P09. Removal Replacement of Exist 10k 30k USTs SOW Attachments ONLY.pdf
PDF 4 MB Posted
- Attached to
- J091--REMOVAL, DISPOSAL, and REPLACEMENT of EXISTING UNDERGROUND DIESEL FUEL STORAGE TANKS (VA-24-00048585)
- Solicitation number
- 36C24524B0016
About this file
This document is a Statement of Work (SOW) for the Removal, Disposal, and Replacement of Existing Underground Diesel Fuel Storage Tanks at the Washington DC VA Medical Center. The SOW provides background on the Washington DC Department of Energy and Environment's (DOEE) requirement for the 30-year old underground storage tanks (USTs) to be removed by February 2025. It outlines the scope of work for a UST certified contractor to remove the existing 10,000 and 30,000 gallon USTs and install new double wall fiberglass diesel fuel tanks of the same capacity. Key details include the project timeline, required submittals, security and safety requirements, environmental compliance, and construction standards. The SOW specifies that the contractor must be certified by DOEE and meet all DC and federal regulations for UST removal and installation. The estimated magnitude of the project is $500,000 to $1 million with a 180 day period of performance from the notice to proceed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI Response Number 15 Attachment.pdf | ||
| 36C24524B0016 RFI.pdf | ||
| Attachement 2.pdf | ||
| 36C24524B0016 0002.docx | DOCX document | |
| 36C24524B0016 0001.docx | DOCX document | |
| Sign In Sheet.pdf | ||
| 2024_0325 Collated Specs Remove Replace Install Diesel Fuel USTs Rev.pdf | ||
| 36C24524B0016_1.docx | DOCX document | |
| S02. RFI Submission.docx | DOCX document | |
| 2024_0311 Rev Compiled Drawings Site Plans and Utilities.pdf | ||
| P09. DOEE 30 Yr UST Notification.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GOVERNMENT OF THE DISTRICT OF COLUMBIA
Department of Energy and Environment Environmental Services Administration
Underground Storage Tank Branch * * * Toxic Substance Division
VETERANS ADMIN MEDICAL CENTER
50 IRVING STREET, NW
C/O Timothy M Williams Environmental Compliance Officer
Washington, DC 20422
Dear Tank Owner/Operator, 01/11/2023
The District of Columbia's Department of Energy and Environment (DOEE) wishes to inform you, as the owner or operator of one or more underground storage tanks in the District, of a UST that is more than thirty (30) years old shall remove the tank from the ground in accordance with Chapter 57 within five (5) years of February 21, 2020. See
20 DCMR § 5700.10 and 5700.11 below:
5700.10 Each owner or operator of a UST that is more than thirty (30) years old shall remove the tank from the ground in accordance with Chapter 61 within five (5) years of February 21, 2020.
5700.11 Each owner or operator of a UST that is more than thirty (30) years old shall perform a tightness test within one (I) year of February 21, 2020, and if the UST fails, remove the UST within one (1) year of the date of the test failure.
If you are receiving this letter our records indicate that you are an owner of an aged tank (30 years or older), or about to an owner of an aged tank that is required to meet this requirement by the year 2025. The facilities included have tanks with an install date of 1994 or greater that are currently in use or temporarily closed. The following tank(s) have met the criteria to meet the aged tank requirement by February 21, 2025:
Address
50 IRVING ST NW
50 IRVING ST NW
Tank# Installed
6 3/1/1992
7 7/1/1994
Capacity Substance
10000 Diesel
30000 Diesel
To meet this requirement, you must perform a Tank Tightness Test or have performed a Tank Tightness Test in the last 12 months. Submit your Tank Tightness Test results within 30 days of this letter to the Underground Storage Tank Program, attention Sharon Hamilton. If any of the information we have is incorrect or was changed recently, e.g.
ownership, tank age, or description, please submit it. Should you fail to comply with this directive DOEE will pursue enforcement action, including a penalty and fine.
Thank you for your cooperation and compliance with this directive. We look forward to working with you to meet this 2025 compliance requirement. Should you have any questions, you may contact Ms. Sharon Hamilton, Environmental Specialist, at (202) 535-1950 or sharon.hamilton@dc.gov. Visit our website https://doee.dc.gov/service/underground-storage-tank-program to access updated UST regulations, staff contact details, and other information and updates.
Sincerely, Fianna Phill, Chief Underground Storage Tank Branch
ATTACHMENT 1a vhawaswillitm Rectangle vhawaswillitm Line vhawaswillitm Typewritten Text Already completed in vhawaswillitm Line
| �� | ||
| �� ����� | � | |
| !��� ����� | � | |
| "##��$$ !�� | % | �# |
&� ����'((()*+ ,-.-/012 03451 4-35607 6-1.-/ 8( 5/,519 2.
