Pages from OIT-InfrastrucStdTelecomSpaces-AppxB-2023-06-01-GMAC.pdf

PDF 1 MB Posted

Attached to
5999--459 | Telecommunications Racks
Solicitation number
36C24W25Q0276
Issued by

About this file

This document is a design guide template for the Department of Veterans Affairs (VA) Enterprise Data Center and Infrastructure Collaboration Team, specifically focusing on telecommunications infrastructure standards. The document provides detailed technical specifications and visual diagrams for various data center components, including:

  1. UTP (Unshielded Twisted Pair) media details, featuring recommended copper trunk cables with specific part numbers, connector types, and cable assemblies. 2. Network rack designs, including vertical cable management systems with dimensions of 76.94" height and 10.26" width, featuring security door options and cable management capabilities. 3. Power Distribution Unit (PDU) specifications for different zones and rooms, including 30A and 60A three-phase zone PDUs with detailed input/output voltage requirements. 4. Uninterruptible Power Supply (UPS) options for computer rooms, telecom, and entrance rooms, showcasing modular UPS systems from manufacturers like Eaton and APC with varying capacities and mounting configurations. 5. Temperature and humidity monitoring equipment, including rack-mounted sensors and placement guidelines for environmental monitoring in data center infrastructure.

View the file

Other files

File Type Posted
36C24W25Q0276_2.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT:

DRAWING No:

DATE

ISSUE:

DESCRIPTIONMARK

FILE:

OIT_DESIGN_GUIDE_TEMPLATES-V4 -

TD.VSDX

DESIGN BY: KEVIN GRZELKA, CTDC

VERIFIED BY:

DOC VERSION No:

PROJECT NO:

SHEET TITLE

ISSUE DATE: June 1, 2023

SHEET: 46 OF 57

MICHAEL JULIAN, RCDD

JOHN WERNAU, KELLY BATES

4.0

OIT DESIGN GUIDE TEMPLATES

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

UTP MEDIA DETAILS

DEPARTMENT OF VETERANS

AFFAIRS

ENTERPRISE DATA CENTER

INFRASTRUCTURE COLLABORATION TEAM

OFFICE OF INFORMATION AND

TECHNOLOGY

INFRASTRUCTURE OPERATIONS –

APPLICATION HOSTING, CLOUD AND

EDGE SOLUTIONS

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

RECOMMENDED UTP PATCH PANEL

LEVITON E2XHD-BLK HIGH-DENSITY ANGLED

48 POSITION

ONE RU PER PANEL

WITH REAR CABLE MANAGER

ANGLED PANEL COVERS

A-SIDE JACK COLOR: BLUE

A-SIDE UTP TRUNK CABLES

UTP PATCH PANEL

PART NUMBER: CTA-U6AP06LXXXF-CLNXA24N-CLNXA24N-CB01E WHERE XXX IS THE LENGTH IN FT

DESCRIPTION:

CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

TESTED TO ANSI/TIA 568.2-D

CUSTOM LABELING, NO PULLING EYE

FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN. BREAKOUT LENGTH. SECOND

END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN. BREAKOUT LENGTH

B-SIDE UTP TRUNK CABLES

B-SIDE JACK COLOR: YELLOW

PART NUMBER: CTA-U6AP06LXXXF-CYNXA24N-CYNXA24N-CB01E WHERE XXX IS THE LENGTH IN FT

DESCRIPTION:

CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

TESTED TO ANSI/TIA 568.2-D

CUSTOM LABELING, NO PULLING EYE

FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK 24 IN. BREAKOUT LENGTH. SECOND

END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK 24 IN. BREAKOUT LENGTH

PART NUMBER: CTA-U6AP06LXXXF-CLNXA24N-CYNXA24N-CB01E WHERE XXX IS THE LENGTH IN FT

DESCRIPTION:

CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

TESTED TO ANSI/TIA 568.2-D

CUSTOM LABELING, NO PULLING EYE

FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN. BREAKOUT LENGTH. SECOND END

TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK 24 IN. BREAKOUT LENGTH

A-SIDE TO B-SIDE CROSS CONNECT UTP TRUNK CABLES

B-SIDE JACK COLOR: YELLOWB-SIDE JACK COLOR: YELLOWA-SIDE JACK COLOR: BLUEA-SIDE JACK COLOR: BLUE

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

VHAHONOshirL Rectangle

DATE

ISSUE:

