P12 Project Drawings (1).pdf
PDF 15 MB Posted
- Solicitation number
- 36C24921R0124
About this file
This document provides details for a federal contract solicitation to upgrade elevators at a Veterans Affairs facility. The solicitation number is 36C24921R0124 and concerns upgrades to elevators P4, P5, S6, and S7 at the Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 facility. Responses are due by 596-21-1-5848-0001. The work includes upgrading the specified elevators. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24921R0124 0002.docx | DOCX document | |
| Pit Ladder Detail.pdf | ||
| Attestation Guidance for Health and Safety Precautions for COVID-19.pdf | ||
| Solicitation RFIs_596A4-18-103.pdf | ||
| Current COVID-19 Workplace Safety Requirements.pdf | ||
| Site Visit Sign-in Sheet.pdf | ||
| 36C24921R0124 0001.docx | DOCX document | |
| Wage Determination KY20210090 3-5-2021.pdf | ||
| Statement of Work.pdf | ||
| P12 Project Drawings.pdf | ||
| Past Performance Questionnaire.pdf | ||
| P12 Project Specifications.pdf | ||
| Copy of eCMS Line Item Template - updated version 1.1.xlsx | XLSX spreadsheet | |
| 36C24921R0124_1.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P
M
COVER SHEET
JAB
GI001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
BID DOCUMENTS
PROJECT # 596A4-18-103
UPGRADE ELEVATORS P4, P5, S6, AND S7
LEXINGTON VA MEDICAL CENTER
VICINITY MAP CAMPUS MAPVICINITY MAP
1 4
LEXINGTON
VA MEDICAL
CENTER CAMPUS
LEXINGTON
VA MEDICAL
CENTER CAMPUS
LOCATION
INDEX OF DRAWINGS
GENERAL
ARCHITECTURE
COVER SHEETGI001
A-102
A-101
GI002 2 OF 4GENERAL INFORMATION
ELECTRICAL
ED101
E-001
ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, ABBREVIATIONS, AND SCHEDULES
PARKING GARAGE LEVEL 'C' POWER PLAN
ELECTRICAL DEMOLITION PLANS
GROUND FLOOR TRANSFORMER & SWITCHGEAR ELECTRICAL DEMOLITION PLANS
A-201
A-400
INFECTION CONTROL RISK ASSESSMENT - (ICRA)
GI003 3 OF 4
GI004 4 OF 4ICRA AND CONSTRUCTION PHASING PLANS
FIRE ALARM
FIRE ALARM NOTES, LEGEND, ABBREVIATIONS, AND RISER DIAGRAM
FA001
FA100
FA101
OVERALL GROUND FLOOR FIRE ALARM PLAN
PARKING GARAGE LEVEL 'C' AND FIFTH FLOOR ELEVATOR EQUIPMENT ROOM FIRE ALARM PLANS
OVERALL GROUND FLOOR PLAN AND CONSTRUCTION ROUTE
PARKING GARAGE FLOOR PLAN AND ENLARGED PLANS
SERVICE ELEVATOR CAB INTERIOR ELEVATIONS
ELEVATOR RISER DIAGRAM
A-202
PASSENGER ELEVATOR CAB INTERIOR ELEVATIONS
MECHANICAL
MECHANICAL PLANS, SCHEDULES AND CONTROLS
M-101 1 OF 1
JJG
NOTE:
FOR ALL ELEVATOR MODIFICATIONS - REFERENCE DIVISION 14 SPECIFICATIONS
THE ELEVATORS CAN BE DOWN FOR 1 HOUR MAXIMUM (COORDINATE WITH ELECTRICAL & VA COR).
AFTER 12:01AM ON A SATURDAY - CONTRACTOR TO PROVIDE SPECIAL SIGNAGE &
TRANSPORTATION FOR EMERGENCY STAFF AS REQUIRED
GROUND FLOOR TRANSFORMER & SWITCHGEAR POWER PLAN
ELECTRICAL HOISTWAY ELEVATION PLAN
ELECTRICAL DETAILS
ED102
EP101
EP102
E-201
E-501
NOTE: FOR ALL ELEVATOR MODIFICATIONS, SEE SPECIFICATIONS
ELEVATORS INCLUDED IN THIS PROJECT - P4, P5, S6, S7
ELEVATORS ARE LOCATED IN MAIN BUILDING 1A.
PREPARE FOR THE REPLACEMENT OF THE ATS.
FA102
FA103
OVERALL SECOND FLOOR FIRE ALARM PLAN
OVERALL THIRD FLOOR FIRE ALARM PLAN
11296
R E G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
T
H
C A
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
N
O
RT
R
O
L
I
N
A
DocuSign Envelope ID: 33FE4D5E-9D7F-48C9-B1D9-935AF5515DE0
8/7/2020
GENERAL NOTES:
ALL ELEVATOR SUBMITTALS TO BE REVIEWED & APPROVED
PRIOR TO MOBILIZATION
COMPLETE ONE ELEVATOR CAB BEFORE STARTING ANOTHER.
FINAL ELEVATOR EQUIPMENT PLANS WILL BE DESIGNED BY
ELEVATOR CONTRACTOR
THE CONTRACTOR AND SUBCONTRACTORS INVOLVED
IN THIS PROJECT SHALL BE RESPONSIBLE FOR
INSTALLING THEIR RESPECTIVE WORK AND
SYSTEMS TO MEET ALL APPLICABLE FEDERAL,
STATE, AND LOCAL CODES, LAWS, SAFETY
REGULATIONS, HAZARDOUS WASTE LAWS, ETC. THE
CONTRACTOR SHALL FURNISH ALL NECESSARY
PERMITS.
THE CONTRACTOR SHALL REVIEW THE DRAWINGS,
SPECIFICATIONS AND UNDERSTAND THE SCOPE OF THE
DRAWINGS TO BE THE FOLLOWING:
THESE CONSTRUCTION DOCUMENTS (DRAWINGS,
SPECIFICATIONS, ADDENDA, ETC.)
INDICATE THE GENERAL SCOPE OF THE PROJECT IN
TERMS OF ARCHITECTURAL DESIGN CONCEPTS, THE
DIMENSIONS OF THE BUILDING, THE MAJOR
ARCHITECTURAL ELEMENTS, AND THE MAJOR
STRUCTURAL, MECHANICAL, ELECTRICAL, AND DATA
SYSTEMS. ON THE BASIS OF THE GENERAL SCOPE
INDICATED IN THESE DOCUMENTS, THE TRADE
CONTRACTORS SHALL FURNISH ALL ITEMS REQUIRED
FOR THE PROPER EXECUTION AND COMPLETION OF THEIR
WORK. ALL WORK SHALL BE COMPLETE IN EVERY DETAIL
AND THE CONTRACTORS SHALL PROVIDE A ONE YEAR
WARRANTY FOR THEIR WORK UNLESS A LONGER
WARRANTY IS INDICATED IN THE SPECIFICATIONS.