1::;<=>?@AB?C
D('DD .54E.FG
:5775042-1,5/E14-1.07 6E4H75016-
EII56-/ *(JDKJD(*)
LMNO
PQ PNRSMTTUV WMSUXYMT ZU[\NVM]
̂\NSMYN_UNS Z̀La ���a��abc� defghij klhjmn lo phom qjmmi rlsm rl� ���a��abt� defghij klhjmn lo phom qjmmi rlsm rl� ���a��abub defghij klhjmn lo phom qjmmi rlsm rl� ���a��abt� defghij klhjmn lo phom qjmmi rlsm rlv ����a�abb� wxymozihee {mxs|lo}mn ~ihejx} �l�yim��hiimn rlc ����a�abb� wxymozihee {mxs|lo}mn ~ihejx} �l�yim��hiimn rlu �u��a�abb� wxymozihee {mxs|lo}mn ~ihejx} �l�yim��hiimn rlLMNO
PV �X\V�[S LMNO
�Q �Y�U L]�U �Q £�¤¥a �xmemi ¦hs§ rlj ̈xejmnqh|m q�}jxls qh|m q�}jxls ~xfxsz rlj ̈xejmn©ª««« ¬®̄°±±²³́ µ¶² ¹º ¼°±½ ®̄ ·¾¿ À®·¶±¿
ÁÁÂÁ©«Á© ð®
IJ³� �xmemi ¦hs§ rlj ̈xejmnqh|m q�}jxls qh|m q�}jxls ~xfxsz rlj ̈xejmn
L̀ ÅÆZ
Ç̂W�̀ �LWÈÅLZ
� ����
Ê���!��� "##��$$ ËÌ� � É�
Í�� 6Î;<<
0JÏ
EÐÑÒ;ABÒ 0;ÒB?
/ÑÓÑ< 8(
5ÒÔ>?@
2ÒC
1-:;<=>?@AB?C
D('DD D(DÕ)'8ÕÖ(((E×?ÑÒ ,-.-/012
03451 4-35607 6-1.-/ 8( 5/,519 2./--.C 1:
6JE
.>ØBA=Ó
:>ÎÎ>;Ø<-?Ô>ÒB?ØÑ?A;Î
6BØÐÎ>;?ÙÑ
EÚÚ>ÙÑÒ:;<=>?@AB?C
D('DD ÛD(DÜ
)'8ÕÖ((( .54E.FGÝ:5775042Þ,0Ý9E,I;Ù>Î>AÓ
4;?;@ÑÒI7E/51-
:02F519.E1 8( 5/,519 2.
1::;<=>?@AB?C
D(((* ÛD(DÜ
)'8ÕÖ(((6Î;<<
0JÏ
EÐÑÒ;ABÒ .=ÑÒBØÑ
ÏÒB×?8(
5ÒÔ>?@
2AC
1-:;<=>?@AB?C
D('DD D(DÕ)'8ÕÖ(((I;Ù>Î>AÓ
4;?;@ÑÒ.54E.FG
:5775042 8( 5/,519 2.
1::;<=>?@AB?C
D('DD D(DÕ)'8ÕÖ((( -ß.
8Ö)(D .54E.FGÝ:5775042Þ,0Ý9E,6Î;<<
0JÏ
EÐÑÒ;ABÒ 7B??ÑÎÎ
/BàÑÒA<8(
5ÒÔ>?@
2AÒÑÑAC
1-:;<=>?@AB?C
D('DD D(DÕ)'8ÕÖ(((6Î;<<
0JÏ
EÐÑÒ;ABÒ 3BÒÑÑ?
,Ý áB?Ñ< 8(
5ÒÔ>?@
2AC
1-:;<=>?@AB?C
D('DD D(DÕ)'8ÕÖ(((
ATTACHMENT 1b
.#%-$/0(1$ 023-#,) 0(1$ 023-#,) 4#5#)6
��7������ ����
���8 "#$%$& '()* .#%-$/0(1$ 023-#,) 0(1$ 023-#,) 4#5#)6
9����� ;��9� ����
",2?&$@(&&
A,)#-,>#)6BC0C
023-#,) BC0C
023-#,) .#)$ '#6D-)$%% '$%-#)6���� ����� �
��������E F�����;�
�;�9:�:�� G���� :H��
���I "#$%$& '()* ",2?&$@(&&
A,)#-,>#)6BC0C
023-#,) BC0C
023-#,) J.."
A,)-D&K
CLM4N
'$%-����� O���� P ��� F�����;�
�;�9:�:�� G���� :H��
��� Q� :9 R: � R��� S� �9 ��T "#$%$& '()* ",2?&$@(&&
A,)#-,>#)6BC0C
023-#,) BC0C
023-#,) J.."
A,)-D&K
CLM4N
'$%-7���� O���� P ��� F�����;�
�;�9:�:�� G���� :H��
��� Q� :9 R: � R��� S� �9
Waitzman, Deborah R.
From: Hamilton, Sharon (DOEE) <sharon.hamilton@dc.gov> Sent: Tuesday, March 14, 2023 2:45 PM To: Williams, Timothy M.
Cc: Staton, Stanley (WAS); Carswell, Vicky; Wilson, McClenton J., (WAS); Warren, Cynthia R.; Gough, Ramon A.; Maistros, Angela; Lucas, Gregory J.; Greene, Jerry; Faye, Elhadji; Pejo, Arben Subject: [EXTERNAL] Re: DC VA Medical Center's 2022 Tank Tightness Tests for DOEE UST Branch 30 Year
Notification
Good Afternoon Mr. Williams, Thank you for submitting your results in a timely manner. I will update your records.
