Plans 3-6-26 - FLEET WASH (S&S SET).pdf
PDF 14 MB Posted
- Attached to
- Fleet Wash at the OC DPW
- Solicitation number
- 2138372
- Issued by
- Orange County, New York
About this file
This is a Request for Bids (RFB-OC085-26) issued by the County of Orange, New York for the construction of a Fleet Wash facility at the Orange County Department of Public Works located at 2455 Route 17M, Goshen, New York 10924. The project involves the design and construction of a new fleet wash building with associated site work, including civil infrastructure, foundation systems, structural framing, masonry walls, roofing, and interior finishes. The facility will include a primary wash bay, utility rooms, electrical and mechanical spaces, and a mezzanine-level mechanical platform. Bids are due on Wednesday, September 16, 2026 at 3:00 P.M. EST, with questions due by September 2, 2026 at 3:00 P.M. sent to generalservices@orangecountygov.com. Bid documents are available beginning Wednesday, August 19, 2026 through the Department of General Services office (9:00 A.M. to 4:45 P.M., Monday through Friday) and via https://www.bidnetdirect.com/newyork/county-of-orange. The project encompasses approximately 2,350 square feet of gross building area with an additional 400 square feet of equipment platform space.
Awarded contractors shall be required to provide Performance and Payment Bonds each equal to 100% of the contract amount, along with comprehensive insurance coverage naming the County and Architect-Engineer as additional insureds. Prior to final payment, contractors must provide a one-year Maintenance Bond against defects in workmanship or materials equal to 10% of the contract price at substantial completion. The project documents indicate that no business enterprises have been awarded an identical or substantially similar procurement contract within the past five years, indicating this is a new undertaking for the County. The contract documents specify compliance with the 2020 Building Code of New York State, New York State Energy Conservation Code, OSHA, ADA, and NFPA standards. Prevailing wage requirements and additional bidding requirements are included in the Instructions to Bidders section of the complete contract documentation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB-OC085-26 Fleet Wash at the Orange COunty DPW FINAL.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMB DATE ISSUED FOR
FLEET WASH AT THE ORANGE COUNTY
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
E T
W
A S
H
O
R A
N G
E
C
O U
N T
Y T d w g
L a y o u t
T
D a t e
M o n
M a r
M
N a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
T-1
LOCATION MAP SITE LOCATION
DEPARTMENT OF PUBLIC WORKS FACILITY
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
C
U s e r s s r b
A p p
D a t a L o c a l T e m p A c P u b l i s h
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-000
SITE - CIVIL GENERAL NOTES:DEMOLITION NOTES: E&S NOTES:
C
B
G
I
N
V
EXISTING
ADMINISTRATION
BUILDING
EXISTING
MAINTENANCE
GARAGE
FUEL
STORAGE
TANKS
B
L
A
C
K
T
O
P
B
L
A
C
K
T
O
P
DEPRESSED CONTAINMENT BASIN
FOR FUEL DELIVERY TRUCKS
C
B
I
N
V
C
B
I
N
V
C
B
I
N
V
O
U
T
L
E
T
I
N
V
C
B
I
N
V
S
E
R
V
I
R
O
A
D
DRIVEWAY
O
U
T
L
E
T
I
N
V
P O
LIC
E
D R
IV
E
H A
T F
I E
D
N E
C
H
A
I
K
F
N
C
E
R
E
M
A
I
S
I L
R
O
N
C
E
N
S
S
W
NO
RT
H
LANDS N/F
VILLAGE OF GOSHEN
TM.# 118-1-2.2
L. 14773, P. 355
LANDS N/F
KENNETH SULLIVAN
TM.# 13-1-73
L. 12602, P. 563
POLICE DRIVE
C
O
N
H
Y
M
O
U
N
D
C
O
N
Y
M
O
U
N
D
C
B
I
N
V
C
B
I
N
V
I
N
V
S
M
H
R
I
I
N
V
S
M
H
R
I
I
N
V
S
'1
W
O
U
T
L
V
S
I
L
FLEET WASH AT THE ORANGE COUNTY
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
S
H
O
R A
N G
E
C
O U
N T
Y C
I V
I L
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-001
CIVIL: EXISTING CONDITIONS PLAN
I
N
V
EXISTING
ADMINISTRATION
BUILDING
EXISTING
MAINTENANCE
GARAGE
FUEL
STORAGE
TANKS
B
L
A
C
K
T
O
P
B
L
A
C
K
T
O
P
DEPRESSED CONTAINMENT BASIN
FOR FUEL DELIVERY TRUCKS
C
B
I
N
V
C
B
I
N
V
C
B
I
N
V
O
U
T
L
E
T
I
N
V
C
B
I
N
V
S
E
R
V
I
A
D
DRIVEWAY
O
U
T
L
E
T
I
N
V
P O
LIC
E
D R
IV
E
H A
T F
I E
N E
C
H
A
N
C
E
R
E
M
A
I
I L
R
O
N
C
E
N
S
S
W
NO
RT
H
LANDS N/F
VILLAGE OF GOSHEN
TM.# 118-1-2.2
L. 14773, P. 355
LANDS N/F
KENNETH SULLIVAN
TM.# 13-1-73
L. 12602, P. 563
POLICE DRIVE
C
O
N
Y
M
O
U
N
D
C
O
N
Y
M
O
U
N
D
C
B
I
N
V
C
B
I
N
V
I
N
V
S
M
H
R
I
I
N
V
S
M
H
R
I
I
N
V
S
'1
W
O
U
T
L
V
S
I
L
FLEET WASH AT THE ORANGE COUNTY
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
S
H
O
R A
N G
E
C
O U
N T
Y C
I V
I L
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-002
CIVIL: EROSION & SEDIMENT CONTROL PLAN
I
N
V
EXISTING
ADMINISTRATION
BUILDING
EXISTING
MAINTENANCE
GARAGE
FUEL
STORAGE
TANKS
B
L
A
C
K
T
O
P
B
L
A
C
K
T
O
P
DEPRESSED CONTAINMENT BASIN
FOR FUEL DELIVERY TRUCKS
C
B
I
N
V
C
B
I
N
V
C
B
I
N
V
O
U
T
L
E
T
I
N
V
C
B
I
N
V
S
E
R
V
I
A
D
DRIVEWAY
O
U
T
L
E
T
I
N
V
P O
LIC
E
D R
IV
E
H A
T F
I E
N E
C
H
A
N
C
E
R
E
M
A
I
I L
R
O
N
C
E
N
S
S
W
NO
RT
H
LANDS N/F
VILLAGE OF GOSHEN
TM.# 118-1-2.2
L. 14773, P. 355
LANDS N/F
KENNETH SULLIVAN
TM.# 13-1-73
L. 12602, P. 563
POLICE DRIVE
C
O
N
Y
M
O
U
N
D
C
O
N
Y
M
O
U
N
D
C
B
I
N
V
C
B
I
N
V
I
N
V
S
M
H
R
I
I
N
V
S
M
H
R
I
I
N
V
S
'1
W
O
U
T
L
V
S
I
L
FLEET WASH AT THE ORANGE COUNTY
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
S
H
O
R A
N G
E
C
O U
N T
Y C
I V
I L
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-101
CIVIL: SITE PLAN
NOTE:
ADD ALTERNATE #1:
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
S
H
O
R A
N G
E
C
O U
N T
Y C
I V
I L
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-901
CONCRETE PAVEMENT DETAIL
CONCRETE PAVEMENT TO ASPHALT PAVEMENT
JOINT DETAIL
HEAVY DUTY
ASPHALTIC PAVEMENT DETAIL
NOTES
CONSTRUCTION SPECIFICATIONS:
PERSPECTIVE VIEW
SECTION VIEW
SILT FENCE W/ WIRE REINFORCEMENT DETAIL
STABILIZED CONSTRUCTION DRIVEWAY ENTRANCE DETAIL
TYPICAL TRENCH - WATER MAIN DETAIL
TYPICAL TRENCH - SEWER LINE
VALVE BOX AND VALVE SLAB
NOTES:
DEPARTMENT OF PUBLIC WORKS FACILITY
ENGINEERING LLPwww.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
F i l e
N a m e
F
O
C D
P W
F
L E
S
H
O
R A
N G
E
C
O U
N T
Y C
I V
I L
C d a y o u t
C
D a t e
M o n
M a r a m e s r b
Call811 New York before you dig
Dig Safely.
HYMAN
HAYES
ASSOCIATES
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
C-902
TYPICAL COMMON TRENCH CONFIGURATION
4" CLEANOUT DETAIL
SANITARY SEWER CONNECTION
WATER SERVICE CONNECTION
GRIT/OIL INTERCEPTOR
MATERIAL PROPERTIES:
MATERIALS BELOW ARE A DESIGN BASIS. SUBSTITUTIONS ARE PERMITTED ONLY WITH APPROVAL.
EARTHWORK MATERIAL PROPERTIES:
1. STRUCTURAL FILL: RUN-OF-BANK WELL DRAINING SAND AND GRAVEL OR CRUSHED STONE.
2. INTEIOR SLAB SUBBASE MATERIAL: CRUSHED STONE, ASTM C33 #56 OR #57 STONE (3/8" TO 3/4" SIZE).
3. EXTERIOR SLAB SUBBASE MATERIAL: NYSDOT ITEM 733-04 ITEM 4
4. FILTER OR SEPARATION FABRIC - DESIGN BASIS: MIRAFI 160N FABRIC
5. STABILIZATION FABRIC - DESIGN BASIS: MIRAFI HP270 FABRIC
6. PIPE BEDDING: WELL GRADED SAND OR SAND AND GRAVEL
7. FOUNDATION DRAIN PIPING: 4" DIA CORRUGATED PERFORATED HDPE PIPING, ADS SINGLE WALL.
8. COMPACTION: 95% MODIFIED PROCTOR UNO.
CONCRETE MATERIAL PROPERTIES:
1. FOOTINGS AND WALLS:
• 1-1/2" MAX AGGREGATE
• 4,000 psi AT 28 DAYS
• 6% AIR ENTRAINMENT.