CONTRACTORS SHALL FOLLOW AND OBEY APPLICABLE
FEDERAL, STATE AND LOCAL CODES, LAWS, SAFETY
REGULATIONS AND HAZARDOUS WASTE LAWS, ETC.
DO NOT SCALE DRAWINGS. DIMENSIONS SHALL
GOVERN EACH BUILDING COMPONENT LOCATION.
BRING DISCREPANCIES TO THE COR'S
ATTENTION IN WRITING IMMEDIATELY.
ALL WORK SHALL BE PERFORMED IN A SKILLED
WORKMANSHIP TYPE AND MANNER ACCEPTABLE TO
THE COR'S.
PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN
DIFFERENT MATERIALS.
EXISTING CONDITIONS SHALL BE FIELD VERIFIED PRIOR
TO BEGINNING OF WORK. ANY ERRORS OR OMISSIONS
SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION IN
WRITING IMMEDIATELY.
ALL CARS TO BE CONSTRUCTED ON THE GROUND FLOOR,
INSIDE THE SHAFT.
CONTRACTOR IS RESPONSIBLE FOR ALL SERVICE CALLS AND
SERVICES FOR ALL 5 ELEVATORS AFTER THE EXECUTION
AND DURING THE DURATION OF THEIR CONTRACT.
FOR OVERHEAD PIPE WORK ABOVE CEILING OUTSIDE THE
ARE OF WORK FOR THIS PROJECT, COORDINATE WITH VA COR
ABOUT OFF-HOUR SCHEDULE AND ICRA PROTECTION
REQUIREMENTS.
CONTRACTOR TO RE-LABEL ALL DOORS WITH SAME SIGNAGE AS
EXISTING FROM 290 SIGN COCOMPANY- (SOLE SOURCE)
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
SYMBOL LEGEND
SITE PLAN NORTH ARROW
BUILDING WALL SECTION INDICATION
DETAIL INDICATION
ROOM NAME
ROOM NUMBER
AREA DETAILED
NORTH ARROW
NORTH
LIMIT OF WORK
BREAK LINE
SECTION NUMBER
SHEET WHERE SHOWN
SHEET WHERE SHOWN
DETAIL NUMBER
KEYNOTE INDICATOR
ROOM NAME
A101
SIM
N
ROOM INDICATION
KEYNOTE SYMBOL
A101
X
EXISTING WALL
TEMPORARY BARRIER
CONSTRUCTION ROUTE
GENERAL DEMOLITION NOTES:
A. REMOVE EXISTING CONSTRUCTION AS
DESIGNATED HEREIN AND CLEAR AREA
OF DEBRIS PRIOR TO PROCEEDING WITH
NEW CONSTRUCTION.
B. EXISTING EQUIPMENT REMOVED
SHALL BE PROPERLY DISPOSED OFF
MEDICAL CENTER GROUNDS.
COORDINATE WITH VA COR.
C. NOTIFY CONTRACTING OFFICER'S
REPRESENTATIVE OF ANY AREA
REQUIRING DEMOLITION FOR
INSTALLATION OF MECHANICAL,
PLUMBING, STRUCTURAL, ELECTRICAL,
OR DATA ITEMS (INCLUDING ROOF
PENETRATIONS) NOT SHOWN IN THESE
DRAWINGS. AFTER SUCH DEMOLITION
AND INSTALLATION, PATCH OR REPLACE
MATERIALS AND FINISHES TO MATCH
EXISTING.
D. THE INFORMATION CONTAINED IN
THESE DEMOLITION DOCUMENTS DEFINES
GENERAL SCOPE ONLY AND DOES NOT
RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY OF PROVIDING ALL
DEMOLITION REQUIRED FOR THE
COMPLETION OF THE PROJECT.
E. REFER TO THE ENGINEER'S
SPECIFICATION & DRAWINGS FOR
FURTHER INFORMATION REGARDING
DEMOLITION OF MECHANICAL,
ELECTRICAL, PLUMBING & ELEVATOR
EQUIPMENT SYSTEMS.
F. ALL DEMOLITION WORK SHALL BE
PERFORMED WITH "CARE AND DILIGENCE"
IN ORDER TO PREVENT ARBITRARY
DAMAGE OR INTERRUPTION OF SERVICE
OR CONCEALED UTILITIES INTENDED TO
REMAIN IN SERVICE. DISCOVERY OF
UTILITIES OR CONDITIONS LOCATED
DIFFERENTLY FROM THAT INDICATED OR
THAT ARE NOT IDENTIFIED. SHALL BE
REPORTED TO THE CONTRACTING
OFFICER.
G. CONTRACTOR IS RESPONSIBLE TO
ENSURE LIGHTING, SMOKE DETECTOR
AND EXIT SIGNS WILL BE AVAILABLE
DURING CONSTRUCTION FOR EACH
PHASE. COORDINATE WITH VA COR AND
SAFETY ABOUT RELOCATION OF THESE
ELEMENTS PRIOR TO ERECTING
TEMPORARY CONSTRUCTION BARRIER.
