEMBER REINFORCEMENT
CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS
MIN COVER,
IN.
CAST AGAINST AND
PERMANENTLY IN
CONTACT WITH
GROUND
ALL ALL 3
EXPOSED TO
WEATHER OR IN
CONTACT WITH
GROUND
1-1/2
REINFORCING STEEL (FOR CONCRETE AND MASONRY)
1. ALL CONCRETE CONSTRUCTION SHALL CONFORM WITH CHAPTER 19 OF THE CODE AND WITH THE
PROVISIONS OF ACI 318, LATEST EDITION.
2. REINFORCED CONCRETE IS DESIGNED BY THE "ULTIMATE STRENGTH DESIGN METHOD".
3. CONCRETE MIXES SHALL BE DESIGNED BY THE APPROVED TESTING LABORATORY AND APPROVED BY THE STRUCTURAL ENGINEER. THE COMPRESSIVE STRENGTH OF THE CONCRETE SHALL BE PROPORTIONED
BASED ON CHAPTER 19 OF THE CODE.
4. SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES:
5. AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS OF ASTM C33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF THE
STRUCTURAL ENGINEER.
6. AGGREGATE FOR LIGHT WEIGHT (115 PCF) CONCRETE SHALL BE EXPANDED SHALE CONFORMING TO ASTM C330 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF THE
STRUCTURAL ENGINEER.
7. CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C94.
8. PLACEMENT OF CONCRETE SHALL CONFORM TO THE CODE AND PROJECT SPECIFICATIONS. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE ALL CONCRETE SURFACES AGAINST WHICH NEW CONCRETE IS TO BE
PLACED.
9. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL SECURED IN
POSITION PRIOR TO PLACING CONCRETE.
10. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE IS NOT PERMITTED. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS. SEE THESE DRAWINGS FOR ADDITIONAL RESTRICTIONS ON THE PLACEMENT OF OPENINGS IN SLABS AND WALLS.
11. PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED BY STRUCTURAL ENGINEER. PIPES SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS, SPACE EMBEDDED PIPES AND SLEEVES AT A MINIMUM OF 3 DIAMETERS ON CENTER.
12. CONCRETE FILL OVER METAL DECK SHALL BE SCREEDED TO A CONSTANT THICKNESS AS SPECIFIED IN THE
DECKING SCHEDULE.
13. ALL CONCRETE MIX DESIGNS SHALL BE SIGNED AND SEALED BY A CIVIL ENGINEER REGISTERED IN THE
STATE IN WHICH THE PROJECT IS LOCATED.
EXPOSURE
CLASSES
LOCATION
F S W C
MIN
STRENGTH
f'c (PSI)
MAX WATER/
CEMENT
RATIO
CEMENT
TYPE
(ASTM C150)
DENSITY
ALL CONCRETE
FOOTINGS
F0 S0 W0 C1 4000 PSI 0.50 II/V 150 PCF
CONCRETE
1. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BY AN APPROVED AND LICENSED FABRICATOR IN ACCORDANCE WITH THE AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (LATEST
EDITION), AND WITH CHAPTERS 17 AND 22 OF THE CODE.
2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED BELOW (UNO):
WF & WT SHAPES A992
ANGLES, CHANNELS, PLATES, BARS,
CONNECTION PLATES, AND MISC A36
PIPE SECTIONS A53, GRADE B
HSS SECTIONS A500, GRADE C
BOLTS F3125, GRADE A325
TWIST-OFF TYPE BOLTS F3125, GRADE F1852
BOLTS IN CONCRETE F1554 GR 36 OR
F1554 GR 55 S1 (WELDABLE)
3. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STEEL TO THE ARCHITECT FOR ARCHITECT'S AND STRUCTURAL ENGINEER'S REVIEW AND APPROVAL BEFORE FABRICATION.
4. BOLT HOLES USED IN STEEL SHALL BE 1/16" LARGER IN DIAMETER THAN NOMINAL SIZE OF BOLT USED, EXCEPT AS NOTED.
5. ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, MASONRY OR SPRAY ON
FIREPROOFING, OR ARE ENCASED BY BUILDING FINISH, SHALL BE LEFT UNPAINTED.
6. ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING FILLER METALS TO MATCH MATERIAL STRENGTH (UNO). ALL WELDS SHALL BE IN CONFORMITY WITH THE PROJECT SPECIFICATIONS AND THE CODE FOR WELDING IN BUILDING CONSTRUCTION (AWS D1.1 LATEST REVISION) OF THE AMERICAN WELDING SOCIETY. SEE SPECIAL INSPECTIONS SECTION FOR WELDING INSPECTION REQUIREMENTS. USE
OF E70T-4 WIRE IS NOT PERMITTED.
7. WHERE FABRICATION OF STRUCTURAL, LOAD-BEARING OR LATERAL LOAD-RESISTING MEMBERS OR ASSEMBLIES IS BEING…