2. SLABS:
• 3/4" MAX AGGREGATE
• 4,500 psi AT 28 DAYS
• 5-1/2 % AIR ENTRAINMENT (± 1.5 %) FOR EXTERIOR SLABS.
• NO AIR ENTRAINMENT ADMIXTURE FOR INTERIOR SLABS.
• INTERIOR SLABS TO RECEIVED MOISTURE VAPOR REDUCING ADMIXTURE
3. CONCRETE SLUMP:
• ALL CONCRETE SHALL CONTAIN A WATER REDUCER
• MAX SLUMP 5" ± 1" WITH A MID-RANGE WATER REDUCER OR A LOW DOSE OF HIGH-RANGE WATER REDUCER OR SUPER PLASTICIZER
• MAX SLUMP 7" ± 1" WITH FULL DOSE OF HIGH-RANGE WATER REDUCER OR SUPER PLASTICIZER
4. REBAR: ASTM A615, GRADE 60, MINIMUM LAP SPICE UNO IS 40 BAR DIAMETERS.
5. WELDED WIRE REINFORCING: ASTM A1064, 6x6 WWR - W4.0xW4.0
6. VAPOR BARRIER: 15 MIL EXTRUDED POLYOLEFIN, STEGO WRAP 15 WITH SEAM TAPE AND MASTIC. DO NOT USE POLYETHYLENE OF ANY THICKNESS AS A VAPOR
BARRIER.
7. SEALANT AT CONCRETE JOINTS: SIKAFLEX 1A.
MASONRY MATERIAL PROPERTIES:
1. CONCRETE MASONRY UNITS (CMU): ASTM C90 TYPE 1, 10x16 NOMINAL TWO CELL UNITS. PROVIDE SPECIAL SHAPES AT CORNERS, JAMBS, ETC. BOND BEAM
SHALL BE SLOTTED STRETCHER BLOCK WITH SLOTTED WEBS TO ALLOW FOR CONTINUOUS REBAR IN HORIZONTAL AND VERTICAL DIRECTIONS. HEADER BLOCK
SHALL BE U-SHAPED BOND BEAM BLOCK WITH SOLID BOTTOMS.
2. MORTAR TYPES: TYPE S (PROPORTIONS BY VOLUME: PORTLAND CEMENT - HYDRATED LIME - SAND).
3. TYPE S MORTAR PROPORTIONS 2-1-9.
4. PORTLAND CEMENT: ASTM C150 GRAY UNO. USE WHITE PORTLAND CEMENT WHEN PIGMENTED MORTAR IS SPECIFIED BY THE ARCHITECT.
5. HYDRATED LIME: ASTM C207 TYPE S UNO.
6. ASTM 476 COURSE SAND GROUT FOR MASONRY CORES, 2,500 PSI
7. HORIZONTAL JOINT REINFORCEMENT: BRICK AND CMU: HOHMANN AND BARNARD 220, LADDER TYPE, STANDARD No. 9 WIRE (W1.7), HOT DIP GALVANIZED, SIZED
FOR FULL WIDTH OF WALL LESS 1-1/2".
8. REBAR: SAME AS CONCRETE REQUIREMENTS.
FRAMING LUMBER MATERIAL PROPERTIES:
SPRUCE PINE FIR (2x8s AND LARGER): SPF KD No. 1/No. 2
Fb 875 Ft 450
Fv 135 Fc, Perp 425
Fc, Prll 1,150 E 1,400
1. SUBSTITUTIONS MUST PROVIDE EQUIVALENT SECTION PROPERTIES TO THOSE SPECIFIED ON THE PLANS.
STEEL MATERIAL PROPERTIES:
1. WIDE FLANGE BEAMS: ASTM A992, 50 ksi.
2. OTHER ROLLED SHAPES: ASTM A36, 36 ksi.
3. HSS (SQUARE AND RECTANGULAR TUBE SECTIONS): ASTM A500 GRADE B.
4. PIPE: ASTM A53 GRADE B.
5. BOLTS CONNECTING STEEL MEMBERS, ASTM A325, OR ASTM F1852
6. WELDING: ALL SHOP AND FIELD WELDING PER CURRENT AWS CODE AND AISC, CONDUCTED BY PERSONNEL WITH CURRENT CERTIFICATIONS FOR ALL TYPES AND
POSITIONS OF WELDS PERFORMED.
7. WELDING ELECTRODES: E70XX UNO.
8. NON SHRINK GROUT: (UNDER BASEPLATES) SIKAGROUT 212.
FASTENER AND ADHESIVE MATERIAL PROPERTIES:
1. WOOD FRAMING NAILS: 3-1/2" x 0.131" (16d NOMINAL) PNEUMATICALLY DRIVEN NAILS, (SMOOTH-COATED, RING SHANK, OR SPIRAL SHANKS)
2. EXTERIOR WOOD SHEATHING NAILS: SEE WOOD PANEL FASTENING DETAIL
3. WOOD FLOOR DECK SCREWS: SEE WOOD PANEL FASTENING DETAIL
4. METAL HANGER/CONNECTOR FASTENERS FOR FACE MOUNT TO SINGLE 2x PLY HEADERS OR LEDGERS SHALL BE SIMPSON SD9-112 SCREWS UNO. USE ONLY
WHEN A SINGLE 2x LEDGER IS CALLED FOR. FOR ALL OTHER APPLICATIONS USE 3" x 0.131" COMMON FACE NAILS AT DOUBLE 2x LEDGERS OR MULTI-PLY BEAMS.
5. SELF-DRILLING WOOD SCREWS (SDWS): FASTEN-MASTER HEADLOK OR SIMPSON SDS SCREWS, UNO.
6. MACHINE BOLTS, NUTS, WASHERS: ASTM A307
7. EXPANSION STUD ANCHORS: HILTI KWIK-BOLT, HOT-DIP GALVANIZED UNO
8. STUD ANCHORS (THREADED ROD) IN CONCRETE: HILTI HIT-HY 200 ADHESIVE.
9. STUD ANCHORS (THREADED ROD) IN WET APPLICATIONS: HILTI HIT-RE 500 MAX.
10. STUD ANCHORS (THREADED ROD) IN COLD WEATHER APPLICATIONS: HILTI HIT-ICE ADHESIVE.
11. STUD ANCHORS (THREADED ROD) IN HOLLOW AND SOLID MASONRY: HILTI HIT-HY 270 ADHESIVE.
12. CONCRETE SCREWS: TAPCON.
13. CONSTRUCTION ADHESIVE FOR WOOD PANELS: POLYURETHANE ADHESIVE MEETING REQUIREMENTS OF ASTM D-3498 AND APA-AFG-01, TITEBOND GREEN-
CHOICE OR LIQUID NAILS LN-902.
PRE-ENGINEERED WOOD TRUSSES:
1. DESIGN AND MANUFACTURE TRUSSES IN A SHOP SPECIALIZING IN THIS WORK, AND UNDER THE DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER LICENSED
IN NYS.
2. DESIGN AND MANUFACTURE TRUSSES IN CONFORMANCE WITH NDS, AFPA, NDSMPCWTC, TPI, AND BC-NYS.
3. SUBMIT TRUSS DESIGNS INCLUDING SHOP DRAWINGS FOR ALL TRUSSES CLEARLY SHOWING THE TRUSS FRAMING CONFIGURATION AS SCHEMATICALLY
INDICATED ON THE CONTRACT DRAWINGS. THE SHOP DRAWING PACKAGE SHALL DETAIL TRUSS ANCHORAGE, BLOCKING, CURBING, AND MISC FRAMING. SHOP
DRAWINGS AND CALCULATIONS SHALL BEAR THE STAMP AND SIGNATURE OF THE ENGINEER RESPONSIBLE FOR THE DESIGN.
4. RETAIN A LICENSED PROFESSIONAL ENGINEER FOR THE DESIGN OF ALL PORTIONS AND COMPONENTS OF THE ROOF FRAMING EXCLUDED BY THE TRUSS
SUPPLIER. A COMPLETE DESIGN PACKAGE SHALL BE SUBMITTED FOR REVIEW AND COMMENT BEFORE TRUSS FABRICATION BEGINS.
5. CONNECTOR PLATES SHALL MEET OR EXCEED ASTM A653.
6. MAXIMUM TRUSS DEFLECTION RATIOS SHALL BE: SPAN /480 (LIVE) AND SPAN / 360 (TOTAL).
7. TRUSSES SHALL BE MANUFACTURED, HANDLED, AND ERECTED TO IN A MANNER TO PRECLUDE EXCESSIVE LATERAL BENDING STRESSES.
8. ANCHOR TRUSSES TO TOP WALL PLATES, GIRDER TRUSSES, AND OTHER BEARING SURFACES ONLY WITH APPROVED CONNECTION. THE MINIMUM DESIGN
UPLIFT FORCE TO BE RESISTED AT BEARING POINTS BY ALL TRUSSES SHALL BE 400 LBS. ALL TRUSSES SHALL BE SECURED WITH SIMPSON H1 CONNECTORS
OAE, UNLESS AN UPLIFT REACTION IN EXCESS OF 400 LBS IS REQUIRED BY THE TRUSS DESIGN. IN THIS CASE THE ENGINEER OF RECORD SHALL SPECIFY AN
ALTERNATE STRONGER UPLIFT CONNECTOR.
9. FIELD CUTTING AND/OR MODIFICATION OF TRUSSES IS STRICTLY PROHIBITED.
10. REPLACE DAMAGED TRUSSES WITH NEW TRUSSES. REPAIR DAMAGED TRUSSES ONLY WITH THE WRITTEN APPROVAL OF THE ENGINEER OF RECORD (EOR).
WHEN APPROVED, THE TRUSS MANUFACTURER SHALL PREPARE REPAIR DETAILS UNDER THE DIRECTION OF THE PROFESSIONAL ENGINEER RESPONSIBLE FOR
THE ORIGINAL TRUSS DESIGN. THE ENGINEER SHALL SEAL ALL REPAIR DETAILS AND SUBMIT THEM FOR REVIEW AND COMMENT BY THE EOR BEFORE ANY
REPAIRS ARE UNDERTAKEN.