A/C AIR CONDITIONING
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
A&E ARCHITECT AND ENGINEERS
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITIES HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ALT TRANS ALTERNATIVE TRANSPORTATION
ALUM ALMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BB BULLETIN BOARD
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOD BASIS OF DESIGN
BRG BEARING
CB CATCH BASIN
CBB CEMENTITIOUS BACKER BOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISH
CONTRACTOR INSTALL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
C & G CURB & GUTTER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNITS
CO CLEANOUT(S)
COL COLUMN
CONC CONCRETE
CONT COTINUOUS
COORD COORDINATE
CP CONCRETE PIPE
CPT CARPET
CR CRASH RAIL
CRS COLD ROLLED STEEL
CS CAST STONE
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION SPECIFICATIONS
INSTITUTE
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CY CUBIC YARD
D DRYER
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DISP DISPENSER
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EF EXHAUST FAN
EFTR EXISTING FINISH TO REMAIN
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATED
ETR EXISTING TO REMAIN
ETS EXPOSED TO STRUCTURE
ARCHITECTURAL ABBREVIATIONS
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE FIXTURES & EQUIPMENT
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLR FLOOR
FLUOR FLUORESCENT
FO FINISH OPENING
FOS FACE OF STUD
FR FIRE RATED
FSP FIRE STANDPIPE
FT FOOT / FEET
FTG FOOTING
FURR FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALLCOVERING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GF CMU GROUND FACE CMU
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLACK
GLU LAM GLUE LAMINATED WOOD
GND GROUND
GT GROUT
GYP BD GYPSUM BOARD
GYP GYPSUM
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIB
HC HOLLOW CORE
HCP HANDICAPPED
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR, HANDRAIL
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IG INSULATING GLASS
IN INCH
INCAN INCANDESCENT
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
ITG INSULATED TEMPERED GLASS
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
L LONG
LAV LAVATORY
LB(S) # POUND(S)
LF LINEAL FEET
LLV LONG LEG VERTICAL
LT LIGHT
LVR LOUVER
M & BH MOP AND BROOM HOLDER
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEPF MECHANICAL, ELECTRICAL,
PLUMBING,
FIRE PROTECTION (CONDUIT)
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
N
NORTH
NA NOT APPLICABLE
NECY NECESSARY
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OH OPPOSITE HAND
OPN OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PAINT
PARTN PARTITION
PBD PARTICLE BOARD
PBSW PATIENT BED SERVICE WALL
PCC PRECAST CONCRETE
PI PSYCHIATRIC INPATIENT
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PMU PSYCHIATRIC MEDICAL UNIT
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT CONCPOST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTL PORCELAIN TILE
PVC POLYVINYL CHLORIDE
QA QUALITY ASSURANCE
QT QUARRY TILE
R-VALUE (INSULATION),
RADIUS, RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE: REFERENCE
REBAR REINFORCING BAR
REC RECESSED
RECPT RECEPTACLE
REF REFRIGERATOR
REG REGISTER
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RFT RESILIENT FLOOR TILE
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RT RUBBER STAIR TREAD
S
SOUTH
SAF SEAMLESS ACRYLIC FLOORING
SAP SUSPENDED ACOUSTICAL PANELS
SAT SUSPENDED ACOUSTICAL TILE
SB SPLASHBLOCK
SC SEALED CONCRETE, SOLID CORE
SCHED SCHEDULE
SCP SCUPPER
SD SOAP DISPENSER
SEAL SEALER
SECT SECTION
SECT SECTION
SF SQUARE FOOT
SF CMU SPLIT-FACE CMU
SHR SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SL SLOPE
SLV SHORT LEG VERTICAL
SND SANITARY NAPKIN DISPOSER
SNV SANITARY NAPKIN VENDOR
SPECS SPECIFICATIONS
SQ SQUARE
SS SOLID SURFACE
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TB TACKBOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TD TUBULAR DAYLIGHTING DEVICE
TEL TELEPHONE
TEMP TEMPERATURE
TG TEMPERED GLASS,
TONGUE & GROOVE,
TRANSFER GRILLE
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
URN URINAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDP WOOD PANELING
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
WR WASTE RECEPTACLE,
WATER RESISTANT
WS WATER STOP
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
INV INVERT
ITG INSULATED TEMPERED GLASS
TT TERRAZZO TILE
BASIS OF DESIGN
· SIMPLEX FIRE ALARM
· TK ELEVATOR
· ASCO TRANSFER SWITCHES
· 290 SIGNS
P
M
GENERAL INFORMATION
KC JJG
GI002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
BID DOCUMENTS
2 4
11296
R E G
I
S
T
E
R
E D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
HEPA
NEGATIVE AIR
UNIT
FINISHED FLOORING TO BE KEPT
CLEAN. FLOORS NOT BEING REPLACED
MUST BE PROTECTED. COVER WITH
ROSIN PAPER / FIRE RATED PLYWOOD.
FIRE RATED PLYWOOD,
TEMPORARY. SALVAGE
PROTECT AND STORE
EXISTING WINDOW TO
BE RE-INSTALLED
AFTER CONSTRUCTION
IS COMPLETE.
V I F
V
I F
V.I.F.
V I F
E X
I S
T I N
G
W
A L L
V I F
E X
I S
T I N
G
W
A L L
PLASTIC WINDOW
SWIVEL CASTERS
WITH TWO
LOCKING BRAKES
MOBILE CART
A D
J U
S T
A B
L E
I G
H T
HEPA NEGATIVE
AIR UNIT
EXISTING WALL
EXISTING CEILING
FLEX DUCT
ILSM SIGNAGE
INTERIM LIFE SAFETY MEASURES IN EFFECT FOR THE
UPGRADE ELEVATOR PROJECT
THIS EXIT IS CLOSED AND LEADS TO A
CONSTRUCTION AREA
PLEASE USE ALTERNATE EXITS AS MARKED
1'-5"
ICRA, ILSM, FIRE WATCH AND
MISC. FORMS
PAPER
CADDY
ISLM TEMPORARY BARRIER TAG
PROJECT:
PRIME CONTRACTOR:
SUB CONTRACTOR:
EMERGENCY CONTACT NO.:
BARRIER INSTALLATION DATE:
BARRIER EXPIRATION DATE:
A P
P R
O X
A
F
F
POST ICRA, ILSM, FIRE
INSPECTION SHEETS
VISIBLE TO PUBLIC
HARD BARRIER
WITH DOOR &
HINGES. SEE
5/GI003
FIRE EXTINGUISHER ON
PORTABLE FLOOR
BRACKET (ILSM MAY
REQUIRE MORE THAN
ONE).
PROVIDE STICKY
MATS (CHANGED END
OF SHIFT OR MORE IF
NECESSARY TO
MAINTAIN
CLEANLINESS).
SUPPLY DUCTS
EITHER KEEP
RUNNING OR COVER
WHEN RUNNING TO
KEEP DUST OUT
COVER ALL RETURNS
AT THE
GRATE/DIFFUSERS
F L E
X
D
U C
T
POST ICRA, ILSM, FIRE
INPECTION SHEETS
VISIBLE TO PUBLIC
FIRE PULL
STATION WITH
AUDIO / VISUAL
HEPA NEGATIVE
AIR UNIT
HARD BARRIER WITH
DOOR & HINGES
P
M
INFECTION CONTROL RISK
ASSESSMENT - (ICRA)
A.
B.
C.
D.
E.
GENERAL
SEE SHEET GI004 FOR PRE-CONSTRUCTION RISK
ASSESSMENT FORMS AND INFECTION CONTROL
PRECAUTIONS.
SEE SHEET GI004 FOR PHASING PLANS AND
DESCRIPTION.
ALL APPLICABLE PERMITS AND COR APPROVALS
SHALL BE COMPLETED PRIOR TO BEGINNING ANY
WORK FOR EACH PHASE. PERMITS INCLUDE: ICRA,
ILSM, ABOVE CEILING FIRE/SMOKE WALL, UTILITY,
FIRE ALARM SYSTEM, MEDICAL GASES, AND
CONFINED SPACES.
WORK REQUIRED BY INFECTION CONTROL SHALL
BE PERFORMED FOR EACH PHASE OF THE
PROJECT.
CONTRACTOR SHALL EXHAUST ALL AIR FROM
SPACES WHERE WORK IS BEING PREFORMED
DIRECTLY TO THE EXTERIOR OF THE BUILDING.