Sharon Hamilton Environmental Protection Specialist Department of Energy and the Environment Underground Storage Tank Program 1200 First Street, NE 5th Floor Washington, DC 20002 Office: 202 535 1950 Cell: 202 878 0326 Fax: 202 535 1383 Email: Sharon.Hamilton@DC.GOV Web: DOEE.DC.GOV Telework: Tuesday and Thursday
COVID 19 Notice to stakeholders:
https://doee.dc.gov/sites/default/files/dc/sites/ddoe/release_content/attachments/3.31.20_DOEE%20FINAL%20USTB% 20Public%20Notice signed.pdf <https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fdoee.dc.gov%2Fsites%2Fdefault%2Ffiles%2Fdc %2Fsites%2Fddoe%2Frelease_content%2Fattachments%2F3.31.20_DOEE%2520FINAL%2520USTB%2520Public%2520No tice signed.pdf&data=05%7C01%7C%7C774948f086724f8d1a2908db24bc3894%7Ce95f1b23abaf45ee821db7ab251ab3bf%7 C0%7C0%7C638144163388399388%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik 1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=J0lDzGey%2BQA968ljWRBF%2Fvx9EwOKZ2%2B9UuN27eGw9q E%3D&reserved=0>
(Link to UST Branch website):
https://doee.dc.gov/service/underground storage tank program <https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fdoee.dc.gov%2Fservice%2Funderground storage tank program&data=05%7C01%7C%7C774948f086724f8d1a2908db24bc3894%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C 0%7C0%7C638144163388399388%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1
(DOEE)
ATTACHMENT 2
haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=utqI4hLRXaeT0JYE8dRVw%2FbVMEHIlvP%2FvYfKtJ7vLHk%3D&re served=0>
From: Williams, Timothy M. <Timothy.Williams@va.gov> Sent: Tuesday, March 14, 2023 2:35 PM To: Hamilton, Sharon (DOEE) <sharon.hamilton@dc.gov> Cc: Staton, Stanley (WAS) <Stanley.Staton@va.gov>; Carswell, Vicky <Vicky.Carswell@va.gov>; Wilson, McClenton J., (WAS) <McClenton.Wilson@va.gov>; Warren, Cynthia R. <Cynthia.Warren4@va.gov>; Gough, Ramon A.
<Ramon.Gough@va.gov>; Maistros, Angela <Angela.Maistros@va.gov>; Lucas, Gregory J. <Gregory.Lucas1@va.gov>;
Greene, Jerry <Jerry.Greene@va.gov>; Faye, Elhadji <Elhadji.Faye@va.gov>; Pejo, Arben <Arben.Pejo@va.gov> Subject: DC VA Medical Center's 2022 Tank Tightness Tests for DOEE UST Branch 30 Year Notification
CAUTION: This email originated from outside of the DC Government. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. If you believe that this email is suspicious, please forward to phishing@dc.gov for additional analysis by OCTO Security Operations Center (SOC).
Facility No. 4000719
Good afternoon Ms. Hamilton, Per our last phone conversation about the notification (attached) sent to the facility by the UST Branch regarding our 10,000 and 30,000 gallon underground storage tanks (both over 30 years old), I have attached copies of the tank tightness tests conducted on each of the USTs on March 6th. Both tanks passed, and the result of the tightness tests can be seen on page 2 of each report. The reports comply with the requirements of the notification for the medical center to provide evidence that the tank tightness tests were conducted on our USTs within the last 12 months.
Also key internal stakeholders have been made initially aware of the primary requirement discussed in the notification and underground storage tank regulations in Title 20 DCMR that mandate both of the 30 + year old tanks be removed:
Chapter 5700, Section 11: “…Each owner or operator of a UST that is more than thirty (30) years old shall remove the tank from the ground in accordance with Chapter 61 within five (5) years of February 21, 2020…”
Consequently, specific stakeholders such as our project engineers have been made aware of the short time line the facility will have to meet to ensure it complies with removal of the tanks before the deadline of February 21, 2025. They
Facility No. 4000719
10,000 and 30,000 gallon underground storage tanks (both over 30 years old), I have attached copies of the tank tightness tests conducted on each of the USTs on March 6th. B have already begun the coordination of getting this endeavor identified as a construction project and getting agency funding for it. Near the start date of the removal project, the facility will submit DOEE’s UST Activity Notification Form to the UST Branch at least 5 days prior to the scheduled date of construction. The medical center will also call the UST Branch at least 24 hours prior to the scheduled date of activity to make an appointment for a DOEE inspector to be present during the tank activity, so he/ she/ they can perform an inspection immediately following the completion of the project for enforcement purposes.
If there is any other additional information you need at this time in regards to our future project plans please let us know.