11. ERECT TRUSSES IN ACCORDANCE WITH HIB-91, TPI.
12. TEMPORARY BRACING IS THE FULL RESPONSIBILITY OF THE CONTRACTOR.
13. PROVIDE MINIMUM PERMANENT TRUSS BRACING CONSISTING OF THE FOLLOWING:
1. CONTINUOUS HORIZONTAL LONGITUDINAL BRACING ALONG BOTTOM CHORDS AT 10 FT MAX O.C.
2. W-BRACING ASSEMBLIES AT BOTTOM CHORDS LATERALLY ALONG LENGTH OF TRUSSES; W-DIAGONALS EXTENDING LONGITUDINALLY OVER MIN. 4
TRUSSES, W-BRACING ASSEMBLIES SPACED AT 20 FT MAX O.C.
3. DIAGONAL GABLE END BRACING AT 10 FT MAX O.C. OVER THE WIDTH OF BUILDING.
4. CONTINUOUS HORIZONTAL LONGITUDINAL BRACING ALONG TRUSS WEBS IDENTIFIED ON TRUSS SHOP DRAWINGS AS REQUIRING COMPRESSION BRACING.
SOME TRUSS WEBS MAY REQUIRE MULTIPLE ROWS OF BRACING AS REQUIRED BY TRUSS DESIGN.
5. CROSS BRACING ASSEMBLIES ALONG TRUSS WEB HORIZONTAL BRIDGING IN 13.4 ABOVE, AT 20 FT MAX OC. EXTEND CROSS BRACING FROM BOTTOM
CHORDS TO TOP CHORDS ACROSS MINIMUM OF TWO TRUSS BAYS.
CONSTRUCTION NOTES:
GENERAL:
1. DESIGN IS PER THE 2020 BUILDING CODE OF NEW YORK STATE (BCNYS).
2. THESE STRUCTURAL DRAWINGS ARE NOT INTENDED AS STAND ALONE DOCUMENTS. REFER TO FULL
CONSTRUCTION DOCUMENT PACKAGE FOR COMPLETE PROJECT INFORMATION AND DETAILS.
3. VERIFY ALL DIMENSIONS IN THE FIELD AS WORK PROGRESSES AND REPORT ANY DISCREPANCIES BETWEEN
EXISTING WORK AND CONTRACT DOCUMENTS TO ARCHITECT AND ENGINEER FOR CLARIFICATION BEFORE
PROCEEDING WITH WORK.
4. DO NOT SCALE DRAWINGS.
5. ALL DETAILS AND NOTES ARE TYPICAL UNO.
6. PROVIDE ALL TEMPORARY SHORING AS REQUIRED BY THE MEANS AND METHODS UNDERTAKEN.
7. RETAIN A LICENSED PROFESSIONAL ENGINEER FOR THE DESIGN OF ALL TEMPORARY SHORING AND SHEETING
FOR REVIEW BY THE ENGINEER OF RECORD (EOR).
8. PROVIDE ALL TEMPORARY BRACING UNTIL ALL REQUIRED STRUCTURAL SYSTEMS ARE IN PLACE.
9. COMPONENTS NECESSARY FOR CONSTRUCTION SAFETY ARE THE FULL RESPONSIBILITY OF THE CONTRACTOR
AND THE MEANS AND METHODS UNDERTAKEN.
10. OBSERVE ALL CURRENT OSHA REQUIREMENTS.
11. PROVIDE PLACARDS, PER EXECUTIVE LAW 382-b, AT ALL ENTRY DOORS DENOTING THE PRESENCE OF:
1. WOOD TRUSSES
2. ENGINEERED WOOD CONSTRUCTION (I-JOISTS, LVLS, GLULAMS, ETC.)
3. PLACARDS ARE AVAILABLE AT WWW.SAFETYSIGN.COM AND MANY OTHER SOURCES.
12. SPECIAL INSPECTIONS (SI) ARE REQUIRED FOR THE PROJECT. SI SHALL BE MADE BY THE OWNER'S
INDEPENDENT INSPECTION AGENCY. NOTIFY BOTH THE OWNER AND THE SI AGENCY PRIOR TO INSTALLING
WORK THAT REQUIRES SI AND ALLOW ACCESS FOR THESE SI TO OCCUR IN A TIMELY MANNER. WORK
REQUIRING SI INSTALLED WITHOUT NOTIFICATION SHALL BE CAUSE FOR REJECTION AND REPLACEMENT OF THE
WORK.
BULK AREA SUBGRADE PREPARATION NOTES:
1. CLEAR AND GRUB THE PROJECT WORK AREA (10 FT OUTSIDE OF EXCAVATION LIMITS OF THE FOOTPRINT
PROPOSED BUILDING FOUNDATION UNO).
2. STRIP ALL TOPSOIL FROM THE PROJECT WORK AREA. STOCKPILE TOPSOIL ON SITE FOR REUSE OR DISPOSE
OF OFF SITE AS DIRECTED ELSEWHERE IN THE CONTRACT DOCUMENTS.
3. PROOF ROLLING IS ONLY REQUIRED IF DIRECTED BY THE GEOTECHNICAL ENGINEER AND TO DETERMINE THE
LIMITS OF A KNOWN SOFT SPOT. USA AN APPROPRIATELY-SIZED VEHICLE
4. EXCAVATE AND REMOVE UNSUITABLE SOIL AND MATERIAL FROM THE PROJECT WORK AREA. UNSUITABLE SOIL
IS ANY SOIL MATERIAL THAT CONTAINS ORGANIC MATERIAL, PEAT, ROOTS, UNCONTROLLED FILL, CONSTRUCTION DEBRIS, ETC. REMOVE ALL UNSUITABLE SOIL AND MATERIAL REGARDLESS OF DEPTH.
DISPOSE OF UNSUITABLE SOIL AND MATERIAL OFF SITE.
5. EXCAVATE TO THE SUBGRADE LAYER FOR THE BUILDING SLABS ON GRADE. SEE THE CONTRACT DRAWINGS
AND DETAILS FOR THIS ELEVATION (THE BOTTOM OF STONE FILL, SUBBASE MATERIAL, AND OR STRUCTURAL
FILL BELOW SLABS ON GRADE). NOTE THAT THIS ELEVATION MAY VARY IN DIFFERENT AREAS OF THE PROJECT.
6. REPLACE ALL OVER-EXCAVATED AREAS WITH STRUCTURAL FILL PLACED IN 8 INCH DEEP MAX LIFTS AND
COMPACTED TO MINIMUM 95% MODIFIED PROCTOR.
BUILDING FOUNDATION / EXCAVATION NOTES:
1. COMPLETE THE BULK AREA SUBGRADE PREPARATION STEPS ABOVE BEFORE PROCEEDING WITH EXCAVATIONS
FOR BUILDING FOUNDATIONS.
2. EXCAVATE TO THE BOTTOM OF SUBGRADE FOR THE FOUNDATION FOOTINGS. SEE THE CONTRACT DRAWINGS
AND OR DETAILS FOR UNDERCUTS REQUIRED FOR STONE FILL, SUBBASE MATERIAL, AND OR STRUCTURAL FILL
BELOW THE BOTTOM OF FOOTING CONCRETE. NOTE THAT SUBGRADE ELEVATIONS MAY VARY IN DIFFERENT
AREAS OF THE PROJECT.
3. EXTEND EXCAVATIONS HORIZONTALLY 1'-6" MIN CLEAR BEYOND EACH SIDE OF FOOTINGS UNO.
4. CAREFULLY TRIM FINAL GRADES TO MINIMIZE DISTURBANCE TO THE EXISTING SUBGRADE SOILS.
5. SLOPE ALL EXCAVATIONS TO ACHIEVE POSITIVE DRAINAGE AND TO PREVENT PUDDLES AND PONDING AT ANY
TIME.
6. REPLACE ALL OVER-EXCAVATED AREAS WITH STRUCTURAL FILL PLACED IN 8 INCH DEEP MAX LIFTS AND
COMPACTED TO MINIMUM 95% MODIFIED PROCTOR.
7. REVIEW PLANNED EXCAVATION DEPTHS WITH RESPECT TO THEIR DISTANCE TO ADJACENT STRUCTURES.
PROVIDE ALL NECESSARY SHEETING AND OR SHORING REQUIRED TO PERFORM THE CONTRACT WORK WITHOUT
DISTURBANCE TO ADJACENT STRUCTURES AND TO PROTECT ALL UTILITIES. (SEE GENERAL NOTES 6 AND 7.)
8. MINIMUM DEPTH OF EXTERIOR FOOTINGS IS 4'-0" MIN BELOW FINISHED GRADE UNO.
9. PERCHED GROUNDWATER MAY BE ENCOUNTERED WITHIN THE EXISTING FILL SOILS.
10. PROVIDE AND MAINTAIN SUMPS AND PUMPING SYSTEMS TO DEWATER AND KEEP EXCAVATIONS FREE OF
WATER AT ALL TIMES.
11. SLOPE ALL EXCAVATION SUBGRADES TO MAINTAIN POSITIVE DRAINAGE OF RAINWATER AND GROUNDWATER
TO SUMPS TO PREVENT THE ACCUMULATION OF STANDING WATER AT ALL TIMES.
12. MAINTAIN DEWATERING CONTINUOUSLY THROUGHOUT THE DURATION OF THE PROJECT UNTIL ALL
EXCAVATIONS ARE BACKFILLED TO ACHIEVE POSITIVE SURFACE DRAINAGE.
13. DO NOT ALLOW SOILS UNDER FOOTINGS OR WITHIN THE BUILDING FOOTPRINT TO FREEZE AT ANY TIME. USE A
COMBINATION OF INSULATION MATERIALS AND SUPPLEMENTAL HEAT SOURCES TO PREVENT FREEZING.
14. REWORK SUBGRADE CONDITIONS THAT ARE ALLOWED TO POOL STANDING WATER, BECOME SATURATED, FREEZE, OR BECOME DISTURBED AT THE DIRECTION OF THE OWNER'S REPRESENTATIVE OR ENGINEER AT NO
ADDITIONAL COST.