ENSURE EXHAUST POINTS ARE LOCATED AWAY
FROM INTAKE POINTS FOR THE BUILDING. EXHAUST
LOCATIONS TO BE APPROVED BY COR.
Scale: 1/2" = 1'-0"
CROSS SECTION 'A'
Scale: 1/2" = 1'-0"
MOBILE CONTAINMENT CART
Scale: 6" = 1'-0"
ILSM SIGNAGE
ILSM TEMPORARY BARRIER TAG
Scale: 1/2" = 1'-0"
ROOM ELEVATION
Scale: 1/2" = 1'-0"
TYPICAL CONSTRUCTION PLAN LAYOUT
JAB
GI003
JJG 3 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
SHEET NOTES:
11296
R E
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
ICRA GENERAL NOTES:
1.
2.
NO MAJOR EQUIPMENT ACCESS THROUGH THE BUILDING BETWEEN 7AM TO
5PM. CONTRACTOR TO COORDINATE WITH VA COR.
LOBBY WORK CAN BE COMPLETED DURING REGULAR BUSINESS HOURS IF A
CONSTRUCTION BARRIER IS INSTALLED PRIOR TO PERFORMING WORK.
UP DN
CORRIDOR
DH001
STAIR
PAS06
MECH
RM
D-B038
EMERGENCY
GENERATOR
D003
TRANSFORMERS &
SWITCHGEAR
D003A
ELEVATOR
LOBBY
PC02
ELEVATOR
PCE05
ELEVATOR
PCE04
FF:VCT
CORRIDOR
DH002
CORRIDOR
TD
D002
ELEVATOR
S7
ELEVATOR
S6
ICRA AND CONSTRUCTION PHASING
PLANS
KC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
SHEET NOTES
SHEET KEY NOTES
1.
1A.
1B
2.
3.
3A
3B
4.
5.
6.
7.
8.
GI004
JJG 4 4
SWITCHGEAR / MECH ROOM ENLARGED PHASING PLAN
SCALE:3/16" = 1'-0"
ICRA TRANSFORMER & SWITCHGEAR / MECH ROOM ENLARGED PHASING PLAN
SCALE:3/16" = 1'-0"
(OFF-HOUR)
PHASE 1
(OFF-HOUR)
PHASE 2
ICRA TRANSFORMER &
5 5
4 4
PHASE 3
(OFF-HOUR)
PHASE 4
(OFF-HOUR)
ICRA ELEVATORS PLAN S6 AND S7
SCALE:3/16" = 1'-0"
PROVIDE TEMPORARY PROTECTIVE HARD BARRIER WITH
DOOR & HINGES, TO BOTTOM OF CEILING
PROVIDE 1-HR RATED TEMPORARY CONSTRUCTION
BARRIER CONSISTING OF SEALED 5/8" GYPSUM BOARD ON
BOTH SIDES OF 3-5/8" METAL STUD PARTITION EXTEND TO
BOTTOM OF FLOOR OR ROOF DECK ABOVE. SEAL TOP AND
BOTTOM OF PARTITION. PARTITION SHALL BE INSPECTED
BY VA ICRA STAFF PRIOR TO START OF CONSTRUCTION IN
SPACE. SEE TEMPORARY PARTITION TYPE "T" ON SHEET
GI003.
PROVIDE RATED 3' WIDE BY 7' TALL HARD DOOR WITH
ASSOCIATED HARDWARE FOR TEMPORARY PARTITION.
COORDINATE WITH VA COR ON SECURING
EGRESS DOOR DURING THIS CONSTRUCTION
PHASE(S).
CONSTRUCTION ROUTE THRU THE BASEMENT
LEVEL TO LOADING DOCK AS INDICATED ON
SHEET GI003
PROVIDE TEMPORARY CONSTRUCTION SIGN FOR
PHASE 9 CONSTRUCTION WORK IN THE
STAIRWELL AND LOBBY AREA. TEMPORARY
CONSTRUCTION SIGN SHALL INCLUDE
ALTERNATE EGRESS MAP TO DIRECT STAFF AND
VISITORS TO THE NEAREST STAIRS 1, 2 AND 4.
COORDINATE WITH VA COR PRIOR TO ERECTING
SIGN.
PROVIDE CONSTRUCTION SIGN FOR PHASE 8
CONSTRUCTION WORK IN the RESTROOM AND
THE LOBBY AREA TO INDICATE NO ACCESS TO
THE LOBBY.
PROVIDE STICKY MAT AT CONSTRUCTION
ACCESS POINT. (MAT SHALL BE INSPECTED AND
CHANGED FREQUENTLY TO ENSURE
EFFECTIVENESS)
USE PORTABLE DUST EXTRACTOR AND AIR
SCRUBBER WITH HEPA FILTRATION SYSTEM
COORDINATE WITH VA COR ABOUT OFF-HOURS
SCHEDULE AND TEMPORARY REROUTING
ACCESS FOR HOSPITAL STAFF/VISTORS PRIOR
TO ERECTING TEMPORARY BARRIER
CONSULT WITH THE VA SAFETY DEPARTMENT TO
MAINTAIN A MINIMUM CLEARANCE IN HALLWAY
REFER TO SHEETS A-101 AND A-102 FOR
CONSTRUCTION ROUTE FOR EACH PHASE
OF CONSTRUCTION
SEE SHEET A-101 FOR CONSTRUCTION ACCESS
FROM BASEMENT TO LOADING DOCK
SPECIFICATION REQUIRES CLASS II ICRA
REQUIREMENTS. SEE SPECIFICATION SECTION
01 35 26 FOR MORE INFORMATION.
GC TO INCLUDE ALL ICRA BARRIER DOOR
HARDWARE
CONTRACTOR TO ENSURE ACCESS TO EXISTING
FIRE EXTINGUISHERS OR FIRE ALARM PULL
STATIONS ARE MAINTAINED. RELOCATE SAID
EXTINGUISHERS OR PULL STATIONS UNTIL SUCH
TIME THAT THEY CAN BE RETURNED TO THEIR
ORIGINAL LOCATIONS. COORDINATE LOCATION WITH
VA COR AND SAFETY IN ADVANCE
DO NOT REMOVE TEMPORARY BARRIERS FOR EACH
PHASE AND ALL HVAC ISOLATION UNTIL
CONTRACTOR HAS CLEANED CONSTRUCTION SITE,
VA INFECTIONS DISEASE CONTROL HAS INSPECTED
AND APPROVED THE CLEANING
VA REQUIRES THAT ALL APPLICABLE PERMITS BE
COMPLETED AND APPROVED PRIOR TO BEGINNING
ANY WORK. PERMITS INCLUDE ICRA, ILSM, ABOVE
CEILING, FIRE ALARM SYSTEM
CONTRACTOR SHALL PROTECT AREA ADJACENT TO
THE DEMOLITION AND NEW CONSTRUCTION WORK
TO PREVENT DAMAGES. (IF DAMAGED, REPAIR,
PATCH, SAND AND REFINISH TO MATCH EXISTING
COORDINATE CONSTRUCTION SCHEDULE WITH VA
COR TO ENSURE STAFF ACCESS FROM ELEVATOR
LOBBIES TO THEIR OFFICES OR OTHER ROOMS
DURING CONSTRUCTION
SEE ARCHITECTURAL PLANS AND DETAILS FOR
DEMOLITION AND RENOVATION WORK
ALL LIGHTING, SMOKE DETECTOR AND EXIT SIGN IN
THE ELEVATOR LOBBY AREAS SHALL REMAIN
AVAILABLE DURING CONSTRUCTION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11296
R E G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
UP
UP DN
GARAGE GATE
UP
MOTOR
CYCLE PARKING
WHEEL
CHAIR PARKING
DN
ATM
DN
RAISED FLOOR
GAS CYL
STORAGE
B005D
HAC
A006F
ELEC.