Regards, Timothy M. Williams
Green Environmental Management System (GEMS) Manager
Washington, D.C. VA Medical Center
50 Irving St. NW, Washington, D.C. 20422
Office: (202) 745 8000, ext. 58702
Cell: (202) 215 4723 timothy.williams@va.gov <mailto:timothy.williams@va.gov>
MONTHLY/ANNUAL UST SYSTEM INSPECTION CHECKLIST - only heating oil USTs under 1,100 gallons are exempt
Facility ID# Facility Name Facility Address Inspector/Operator Date
Signature: Correct & Report evidence of a release/product or damaged/broken spill bucket, equipment, failures to DC
Description
PEI/RP900 Tank1 Tank 2 Tank 3 Tank 4 Tank 5
Category 7.4 g7.5.1
Release Detection Recordkeeping
Circle method of tank leak detection: ATG, CIM, SIR, IC, GWM, SVM, MIMT Circle method of piping leak detection: CIM, MPLT, SIR, GWM, SVM, MIMP 7.6
Automatic Tank Gauge (ATG) On, working, no alarms,test report printed & filed 7.6.1.1 Continuous Interstitial Monitoring
(CIM) Sensor status report printed and properly filed 7.6.2.1
Monthly Piping Leak Test (MPLT) Piping leak test report printed/documented and properly filed 7.6.3.1 Statistical Inventory
Reconciliation (SIR) Last month’s SIR results passed and available for inspection 7.6.4.1
Inventory Control (IC) Inventory reconciled and within the company or regulatory standard 7.6.5.1 Manual Groundwater Monitoring
(GWM) Groundwater bailer in good condition 7.6.6.1
Manual Groundwater (GWM) or Soil Vapor Monitoring (SVM) Wells sampled and results pass 7.6.6.2
Manual Interstitial Monitoring for Tanks (MIMT)
Steel tank: interstitial space checked and found dry 7.6.7.1
Fiberglass tank: interstitial space checked and found dry 7.6.7.2
Fiberglass tank: level of monitoring fluid within normal range 7.6.7.3 For steel and fiberglass tanks, vacuum level is within tolerances 7.6.7.4 Tnk 1 vac: Tnk 2 vac: Tnk 3 vac: Tnk 4 vac:
Manual Interstitial Monitoring for Piping (MIMP)
Containment Sump (STP and/or remote fill sump) inspected and no liquid or debris found and senors in correct position. 7.6.8.1
All Tanks 7.7
7.7.1 Spill Kit All components of the spill kit are present and in good condition
Grade-Level Covers All covers present, in good condition,seated firmly on correct tank, color coded 7.7.2.1
Spill Containment Manhole Drain valve in spill containment manhole in good condition 7.7.3.1
Interstitial space of double-walled containment manhole is dry, free of debris 7.7.3.2
D.C. DOEE MONTHLY WALK THROUGH UNDERGROUND STORAGE TANK SYSTEM INSPECTION FORM
Adopted from www.pei.org/RP900-Appendix A2, 2017. In accordance with 20 DCMR 5904 DOEE V-1-09.21.21
DOEE - 202-535-2600
Take action of any unusual conditions, e.g. alarms, damage, leaks and note corrective actions on next page.
Email: ust.doee.dc.gov
USTs receiving deliveries >30 days intervals, may check their spill buckets prior to each delivery.
Visit: https://doee.dc.gov/service/underground-storage-tank-program OR DOEE-UST Branch, 1200 1ST NE, 5th Fl. Washington DC 20002 OR e-mail:ust.doee@dc.gov
ATTACHMENT 3a fianna.phill Highlight fianna.phill Highlight fianna.phill Highlight fianna.phill Highlight fianna.phill Highlight fianna.phill Highlight
Category Description PEI/RP900 N/A Tank 1 Tank 2 Tank 3 Tank 4
Drop Tube Drop tube present, smooth, no ragged edges, in good condition, no obstruction7.7.4.1 Top edge of coaxial drop tube smooth, round, slightly below the top edge 7.7.4.2 of the fill pipe Hand Held Devices & Tank Gauge Stick Tank gauge stick can be clearly read, is not warped or broken,tip present 7.7.5.1
Check for Water No water present in the tank 7.7.6.1
Tank Vents Vent cap present, vent pipe solidly supported and vertical 7.7.7.1
Stage I Vapor Recovery 7.8
Two-Point (Dual-Point) Vapor Recovery
7.8.1.1 Cover present, colored orange, seated firmly at grade, not broken, cracked or chipped If spill containment manhole is present, no debris, water or product 7.8.1.2
If spill containment manhole is present, no cracks, bulges or holes 7.8.1.3
Vapor recovery cap and poppet of adaptor in good condition, seals tightly 7.8.1.4
Flex connectors has no signs of damage, leaks 7.8.1.5
Observation and Monitoring Wells 7.9
Observation well cover is properly identified and secured 7.9.1.1
Corrosion Protection 7.10
Impressed-Current Cathodic Protection
Record Volt, Amp/Hours readings, check consistency with previous months 7.10.1.1 Check Rectifier if powered on, for normal operation and record green light indicator (if equipped) 7.10.1.2
Dispensers and Submersible Turbine Pumps (STPs) 7.11
Components are clean & dry, no damage or signs of cracks of homes 7.11.1
7.11.2 Shear valve correctly anchored & sensors in correct positions
DESCRIBE ANY DEFICIENCIES & CORRECTIVE ACTIONSTAKEN HERE OR USE EXTRA PAGE:
Instructions: Mark each tank where no problem is observed with a checkmark: √ If certain equipment is not required and / or not present, mark checklist in the N/A column. If a defect is found, mark the checklist with an “X,” describe the problem in the “DEFICIENCIES” section, and notify the appropriate person. Refer to the section listed in the “PEI/RP900” column for additional information.
Refer to PEI RP500, Recommended Practices for Inspection and Maintenance of Motor Fuel Dispensing Equipment, for inspection procedures that apply to fuel dispensing equipment.
UST Owners & Operators are required to maintain a copy of this record for 10 years, including delivery records if spill prevention equipment are not checked every 30 days.
Functionality tests of the LLD, Sumps/spill buckets, and overfill and testing equipment should be completed as is required, records kepts and failures reported to DOEE .