15. PLACE BACKFILL AGAINST BASEMENT FOUNDATION WALLS ONLY AFTER THE FIRST FLOOR STRUCTURE IS IN
PLACE, AND CONCRETE STRENGTH HAS ACHIEVED 70% fc' (TYPICALLY 7 DAYS MINIMUM) .
16. PLACE BACKFILL AGAINST FOOTINGS, FROST WALLS, AND PIERS AFTER NO LESS THAN 3 FULL DAYS AFTER
CONCRETE PLACEMENT. PLACE AND COMPACT BACKFILL EVENLY AGAINST EACH SIDE IN 8 INCH MAX LIFTS.
17. PLACE BACKFILL ONLY AFTER FOUNDATION WATERPROOFING, INSULATION, AND DRAINAGE HAS BEEN
INSPECTED AND APPROVED.
CONCRETE PLACEMENT NOTES:
1. SEE STRUCTURAL DRAWINGS FOR FOOTING DETAILS.
2. SEE STRUCTURAL DRAWINGS FOR FOUNDATION WALL SECTIONS.
3. PROVIDE SCHEDULE 40 PVC PIPE SLEEVES FOR ALL FOUNDATION WALL PENETRATIONS. COORDINATE PIPE
SLEEVE SIZES AND LOCATIONS WITH WITH ALL TRADES. REMOVE SLEEVES AFTER WALL IS CAST. PACK
AROUND UTILITIES WITH NON-SHRINK GROUT BEFORE WATERPROOFING WALL EXTERIOR.
4. CONCRETE COVER DISTANCES:
• FOOTINGS: 3" UNO
• WALLS 1-1/2" UNO
• FLOOR SLABS: 1-1/4" UNO
5. PROVIDE MATCHING TIE BARS FOR ALL CONTINUOUS HORIZONTAL REINFORCEMENT IN ALL FOOTINGS AND
WALLS AT CORNERS AND INTERSECTIONS. SEE DETAILS ON STRUCTURAL DRAWINGS.
6. PLACE ALL FORMWORK AND REINFORCEMENT PER CURRENT EDITION OF ACI 301.
7. TIE ALL REINFORCING SECURELY IN PLACE PRIOR TO CONCRETE POUR. WET SETTING OF DOWELS IS NOT
PERMITTED.
8. FOLLOW THE RECOMMENDATIONS OF ACI 305R DURING HOT WEATHER PLACEMENT
9. FOLLOW THE RECOMMENDATIONS OF ACI 306R DURING COLD WEATHER PLACEMENT.
10. CONSOLIDATE ALL CONCRETE WITH A VIBRATOR PER ACI RECOMMENDATIONS, INCLUDING SLABS.
11. LEAVE FORMWORK IN PLACE TO AID IN CURING CONCRETE FOR A MINIMUM OF 7 DAYS PER ACI
RECOMMENDATIONS. FORMWORK MAY BE STRIPPED SOONER ONLY IF THE CONCRETE IS CURED BY MEANS OF
A SPRAY-ON DISSIPATING ACRYLIC POLYMER CURING COMPOUND, OR BY MOIST CURING METHODS. EARLY
FORM REMOVAL AND CURING METHODS AND MATERIALS MUST BE APPROVED BY THE ENGINEER OR ARCHITECT.
12. WHERE CONCRETE IS EXPOSED TO VIEW AND NOTED TO HAVE A SMOOTH FORM FINISH, REMOVE FORMS
AFTER A MAXIMUM OF 2 DAYS. REMOVE ALL CONCRETE FINS OR OTHER PROJECTIONS AT BETWEEN
FORMWORK JOINTS. PATCH ALL VOIDS AND FORM-TIE HOLES WITH NON-SHRINK GROUT AND FINISH SMOOTH ON
THE SAME DAY THAT FORMWORK IS STRIPPED. GRINDING THE CONCRETE OR PARGING OVER THE CONCRETE
SURFACE LATER WILL NOT BE ACCEPTED AND THE CONCRETE WILL BE REJECTED.
13. WHERE CONCRETE IS EXPOSED TO VIEW AND NOTED TO HAVE A RUBBED FINISH, REMOVE FORMS AFTER 1
DAY. WET THE CONCRETE AND RUB THE SURFACE WITH A CARBORUNDUM BRICK UNTIL A UNIFORM COLOR AND
TEXTURE ARE PRODUCED. REMOVE ALL CONCRETE FINS OR OTHER PROJECTIONS AND FILL ALL VOIDS AND
FORM-TIE HOLES. WHEN INSUFFICIENT PASTE CAN BE DRAWN FROM THE CONCRETE ITSELF, SUPPLEMENT
WITH CEMENTITIOUS MATERIALS GROUT MADE FROM THE SAME SOURCE AS THE CONCRETE. GRINDING THE
CONCRETE OR PARGING OVER THE CONCRETE SURFACE LATER WILL NOT BE ACCEPTED AND THE CONCRETE
WILL BE REJECTED.
14. SEE A-SERIES DRAWINGS FOR EXTERIOR WATER PROOFING, AND DRAINAGE SYSTEM DETAILS AND
REQUIREMENTS. FOUNDATION WATERPROOFING MUST BE COMPATIBLE WITH EXTERIOR INSULATION
MATERIALS.
15. PROVIDE SLAB-ON-GRADE CRACK CONTROL JOINTS AT LOCATIONS SHOWN ON PLANS. .
16. SAW CUT SLAB ON GRADE CRACK CONTROL JOINTS PER DRAWING DETAILS WITH AN EARLY ENTRY SAW AS
SOON AS CONCRETE MAY BE CUT WITHOUT DISLODGING AGGREGATE, BUT NOT LATER THAN 4 HOURS AFTER
PLACEMENT FINAL FINISHING.
MASONRY CONSTRUCTION NOTES:
1. USE MATERIALS FROM A SINGLE SOURCE FOR EACH TYPE OF MATERIAL THROUGHOUT THE PROJECT.
2. DO NOT USE MORTAR AS GROUT TO FILL CMU CORES. USE OF MORTAR AS GROUT IS CAUSE FOR REJECTION AND
REPLACEMENT OF THE WORK.
3. DO NOT USE ADMIXTURES IN THE MORTAR UNLESS APPROVED IN WRITING.
4. FULLY BED BOTH FACE SHELLS AND WEBS OF CMU UNO.
5. PLACE VERTICAL AND HORIZONTAL STEEL BAR REINFORCEMENT AND GROUT WITHIN CMU CORES DETAILED ON THESE
DRAWINGS AND PER NCMA TEK MANUAL 3.2 GROUTING CONCRETE MASONRY WALLS, LATEST EDITION.
6. PLACE CMU IN 7 COURSE INTERVALS WITH A HORIZONTAL BOND BEAM AT THE TOP OF EACH.
7. PLACE REGULAR GROUT IN LOW-LIFT POURS FILLING EACH 7 COURSE INTERVAL.
8. PLACE SELF-CONSOLIDATING GROUT (SCG) IN MAXIMUM HEIGHTS UP TO 12 FEET.
HOLD TOP OF GROUT LIFTS 1-1/2" BELOW TOP OF CORES TO ESTABLISH A KEY-JOINT BETWEEN NEXT COURSE OF CMU ABOVE.
WOOD FRAMING NOTES:
1. INSTALL FRAMING CONSTRUCTION FOLLOWING PRACTICES OF THE LATEST EDITION OF THE WOOD FRAME CONSTRUCTION
MANUAL (WFCM) PUBLISHED BY THE AMERICAN WOOD COUNCIL AND THE AMERICAN FOREST & PAPER ASSOCIATION.
2. SEE WOOD PANEL FASTENING DETAIL FOR ROOF, AND FLOOR SHEATHING MATERIALS AND FASTENING INFORMATION
3. PROVIDE NON-CCA PRESSURE TREATED WOOD AT ALL AREAS IN CONTACT WITH CONCRETE OR WITHIN 6" OF GRADE .
4. MAKE FLUSH FRAMED 2x CONNECTIONS WITH SIMPSON LUS TYPE JOIST HANGERS, SIZED FOR FULL JOIST DEPTH. (LUS210
FOR 2x10S RATHER THAN LUS28)
5. PROVIDE G180 GALVANIZED METAL PLATE CONNECTORS AND HOT DIP GALVANIZED FASTENERS IN CONTACT WITH
PRESSURE TREATED LUMBER . ZMAX COATING SHALL BE SUFFICIENT FOR SIMPSON CONNECTORS.
PROVIDE FLOOR JOIST CROSS BRIDGING BETWEEN 2X LUMBER JOISTS AT JOIST MID-SPANS, AND AT MAX 10'-0" INTERVALS.