B009
ELECTRICAL
AU003
ELECTRICAL
AU002ELECTRICAL
AU001
SIGNAL CLOSET
D008
TOILET
FEMALE
B019
PREPARATION STERILIZATION
WORK RM
A005C
STORAGE
A008
FOOD
SERVICING
A006D
CLERK
TYPIST
A011
ASST
CHIEF
A012
CHIEF
A010
PARKING LEVEL A
PA01
MECH RM
D-B038
CORRIDOR
BH005
STORAGE
PA08
OTHER SPACE
PAM03
STORAGE
PA07
ELEVATOR
LOBBY
PA02
STAIRWELL
PAS05
STORAGE
D006STORAGE
D005A
EMS
D005
MECH RM
D004
CORRIDOR
DH001
CORRIDOR
DH002
CORRIDOR
DH004
CORRIDOR
DH003
CORRIDOR
DH003
COMM EQUIP
RM
D007D
TD
D002
ELECTRICAL
D001
STAIR
PAS06 STAIR
PAS07
STORAGE AREA
PA06
PAINT SHOP
D007C
CARPENTER SHOP
D007
LOCKSMITH
D007B
CHIEF
D007A
CORRIDOR
DH005
STAIR
PAS08
CORRIDOR
BH002
M&O
FORMAN
B013
CHIEF
ELECTRICIAN
B014B
ELECTRIC SHOP
B014C
ELECTRONIC
B014
CORRIDOR
BH003
CORRIDOR
BH003
STORAGE
FLAMMABLE
B016
OFFICE
B017
STAFF
TOILET
B015A
WARE HOUSE
B015
STORAGE
GENERAL
B020
MAIL RM
B015B
EMS EQUIP
B021
TOILET
MALE
B018
SOILED
UTILITY
B022A
CORRIDOR
BH004
OFFICE
B022D
OFFICE
B022E
LOGISTICS SVC
INVENTORY MGMT
B022
OFFICE
B022C
OFFICE
B022B
OFFICE
B022A
EMERGENCY GENERATOR
RM
B037
TRANSFORMER RM
B037A
A/C REFRIGERATION
EQUIP RM
B038
CORRIDOR
BH004
ELECTRICAL DISTRIBUTION
RM
B037B
SVC RM
B039
CORRIDOR
BH006
CORRIDOR
BH006
HAS
B044
HAS
B044C
HAS
B044B
EMS OFFICE
B042A
EMS CHECK IN
B042B
SECY/
RECEPTIONIST
B-042
OFFICE
ASST CHIEF
WORK RM
B-042C
TOILET
B044A
IT
B046
EMS
B043
ELECTRIC
CLOSET
B043A
CHARTING
A032E
HALL
A032
CONFERENCE RM
A032D
RESIDENTS
OFFICE
A032C
SECY
OFFICE
A032B
PM&RS CHIEF'S
OFFICE
A032A
MAIN KITCHEN
B036
DISH
WASHING
A020
CONFERENCE M
A029
BREAK RM
B045A
SUPV OFFICE
B045
SURGICAL PACK
B045C
ENVIRONMENTAL
MGMT SUPPLY
B045D
STORAGE
B045B
MAIN KITCHEN
B036
LINEN
B036D
EMS
B036C
MENS
TOILET
B041
FEMALE
TOILET
B040
CANTEEN STORAGE
B036B
OFFICE
B035
STORAGE
B035A
DAIRY & EGG
REFRIG
B036G
OFFICE SUPVS
B036F
CORRIDOR
AH005
CORRIDOR
AH004
CORRIDOR
AH006
CORRIDOR
AH004
SECY
A028
DIETICIANS
OFFICE
A025A
ASST CHIEF
A027
DIETICIANS
OFFICE
A025EMS
A023
ELECTRIC
CLOSET
AU004
ELEVATOR
LOBBY
A000
ELEVATOR LOBBY
A001
BREAK RM
A021
EQUIP
STORAGE AREA
B001
STORAGE
& ISSUE
B034
OFFICE
A019
ELECTRIC
CLOSET
BU003
EMS
A001B
DUMB
ELEVATOR
SOILED RECEIVING
DECONTAMINATION AREA
B005
MANUAL
CART WASH
B005B
STAIRWELL
BS003HALL
B004
EMS
B005A
WOMENS TOILET
B002
MENS TOILET
B003
STORAGE
B009A
HALL
B006A
CORRIDOR
OX101
BULK
STORAGE
B010
LOGISTICS
STORAGE
B011
ELECTRIC
CLOSET
BU002
UNION OFFICE
B011A
FF: VCT
AC PLUMBING
MACH
B012
OFFICE
B012A
CORRIDOR
BH001
CORRIDOR
AH003
CLEAN RECEIVING
B007
CORRIDOR
AH002
STERILE AND NON-STERILE
STORAGE
A001A
RETAIL STORE
A009
STAIRWELL
PAS04
CORRIDOR
AH001
ELECTRIC
CLOSET
AU005
OFFICE
ASST CHIEF
A003
KITCHEN
A006
OFFICE
CANTEEN
A007
REFR WALK IN
A006B
PREFAB
REFRIG
A006C
FOOD
STORAGE
A006A
SERVING LINE
A005
AU008 AU007 AU006
STAIR
AS002
CAFETERIA
A004A
VCS OFFICE
A004E
VCS OFFICE CHIEF
A004A
STORAGE
A004
STORAGE
A004A
EMS
A004B LOUNGE
A002
LOCKERS
FEMALE
A002A
TOILET &
SHOWERS
A002B
IT CLOSET
A002C
TOILET
A024TELEPHONE EQUIP RM
A022
LOCKERS
A026B
EMS
A026
PHYSICAL
THERAPY
A035
STORAGE
A033
HYDROTHERAPY
A034
RECEPTION
A030
CORRIDOR
AH007
PHYSICAL THERAPY
OUTPATIENT
A036
CORRIDOR
A030A
WAITING AREA
A042
EXAM/EMG
A037
PROVIDER
A038
EXAM
A041
EXAM
A040 PROVIDER
A039
STAIRWELL
AS001
TOILET & SHOWERS
A046
A026A TOILET
FEMALE
A045
OT CLINIC
A044
OT OFFICE
A043
OT OFFICE
A043A
RECEPTION AREA
A050
CORRIDOR
AH009
OFFICE
A070RECEIVING
A071
SVC MGR
A072
CORRIDOR
AH008PGM MGR
A068
OFFICE
A069
COMPUTER RM
A073
CORRIDOR
AH010
SOFTWARE APPL
SUPPORT
A067
APPLICATION
SUPPORT
A066
SYSTEMS
MGR
A065
NETWORKING
MGR
A064
PROG MGR SYST &
NETWORKING
A063
ADP
WORKSHOP
A062
STAIRWELL
AS004
TELECOMM
SVCS
A061
TELECOMM
SVCS
A060
SUPPORT
A059
APPLICATION
SUPPORT
A058
APPLICATION
SUPPORT
A057
OFFICE
A051
PGM
SPECIALISTS
A052
PGMMING &
INFO
A053
PGMMING &
INFO
A054
CONFERENCE
RM
A055
ELECTRICAL
A056
MECHANICAL
B015F
FF: CONC.