DESCRIPTIONMARK

FILE:

OIT_DESIGN_GUIDE_TEMPLATES-V4 -

TD.VSDX

DESIGN BY: KEVIN GRZELKA, CTDC

VERIFIED BY:

DOC VERSION No:

PROJECT NO:

SHEET TITLE

ISSUE DATE: June 1, 2023

SHEET: 53 OF 57

MICHAEL JULIAN, RCDD

JOHN WERNAU, KELLY BATES

4.0

OIT DESIGN GUIDE TEMPLATES

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL NETWORK RACK

DEPARTMENT OF VETERANS

AFFAIRS

ENTERPRISE DATA CENTER

INFRASTRUCTURE COLLABORATION TEAM

OFFICE OF INFORMATION AND

TECHNOLOGY

INFRASTRUCTURE OPERATIONS –

APPLICATION HOSTING, CLOUD AND

EDGE SOLUTIONS

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

6 IN. WIDE VERTICAL CABLE MANAGEMENT3

P/N: OR-MM20VMD706 (OR EQUIVALENT)

MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH DOOR,

6.45 IN. X 10.26 IN. X 76.94 IN. WHITE

CAPACITY: 350 CATEGORY 6A PATCH CORDS OR 245

CATEGORY 6A PATCH CORDS

LARGER VCM AUTHORIZED IN ACCORDANCE WITH CABLING

REQUIREMENT

6 IN

TYPICAL RACK DIMENSIONS AND SPECIFICATIONS2

FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-MM20724PDHD-W) (OPTIONAL)

SECURITY DOOR FRONT MOUNTAING HARDWARE

(OR-MM2024DMFHD-W)

SECURITY DOOR REAR MOUNTING HARDWARE

(OR-MM2024DMRHD-W)

PDU MOUNTING BRAACKET KIT (TWO KITS

PER RACK)

P/N: OR-MM20PDUMB1D2W-W

NOTE: TELECOMMUNICATION CHANNEL RACKS ARE REQUIRED IN ALL

TELECOMMUNICATION ROOMS. TELECOMMUNICATION CHANNEL RACKS OR

TELECOMMUNICATION CABINETS MAY BE USED IN THE HORIZONTAL AND

MAIN DISTRIBUTION AREAS.

P/N: OR-MM2073038-W (OR EQUIVALENT)

MIGHTY MO 20 CABLE MANAGEMENT RACK

30 IN. CHANNEL DEPTH, 7 FT HIGH, WHITE FINISH OR EQUIVALENT

DIMENSIONS:

USABLE HEIGHT: 45 RU

DEPTH (US): 30 IN.

HEIGHT (US): 7 FT

WIDTH (US): 23.75 IN.

STATIC LOAD CAPACITY: 2000 LB

SQUARE HOLE

DATE

ISSUE:

DESCRIPTIONMARK

FILE:

OIT_DESIGN_GUIDE_TEMPLATES-V4 -

TD.VSDX

DESIGN BY: KEVIN GRZELKA, CTDC

VERIFIED BY:

DOC VERSION No:

PROJECT NO:

SHEET TITLE

ISSUE DATE: June 1, 2023

SHEET: 55 OF 57

MICHAEL JULIAN, RCDD

JOHN WERNAU, KELLY BATES

4.0

OIT DESIGN GUIDE TEMPLATES

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL RACK AND ZONE PDUS

DEPARTMENT OF VETERANS

AFFAIRS

ENTERPRISE DATA CENTER

INFRASTRUCTURE COLLABORATION TEAM

OFFICE OF INFORMATION AND

TECHNOLOGY

INFRASTRUCTURE OPERATIONS –

APPLICATION HOSTING, CLOUD AND

EDGE SOLUTIONS

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

CHATSWORTH ECONNECT PDU OR EQUIVALENT; VERTICAL; MONITORED;

L21-20 PLUG; THREE-PHASE; 120/208 V INPUT; 20 A; (30) C13 (6)