CONSTRUCTION NOTES:MATERIAL PROPERTIES:
COMPONENTS AND CLADDING WIND PRESSURES (ASCE 7-16)
DISTANCE "a" = 6 FT
ZONE LRFD WIND PRESSURE
1, 2e -41.7 PSF
2n, 2r -60.9 PSF
ASD WIND PRESSURE
-25.0 PSF
-36.5 PSF
θ a
WALLS ROOF PLAN
a a
NOTES:
1. VALUES ARE CALCULATED ACCORDING TO ASCE 7-16 C+C PART 1 FOR BUILDING HEIGHT h ≤ 60 FT.
3e -72.5 PSF
4 +22.6 PSF / -24.5 PSF
5 +22.6 PSF / -30.2 PSF
-43.4 PSF
SEE ROOF PLAN
GABLE ROOF WITH SLOPE 27°< θ ≤ 45° a
2e
1 2r
3e 2n 3r
3e 2n 3r
2e12r
3e2n3r
3e2n3r a a a a aa
EFFECTIVE WIND AREA = 10 SF
a a a a a a
+13.6 PSF / -14.7 PSF
+13.6 PSF / -18.1 PSF
X
S-XXX
X
S-XXX
REF: SCALE
NUMBER TITLE
CAST-IN-PLACE CONCRETE
EXISTING CONCRETE
EXISTING SUBGRADE,
EARTH
GENERAL
GRAVEL BACKFILL, CMU
GROUT
LOAD-BEARING MASONRY
MASONRY VENEER, MASONRY PARTITIONS
NON-SHRINK GROUT, DEPRESSED TOP OF
FOUNDATION WALL
PLYWOOD
OSB - ORIENTED STRAND BOARD
RIGID INSULATION
STEEL
SUBBASE
TOP SOIL,
LOAM
WASHED STONE
STRUCTURAL DRAWING LEGEND
DETAIL NUMBER
DRAWING NUMBER
SECTION MARK
ELEVATION NUMBER
DRAWING NUMBER
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-001
0462401812-12-2025
JPJP
STRUCTURAL GENERAL NOTES, LOADS, AND LEGEND
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SEISMIC BASE SHEAR 10 KIPS
SEISMIC RESPONSE COEFFICIENT, Cs 0.0370
SEISMIC DESIGN CATEGORY (SDC) B
RESPONSE MODIFICATION FACTOR, R 3
BASIC FORCE RESISTING SYSTEM INTERMEDIATE REINFORCED MASONRY SHEAR WALLS
SITE CLASSIFICATION (SOIL TYPE) C
SPECTRAL RESPONSE COEFFICIENT, Sd1 0.056
SPECTRAL RESPONSE COEFFICIENT, Sds 0.195
MAPPED SPECTRAL RESPONSE ACCELERATION, S1 0.056
MAPPED SPECTRAL RESPONSE ACCELERATION, Ss 0.224
SEIMIC LOAD IMPORTANCE FACTOR, Ie 1.0
SEISMIC DESIGN SEISMIC DESIGN
INTERNAL PRESSURE COEFFICIENT, GCpi +/- 0.18
WIND EXPOSURE CATEGORY B
SERVICE DESIGN WIND SPEED, Vasd 89 MPH
BASIC DESIGN WIND SPEED, Vult 115 MPH
WIND LOAD DESIGN WIND LOAD DESIGN
DRIFT SURCHARGE PER ASCE 7-16
SLOPE FACTOR, Cs 1.0
THERMAL FACTOR, Ct 1.1
SNOW LOAD IMPORTANCE FACTOR, Is 1.0
SNOW EXPOSURE FACTOR, Ce 1.0
SLOPED ROOF SNOW LOAD, Ps 31 PSF
FLAT ROOF SNOW LOAD, Pf 31 PSF (MINIMUM FLAT)
GROUND SNOW LOAD, Pg 40 PSF
SNOW LOAD DESIGN SNOW LOAD DESIGN
MEP ALLOWANCE 5 PSF (ROOFS)
ROOFING MATERIALS 10 PSF
DEAD LOADS DEAD LOADS
RAIN INENSITY, i 3.0 INCHES PER HOUR
ROOF RAIN LOADS ROOF RAIN LOADS
LIVE LOADS 100 PSF UTILITY ROOMS
NOVEMBER 6, 2024
INVESTIGATIN REPORT BY KEVIN PATTON PE AND...
SOIL BEARING CAPACITY 2,500 PSF IN ACCORDANCE WITH GEOTECHNICAL
RISK CATEGORY II
STRUCTURAL DESIGN DATA
STRUCTURAL DRAWING ABBREVIATIONS
ADD ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
B/FTG BOTTOM OF FOOTING
BLDG BUILDING
BOT BOTTOM
BP BASE PLATE
BRG BEARING
CANT CANTILEVER
CFMF COLD FORMED METAL FRAMING
CJ CONTROL, CONTRACTION, OR
CONSTRUCTION JOINT
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DITTO
DWG DRAWING
EA EACH
EL ELEVATION
EMBD EMBED, EMBEDMENT
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FDN FOUNDATION
FOW FACE OF WALL
FS FAR SIDE
FTG FOOTING
GA GAGE
GWB GYPSUM WALL BOARD
HDG HOT DIP GALVANIZED
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL SHAPE
ID INSIDE DIAMETER
INFO INFORMATION
INT INTERIOR
INV INVERT
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LVL LAMINATED VENEER LUMBER
LW LIGHT WEIGHT
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
NIC NOT IN CONTRACT
No. NUMBER
NTS NOT TO SCALE
NW NORMAL WEIGHT
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
PAF POWDER ACTUATED FASTENER
PCF POUNDS PER CUBIC FOOT
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
REINF REINFORCEMENT
REQD REQUIRED
REV REVISED, REVISION
RO ROUGH OPENING
SIM SIMILAR
SP SPACE, SPACES, SPACED
SQ SQUARE
STD STANDARD
STL STEEL
T/ TOP OF
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
WCJ WALL CONTROL JOINT
WWR WELDED WIRE REINFORCEMENT
3' -0
F
O O
T
IN
G , T
Y P
1' -6
W
A
LL
, T Y
P
S T
E M
, T Y
P
8" S
H E
LF
, T
Y P
55'-5"
'-9
'-6
'-5
S-502
S-501
S-501
S-502
TYP
3' -0
F
O O
T
IN
G
W A
LL
T/WALL = (1'-4"), TYP UNO
T/SHELF = (-0'-8"), TYP UNO
T/FOOTING = (-4'-0"), TYP UNO
FOUNDATION DRAIN PER
1/S-501, SEE C-DRAWINGS
FOR MORE INFORMATION, TYP
'-6
5'
-0
'-3
3'-0"
'-9
5'
-0
'-6
3'-0"
WASH BAY SLAB ON
GRADE ABOVE PER 1/S-101
SLAB ON GRADE
ABOVE PER 1/S-101
12 INCH THICK FOOTING CENTERED BENEATH
BOLLARD REINFORCE WITH NO. 4 BARS AT 8
INCHES ON CENTER EACH WAY,TYP 4 LOC
COORD EXACT LOCATION WITH BOLLARD
2'-3" TYP
3' -0
T
Y P
WATER SERVICE SLEEVE
INVERT (-4'-8'), SEE FOUNDTION PLAN NOTE 7
GAS SERVICE SLEEVE
TOP OF PIPE (-2'-6"), SEE FOUNDATION PLAN NOTE 7
OWS SLEEVE
INVERT (4'-0"), SEE
FOUNDATION PLAN NOTE 7
STEP FOOTING DOWN BELOW OWS
SLEEVE TO (-5'-0"), SEE 11/S-501
WCJ
WCJ
WCJ
WCJ
WCJ
WCJ
WCJ WCJ
FOUNDATION PLAN NOTES
1. PROJECT REFERENCE ELEVATION = 0'-0" AT TOP OF FIRST FLOOR SLAB.
2. THE PROJECT REFERENCE ELEVATION IN NOTE 1 IS EQUIVALENT TO SITE ELEVATION 455.00'.
3. ELEVATIONS NOTED THUS ( ) ON THIS PLAN ARE ABOVE OR BELOW THE REFERENCE ELEVATION IN NOTE 1.
4. TOP OF FOUNDATION WALL STRIP FOOTINGS ON THE PROJECT ARE AT ELEVATION -4'-0" TYPICAL UNO.
5. TOP OF FOUNDATION WALLS ON THE PROJECT ARE AT ELEVATION 1'-4" TYPICAL UNO.
6. SEE DETAIL 7/S-501 AND 8/S-501 FOR REQUIRED WALL REINFORCING AT FOUNDATION CORNERS AND INTERSECTIONS.
7. SLEEVE ALL OPENINGS GREATER THAN 1-1/2" ∅ THROUGH FOUNDATION WALL. SEE 12/S-501.
8. SEE 3/S-501 AND 4/S-501 FOR FOUNDATION WALL JOINT DETAILS. ALIGN ALL FOUNDATION WALL JOINT WITH MASONRY
CONTROL JOINTS, APPROXIMATE JOINT LOCATIONS ARE DESIGNATED AS WCJ
9. SEE S-001 FOR ADDITIONAL FOUNDATION, EXCAVATION, AND GENERAL NOTES.
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-100
0462401812-12-2025
JPJP
FOUNDATION PLAN
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
11SCALE: 1/4" = 1'-0"