D.C. DOEE MONTHLY WALK THROUGH UNDERGROUND STORAGE TANK SYSTEM INSPECTION FORM Adopted from www.pei.org/RP900-Appendix A2, 2017. In accordance with 20 DCMR 5904 DOEE V-1-09.21.21 – Page 2
Visit: https://doee.dc.gov/service/underground-storage-tank-program OR DOEE-UST Branch, 1200 1ST NE, 5th Fl. Washington DC 20002 OR e-mail:ust.doee@dc.gov
- 1 of 3 -
Form Version 1, September, 2021
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
SPILL PREVENTION EQUIPMENT/CONTAINMENT SUMP INTEGRITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TEST METHOD
Method Used Hydrostatic1 Vacuum Pressure
Other
Method Developer Manufacturer Industry Standard Other
IV. VISUAL INSPECTION INFORMATION
Tank Number
Product Stored
Containment Number2
Containment Type Dispenser
Tank Top Sump
Fill Spill Bucket
Transition
Dispenser
Tank Top Sump
Fill Spill Bucket
Transition
Dispenser
Tank Top Sump
Fill Spill Bucket
Transition
Dispenser
Tank Top Sump
Fill Spill Bucket
Transition
Dispenser
Tank Top Sump
Fill Spill Bucket
Transition
Containment Capacity
Manufacturer
Model3
Were There Visible Cracks, Holes or Other Failures in the Containment?
Yes No Yes No Yes No Yes No Yes No
Was There Product in the Containment Prior to Testing?
Yes No Yes No Yes No Yes No Yes No
Was Product and Debris Removed from the Containment Prior to Testing?
Yes
No
N/A
Yes
No
N/A
Yes
No
N/A
Yes
No
N/A
Yes
No
N/A
V. VISUAL RESULT4 Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
ATTACHMENT 3b http://doee.dc.gov/
- 2 of 3 -
1. For hydrostatic testing, attach documentation of proper disposal of the test fluids to this form. Describe level measurement methods in Section IX.
Comments.
2. Designate each device tested, numerically or by code, on the site drawing in Section X.
3. If model cannot be determined, describe device construction (Single-walled/Double-walled, Fiberglass, HDPE, etc.)
4. Failed visual inspections may constitute a suspected release. Certified individuals must report confirmed or suspected contamination to the Department within 24 hours of observing it. Facility owners/operators must investigate suspected releases within 7 days. Do not conduct additional testing if the device fails visual inspection.
Facility ID #: Facility Name: Test Date:
VI. TESTING INFORMATION
Tank Number
Product Stored
Containment Number5
Portion Tested6
Test Start Time
Test Start Level
Test End Time
Test End Level
Test Period
Level Change
Pass/Fail Threshold
VII. TEST RESULT7 Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
5. Designate each device tested, numerically or by code, on the site drawing in Section X.
6. If the entire depth of the device was not tested, specify how much was tested. The start level for hydrostatic testing must be within 1.5” of the top of a spill bucket and at least 4” above the highest penetration in a containment sump.
7. Failed test results may constitute a suspected release. Certified individuals must report confirmed or suspected contamination to the Department within
24 hours of observing it. Facility owners/operators must investigate suspected releases within 7 days.
VIII. FAILURE DESCRIPTION
If any device fails visual inspection or testing, describe the reason for the failure and the location of the failure for each failed device (i.e. “Cracked entry boot 4” from the bottom of dispenser sump #A1” or “Hole in bottom of Tank 002 fill spill bucket”)
- 3 of 3 -
Facility ID #: Facility Name: Test Date:
IX. COMMENTS
The comments section should be used to note additional information discovered or actions taken during integrity testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices. Repairs to containment sumps and spill buckets require the use of a Department certified individual.
Attach documentation/manifest of proper disposal of hydrostatic test fluids at an offsite treatment/disposal facility, not to be reused on other DC sites.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to this form.
HYDROSTATIC TEST LEVEL MEASUREMENT
If devices were tested using a hydrostatic test, describe how level measurements were taken (i.e. from the bottom up, from the top down, from a mark on the sump wall)
X. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, fill lines, and containment device layout in the space below (or attach a detailed site drawing prepared on a separate sheet). In addition, clearly indicate which devices were tested. Label each device tested with a unique number or code, used in Sections IV and VI, above. Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Tester’s Signature: Date Signed:
- 1 of 2 -
Form Version 1, September 2021
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
GROUNDWATER/VAPOR MONITORING SYSTEM FUNCTIONALITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TEST PROCEDURE – Briefly describe procedure(s) used to evaluate/test the groundwater or vapor monitoring system.
IV. GROUNDWATER/VAPOR MONITORING SYSTEM TESTING INFORMATION
Tank Number
Product Stored
Site evaluated by a licensed professional to establish the number and positioning of monitoring wells that will detect releases within the excavation zone from any portion of the tank that routinely contains product. Yes No
Written site evaluation readily available at the facility: Yes No Date of site evaluation:
Name of licensed professional: License number:
Wells are installed in accordance with the site evaluation: Yes No
A. GROUNDWATER MONITORING
Product detection devices can detect 1/8-inch or less of leaked product on top of the groundwater:
Yes No
Electronic sampling equipment tested and operating properly: Yes No N/A
Date sampling equipment was last calibrated:
B. VAPOR MONITORING
Monitoring devices are capable of detecting increases in concentrations of stored regulated substances:
Yes No
Electronic sampling equipment tested and operating properly: Yes No
Date sampling equipment was last calibrated:
V. TEST RESULT Pass Fail
Any “No” answer in Section IV. Indicates the Groundwater or Vapor monitoring system fails. Failure of a release detection method may constitute a suspected release. Certified Individuals must report confirmed or suspected contamination to the Department within 48 hours of observing it. Facility owners/operators must investigate suspected releases within 7 days. If a reportable release is confirmed, it must be reported to the Department by telephone within 24 hours and requires immediate repair or replacement.
