P09 - SOW.docx

DOCX document 17 KB Posted

Attached to
H161--Generator Load Banking
Solicitation number
36C24825Q0498
Issued by

About this file

This is a Statement of Work (SOW) for generator load banking services at the CW Bill Young VA Medical Center in Bay Pines, Florida. The document outlines requirements for performing annual load testing on eight generators across different buildings, with specifications including a four-hour load bank process at 30%, 50%, and 75% of nameplate ratings. Contractors must have at least five years of generator operations experience, electrical safety training, and meet Joint Commission requirements.

The related federal contract opportunity is a Sources Sought notice (Solicitation #36C24825Q0498) seeking Service-Disabled Veteran-Owned Small Businesses (SDVOSB), Veteran-Owned Small Businesses (VOSB), Women-Owned Small Businesses (WOSB), or other small businesses. The anticipated contract is firm-fixed price with a base year and four option years, starting 06/28/2025. Responses were due by 10:00 AM EST on March 14, 2025, via email to william.penhallegon@va.gov, with NAICS code 811310. The Department of Veterans Affairs will determine competitive procurement based on the responses received.

View the file

Other files

File Type Posted
36C24825Q0498.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK FOR GENERATOR LOAD BANKING

AT CW BILL YOUNG VA MEDICAL CENTER

10000 BAY PINES BLVD., BAY PINES, FL 33744

OVERVIEW

The contractor shall provide all the necessary labor, equipment, cables, transportation and supervision for an annual load banking of eight (8) generator units at CW Bill Young VA Medical Center. This is for a four hour load bank.

GENERATORS

The generators in this scope of work are:

Bldg. 1, Marathon 600 kW, 750 kVA, 277/480v Bldg. 19, Magnetek 100 kW, 120 kVA, 120/208v Bldg. 24, Allis-Chalmers 100 kW, 113 kVA, 120/208 Bldg. 37, Caterpillar 300 kW, 375 kVA, 120/208v Bldg. 46, Onan 350 kW, 437 kVA, 277/480v Bldg. 101, Caterpillar 210 kW, 263 kVA, 277/480v Bldg. 102, Caterpillar 350 kW, 400 kVA, 277/480v Bldg. 106, Generac 600 kW, 750 kVA, 277/480v

GENERAL REQUIREMENTS

The load banking shall meet the Joint Commission’s requirements and are as follows:

30% of nameplate rating for 2 hours, followed by 50% of nameplate rating for 1 hour, followed by 75% of nameplate ratings for 1 hour, plus warm up and cool down time for a total continuous run of 4 hours.

A written record shall be kept of each generator run. At 15 minute intervals, the following readings will be recorded:

Lube Oil Pressure
Water Temperature
Exhaust Temperature
Amperes
Volts
Frequency

Prior to starting the generators, the contractor shall perform a pre-run inspection to include checking the oil level, coolant level and a visual inspection of the motor/generator.

The contractor will be required to furnish and make the necessary cable connections from the generator to the load bank. This may require parallel runs of cabling. In some locations, this may require barricades, safety cones or both.

A site visit will be required to determine parking, pathways and proper connections to the generator units.

Hours of work will be Monday through Friday, 6:00 AM - 4:00 PM. Government Holidays will not be worked. The target month for this work will be June.

The work performed shall not interrupt any power to the buildings in this Scope of Work.

QUALIFICATIONS OF CONTRACTORS

The contractor shall have technical training and track records of proven experience with generator operations and load banking for a minimum of five (5) continuous years.

The contractor shall have safety training – either on-the-job or class-room type in electrical safety outlined in the OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S – Electrical and NFPA 70E – Standard of Electrical Safety in the Workplace. Training certifications shall be submitted to the VA Contracting Officer prior to work. If no training certificates are available, the contractor’s employer shall certify that the service technician has met this requirement and submit it to the VA Contracting Officer.

The contractor shall contact the Supervisor of the Electric Shop, Greg Thomas, at (727) 410-4808 to schedule the load banking a minimum of two weeks in advance.

SUMMARY OF WORK

Provide a complete written report of the load banking for each generator. Information in the report shall have the following data:

1. Company’s name, address, telephone number and fax number

2. Name and signature of contractors who performed the load bank.

3. VA purchase order number or Contract Number.

4. Date and time of work.

5. Generator building number.

6. Generator model, Engine model, Nameplate rating

7. The fifteen minute interval log that was that was recorded during the load bank.

8. Description of generator condition and any deficiencies, if any.

File details come from the government source that posted it. Updated .