C19 OUTLETS; 208 V OUTPUT; 3 X 2P 20 A; LCD; ETHERNET, USB,

AND ENVIRONMENTAL SENSOR PORTS; IP AND SERIAL MONITORING; IP

CONSOLIDATION (PDU LINKING); TOOL-LESS MOUNTING; 70.5 IN. H (1791

MM) X 2.2 IN. W (56 MM) X 2.2 IN. D (56 MM)

30 A THREE-PHASE ZONE PDU BASE UNIT – REAR CIRCUITS WITH FOUR L21-20R AND SIX

NEMA 5-20 OUTLETS AND TWO 10 FT POWER CORDS TERMINATING IN L21-30P

ZONIT ZPDS-208V30A-L21-4L21-20R-CR OR EQUIVALENT

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2

C H

A T

S W

O R

T H

P R

O D

U C

T

T e m p

/H u m id ity O u t

In

/ IO

IO

IO

/1

R e s e t

W a rn in g

O K

C ritic a l

CB2

CB2

CB1

CB1

CB1

CB1

CB3

CB3

CB3

CB3

CB2

CB2

O F

F

O

O

NI

C B

O F

F

O

O

NI

C B

O F

F

O

O

NI

C B

60 A THREE-PHASE ZONE PDU BASE UNIT - REAR SIX L21-20R OUTPUT RECEPTACLES WITH 10 FT POWER CORDS

TERMINATING IN HARDWIRE BOX

ZONIT ZPDS-208V60A-HW-6L21-20R OR EQUIVALENT

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

LEG 2LEG 1

APC AP8861 RPDU OR EQUIVALENT; RACK PDU 2G,

METERED; L21-20 PLUG; THREE-PHASE; 120/208 V INPUT;

20 A; ZERO U; 5.7 KW, 208V, (36) C13 & (6) C19 & (2)

5-20 OUTLETS; FOR USE IN TELECOMMUNICATIONS ROOMS

AND LOCATIONS WITH LEGACY 110 V ONLY EQUIPMENT

R A

C K

P D

U R

A C

K P

D U

REQUIRES ONE L21-20R

20A

120/ 208V

Y

REQUIRES ONE L21-20R

20A

120/ 208V

Y

REQUIRES ONE L21-20R

20A

120/ 208V

Y

REQUIRES ONE L21-20R

20A

120/ 208V

Y

THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM TWO INDEPENDENT POWER SOURCES.

EACH INPUT WILL USE IDENTICAL SPECS: WYE (5-WIRE), 208 V, 30 A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

NOTE: THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM TWO INDEPENDENT POWER SOURCES.

EACH INPUT WILL USE IDENTICAL SPECS: WYE (5-WIRE), 208 V, 30 A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

NOTE: NOTE: THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM TWO INDEPENDENT POWER SOURCES. EACH

INPUT WILL USE IDENTICAL SPECS: WYE (5-WIRE), 208 V, 60 A, THREE-PHASE, TERMINATING IN A JUNCTION BOX TO BE HARDWIRED INTO THE ZONE PDU. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

NOTE: THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM TWO INDEPENDENT POWER SOURCES. EACH

INPUT WILL USE IDENTICAL SPECS: WYE (5-WIRE), 208 V, 60 A, THREE-PHASE, TERMINATING IN A JUNCTION BOX TO BE HARDWIRED INTO THE ZONE PDU. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE ZONE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

APC AP9560 OR EQUIVALENT RACK MOUNT PDU; L5-30 PLUG;

(10) NEMA 5-20 OUTLETS; 1 RU; TWO PER ENCLOSURE;

ONE ENERGIZED BY UPS; ONE ENERGIZED BY WALL OUTLET

SPECIFICATIONS: RATED INPUT VOLTAGE: 208 V THREE-PHASE; AMPERAGE: 60 A

INPUT CORD TERMINATION: HARDWIRE BOX

OUTPUT RECEPTACLES: SIX L21-20R

OUTPUT BRANCH CIRCUIT PROTECTION:

INDIVIDUAL 20 A CIRCUIT BREAKERS PROTECT EACH OUTPUT PHASE

OF EACH OUTPUT RECEPTACLE

SPECIFICATIONS: RATED INPUT VOLTAGE: 208 V THREE-PHASE; AMPERAGE: 60 A

INPUT CORD TERMINATION: HARDWIRE BOX

OUTPUT RECEPTACLES: SIX L21-20R

OUTPUT BRANCH CIRCUIT PROTECTION:

INDIVIDUAL 20 A CIRCUIT BREAKERS PROTECT EACH OUTPUT PHASE

OF EACH OUTPUT RECEPTACLE

ZONE PDU INPUTS

REQUIRE TWO L21-30RS

ZONE PDU INPUTS

REQUIRE TWO L21-30RS

TYPICAL 30A ZONE PDU

TYPICAL 30A ZONE PDU

4 TYPICAL 60A ZONE PDU

TYPICAL 60A ZONE PDU

USED IN TELECOMMUNICATIONS ROOMS AND ENTRANCE

ROOMS WHERE 110 V DISTRIBUTION USING NEMA 5-15 OR

NEMA 5-20 RECEPTACLES ARE REQUIRED IN ADDITION TO

THE STANDARD 208 V

NOTE: USED IN TELECOMMUNICATIONS ROOMS AND ENTRANCE

ROOMS WHERE 110 V DISTRIBUTION USING NEMA 5-15 OR

NEMA 5-20 RECEPTACLES ARE REQUIRED IN ADDITION TO

THE STANDARD 208 V

NOTE:

208V RACK PDU FOR COMPUTER ROOMS

208V RACK PDU FOR COMPUTER ROOMS

208V RACK PDU FOR TRS AND ENTRANCE ROOMS2120V RACK PDU FOR TES

120V RACK PDU FOR TES

USED IN TELECOMMUNICATIONS ENCLOSURES ONLYNOTE: USED IN TELECOMMUNICATIONS ENCLOSURES ONLYNOTE:

REQUIRES ONE L5-30RREQUIRES ONE L5-30R

DATE

ISSUE:

DESCRIPTIONMARK

FILE:

OIT_DESIGN_GUIDE_TEMPLATES-V4 -

TD.VSDX

DESIGN BY: KEVIN GRZELKA, CTDC

VERIFIED BY:

DOC VERSION No:

PROJECT NO:

SHEET TITLE

ISSUE DATE: June 1, 2023

SHEET: 56 OF 57

MICHAEL JULIAN, RCDD

JOHN WERNAU, KELLY BATES

4.0

OIT DESIGN GUIDE TEMPLATES

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL UPSS

DEPARTMENT OF VETERANS

AFFAIRS

ENTERPRISE DATA CENTER

INFRASTRUCTURE COLLABORATION TEAM

OFFICE OF INFORMATION AND

TECHNOLOGY

INFRASTRUCTURE OPERATIONS –

APPLICATION HOSTING, CLOUD AND

EDGE SOLUTIONS

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

EATON 93PM (93PM-L FOR 208 V MODEL)

• CLEARANCE

• FRONT: 36 IN.

• BACK (TOP EXHAUST): 0 IN.

• BACK (REAR EXHAUST): 10 IN.

• BATTERY CABINET

• 16.7 IN. FOR SMALL

• 34.2 IN. FOR LARGE

• DISTRIBUTION PANEL

31.3 IN.

APC SYMMETRA PX 10-100

1 RACK-MOUNT 5 KW UPS FOR TRS AND ENTRANCE ROOMS

RACK MOUNT UPS.

CAPACITY: 5 KW (EXTERNAL BATTERY MODULES AVAILABLE)

INPUT VOLTAGE: 208 V

INPUT CONNECTION: L21-20P, THREE-PHASE, FOUR-WIRE +

GROUND

OUTPUT CONNECTION: L21-20R

SIZE: 6 RU, 19 IN. RACK-MOUNTABLE

RUNTIME: 16.5 MINUTES AT 50% LOAD

(EATON BLADEUPS ZC0517700110000

OR EQUIVALENT)

Smart-UPS 3000

Esc

• CLEARANCE

• FRONT: 36 IN.

• REAR: 40 IN.

• BATTERY CABINET

• 23.62 IN.

• DISTRIBUTION PANEL

• 11.8 IN.

• BYPASS

• 11.8 IN.

• POWER MODULES

23.62 IN.

P O

W E

R M

O D

U

LE

B Y

P A

S S

B A

T

TE

R Y

C

A B

IN

E

T

D

IS

T R

O

P O

W E

R M

O D

U

LE

B Y

P A

S S

B A

T

TE

B

IN

E

T

D

IS

T R

O

• CLEARANCE

• FRONT: 36 IN.