ATTACHMENT 3c
- 2 of 2 -
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, and monitoring well locations (or attach a detailed site drawing prepared on a separate sheet). Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
- 1 of 2 -
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315 Phone: (202) 535-2600 FAX: (202) 535-1383
Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
OVERFILL PREVENTION EVALUATION FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TANK AND DEVICE INFORMATION
Tank Number
Tank Capacity
Tank Diameter
Product Stored
Overfill Manufacturer
Overfill Model
Product Delivery Method
Pressurized
Gravity
Pressurized
Gravity
Pressurized
Gravity
Pressurized
Gravity
Pressurized
Gravity
Overfill Type
Drop Tube Shutoff
Alarm
Ball Float
Other
None
Drop Tube Shutoff
Alarm
Ball Float
Other
None
Drop Tube Shutoff
Alarm
Ball Float
Other
None
Drop Tube Shutoff
Alarm
Ball Float
Other
None
Drop Tube Shutoff
Alarm
Ball Float
Other
None
IV. TEST INFORMATION (Complete all applicable overfill types)
A. DROP TUBE SHUTOFF DEVICE
Drop tube and float free of debris?
Yes No Yes No Yes No Yes No Yes No
Float and poppet move freely?
Yes No Yes No Yes No Yes No Yes No
Poppet enters flow path when float is engaged?
Yes No Yes No Yes No Yes No Yes No
Tank capacity when flow is stopped (%)
B. OVERFILL ALARM
Visible and audible to delivery driver?
Yes No Yes No Yes No Yes No Yes No
Probe and float in good condition?
Yes No Yes No Yes No Yes No Yes No
Float moves freely? Yes No Yes No Yes No Yes No Yes No
Does simulated overfill trigger alarm?
Yes No Yes No Yes No Yes No Yes No
Tank capacity when alarm is triggered (%)
ATTACHMENT 3d
- 2 of 2 -
C. BALL FLOAT VALVE
Standard drop tube installed?
Yes No Yes No Yes No Yes No Yes No
Is the only fill present a direct fill? Yes No Yes No Yes No Yes No Yes No
Ball and cage present and in good condition?
Yes No Yes No Yes No Yes No Yes No
Ball moves freely in cage?
Yes No Yes No Yes No Yes No Yes No
Tank capacity when flow is restricted (%)
D. OTHER, E.G. WHISTLE VENT
ALARM
Permanently Installed?
Yes No Yes No Yes No Yes No Yes No
Audible to delivery driver?
Yes No Yes No Yes No Yes No Yes No
Tank capacity when whistle stops (%)
OTHER
COMMENTS
V. TEST RESULTS Any “No” answer in Section IV. Indicates the overfill device fails. Failure of any overfill prevention device requires immediate repair or replacement. Underground Storage Tanks may not receive product deliveries without functional overfill prevention.
Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during functionality testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices. Installation, repair, and removal of overfill prevention devices requires the use of a Department certified individual. Failed ball float valves may not be repaired or replaced; an alternate form of overfill prevention must be installed.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law as provided in that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law as provided in that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
PRESSURE/VACUUM MONITORING FUNCTIONALITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TEST PROCEDURE – Briefly describe procedure(s) used to test the probes (i.e. PEI/RP1200, manufacturer’s testing procedure, etc.)
IV. PRESSURE/VACUUM MONITORING
Tank Number
Product Stored
Line Number1 N/A N/A N/A N/A
ATG Manufacturer
ATG Model
P/V Monitoring System Manufacturer
P/V Monitoring System Model
P/V Monitoring System is functional
Yes No Yes No Yes No Yes No
Manufacturer’s test method followed
Yes No Yes No Yes No Yes No
Interstice is air tight Yes No Yes No Yes No Yes No
Leak in interstice triggers alarm
Yes No Yes No Yes No Yes No
Leak in piping interstice disables
STP2
Yes No N/A Yes No N/A Yes No N/A Yes No N/A
V. TEST RESULT3 Pass Fail Pass Fail Pass Fail Pass Fail
1. Designate each product line that has its interstice under pressure or vacuum by P/V system numerically or by code on the site drawing.
2. Required for pressurized piping systems installed after 2007, using P/V monitoring for 3gph piping release detection.
3. Any “No” answer in a required row indicates the P/V system fails. Failed leak detection systems must be repaired or replaced immediately.
ATTACHMENT 3e
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during functionality testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, and containment structure layout in the space below (or attach a detailed site drawing prepared on a separate sheet). Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
- 1 OF 2 -
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
SENSOR FUNCTIONALITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TEST PROCEDURE – Briefly describe procedure(s) used to test the sensors (i.e. PEI/RP1200, manufacturer’s testing procedure, etc.)
IV. SENSOR AND TESTING INFORMATION
Sensor Location
Sensor Number1
Manufacturer
Model
Sensor Type Discriminating
Non-Discriminating
Discriminating
Non-Discriminating
Discriminating
Non-Discriminating
Discriminating
Non-Discriminating
Discriminating
Non-Discriminating
Test Liquid Water
Product
Water
Product
Water
Product
Water
Product
Water
Product
Is the ATG console clear of alarms?
Yes No Yes No Yes No Yes No Yes No
Is the sensor properly positioned?
Yes No Yes No Yes No Yes No Yes No
Is the sensor in a good state of repair?
