Page_C-103.00_Cable_Conductor_Wire_Primary_Overhead_Copper_4.6.26.pdf

PDF 159 KB Posted

Attached to
Annual Procurement of Wire & Cable
Solicitation number
RFP 2026-067
Issued by
Alachua County, Graceville City, Florida

About this file

This is an Approved Materials Manual excerpt from Gainesville Regional Utilities (GRU) Electric System in Florida, detailing specifications for overhead copper conductor wire products. The document specifies multiple conductor types and gauges available for procurement, including soft-drawn bare solid copper (No. 6 and No. 4), hard-drawn bare solid copper in various gauges (No. 6, No. 4, No. 2, No. 1/0, No. 4/0, and No. 750 STR), with specifications for weight per 1,000 feet, ampacity ratings, and outside diameter measurements. The related contract opportunity indicates that GRU seeks supplier(s) for a five-year contract to furnish one or more groups of wire and cable products, with the objective of generating supply chain efficiencies and reducing total cost of ownership through cooperative partnerships between GRU, successful suppliers, and manufacturers.

The materials manual establishes that manufacturers will be selected based on conformance to the specified technical requirements outlined in the document. All conductor products must comply with packaging standards referenced in the Cable Supplementary Conditions on pages C-9.00 through C-9.02 of the manual. The specifications provide detailed performance metrics including ampacity ratings ranging from 125 amps for No. 6 solid copper to 1,040 amps for No. 750 STR hard-drawn copper, enabling GRU to procure appropriate conductors for various electrical system applications. The five-year contract structure allows for long-term supplier relationships while maintaining flexibility to source multiple product groups from qualified vendors.

View the file

Other files

File Type Posted
Annual_Procurement_of_Wire_&_Cable_(Addendum_#7_Revision).pdf PDF
Annual_Procurement_of_Wire_&_Cable_(Addendum_#4_Revision).pdf PDF
Page_C-26.02_Cable_Conductor_Wire_Primary_Underground_EPR_Revised_5.19.26.pdf PDF
Page_C-26.00_Cable_Conductor_Wire_Primary_Underground_EPR_Technical_Specifications_5.5.26_revised.pdf PDF
Page_C-30.00_Cable_Conductor_Wire_Underground_Secondary_4.6.26.pdf PDF
Page_C-32.00_Cable_Conductor_Wire_Primary_Overhead_Aerial_4.6.26.pdf PDF
Page_C-9.00_-_C-9.03_Supplementary_Conditions.pdf PDF
Page_C-105.00_Cable_Conductor_Wire_Primary_Overhead_Aluminum_4.6.26.pdf PDF
Page_C-31.00_Cable_Conductor_Wire_Primary_Overhead_Aerial_Technical_Specifications_4.6.26.pdf PDF
Page_C-10.00_Cable_Conductor_Wire_Overhead_Secondary_4.6.26.pdf PDF
Page_C-20.00_Cable_Conductor_Wire_Primary_Underground_Copper_4.6.26.pdf PDF
Cable_Conductor_Wire_Overhead_Secondary_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aluminum_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aerial_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aerial_Technical_Specifications_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_EPR_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Copper_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_Copper_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_EPR_Technical_Specifications_4.6.26.pdf PDF
Cable_Conductor_Wire_Supplementary_Conditions_4.6.26.pdf PDF
Cable_Conductor_Wire_Underground_Secondary_4.6.26.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Stock No.Catalog No.ManufacturerDescription

ITEM NAME

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (SOLID COPPER)

Page C - 105.30

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

OVERHEAD CONDUCTOR SOFT DRAWN BARE

SOLID COPPER.

NO. 6

WEIGHT: 79.5 LBS/1000'

AMPACITY: 125

OUTSIDE DIAMETER: O.162"

NO. 4

WEIGHT: 126.4 LBS/1000'

AMPACITY: 170

OUTSIDE DIAMETER: 0.204"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00, THRU C-9.02, THIS MANUAL.

03055-4

76570-8

3-24-87 7-11-88

C D

L

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 105.40

56605-5

27426-7

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

OVERHEAD CONDUCTOR HARD DRAWN BARE SOLID

COPPER.

NO. 6

WEIGHT: 79.5 LBS/1000'

AMPACITY: 125

OUTSIDE DIAMETER: O.162"

NO. 4

WEIGHT: 126.4 LBS/1000'

AMPACITY: 185

OUTSIDE DIAMETER: 0.204"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

SUPPLEMENTARY CONDITIONS, ON PAGES C-9.00,

THRU C-9.02,THIS MANUAL.

1-25-88 7-11-88

C D

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 105.50

OVERHEAD CONDUCTOR

HARD DRAWN COPPER

NO. 2,7 STR.

(66.37 KCMIL):

WEIGHT: 204.9LBS./1000'

AMPACITY: 2 50

OUTSIDE DIA.: 0.292"

NO. 1/0, 7 STR.

(105.5 KCMIL):

WEIGHT: 325.7 LBS./1000'

AMPACITY: 335

OUTSIDE DIA.: 0.368"

NO. 4/0, 7 STR.

(211.6 KCMIL)

WEIGHT: 653.3 LBS./1000'

AMPACITY: 480

OUTSIDE DIA.: 0.522"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00 THRU C-9.02, THIS MANUAL.

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

36176-3

43481-7

54966-5

1-25-88 7-11-88

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 107.00

OVERHEAD CONDUCTOR

HARD DRAWN COPPER

NO. 750 STR. (61)

WEIGHT: 2316.0 LBS./1000'

AMPACITY: 1040

OUTSIDE DIA.: 0.998"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00 THRU C-9.02, THIS MANUAL.

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

45245-9

8-24-01 KLC L

File details come from the government source that posted it. Updated .