PROSTHETICS STORAGE
B015C
FF: VCT
MORGUE
B015A
FF: VCT
LOGISTICS BREAKDOWN
B006B
FF: VCT
LOADING DOCK
AREA
LIMIT OF
WORK
LIMIT OF
WORK
TRAVEL DISTANCE: 55'-6"
T R
A V
E L
D
I S
T
T R
A V
E L
D
I S
T
TR. DIST.: 20'-2"
PROPOSED
CONTRACTOR
LAY DOWN AREA
VERIFY FINAL
LOCATION W/ COR
PROVIDE 8'-0" TALL
SECURITY FENCE ON
THREE SIDES.
EXIT
T R
A V
D
I S
T
TRAVEL DISTANCE: 16'-11"
"TOWER" BUILDING #1
NO SCOPE THIS PROJECT
MAIN BUILDING #1A
P
M
OVERALL GROUND FLOOR
PLAN AND CONSTRUCTION
ROUTE
KC JJG
A-101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
OVERALL GROUND PLAN AND CONSTRUCTION ROUTE
SCALE:1/16" = 1'-0"
SHEET KEY NOTES - NEW
1 5
GROUND FLOOR CONSTRUCTION ROUTE
INDICATES PROPOSED
CONSTRUCTION PATHWAY
ELEV
S7
ELEV
S6
ELEV
PAE04
ELEV
PAE05
MECH
RM
D-B038
EMERGENCY
GENERATOR
D003
TRANSFORMERS
& SWITCHGEAR
D003A
A-102
11296
R E G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
DocuSign Envelope ID: 33FE4D5E-9D7F-48C9-B1D9-935AF5515DE0
8/7/2020
AutoCAD SHX Text
NORTH
DOWN
UP
MOTORCYCLE
MOTORCYCLE
STAIRWELL
PCS04
PARKING
PC01
SUMP
00-C-3
OTHER SPACE
PCM17
FAN RM
00-C-2
STORAGE
PC14
STORAGE
00C6
MECH
RM
PC15
STORAGE
PC16
ELEVATOR
LOBBY
PC02
STAIR
PCS05
STORAGE
PC05
STORAGE
PC09
MECH RM
PC10
TC
00-D-3
EC
00-D-2
STAIR
PCS06
FAN RM
00-D-1
OTHER
SPACE
PCM11
FF:CONCRETE
FF:CONCRETE
FF:VCT FF:CONCRETE FF:CONCRETE
FF:CONCRETE
FF:VCT
FF:VCT
FF:VCT
FF:VCT
FF:VCT
FF:CONCRETE
FF:VCT
FF:VCT
FF:CONCRETE
FF:CONCRETE
FF:CONCRETE
FF:CONCRETE
FF:VCT
P
M
PARKING GARAGE FLOOR PLAN
AND ENLARGED PLANS
KC JJG
A-102
ELEVATOR LEVEL C - PARKING GARAGE
SCALE:1/16" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
2 5
P4 & P5 TRANSFORMER & SWITCHGEAR / MECH ROOM ENLARGED PLAN
SCALE:3/16" = 1'-0"
TRANSFORMER & SWITCHGEAR / MECH ROOM ENLARGED PLAN - GROUND FLOOR
SCALE:3/16" = 1'-0"
ELEV
P05
ELEV
P04
ELEV
EQUIP
00-C-1
A-102
EMERGENCY
GENERATOR
D003
TRANSFORMER &
SWITCHGEAR
D003A
MECH RM
D-B038
ELEV
P05
ELEV
P04
ELEV
EQUIP
00-C-1
GENERAL CONTRACTOR TO THOROUGHLY CLEAN
FLOOR IN ELEVATOR MECHANICAL ROOM BEFORE NEW
EQUIPMENT IS PLACED
11296
R E G
I
S
T
E
R
E D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
DocuSign Envelope ID: 33FE4D5E-9D7F-48C9-B1D9-935AF5515DE0
8/7/2020
AutoCAD SHX Text
NORTH
TYPICAL PASSENGER CAB
(F.V.)
SEE NOTE 1
F
V
S E
E
N
O T
E
COORDINATE FUTURE
SECURITY CAMERA
LOCATION WITH VA
COR AND SAFETY
EXISTING CEILING
TO REMAIN
PROVIDE NEW LED
LIGHTING IN EXISTING
S.S. HOUSING. SEE
ELEVATOR
SPECIFICATION FOR
MORE INFORMATION
STAINLESS STEEL
FRONT PANEL PER
SPECIFICATIONS
ALL CONTROLS TO BE MFR
STANDARD AS SPECIFIED
AND REQUIRE ADA
EXISTING BASE
TO REMAIN
6'-1 1/2"
LED LIGHTS
- CENTER IN PANELS
AS INDICATED - SEE
ELEC. DWG.
EXISTING CEILING
TO REMAIN
NEW COMPLETE
DOORS & ACTUATORS
- SEE SPECS.