Yes No Yes No Yes No Yes No Yes No
Does the sensor trigger an alarm when placed in the test liquid?
Yes No Yes No Yes No Yes No Yes No
Is the sensor correctly identified on the ATG?
Yes No Yes No Yes No Yes No Yes No
Does a sensor alarm automatically disable the pump? 2
Yes No Yes No Yes No Yes No Yes No
V. TEST RESULT3 Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
1. Designate each sensor tested numerically or by code on the site drawing.
2. Required for pressurized piping systems installed after 2007, using sensors for 3 gph piping release detection.
3. Failed sensors must be repaired or replaced immediately.
ATTACHMENT 3f
- 2 OF 2 -
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during functionality testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, and containment structure layout in the space below (or attach a detailed site drawing prepared on a separate sheet). In addition, clearly indicate which sensors were tested. Label each sensor with a unique number or code, used in section V, above. Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
- 1 OF 2 -
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
AUTOMATIC TANK GAUGE FUNCTIONALITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. AUTOMATIC TANK GAUGE Pass Fail
ATG Manufacturer: ATG Model:
Detected leak will trigger an alarm? Yes No Battery Backup Functional? Yes No
ATG software properly programmed? Yes No Is the ATG equipped with CITLDS? Yes No
III. TEST PROCEDURE – Briefly describe procedure(s) used to test the probes (i.e. PEI/RP1200, manufacturer’s testing procedure, etc.)
IV. PROBE AND TESTING INFORMATION
Tank Number
Product Stored
Manufacturer
Model
Measured Product Level (in.)
ATG Product Level (in.)
Measured Water Level (in.)
ATG Water Level (in.)
Measured product and water levels match ATG values?
Yes No Yes No Yes No Yes No Yes No
Is the probe in a good state of repair?
Yes No Yes No Yes No Yes No Yes No
Is the ATG console clear of alarms? Yes No Yes No Yes No Yes No Yes No
Float(s) move freely Yes No Yes No Yes No Yes No Yes No
V. TEST RESULT1 Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
1. Any “No” answer in a required row indicates the probe fails. Failed probes and ATGs must be repaired or replaced immediately.
ATTACHMENT 3g
- 2 OF 2 -
Facility ID #: Facility Name: Test Date:
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during functionality testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, and containment structure layout in the space below (or attach a detailed site drawing prepared on a separate sheet). Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law, that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
- 1 -
GOVERNMENT OF THE DISTRICT OF COLUMBIA
DEPARTMENT OF ENERGY AND ENVIRONMENT
UNDERGROUND STORAGE TANKS BRANCH
1200 FIRST STREET, NE, 5TH FLOOR, Washington, D.C. 20002-3315
Phone: (202) 535-2600 FAX: (202) 535-1383 Website: http://doee.dc.gov, Email: UST.DOEE@dc.gov
UNDERGROUND STORAGE TANK
AUTOMATIC LINE LEAK DETECTOR FUNCTIONALITY TESTING FORM
I. FACILITY INFORMATION – Type or print (in ink) all items.
Facility ID #: Facility Name:
Facility Street Address:
Facility Telephone: Facility Email: Ward:
II. TESTER INFORMATION
Tester Name: Tester Cert. #: Tester Telephone:
Company Name: Company Cert. #: Test Date:
III. TEST PROCEDURE – Briefly describe procedure(s) used to test the probes (i.e. PEI/RP1200, manufacturer’s testing procedure, etc.)
IV. LINE LEAK DETECTOR TESTING INFORMATION
Tank Number
Product Stored
Line Number1
Manufacturer
Model
Leak Detector Type Electronic
Mechanical
Electronic
Mechanical
Electronic
Mechanical
Electronic
Mechanical
Electronic
Mechanical
STP Operating Pressure
A. MECHANICAL LINE LEAK DETECTORS
Check Valve Holding Pressure
Metering Pressure
Opening Time
Simulated leak causes slow-flow
Yes No Yes No Yes No Yes No Yes No
Leak detector resets when line pressure is bled off to zero
Yes No Yes No Yes No Yes No Yes No
B. ELECTRONIC LINE LEAK DETECTORS
Simulated leak causes an alarm
Yes No Yes No Yes No Yes No Yes No
Simulated leak disables the STP2
Yes No Yes No Yes No Yes No Yes No
V. TEST RESULT3 Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail
1. Designate each product line, on which a line leak detector was tested, numerically or by code on the site drawing.
2. Required for pressurized piping systems installed after 2007, using LLD for 3gph piping release detection.
3. Any “No” answer in a required row indicates the line leak detector fails. Failed line leak detectors must be repaired or replaced immediately.
ATTACHMENT 3h
- 2 -
VI. COMMENTS
The comments section should be used to note additional information discovered or actions taken during functionality testing that affect compliance at the facility. For example, include comments concerning any observations made by the tester that would affect the test results.
Include actions taken to repair or replace failed devices.
If additional comment sheets are needed, label each sheet with the report header information and attach the sheet(s) to the back of this form.
VII. SITE DRAWING
Provide a detailed site drawing of the applicable UST(s), product piping, and containment structure layout in the space below (or attach a detailed site drawing prepared on a separate sheet). Any other pertinent information should also be included.
VII. OWNER’S REPRESENTATIVE CERTIFICATION
I have reviewed this report. I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Signature: Date Signed:
VIII. TESTER CERTIFICATION
By signing this document as the Tester, I certify under penalty of law that the information provided by me is true, accurate, and complete to the best of my knowledge and belief. Pursuant to D.C. Official Code § 22-2405, the making of a false statement in writing to any instrumentality of the District of Columbia government is a criminal offense punishable by criminal penalties.