1 FOUNDATION PLAN
PLAN NORTH
WCJ
8" THICK CONCRETE SLAB ON
GRADE PER DETAIL
T/SLAB AT HIGH POINT = 0'-0", TYP
C J
4" THICK CONCRETE SLAB ON
GRADE PER DETAIL 2/S-501
T/SLAB = 0'-0", TYP
S-501
S-502
S-501
S-501
S-502
TYP
S-501
S-501
S-501
S-501
BOLLARD PER A-DRAWINGS, TYP
/2 S-501
STAIRS BY OTHERS, TYPPOSTS FOR MECHANICAL
PLATFORM BY OTHERS ABOVE, TYP
SLOPE SLAB 1/8" PER FT
MINIMUM UNIFORMLY TO
DRAIN, TYP
POSTS FOR MECHANICAL
PLATFORM BY OTHERS ABOVE, TYP
REENTRANT CONRNER
REINFORCEMENT PER
8/S-502, TYP
TRENCH DRAIN
PER 7/S-502
S-502
8" THICK CONCRETE KNEE WALL
ON TOP OF SLAB, SEE 10/S-501
8" THICK CONCRETE KNEE WALL
ON TOP OF SLAB, SEE 10/S-501
THICKENED SLAB HAUNCH UNDER KNEE WALL
AND CMU BEARING WALL, TYP
THICKENED SLAB HAUNCH UNDER KNEE
WALL AND CMU BEARING WALL, TYP
FLOOR FRAMING PLAN NOTES
1. PROJECT REFERENCE ELEVATION = 0'-0" AT TOP OF FIRST FLOOR SLAB.
2. THE PROJECT REFERENCE ELEVATION IN NOTE 1 IS EQUIVALENT TO SITE ELEVATION XXX.XX'.
3. SEE DETAIL 2/S-501 FOR CONCRETE SLAB-ON-GRADE AND CONTROL JOINT DETAILS.
4. THICKEN SLABS-ON GRADE UNDER ALL CMU WALLS AND NOTED BEARING WALLS.
5. SEE DETAIL 9/S-502 FOR HOUSEKEEPING PADS, COORDINATE WITH APPLICABLE TRADES FOR QUANTITY AND LOCATIONS.
6. SEE NOTE ON S-001 FOR ADDITIONAL REQUIREMENTS.
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-101
0462401812-12-2025
JPJP
SLAB ON GRADE PLAN
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
12SCALE: 1/4" = 1'-0"
1 SLAB ON GRADE PLAN
PLAN NORTH
EXTEND BOLLARD BASE DOWN
INTO FOOTING BELOW, SEE
FOUNDATION PLAN, TYPICAL
2x
2s A
T
6" O
C
BOND BEAM ABOVE OPENINGS,
SEE 5/S-502 , TYP UNO
OPEN TO BELOW
LINE OF MECHANICAL
PLATFORM BY OTHERS
RTU-1 DESIGN WEIGHT = 1,600 LBS,
NOTIFY ENGINEER IF THIS
WEIGHT IS TO BE EXCEEDED
LINE OF MECHANICAL
PLATFORM BY OTHERS
10" CMU WALLS: SEE 1/S-502
FOR TYPICAL REINFORCING
2x
2s A
T
6" O
C
2x
2s A
T
6" O
C
PT 2x12 LEDGER TYPICAL ALONG EACH
SIDE, TYP, SEE SECTION 3/S-201
STAIRS BY OTHERS, TYP
SIMPSON LUS210
HANGER, TYP UNO
S-201
S-201
S-502
S-502
S-502
PROVIDE 2x12 BLOCKING BETWEEN
JOISTS, ALIGN BENEATH RTU CURB
S-502
S-502
S-502
S-502
_____________________ 6
S-502
S-502
S-502
MEZZANINE FLOOR FRAMING PLAN NOTES
1. MEZZANINE FLOOR SHEATHING ELEVATION IS (+10'-0") ABOVE THE PROJECT REFERENCE ELEVATION NOTED ON THE FOUNDATION PLAN NOTES
2. ELEVATIONS NOTED THUS ( ) ON THIS PLAN ARE ABOVE OR BELOW THE FLOOR SHEATHING ELEVATION IN NOTE 1
3. REFER TO A-SERIES FOR HEAD HEIGHT ELEVATIONS NOT NOTED ON THIS PLAN
4. MEZZANINE FLOOR FRAMING ON THIS PLAN IS (-0'-3/4") BELOW THE FLOOR SHEATHING ELEVATION IN NOTE 1, TYPICAL UNLESS NOTED OTHERWISE
5. SEE A-DRAWINGS FOR WALL PLATE ELEVATIONS AND ROOF SLOPES NOT NOTED ON THIS PLAN, TYP
6. SEE 5/S-510 FOR BOND BEAM SCHEDULE AND 9/S-510 FOR LOOSE LINTEL SCHEDULE. NOTE THAT NOT ALL BOND BEAMS AND LINTELS IN WALLS ARE
SHOWN ON PLAN
7. REFER TO S-001 FOR ADDITIONAL NOTES AND FRAMING REQUIREMENTS.
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-102
0462401812-12-2025
JPJP
MEZZANINE FRAMING PLAN
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
13SCALE: 1/4" = 1'-0"
1 MEZZANINE LEVEL FRAMING PLAN
PLAN NORTH
S-601
DORMER OVERBUILD TRUSSES
INSTALLED OVER ROOF SHEATHING ,TYP
DORMER OVERBUILD TRUSSES
INSTALLED OVER ROOF SHEATHING ,TYP
JACK TRUSSES
AT 2'-0" OC, TYP
HIP
G
IR
DER T
RUSS
T
A G
IR
D
E R
T R
U S
S
HIP GIRDER TRUSS
T
A G
IR
D
E R
T R
U S
S
HIP GIRDER TRUSS
HIP
G
IR
DER T
RUSS
x1
R
A F
T E
R S
, L A
P W
IT
U S
S T
O P
C H
O R
D , T
Y P x1
R
A F
T E
R S
, L A
P W
IT
U S
S T
O P
C H
O R
D , T
Y P
LOOKOUT FRAMING
PER 5/S-510, TYP
T
A
T
A
T
A
T
A
T
T
T
T
T
T
T
T
T
T
T
A
T
A
T
A
T
A
T
JACK TRUSSES AT 2'-0" OC, TYP
JACK TRUSSES AT 2'-0" OC, TYP
JACK TRUSSES AT 2'-0" OC, TYP
JACK TRUSSES AT 2'-0" OC, TYP
LOOKOUT FRAMING
PER 5/S-510, TYP
LOOKOUT FRAMING
PER 5/S-510, TYP
S-510
S-510
OPEN TO BELOW
JACK TRUSSES
AT 2'-0" OC, TYP
LOOKOUT FRAMING
PER 5/S-510, TYP
S-510
S-510
S-201
S-201
BOND BEAM WITH CONTINUOUS LINTEL
ABOVE WINDOW OPENING PER 5/S-502
AND 11/S-502, TYP (3) LOCATIONS
BOND BEAM WITH CONTUNOUS
LINTEL ABOVE WINDOW OPENING
PER 5/S502 AND 11/S-502
T1 AND T1A PRE -ENGINEERED
TRUSSES AT 2'-0" OC, TYP
BOND BEAM WITH LOOSE LINTEL
ABOVE OPENINGS PER 5/S-502
AND 10/S-502, TYP UNO
BOND BEAM WITH CONTINUOUS
LINTEL ABOVE OVERHEAD DOOR
OPENING PER 5/S-502 AND 11/S-502
BOND BEAM WITH CONTINUOUS
LINTEL ABOVE OVERHEAD DOOR
OPENING PER 5/S-502 AND 11/S-502
S-510
ROOF FRAMING PLAN NOTES
1. SEE A-DRAWINGS FOR WALL PLATE ELEVATIONS AND ROOF SLOPES NOT NOTED ON THIS PLAN, TYP.
2. SEE S-510 FOR WOOD FRAMING DETAILS.
3. SEE S-601 FOR TRUSS SECTIONS AND TRUSS FRAMING DETAILS.
4. ALL TRUSS OR STICK FRAMED OVERBUILDS SHALL CONSTRUCTED OVER FULLY SHEATHED ROOF FRAMING BELOW.
5. SEE 5/S-510 FOR BOND BEAM SCHEDULE AND 9/S-510 FOR LOOSE LINTEL SCHEDULE. NOTE THAT NOT ALL BOND
BEAMS AND LINTELS IN WALLS ARE SHOWN ON PLAN
6. T/MASONRY (23'-4") UNLESS NOTED OTHERWISE.
7. REFER TO S-001 FOR ADDITIONAL NOTES AND FRAMING REQUIREMENTS.
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-103
0462401812-12-2025
JPJP
ROOF FRAMING PLAN
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
14SCALE: 1/4" = 1'-0"
1 ROOF FRAMING PLAN
PLAN NORTH
BOND BEAM HEADER ABOVE
DOOR OPENING, TYP, SEE
1/S-502 AND 5/S-502, TYP
T/MASONRY (18'-0") T/MASONRY (18'-0")
T/MASONRY SLOPES
T/MASONRY SLOPES
FULLY GROUT AND REINFORCE (3) CORES
WITH CONTINUOUS No. 5 BARS ADJACENT
TO WASH BAY DOOR OPENING, SEE 1/S-502
FOR ADDITIONAL INFORMATION, TYP
BOND BEAM PER
5/S-502, TYP
No. 5 JAMB BAR AND
FULLY GROUT CELL
BOND BEAM PER
5/S-502, TYP
No. 5 CORNER BAR IN GROUTED CORE
BOND BEAM PER
1/S-502, TYP
No. 5 CORNER BAR IN GROUTED CORE
No. 5 VERTICAL AT 2'-8" OC
TYPICAL, SEE 1/S-502, NOT
ALL ARE SHOWN
FULLY GROUT AND REINFORCE (3) CORES
WITH CONTINUOUS No. 5 BARS ADJACENT
TO WASH BAY OH DOOR OPENING, SEE
1/S-502 FOR ADDITIONAL INFORMATION, TYP
BOND BEAM PER
5/S-502, TYP
No. 5 JAMB BAR AND
FULLY GROUT CELL
BOND BEAM PER
5/S-502, TYP
FULLY GROUT AND REINFORCE (2) CORES
WITH CONTINUOUS No. 5 BARS ADJACENT
TO OH DOOR OPENING, SEE 1/S-502 FOR
ADDITIONAL INFORMATION, TYP
