Cable_Conductor_Wire_Primary_Overhead_Copper_4.6.26.pdf

PDF 159 KB Posted

Attached to
Annual Procurement of Wire & Cable
Solicitation number
RFP 2026-067
Issued by
Alachua County, Graceville City, Florida

About this file

This is an Approved Materials Manual specification document from Gainesville Regional Utilities (GRU) Electric System outlining overhead copper conductor wire specifications for a five-year annual procurement contract. The manual details multiple conductor types and gauges, including soft-drawn bare solid copper (No. 6 and No. 4), hard-drawn bare solid copper (No. 6, No. 4, No. 2, No. 1/0, and No. 4/0), and large-capacity hard-drawn copper conductors (No. 750 STR). Each specification includes electrical characteristics such as ampacity ratings ranging from 125 amps for No. 6 gauge up to 1,040 amps for No. 750 STR, physical dimensions, and weight per 1,000 feet. All materials must conform to GRU specifications with manufacturers selected based on compliance standards. Packaging requirements are referenced in the manual's supplementary conditions sections (pages C-9.00 through C-9.02).

GRU's procurement objective is to establish supplier agreements that generate supply chain efficiencies while reducing total cost of ownership through cooperative efforts between the utility and successful suppliers and their manufacturers. The contract structure allows for multiple suppliers to be awarded for different wire and cable product groups, with the five-year term designed to provide stability and cost optimization opportunities. Specific pricing, set-aside provisions, contract award dates, and response deadlines are not detailed in this specifications document but would be contained in the associated RFP documentation.

View the file

Other files

File Type Posted
Annual_Procurement_of_Wire_&_Cable_(Addendum_#7_Revision).pdf PDF
Annual_Procurement_of_Wire_&_Cable_(Addendum_#4_Revision).pdf PDF
Page_C-26.02_Cable_Conductor_Wire_Primary_Underground_EPR_Revised_5.19.26.pdf PDF
Page_C-26.00_Cable_Conductor_Wire_Primary_Underground_EPR_Technical_Specifications_5.5.26_revised.pdf PDF
Page_C-10.00_Cable_Conductor_Wire_Overhead_Secondary_4.6.26.pdf PDF
Page_C-30.00_Cable_Conductor_Wire_Underground_Secondary_4.6.26.pdf PDF
Page_C-32.00_Cable_Conductor_Wire_Primary_Overhead_Aerial_4.6.26.pdf PDF
Page_C-9.00_-_C-9.03_Supplementary_Conditions.pdf PDF
Page_C-105.00_Cable_Conductor_Wire_Primary_Overhead_Aluminum_4.6.26.pdf PDF
Page_C-31.00_Cable_Conductor_Wire_Primary_Overhead_Aerial_Technical_Specifications_4.6.26.pdf PDF
Page_C-103.00_Cable_Conductor_Wire_Primary_Overhead_Copper_4.6.26.pdf PDF
Page_C-20.00_Cable_Conductor_Wire_Primary_Underground_Copper_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aerial_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aerial_Technical_Specifications_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_EPR_4.6.26.pdf PDF
Cable_Conductor_Wire_Overhead_Secondary_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Overhead_Aluminum_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_Copper_4.6.26.pdf PDF
Cable_Conductor_Wire_Primary_Underground_EPR_Technical_Specifications_4.6.26.pdf PDF
Cable_Conductor_Wire_Supplementary_Conditions_4.6.26.pdf PDF
Cable_Conductor_Wire_Underground_Secondary_4.6.26.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Stock No.Catalog No.ManufacturerDescription

ITEM NAME

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (SOLID COPPER)

Page C - 105.30

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

OVERHEAD CONDUCTOR SOFT DRAWN BARE

SOLID COPPER.

NO. 6

WEIGHT: 79.5 LBS/1000'

AMPACITY: 125

OUTSIDE DIAMETER: O.162"

NO. 4

WEIGHT: 126.4 LBS/1000'

AMPACITY: 170

OUTSIDE DIAMETER: 0.204"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00, THRU C-9.02, THIS MANUAL.

03055-4

76570-8

3-24-87 7-11-88

C D

L

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 105.40

56605-5

27426-7

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

OVERHEAD CONDUCTOR HARD DRAWN BARE SOLID

COPPER.

NO. 6

WEIGHT: 79.5 LBS/1000'

AMPACITY: 125

OUTSIDE DIAMETER: O.162"

NO. 4

WEIGHT: 126.4 LBS/1000'

AMPACITY: 185

OUTSIDE DIAMETER: 0.204"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

SUPPLEMENTARY CONDITIONS, ON PAGES C-9.00,

THRU C-9.02,THIS MANUAL.

1-25-88 7-11-88

C D

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 105.50

OVERHEAD CONDUCTOR

HARD DRAWN COPPER

NO. 2,7 STR.

(66.37 KCMIL):

WEIGHT: 204.9LBS./1000'

AMPACITY: 2 50

OUTSIDE DIA.: 0.292"

NO. 1/0, 7 STR.

(105.5 KCMIL):

WEIGHT: 325.7 LBS./1000'

AMPACITY: 335

OUTSIDE DIA.: 0.368"

NO. 4/0, 7 STR.

(211.6 KCMIL)

WEIGHT: 653.3 LBS./1000'

AMPACITY: 480

OUTSIDE DIA.: 0.522"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00 THRU C-9.02, THIS MANUAL.

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

36176-3

43481-7

54966-5

1-25-88 7-11-88

Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y

SM

TM

CONDUCTOR, OVERHEAD (HARD DRAWN COPPER)

Page C - 107.00

OVERHEAD CONDUCTOR

HARD DRAWN COPPER

NO. 750 STR. (61)

WEIGHT: 2316.0 LBS./1000'

AMPACITY: 1040

OUTSIDE DIA.: 0.998"

PACKAGING SHALL BE IN ACCORDANCE WITH THE

CABLE SUPPLEMENTARY CONDITIONS, ON PAGES

C-9.00 THRU C-9.02, THIS MANUAL.

MANUFACTURER TO BE

SELECTED BASED ON

CONFORMANCE TO

SPECIFICATIONS

45245-9

8-24-01 KLC L