PF240407JA Amendment 2 Q&A .pdf
PDF 154 KB Posted
- Attached to
- WDFW Incubation chiller system
- Solicitation number
- PF240407JA
- Issued by
- Skagit County, Washington
About this file
This document is an amendment to a Request for Quotation (RFQ) issued by the Washington Department of Fish and Wildlife (WDFW) for an incubation chiller system to be delivered to the Marblemount Hatchery. The amendment provides responses to questions regarding the minimum water temperature, minimum operating load, purpose of the containerized system, and the acceptability of an FRP tank in place of the 200-gallon stainless steel tank. The amendment also clarifies that the cooling tower is intended to minimize the amount of water used for the chiller unit.
The RFQ is seeking bids for the incubation chiller system, which will be installed by WDFW at the Marblemount Hatchery. The project is located in Skagit County, Washington. The amendment does not provide any information on the quantities, response dates, due dates, site visits, bidder's meetings, award dates, or the term of the contract.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| PF240407JA.pdf | ||
| PF240407JA Amendment 1 .pdf | ||
| PF240407JA.pdf.crdownload | CRDOWNLOAD file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Washington Department of Fish and Wildlife Request for Quotation Amendment
Quotation No.:
PF240407JA
Title:
WDFW Incubation chiller System
Date issued: August 22, 2024
Amendment No: 2
Purpose: The purpose of this amendment is to provide responses to questions asked
All other terms, conditions, and specifications remain unchanged.
Attachments: None
Q -What is the minimum water temperature required for the incubation system. A-Minimum temperature would be: 37 degrees F Q- Maximum operating load willb e 60gpm @10F DeltaT. What will be the minimum operating load? (60GPM @ _____Delta) A-Min. operating load is 6gpm @ 10F Delta-T Q-What is the purpos of the containerized system? Outdoor exposure concerns, transportability, etc? A-The purpose of the containerized system is to protect it from the elements, noise reduction and for consolidation.
Q-Will a pressure rated FRP Tank be acceptable in place of the 200-gallon stainless steel tank?
A-No, we would not accept an FRP tank.
Q-Will alternate, DX designs be accepted with/without container? A-Need further detail on “DX designs” to determine whether they would be acceptable or not.
For clarification purposes, the cooling tower is to minimize the amount of water used for this chiller unit. This unit only utilizes 68 gpm to provide 60 gpm of chilled water, other units use 120 gpm to put out 60 gpm.
As a reminder any questions must be directed to JoAnna Anderson at contractspurchasing@dfw.wa.gov .