BOND BEAM PER
5/S-502, TYP
No. 5 CORNER BAR IN GROUTED CORE
No. 5 VERTICAL AT
2'-8" OC TYPICAL, SEE
1/S-502, NOT ALL ARE
SHOWN
BOND BEAM PER
1/S-502, TYP
BOND BEAM
HEADER PER
5/S-502, TYP
FULLY GROUT AND REINFORCE (3) CORES
WITH CONTINUOUS No. 5 BARS ADJACENT
TO EACH WASH BAY WINDOW OPENING, SEE
1/S-502 FOR ADDITIONAL INFORMATION, TYPNo. 5 VERTICAL AT
2'-8" OC, SEE 1/S-502,
TYPICAL, NOT ALL ARE
SHOWN
No. 5 CORNER BAR
IN GROUTED CORE
No. 5 CORNER BAR IN
GROUTED CORE
BOND BEAM PER
1/S-502, TYP
BOND BEAM PER
1/S-502, TYP
FULLY GROUT AND REINFORCE (2) CORES
WITH CONTINUOUS No. 5 BARS ADJACENT
TO WINDOW OPENING, EXTEND BARS
DOWN TO TOP OF FOUNDATION WALL, SEE
1/S-502 FOR ADDITIONAL INFORMATION, TYP
BOND BEAM
HEADER OVER
WINDOW
OPENING PER
5/S-502, TYP
No. 5 VERTICAL AT
2'-8" OC, SEE 1/S-502,
TYPICAL, NOT ALL ARE
SHOWN
BOND BEAM
PER 1/S-502, TYP
BOND BEAM
PER 1/S-502, TYP
BOND BEAM
PER 1/S-502, TYP
No. 5 CORNER BAR
IN GROUTED CORE,
TYPICAL AT ALL
CORNERS
BOND BEAM
PER 1/S-502, TYP
SCALE: 3/16" = 1'-0"
1 WEST ELEVATION
SCALE: 3/16" = 1'-0"
2 EAST ELEVATION
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-201
0462401812-12-2025
JPJP
STRUCTURAL ELEVATIONS
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
SCALE: 3/16" = 1'-0"
5 NORTH ELEVATION
SCALE: 3/16" = 1'-0"
6 SOUTH ELEVATION
PLACE BACKFILL AGAINST
FOUNDATION WALLS IN EQUAL LIFTS
ON OPPOSITE SIDES OF FROST WALL
PROVIDE CONTINUOUS FOUNDATION
DRAINS PER DETAIL AND AS SHOWN ON
FOUNDATION PLAN, CONNECT TO SITE
DRAINAGE PIPING PER SITE PLAN
UNDERCUT BY 3" MIN BELOW BOTTOM OF FOOTING, SLOPE
SUBGRADE TO DRAIN TO OUTSIDE OF EXCAVATION AT 1/2" PER FT
MIN AND DEWATER CONTINUOUSLY PER NOTES, PROOF COMPACT
SUBGRADE PER EARTHWORK NOTES, ESTABLISH FOOTING
SUBGRADE WITH COARSE AGGREGATE, TYP
COARSE AGGREGATE, TYP
BACKFILL WITH SELECT GRANULAR MATERIAL,
DO NOT BACKFILL AGAINST FOUNDATION WITH
EXISTING ON-SITE MATERIAL UNLESS
APPROVED BY THE ENGINEER SEE A-SERIES DETAILS FOR FOUNDATION
INSULATION REQUIREMENTS
SEE PROJECT SPECIFIC FOUNDATION
WALL SECTIONS FOR WALL AND FOOTING
REINFORCEMENT IN EACH AREA, TYP
SEE FOUNDATION PLAN FOR FOUNDATION
WALL WIDTHS AND TOP OF WALL ELEVATIONS,
SEE PROJECT SPECIFIC FOUNDATION WALL
SECTIONS FOR TOP OF WALL GEOMETRY
PITCH GRADE AWAY FROM FOUNDATION
WALLS AT 1/2" PER FT MIN UNO
PROVIDE SCREENED TOPSOIL AND SEED TO
ESTABLISH TURF IN ALL DISTURBED AREAS UNO
SEE FOUNDATION PLAN FOR FOOTING WIDTHS
AND TOP OF FOOTING ELEVATIONS
3" M
IN
SUBGRADE CONSISTING OF UNDISTURBED EARTH OR STRUCTURAL FILL
ZZZSEE FOUNDATION PLAN FOR SLAB-ON-GRADE
THICKNESS AND SUBBASE REQUIREMENTS
4" PERFORATED CORRUGATED
HDPE DRAINAGE PIPE INSTALLED
LEVEL AROUND FOOTINGS
CONNECT TO SOLID WALL PIPING
PITCHED TO SUMP OR TO
DAYLIGHT AT 1% MINIMUM SLOPE
CONTINUOUS WRAP: 4 oz NON-WOVEN
FILTER FABRIC MIRAFI 140N OR EQUAL
LAP FABRIC
EDGES 6" MIN
1'-0" MIN
DO NOT CONNECT ROOF DRAIN
LEADERS TO FOOTING DRAIN PIPING
S
LA
B T
H
IC
K N
E S
S P
E R
P
LA
N
8" A
S R
E Q
U
IR
E D
COARSE AGGREGATE
STRUCTURAL FILL AS REQUIRED TO ESTABLISH SUBGRADE
PROOF COMPACTED SUBGRADE PER NOTES AND SPECIFICATIONS
1" M
IN
EPOXY COATED No. 4 BARS AT 12" OC EACH WAY AT WASH BAY, No.
4 BARS AT 18" OC EACH WAY AT ELECTRICAL, MECHANICAL AND
STORAGE ROOMS, PROVIDE 20" MIN LAP SPLICE, AND SUPPORT
REBAR ON CONTINUOUS WIRE CHAIRS AT 3'-0" MAX OC, TYP
CONTROL JOINTS, SEE PLAN FOR LOCATIONS. SAW CUT CONTROL JOINTS
IN SLAB WITH EARLY ENTRY SYSTEM AS SOON AS AGGREGATE WILL CUT
CLEANLY WITHOUT DISLODGING, USUALLY WITHIN 8 HOURS BUT NO LATER
THAN 12 HOURS AFTER FINISHING, CUT JOINTS AT A MAXIMUM SPACING
OF 30 TIMES THE SLAB THICKNESS, UNO
DISCONTINUE OR FIELD CUT EVERY OTHER BAR AT CONTROL JOINTS
1/
4" C
O V
E R
"D"
R E
G U
LA
R
W A
LL
R
E
IN
F O
R C
IN
G
REGULAR WALL
REINFORCING
INSTALL PVC SLEEVE WITHIN CONCRETE
FORMWORK, SLEEVES SHALL BE
PROVIDED BY OTHER TRADES UNO.
COORDINATE QUANTITIES AND
LOCATIONS WITH OTHER TRADES.
ADD (4) ADDITIONAL BARS AT EACH MAT OF
CUT REINFORCING (NOT REQUIRED IF
REGULAR REINFORCING IS NOT CUT)
"D" + 2'-0", M
INIM
UM
, TYP
REMOVE PVC PIPE SLEEVE AFTER
STRIPPING CONCRETE FORMS
CLEAN FORM OIL FROM CONCRETE,
PACK AROUND INSTALLED UTILITY
WITH NON-SHRINK GROUT, UNO
CUT REGULARLY SPACED REINFORCING
BACK TO ACCOMMODATE SLEEVE.
POSITION SLEEVE BETWEEN
REINFORCING WHERE POSSIBLE.
PROVIDE LINK SEAL IN LIEU OF
GROUT WHEN REQUIRED WITHIN
CONTRACT DOCUMENTS.
WALL CONSTRUCTION JOINT
(PLACED AT CONTRACTOR'S DISCRETION)
(CAN BE SUBSTITUTED FOR A CONTROL JOINT)
WALL CONTROL JOINT
(LABELED WCJ ON PLANS)
FIRST POUR SECOND POUR
CUT EVERY OTHER HORIZONTAL BAR AT
EACH FACE AT CONTROL JOINTS NOTED
ON PLAN, TYP ALTERNATE BARS TO
REMAIN CONTINUOUS ACROSS JOINT, TYP
BACKER ROD AND
SEALANT, TYP
T /3
T/6
BACKER ROD AND
SEALANT, TYP
BACKER ROD AND
SEALANT, TYP
LAP SPLICE 24 BAR DIA, TYP
1/2"
3/4"
1/
2"
3/4"
1/
2"
1/ 4"
3/
8"
3/ 8"
T
40 BAR DIAs TYP
ADD L-BARS AT
EACH HORIZONTAL
REINFORCEMENT
WALL TEE REINFORCEMENT
ADD L-BARS AT
EACH HORIZONTAL
REINFORCEMENT
WALL CORNER REINFORCEMENT
B
A R
D
IA
s T
Y P
E Q
E Q
40 BAR DIAs TYP
3"
DIM "D" x 3.0 MIN TO NEXT
STEP (UNO ON PLANS)
(U N
O O
N P
LA
N
S
D
IM
D
2' -0
M
A X
F O
R M
U
LT
IP
LE
S T
E P
S
'-0
M
A X
F O
R A
S
IN
G
LE
S T
E P
1'-0"
LAP 40 DIAs
LAP 40 DIAsLAP 40 DIAs
UNDISTURBED SOIL
SIZE AND QUANTITY OF FTG STEP
REINF TO MATCH LONG STRIP FTG
REINF SHOWN ON FND WALL SECTIONS
HAND TRIM TO 2-ON-3
OR STEEPER SLOPE
SEE FOUNDATION WALL
SECTIONS FOR REINFORCING
EXTEND COARSE AGGREGATE
SUBBASE 2 FT BEYOND PERIMETER
EDGES OF ENTRY SLAB, TYP
FOUNDATION WALL BACKFILL
2" RIGID INSULATION, TYP
3/4" x 18" LONG SMOOTH HDG DOWELS
AT 12" MAX OC, CENTERED ON JOINT
SLOPE ENTRY SLAB
AWAY AT 1/4" PER FT
CENTER 2" JOINT AT MIDDLE OF DOOR
THRESHOLD SADDLE, COORDINATE WITH
DOOR SCHEDULE, VARIES BY LOCATION
SLAB ON GRADE AND COARSE AGGREGATE
SUBBASE PER PLAN AND DETAILS
FOUNDATION WALL AND
PERIMETER INSULATION BEYOND
D R
O P
T O
P O
F F
O U
N D
A T
IO
N
W A
LL
A
T E
N T
R
IE
S , T
Y P
FOUNDATION WALL PER
PLANS AND SECTION DETAILS
3"
E Q
E Q
FOUNDATION WALL AND
PERIMETER INSULATION BEYOND
BEND VERTICAL BAR PER WALL