CAB AT OPPOSITE DOOR SIDE ELEVATION
FIELD VERIFY CAB DIMENSIONS
EXISTING WALLS TO
REMAIN
EXISTING HAND RAILS
TO REMAIN
EXISTING BUMPER
RAIL AND BASE TO
REMAIN
CAB AT DOOR SIDE ELEVATION
FIELD VERIFY CAB DIMENSIONS
ELEVATOR
DOOR
SIDE
VA INTERIOR
DEPARTMENT TO
PROVIDE
DIRECTORY SIGN
ALL CONTROLS TO
BE MFR STANDARD
AS SPECIFIED AND
REQUIRE ADA
DOOR
SIDE
EXISTING WALLS TO REMAIN
8'-1 1/2"8'-1 1/2"
PROVIDE NEW LED
LIGHTING IN EXISTING
S.S. HOUSING. SEE
ELEC.DWG. FOR
MORE INFORMATION
EXISTING CEILING
TO REMAIN
PROVIDE NEW LED
LIGHTING IN EXISTING
S.S. HOUSING. SEE
ELEC.DWG. FOR
MORE INFORMATION
EXISTING CEILING
TO REMAIN
EXISTING WALLS TO
REMAIN
EXISTING HAND RAILS
TO REMAIN
EXISTING BUMPER RAIL
AND BASE TO REMAIN
EXISTING WALLS TO REMAIN
6'-0 7/16"
LED LIGHTS
- CENTER IN PANELS
AS INDICATED - SEE
ELEC. DWG.
EXISTING CEILING
TO REMAIN
PROVIDE LVT
FLOORING. 6"
NOMINAL WIDTH:
SHAW PATCRAFT /
TIMBER GROVE II /
00775 BOXWOOD
PASSENGER ELEVATORS CAB FINISH SCHEDULE:
CEILINGS TO REMAIN. RE-LAMP EXISTING LIGHT FIXTURES WITH LED LIGHTING.
EXISTING TO REMAIN.
FLOORS TO BE SHAW PATCRAFT; TIMBER GROVE II; STYLE: 1438V; 30 MIL
COLOR: 00775 BOXWOOD; SIZE: 5.96 X 48" X .118" THICK (GLUE DOWN).
ALL DOORS TO BE SS ON BOTH SIDES. RE-LABEL ALL DOORS WITH SAME
SIGNAGE AS EXISTING FROM 290 SIGN COMPANY
STAINLESS STEEL RAIL TYPE BASE SLOPED 6" FROM WALL TO FLOOR.
3" WIDE S.S. HANDRAIL AND GUARDRAILS. SEE ELEVATIONS.
CEILING:
WALLS:
FLOOR:
DOORS:
BASE:
HANDRAILS:
P
M
PASSENGER ELEVATOR CAB INTERIOR
ELEVATIONS
KC JJG
A-201
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
3 5
CAR REAR ELEVATIONS
SCALE: 3/4" = 1'-0"
CAR CEILING PLAN
SCALE: 3/4" = 1'-0"
CAR FRONT ELEVATION
SCALE: 3/4" = 1'-0"
LEFT SIDE ELEVATIONS
SCALE: 3/4" = 1'-0"
CAR FLOOR TILE PLAN
SCALE: 3/4" = 1'-0"
CAR RIGHT SIDE ELEVATIONS - P4, P5
SCALE: 3/4" = 1'-0"
ELEVATOR
P4 & P5
Replace Ceiling
(1)
1A
Replace Walls
(2)
NO - SEE 1A
Replace Flooring
(3)
YES
Replace Doors
(4)
YES
Replace Handrails
(5)
NO - EXISTING TO REMAIN
1. CEILING- N/A.
1A. THE GARAGE ELEVATORS ARE CURRENTLY CLAD WITH SS WALLS - RE-LAMP WITH LED SOFFIT IN ORDER TO KEEP SS WALLS IN TACT.
11296
R E
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
SIX LED DOWNLIGHTS WITH BRUSHED STAINLESS PANELS AND CONCEALED ACCESS PANEL - S6 & S7
ELEVATOR S7: EXISTING WALLS TO REMAIN
ELEVATOR S6: BRUSHED STAINLESS STEEL WAINSCOT W/ WOOD VENEERING ON UPPER PORTION W/ MIRROR POLISHED STAINLESS STEEL REVEALS. BACK WALL PANEL TO HAVE IMPRINT OF EACH SERVICE BRANCH INSIGNIA IN HONORING THE SERVICE. BRANCHES INCLUDE US AIR FORCE, ARMY, US MARINE CORPS, AND NAVY. OBTAIN FINAL IMAGE APPROVAL FROM THE VA INTERIOR DEPARTMENT.
EXISTING FLOORING TO REMAIN.
ALL DOORS TO BE SS ON BOTH SIDES. RE-LABEL ALL DOORS WITH SAME SIGNAGE AS EXISTING FROM 290 SIGN COMPANY
STAINLESS STEEL RAIL TYPE BASE SLOPED 3" FROM WALL TO FLOOR.
3" WIDE S.S. HANDRAIL AND GUARDRAILS. SEE ELEVATIONS.
CEILING:
WALLS:
FLOOR:
DOOR:
BASE:
HANDRAILS:
SERVICE ELEVATORS CAB FINISH SCHEDULE:
CAB RIGHT AND LEFT SIDE
ELEVATION
NEW STAINLESS
STEEL CAB LINING
- (ELEVATOR S6)
NEW STAINLESS STEEL
3" HANDRAILS
NEW STAINLESS STEEL
WALL PANEL
CAB REAR ELEVATION CAB FRONT ELEVATION
NEW STAINLESS
STEEL CAB LINING
- (ELEVATOR S6)
NEW STAINLESS STEEL
3" HANDRAILS
NEW STAINLESS STEEL
WALL PANEL
ALL CONTROLS TO BE
MFR STANDARD AS
SPECIFIED AND
REQUIRED BY ADA
NEW STAINLESS
STEEL BASE
NEW STAINLESS
STEEL BASE
7'-8 1/2" 0"6'-4 1/2" 0" 7'-8 1/2" 0"
EXISTING WALLS
TO REMAIN
- (ELEVATOR S7)
EXISTING WALLS
TO REMAIN
- (ELEVATOR S7)
NOTE: DIMENSION ARE PROXIMATE - GC TO VERIFY
PROVIDE NEW LED
LIGHTING IN EXISTING
S.S. HOUSING. SEE ELEV.
SPECIFICATION FOR
MORE INFORMATION -
(ELEVATOR S7 ONLY)
NEW COMPLETE
DOORS & ACTUATORS
- SEE SPECS.