• REAR: 40 IN.

• BATTERY CABINET

• 23.62 IN.

• DISTRIBUTION PANEL

• 11.8 IN.

• BYPASS

• 11.8 IN.

• POWER MODULES

23.62 IN.

P O

W E

R M

O D

U

LE

B Y

P A

S S

B A

T

TE

B

IN

E

T

D

IS

T R

O

D

IS

TR

O

P

N

E L

B A

TTE

B

IN

E T

P O

W E

M

D U

LE

S

B Y

P A

S S

D

IS

N

E L

B A

TTE

B

IN

E T

P O

W

D U

LE

S

B Y

P A

S S

B A

TTE

B

IN

E T

P O

W

D U

LE

S

B Y

P A

S S

D

IS

N

E L

B A

TTE

B

IN

E T

P O

W

D U

LE

S

B Y

P A

S S

D

IS

N

E L

• BYPASS

• 14.69 IN. FOR 480 V

• 12.45 IN. FOR 208 V

• POWER MODULES

• 480 V

• 30-150 KW – 22 IN.

• 160-200 KW – 32 IN.

• 208 V

• 10-120 KW – 22 IN.

• 10-160 KW – 34.4 IN.

10-200 KW – 43.3 IN

20A 120/ 208V

Y

2 RACK-MOUNT 2.88 KW UPS FOR TES

4 MODULAR UPS OPTION SFOR COMPUTER ROOMS3 MODULAR UPS OPTION FOR COMPUTER ROOMS

RACK MOUNT UPS. L5-30 INPUT. L5-30 OUTPUT.

CAPACITY NTE 2880 VA. 2 RU. METERED

(APC SMX3000RMLV2U OR EQUIVALENT)

10-100 KW MODULAR UPS

FRAME COMMENSURATE WITH COMPUTER ROOM

ULTIMATE CAPACITY; POWER MODULES BUILT OUT

TO N+1 INTERNAL REDUNDANCY BASED ON

CRITICAL LOAD

REQUIRES FRONT AND REAR CLEARANCE

10-200 KW MODULAR UPS

FRAME COMMENSURATE WITH COMPUTER ROOM ULTIMATE CAPACITY; POWER MODULES

BUILT OUT TO N+1 INTERNAL REDUNDANCY BASED ON CRITICAL LOAD

ONLY REQUIRES FRONT CLEARANCE

DATE

ISSUE:

DESCRIPTIONMARK

FILE:

OIT_DESIGN_GUIDE_TEMPLATES-V4 -

TD.VSDX

DESIGN BY: KEVIN GRZELKA, CTDC

VERIFIED BY:

DOC VERSION No:

PROJECT NO:

SHEET TITLE

ISSUE DATE: June 1, 2023

SHEET: 57 OF 57

MICHAEL JULIAN, RCDD

JOHN WERNAU, KELLY BATES

4.0

OIT DESIGN GUIDE TEMPLATES

N/A

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL TEMPERATURE AND

HUMIDITY MONITORING

DEPARTMENT OF VETERANS

AFFAIRS

ENTERPRISE DATA CENTER

INFRASTRUCTURE COLLABORATION TEAM

OFFICE OF INFORMATION AND

TECHNOLOGY

INFRASTRUCTURE OPERATIONS –

APPLICATION HOSTING, CLOUD AND

EDGE SOLUTIONS

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

CHATSWORTH 14665-001

USB TEMPERATURE AND

HUMIDITY SENSOR (OR

EQUIVALENT)

EcoControl4

A u x

A u x

R e s e t

Console 2

O K

W a rn in g

C ritic a l

/1

/1

C o n s o le

O u t

In

/ IO

IO

IO

Secure Array

EcoControl4

A u x

A u x

R e s e t

Console 2

O K

W a rn in g

C ritic a l

/1

/1

C o n s o le

O u t

In

/ IO

IO

IO

Secure Array

FRONT OF RACK

BACK OF RACK

TEMPERATURE AND HUMIDITY SENSOR

TEMPERATURE AND HUMIDITY SENSOR LOCATIONS AND CONNECTIONS

File details come from the government source that posted it. Updated .