SECTION DOWN INTO EXTERIOR SLAB
1'-10"
FOUNDATION WALL BEYOND, DROP
TOP OF WALL 8" AT DOORWAYS, UNO
PIN ENTRY SLAB FROST WALLS AND
FOOTINGS TO BUILDING FOUNDATION
WALL AND FOOTING, TYP
EXTEND FOUNDATION WALL
REINFORCEMENT 30" FROM TOP
OF SLAB ELEVATION AND BEND
INTO SLAB PERPENDICULAR TO
FOUNDATION WALL AT 24" OC, TYP
WALL BEYOND
1'-4"
8"
12 BUILDING FOUNDATION WALL
BACKFILL WITHIN
WALLS WITH COARSE
AGGREGATE, TYP
F
T M
IN
F
R O
P T
H
T Y
P
4"8"4"
No. 4 VERTICAL AT 18" OC
CONTINUOUS HORIZONTAL
No. 4 AT 12" OC
No. 4 L-BARS AT 24" OC
No. 4 CROSS BARS AT 18" OC
(2) No. 4 BARS CONTINUOUS
24" MIN
LEGS, TYP
CENTER 2" JOINT AT MIDDLE OF
DOOR THRESHOLD SADDLE,
COORDINATE WITH DOOR
SCHEDULE, VARIES BY LOCATION
PIN SLAB TO FOUNDATION WALL
WITH No. 4 BARS AT 12" OC SET
4" DEEP IN 2-PART ADHESIVE
3 1/2"
8" ENTRY SLAB, REINFORCE WITH
No. 4 BARS AT 12" MAX OC, 3/8" TOOLED
EDGES, LIGHT BROOM FINISH UNO
SLOPE ENTRY SLAB
AWAY AT 1/4" PER FT
SEE SITE PLANS FOR
ADJACENT SIDEWALKS
PIN ADJACENT SIDEWALKS
TO EDGE OF SLAB WITH No. 4
DOWELS AT 16" MAX OC
3/4"∅ x 18" LONG SMOOTH HDG
DOWELS AT 12" MAX OC, CENTERED ON
JOINT AND WITHIN SLAB THICKNESS
SLAB ON GRADE AND COARSE AGGREGATE
SUBBASE PER PLAN AND DETAILS
2" RIGID INSULATION
EMBEDDED ANGLE:
L2 1/2" x 2 1/2" x 3/8" WITH 1/2"x4"
SHEAR STUDS AT 24" OC HOT DIP
GALVANIZED AFTER FABRICATION
EXTEND VERTICAL BARS IN WALL
AND BEND DOWN INTO SLAB, TYP
HAUNCH EDGE OF SLAB TO 8" THICK AT
STORAGE OH DOOR OPENING, TYP
SLOPE GARAGE FLOOR
TO OVERHEAD DOORS
AT 1/8" PER FT TYP UNO
2'-0" TYP
8"
1/
2"
S
LO
P E
L E
A D
IN
G
E D
G E
D O
W N
OVERHEAD DOOR
FOUNDATION WALL BACKFILL
1/2" PER FT SLOPE
W A
S H
E D
S T
O N
E U
P D
E R
A P
R O
N
FOUNDATION WALL PER PLANS
AND SECTION DETAILS
3'-0"
1'-6"1'-6"
1'-6"TYP
1' -0
3"
1' -0
M
IN
S
E E
S
LA
B O
N G
R A
D E
D E
T A
IL
(2) No. 5 BARS CONTINUOUS
No. 5 BARS AT SPACING TO MATCH VERTICAL
REINFORCEMENT WITHIN CMU ABOVE
No. 4 DOWELS INTO CMU ABOVE, LAP WITH CMU WALL REINFORCING
SEE CMU WALL REINFORCEMENT
DETAIL FOR REQUIRED SPACING
SEE SLAB ON GRADE DETAIL FOR
REINFORCING REQUIREMENTS
SAW-CUT CONTROL JOINTS, SEE SLAB ON
GRADE DETAIL AND FOUNDATION PLAN 34
MAINTAIN SUBBASE
DEPTHS UNDER HAUNCH
PLACE AND TIE ALL REINORCEMENT PRIOR TO
CONCRETE POUR, DO NOT "WET-STICK" DOWELS
ALTERNATELY, DOWELS MAY BE DRILLED
AND EPOXIED 6" DEEP INTO TOP OF WALL
2'-0"
2'-0"
2'-0"
(3) No. 4 BARS CONTINUOUS
WALL CONSTRUCTION JOINT
(PLACED AT CONTRACTOR'S DISCRETION)
(CAN BE SUBSTITUTED FOR A CONTROL JOINT)
WALL CONTROL JOINT
(LABELED WCJ ON PLANS)
FIRST POUR SECOND POUR
CUT EVERY OTHER HORIZONTAL BAR AT
EACH FACE AT CONTROL JOINTS NOTED
ON PLAN, TYP ALTERNATE BARS TO
REMAIN CONTINUOUS ACROSS JOINT, TYP
BACKER ROD AND
SEALANT, TYP
T /3
1/ 4"
LAP SPLICE 24 BAR DIA, TYP
T/6
BACKER ROD AND
SEALANT, TYP
BACKER ROD AND
SEALANT, TYP
1/2"
3/4"
1/
2"
3/4"
1/
2"
3/
8"
3/ 8"
T
WALL TEE REINFORCEMENT
WALL CORNER REINFORCEMENT
ADD (3) L-BARS AT
EACH HORIZONTAL
REINFORCEMENT
ADD L-BARS AT
EACH HORIZONTAL
REINFORCEMENT
REQUIRED COVER, TYP
SEE GENERAL NOTES FOR
40 BAR DIAs TYP
B
A R
D
IA
s T
Y P
R E
Q U
IR
E
D C
O V
E R
, T Y
P S
E E
G E
N E
R A
L N
O T
E S
F O
R
40 BAR DIAs TYP
Call 811 New York before you dig
Dig Safely.
ENGINEERING LLP
1/8" 1/4" 1/2" 0 1" 2" UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN
BEARING A LICENSED PROFESSIONAL ENGINEER'S
SEAL IS A VIOLATION OF SECTION 7209,
SUB-DIVISION 2 OF THE N.Y. STATE EDUCATION LAW.
DRAWING #:
PAGE
DESIGNED BY: DRAWN BY:
DATE: SCALE: FE PROJECT #:
APPROVED BY:
DRAWING TITLE:
PROJECT TITLE:
OF
800 Troy-Schenectady Road
Suite 103
Latham, NY, 12110
(518) 452-3470 www.hymanhayes.com
HYMAN
HAYES
ASSOCIATES
SYMB DATE ISSUED FOR
REFERENCE SCALE
ADENDUM
www.fellp.com
85 Market St., Suite 200, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454-9705
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
/1 /2
:2
:2
P M
As indicated S-501
0462401812-12-2025
JPJP
CONCRETE SECTIONS AND DETAILS
DEPARTMENT OF PUBLIC WORKS FACILITY
2455-2459 ROUTE 17M AND 10 WELLS FAM ROAD, GOSHEN NY
FLEET WASH AT THE ORANGE COUNTY
16SCALE: 3/4" = 1'-0"
1 TYPICAL EXCAVATION AND BACKFILL AT FOUNDATIONS
SCALE: 1 1/2" = 1'-0"
2 SLAB ON GRADE DETAIL
SCALE: 3/4" = 1'-0"
12 FOUNDATION WALL SLEEVE DETAIL
SCALE: 1" = 1'-0"
3 FOUNDATION WALL JOINT DETAILS
SCALE: 3/4" = 1'-0"
7 WALL CORNER AND TEE REINFORCEMENT
SCALE: 1/2" = 1'-0"
11 TYPICAL FOOTING STEP
SCALE: 3/4" = 1'-0"
6 FROST PROTECTED ENTRY SLAB, THERMAL BREAK
SCALE: 3/4" = 1'-0"REF: 1 / S-100
5 ENTRY SLAB WITH FROST WALLS
SCALE: 1" = 1'-0"REF: 1 / S-101
9 SLAB EDGE AT OVERHEAD DOORS
SCALE: 3/4" = 1'-0"REF: 1 / S-101
10 HAUNCH UNDER 8 INCH BLOCK WALL DETAIL
SCALE: 1" = 1'-0"
4 FOUNDATION WALL JOINT DETAILS
SCALE: 3/4" = 1'-0"
8 WALL CORNER AND TEE REINFORCEMENT
5'
A X
L
IF
T S
G R
O U
T C
O R
E S
IN
IN
-C
O U
R S
E O
R
AT TEE- WALLS, AND AT INTERRUPTIONS, TYP
VERTICAL REINFORCEMENT AND SOLID GROUT
WITHIN CMU CORES, ALSO GROUT AT CORNERS,
No. 5 AT EACH SIDE OF CONTROL
JOINTS, CONTINUE REINFORCEMENT
THRU TOP MOST JOINT, TYP
(2) No. 5 HORIZONTAL REINFORCEMENT AND SOLID
GROUT WITHIN SLOTTED OPEN BOTTOM BOND BEAM
BLOCK AT TOP OF EACH GROUT LIFT (SEVEN
COURSE INTERVALS UNO) AND ALONG TOP OF WALL
SEE 5/S-502 FOR BOND BEAM
SCHEDULE AND DETAILS
FULLY GROUT AND REINFORCE (2)
CORES WITH CONTINUOUS No. 4 BARS
ADJACENT TO OPENING, TYP UNO
NOTES:
1. THIS DETAIL APPLIES TO ALL CMU WALLS INDICATED ON THE S-SERIES PLANS. SEE OTHER DETAILS FOR NON LOAD-BEARING CMU PARTITIONS.
2. INSTALL HORIZONTAL JOINT REINFORCING PER SPECIFICATIONS AT EVERY OTHER COURSE AND AT TOP COURSE.
3. PERFORM LOW-LIFT GROUTING PER CURRENT NCMA TEK NOTES 3-2.
4. USE SLOTTED OPEN BOTTOM BOND BEAM BLOCK TO ALLOW CONTINUOUS (UNINTERRUPTED) HORIZ AND VERT REINF AND GROUT.
5. USE No. 5 BAR REINF UNLESS OTHERWISE NOTED ON PLANS.
PROVIDE VERTICAL BARS TO ALIGN WITH
VERTICAL WALL REINFORCEMENT, MATCH
SIZE AND EXTEND 48 BAR DIAMETERS
INTO FOUNDATION WALL BELOW AND
INTO BLOCK CMU WALL ABOVE
OPENING EDGE, TYP
EXTEND REINFORCEMENT
2'-0" MIN BEYOND
MIN LAP 48
BAR…
This is the start of the file's text. The full file is on GovTribe.