LED LIGHTS
-CENTER IN PANELS
AS INDICATED
TYPICAL SERVICE CAB
SUSPENDED METAL
CEILING
FIELD VERIFY HIGH
CEILING & CEILING
ACCESS DOOR
EQ
1'-4 1/4"
EQ
1'-4 1/4"
1'-4 1/4"
EQ 2' 0" EQ2' 0" 2' 0"
EXISTING FLOORING
TO REMAIN
P
M
SERVICE ELEVATOR CAB INTERIOR
ELEVATIONS
JAB JJG
SHEET NOTES
A-202
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
INTERIOR ELEVATIONS - SERVICE ELEVATORS - S6, S7
SCALE: 3/4" = 1'-0"
CEILING PLAN S6 & S7
SCALE: NTS
FLOOR PLAN
SCALE: NTS
4 5
LOCATE PIT LADDERS IN EXISTING LOCATION
A
ELEVATOR
S6 & S7
Replace Ceiling
(1)
Replace Walls
(2)
S6 ONLY
Replace Flooring
(3)
NO
Replace Doors
(4)
YES
Replace Handrails
(5)
YES
1. CEILING- REPLACE CEILING IN BOTH ELEVATORS S6 & S7. SEE DETAIL 3/A-202.
2. WALLS- WHEREVER THE EXISTING HANDRAILS ARE REMOVED AND REPLACED REQUIRE NEW WALL PANELS - UNLESS EXISTING HOLES CAN BE REUSED FOR HANDRAIL
ATTACHMENT
- VERIFY WHETHER EXISTING HOLES CAN BE REUSED WITH C.O.R. -
11296
R E G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
3RD LEVEL PARKING
2ND LEVEL PARKING
1ST LEVEL PARKING
1ST FLOOR
3RD LEVEL PARKING
2ND LEVEL PARKING
GROUND FLOOR
1ST FLOOR
BUILDING 1A
PASSENGER ELEV. 4 FLOORS (2)
P-4, P-5
(HYDRAULICS)
BUILDING 1A
SERVICE ELEV. 5 FLOORS (2)
S-6, S-7
(TRACTIONS)
1 2
2ND FLOOR
3RD FLOOR
4TH FLOOR
PENTHOUSE
MACH.
RM. FL.
TOP FOOTING
PIT
P
M
ELEVATOR RISER DIAGRAM
JAB
SHEET NOTES
A-400
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
FULLY SPRINKLERED
Engineers Architects
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
ELEVATOR RISER DIAGRAM
N.T.S.
5 5ANP
SEE ELECTRICAL SHEETS FOR SHAFT LIGHTING
LOCATIONS
A.
11296
R E G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
N
O
R
R
O
L
I
N
A
J
E
F
F
R
E
Y
A
B
R
O
O
K
S
R
A
L
E
I
G
R
O
L
I
N
A
DocuSign Envelope ID: 138874F2-128C-46CB-9ADE-FEB5196AEEEF
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORDCOORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
MVOLT MULTIVOLT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING
FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND
ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON
VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND
CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,
LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
J
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
STRIP LIGHT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
Engineers Architects M101
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
BID DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL GENERAL NOTES, SYMBOL
LEGENDS, ABBREVIATIONS, AND
SCHEDULES
JKM NJ
E-001
1 7
LIGHT FIXTURE SCHEDULE
SYMBOL LABEL
TYPE OF
LAMP
BALLAST/
DRIVER
WATTS/
FIXTURE
VOLTAGE DESCRIPTION
BASIS OF DESIGN
MANUFACTURER/CATALOG NUMBER
OR A
LED; 4000
LUMENS;
80 CRI;
3500K
ELECTRONIC 42 MVOLT
4' LINEAR SURFACE MOUNTED EXTREME ENVIRONMENT LED
ELEVATOR PIT LIGHT; WITH RIBBED FROSTED ACRYLIC LENS;
ENCLOSED AND GASKETED; WET LOCATION; MVOLT
COLUMBIA LIGHTING MODEL #
LXEM4-40LW-RFA-EU
OR APPROVED EQUIVALENT
B
LED; 4600
LUMENS;
80 CRI;
3500K
ELECTRONIC 41 MVOLT
4' LINEAR LED STRIPLIGHT WITH LENS; SUSPENDED FROM
STRUCTURE WITH ALL THREAD; DLC QUALIFIED; INSTALLED
HEIGHT OF 9'-0" AFF. MVOLT.
METALUX MODEL #
4SNLED-LD4-46SL-LN-UNV-L840-CD1-U
OR APPROVED EQUIVALENT
NOTES:
1. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND
APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE
PART NUMBERS.
2. EM - SWITCHED EMERGENCY LIGHT (CIRCUITED FROM NORMAL AND EMERGENCY BACK-UP POWER)
EM NL - UN-SWITCHED EMERGENCY LIGHT (CIRCUITED FROM EMERGENCY POWER)
3. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
4. FOR ALL LED LIGHT FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
DocuSign Envelope ID: D4321D85-CDC5-46A0-B8A1-1D1ACD76F467
MECH
RM
PC15
STORAGE
PC16
ELEVATOR
LOBBY
PC02
ELEVATOR
PCE05
ELEVATOR
PCE04
ELEV
EQUIP
00-C-1
P5
P4
(TYP)
LPE3 PPE3
4 4
S6
S7
RAIL
(TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Dwg. of
17-274
ACG Project Number
Engineers Architects M101
BID DOCUMENTS
08/10/2020
MAIN BLDG
UPGRADE ELEVATORS P4, P5,
S6, AND S7
596A4-18-103
LEXINGTON, KY 40502
Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420
Elevator Consultant:
N
AREA OF WORK
WITHIN BUILDING #1
KEY PLAN
N
AREA OF WORK
WITHIN BUILDING #1
N
AREA OF WORK
WITHIN BUILDING #1
BID DOCUMENTS
S6, S7
P4, P5
FULLY SPRINKLERED
ELECTRICAL DEMOLITION PLANS
JKM NJ
ED101
A. EQUIPMENT SHOWN IS INDICATIVE OF THE
ITEMS EXISTING, HOWEVER SOME ITEMS MAY
HAVE BEEN CONCEALED DURING THE
SURVEY. THE CONTRACTOR SHALL VISIT THE
SITE PRIOR TO THE BID TO VERIFY THE
EXTENT OF THE DEMOLITION, AND SHALL
FIELD VERIFY THE TOTALITY OF THE
EQUIPMENT INDICATED.
B. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS AND
CONDUITS THAT ORIGINATE, PASS THROUGH,
OR TERMINATE IN THE AREA OF WORK.
DEMOLISH ALL CIRCUITS THAT ARE NO
LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE NOT
COMPLETELY REMOVED.
C. CONTRACTOR TO DISCONNECT AND REMOVE
ELECTRICAL CONNECTION TO OUTLETS,
RECEPTACLES, HVAC EQUIPMENT AND OTHER
ELECTRICAL DEVICES. REMOVE CONDUCTORS
AND CONDUIT BACK TO PANELBOARD
SERVING EQUIPMENT OR TO THE POINT
WHERE OTHER REMAINING LOADS ARE
CONNECTED. UPDATE AFFECTED PANEL
DIRECTORIES TO INDICATE ANY REMAINING
LOADS OR LABEL CIRCUITS "SPARE (UNUSED)"
AS APPLICABLE.
D. CONTRACTOR SHALL REMOVE ALL
ELECTRICAL CONDUIT, CABLE,…