Title 20 District of Columbia Municipal Regulations
65‐1
CHAPTER 65 LICENSING AND CERTIFICATION OF TANK
INSTALLERS, REMOVERS, TESTERS AND OPERATORS
TRAINING REQUIREMENTS
Secs.
6500 General Provisions 6501 Certification Procedures 6502 Operator Training 6503 Approval of Training Programs for Operator Training
6500 GENERAL PROVISIONS
6500.1 The owner or operator of each UST system shall ensure that the UST system or any component of the UST system, including the release detection system, is installed under the continuous on-site supervision of a UST System Technician who is certified in accordance with the provisions of this chapter and who is licensed to do business in the District of Columbia.
6500.2 The owner or operator of each UST system that is to be permanently closed or that the type of service will change shall ensure that the UST system is abandoned or removed under the continuous on-site supervision of a UST System Technician or UST Closer Specialist who is certified in accordance with the provisions of this chapter and who is licensed to do business in the District of Columbia.
6500.3 The owner or operator of each UST system to be tested for tightness shall ensure that the test is conducted under the continuous on-site supervision of a UST System Tester who is certified in accordance with the provisions of this chapter and licensed to do business in the District of Columbia.
6500.4 Each business that provides services for UST system installation, upgrade, retrofit, repair or permanent closure in the District of Columbia shall be certified to perform UST activities by the Director in accordance with the provisions of this chapter and licensed to do business in the District of Columbia. A business may be certified to perform only those UST activities for which it employs a UST System Technician, UST Closer Specialist, UST System Tester who has a current valid District of Columbia certification and license for the applicable UST activity or an equivalent category.
6500.5 Each UST System Technician, UST Closure Specialist and UST System Tester who provides his or her services for UST system installation, upgrade, retrofit, repair, or permanent closure in the District of Columbia shall be certified to perform UST system activities by the Director in accordance with the provisions of this chapter and licensed to do business in the District of Columbia.
6500.6 Each business that is certified to perform UST system activities in the District of Columbia shall provide the Director with a list of employees, who are not certified as UST System Technicians, Closer Specialists or Testers, but who
ATTACHMENT 4
Title 20 District of Columbia Municipal Regulations
65‐2 perform supervised on-site UST activities.
6500.7 Each certified UST System Technician, Closure Specialist and Tester shall carry the identification card or the certificate issued by the Director at all times while conducting the applicable UST activity. The identification card shall be available for inspection by the owner, operator or the Director when the technician, specialist or tester is engaged in the UST activity for which he or she is certified.
6500.8 No business may transfer the UST System certification or license issued to it by the District of Columbia.
6500.9 Within ten (10) business days after close or termination of the business, the licensee shall surrender the certification and license to the Director for cancellation.
6500.10 An owner of any active regulated UST system in the District shall designate at least one Class A, one Class B, and one Class C operator for each active UST facility, and all designated classes shall comply with the requirements of § 6502.
6501 CERTIFICATION PROCEDURES
6501.1 The Director shall certify to perform UST System activities as set forth in §6500 in the District of Columbia, any individuals who satisfy the following requirements:
(a) Show evidence of having satisfactory completion of a recognized training program in the UST System activity(ies) for which the applicant seeks certification;
(b) Submission of a completed application and payment of the initial application fee of $200.00 in the form of a check made payable to the D.C. Treasurer;
(c) Possess a current OSHA certification; and
(d) Satisfactory completion of a test upon their knowledge in the technical area in which they seek certification as well as the District's statutes and regulations pertaining to USTs.
6501.2 The Director shall certify businesses that wish to perform UST System activities in the District of Columbia, as set forth in §6500, provided they satisfy the following requirements:
(a) Submission of a completed application and payment of the initial application fee of $350.00 in the form of a check made payable to the D.C. Treasurer;
Title 20 District of Columbia Municipal Regulations
65‐3
(b) Demonstrate, to the satisfaction of the Director, that the business is qualified to perform the UST System activities for which it seeks certification;
(c) Demonstrate, to the satisfaction of the Director, that the business employs at least one individual who has expertise and is certified in the District in each of the UST System activities the business will offer;
(d) Possess a current OSHA certification; and
(e) Possess a valid, current District of Columbia business license for the business in which certification is sought.
6501.3 The Director may recognize individuals or businesses that are certified by neighboring states and so certify, to perform UST System activities as set forth in § 6500, individuals or businesses that satisfy the requirements of this section:
(a) Possess a current valid certification as a UST System Technician, Closer
Specialist or Tester, or an equivalent certification category as determined by the Director, issued by either of the states of Virginia, West Virginia, Maryland, Delaware, or Pennsylvania;
(b) Are currently in good standing in each of the states, named in
§6501.3(a), for which it holds a certification;
(c) Possess a current OSHA certification;
(d) Possess a valid, current District of Columbia business license for the business in which certification is sought;
(e) Demonstrate, to the satisfaction of the Director, a knowledge of the provisions of this Subtitle; and
(f) Submit a completed application form and pays an initial application fee of $150.00 for individuals or $250 for businesses.
6501.4 An applicant certified in one of the states in §6501.3(a) may be tested by the
Director to verify the knowledge of the provisions of this subtitle or shall submit…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .