This is the Oregon Standard Drawing Set, a technical reference document produced by the State of Oregon containing standardized specifications and design details for infrastructure construction projects. The document provides comprehensive drawing specifications for pipe installations, trench work, street cuts, concrete pipe anchors, manholes, and inlet structures. The standard drawings cover multiple installation scenarios including pipe zone and trench backfill specifications (RD300), street cut requirements (RD302), concrete pipe slope anchors (RD332), manhole standards with precast components (RD335-RD336), pipe-to-structure and pipe-to-manhole connections (RD339 and RD345), manhole base sections (RD344), manhole covers and frames (RD356), and concrete inlet types G-1, G-2, G-2M, and G-2MA (RD364). The drawings include detailed dimensional specifications, material requirements, reinforcement details, and construction methodology for various pipe diameters ranging from 4 inches to 72 inches.
The document specifies material standards including Class A through Class E backfill materials, commercial-grade concrete requirements, ASTM C478 compliance for precast products, and tracer wire specifications for all connecting pipes. Key construction details address pipe bedding depths, spacing requirements for multiple installations, compaction specifications, slope requirements for pipes on grades of 20 percent or greater, and watertight sealing requirements for manhole connections. The standard drawings maintain an effective date of December 1, 2025 through May 31, 2026, and include general notes requiring consultation with a registered professional engineer for projects utilizing these standards. All materials and specifications must comply with current Oregon Standard Specifications, and the drawings reference additional standard details for specialized components such as manhole steps, adjustment rings, and alternate products approved by Oregon Department of Transportation's Qualified Products List.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Specification Documents.pdf | ||
| Design Drawing Set.pdf | ||
| 24PW11 - Addendum No. 1.pdf | ||
| 24PW11 - Bid Opening Results.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RD300
INSTALLATIONS
PIPE ZONE AND MULTIPLE
TRENCH BACKFILL, BEDDING,
R D
.d g n
14-JUL-2014N/A
J U
L
C
"A" note 4)
(See general
Tracer wire
MULTIPLE INSTALLATIONS
DIAMETER MIN. SPACE BETWEEN PIPES
(in)
"A"
(in)
"B"
(in)
"C"
(in)
"D"
TABLE A
Finish grade stabilization, as required
Trench foundation see Table A
"C" Pipe bedding, Top of subgrade as directed
Topsoil or existing material
Surfacing-match
Base material m a te r ia l
E x c a v a te d n a ti v e
C la s s A c r u s h e d r o c k
C la s s B o r m a x
1 ( c le a n s a n d
C la s s C
A s d ir e c te d m a te r ia l m a x
C la s s D p it o r b a r r u n
C L
S M
C la s s E
T re n c h b a c k fi ll a re a P ip e z o n eS e e T a b le
A
D
Nom."B" "B"
Pipe diameter
24" min.
m in
D ia
Up to 48"
48" to 72"
24"
) dia. of pipe2
One half (
4. See Std. Dwg. RD336 for tracer wire details (When required).
3. Pipes over 72" diameter are structures, and are not applicable to this drawing.
diameter.
used and the pipe is ≥ 36" diameter, increase dimension "B" to nominal pipe
2. For pipe installation in embankment areas where the trench method will not be
1. Surfacing of paved areas shall comply with street cut Std. Dwg. RD302.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
see general note 3.
For pipes over 72" diameter, the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
Standard Drawing, while
The selection and use of this
RD302
STREET CUT
R D
.d g n
20-JUL-2020N/A
J U
L
(Actual)
Trench width whichever is greater. Compact as specified.
4. Place AC mix minimum thkn. of 6" or the thkn. of the removed pavement, details.
3. For joining new concrete to existing concrete, see contract plans for sepecific or to the thickness of removed pavement, whichever is greater.
2. Concrete pavement shall be replaced with concrete to a minimum thickness of 8"
1. All existing AC or PCC pavement shall be sawcut prior to repaving.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
(AC patch only) with tack material and sand
Seal surface over joint concrete as specified
CLSM or full depth asphalt
Compacted aggregate base, backfill as specified
Compacted trench
(Extg.)
Undisturbed base
Extg. pvmt.
see general notes
Pvmt. replacement, min.
6" min.
6"
Min. width=Roller width plus 2" m in
Tack coat cut edges (AC only) the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD332
CONCRETE
PIPE SLOPE ANCHORS
R D
.d g n
12-JAN-2015N/A
J U
L
Pipe bedding undisturbed native soil
Pour against
ELEVATIONPLAN
6. See Std. Dwg. RD336 for tracer wire details (When required).
5. See Std. Dwgs. RD300 & RD304 for pipe installation details.
engineer.
4. Dimensions for embedment for pipes larger than 12" shall be approved by the
50+ % 15' or concrete encasement
35-50% 25'
20-34% 35'
SLOPE SPACING (on slope)
3. Center to center max. spacing of concrete pipe anchors shall be:
2.All concrete shall be commercial grade concrete.
Remove forms prior to backfilling trench.
drains and other pipelines are constructed with slopes 20% or greater.
1. Concrete pipe anchors shall be constructed using forms when sewers, storm
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
(See general note 6)
Tracer wire on inlet end
Install over 3" weep hole
" openings.4 mesh with
5" square galvanized wire trench wall
Undisturbed at bottom of trench
Install 3" weep holes
Native soil
(See general note 6)
Tracer wire see general note 4
12" and smaller pipe, trench wall
Undisturbed
Fi ni sh gr ad e
Native soilmin.
18" Trench width min.
18" m in
12" when using slope anchors made with concrete.
Metal pipe requires polymeric coating the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD335
R D
.d g n
21-JUN-2019N/A
J U
L
(See general note 5)
24" max.
MANHOLE WITH PRECAST CONICAL TOP
MANHOLE WITH PRECAST FLAT SLAB TOP
6. All connecting pipes shall have a tracer wire, or approved alternate.
5. Adjust 24" maximum.
4. See Std. Dwg. RD344 for manhole base section.
3. See Std. Dwg. RD345 for pipe to manhole connections.
the Engineer.
2. Standard precast manhole section diameter shall be 48". Use 42" if specified by
1. All precast products shall conform to requirements of ASTM C478.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
12. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.
11. See Std. Dwg. RD342 for shallow manholes.
10. Max. pipe diameter varies with pipe material.
9. See Std. Dwg. RD356 for manhole covers and frames, manhole adjustment rings, etc.
8. See Std. Dwg. RD336 for details not shown.
7. See Std. Dwg. RD336 for manhole steps.
plastic or rubber ring to form a watertight seal sealed with non-shrink grout, preformed
Frame and precast grade ring(s) shall be
(See Details "B" & C" on Std. Dwg. RD336)
See general note 7, if steps are not required.
specified. Concentric cone may be used
Provide manhole steps unless otherwise to form a watertight seal grout, preformed plastic or rubber ring
All joints shall be sealed with non-shrink
Joint type varies with manufacturer (Typ.)
(See Detail "A" on Std. Dwg. RD336)
Tracer wire, (See general note 10)
Pipe (Typ.)
(Precast base shown)
Manhole base
Base rock
"/ft. min.2 slope varies:
Concrete bench, (As required)
Precast riser(s) conical top
Precast on Std. Dwg. RD336)
(See Detail "A"
Tracer wire, (As required)
Adjustment ring(s)
Manhole cover and frame
Finish grade
(As required)
Precast grade ring(s)
(See general note 5)
24" max.
Varies (12" max.)
25"
(42" if specified)
48"
(See general note 3)
Pipe connection varies (Typ.)
T y p m in m in
25"
Manhole cover and frame
Finish grade
(As required)
Precast grade ring(s) on Std. Dwg. RD336)
(See Detail "A"
Tracer wire, on Std. Dwg. RD336)
(See Detail "A"
Tracer wire, (As required)
Adjustment ring(s)
Varies (12" max.)
Precast flat slab top
Precast riser(s) (As required)
STORM SEWER MANHOLE
STANDARD
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD336
MANHOLE DETAILS
STANDARD
R D
.d g n
16-JAN-2019N/A
J U
L
X m in
Manhole cover and frame
Finish grade
(Typ.)
tracer wire fastener for
Non corrosive
Tracer wire
18" above top of manhole cover
Leave enough free wire to extend
Coil and secure wire to fastener.
precast flat slab top)
(See Std. Dwg. RD335 for
Precast conical top shown
Tracer wire
(As required) ring(s)
Precast grade
(As required)
Adjustment ring(s)
Place tracer wire directly over pipe centerline and on top of the pipe zone material.
6. All connecting pipes shall have a tracer wire, or approved alternate.
5. Adjust 24" maximum.
4. See Std. Dwg. RD344 for manhole base section.
3. See Std. Dwg. RD345 for pipe to manhole connections.
Engineer.
2. Standard precast manhole section diameter shall be 48". Use 42" if specified by the
1. All precast products shall conform to requirements of ASTM C478.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
12. See project plans for details not shown.
11. See Std. Dwg. RD342 for shallow manholes.
10. Max. pipe diameter varies with pipe material.
9. See Std. Dwg. RD356 for manhole covers and frames, manhole adjustment rings, etc.
8. See Std. Dwg. RD335 for details not shown.
See Detail "C" for alignment of steps, and manhole cover and frame.
When H=42" or less omit steps.
7. Steps shall conform to requirements of ASTM C478.
and frame
Manhole cover Finish grade
Lowest flow line outfall pipe), or as directed.
azimuth right from lowest
See plans for X (measured
Manhole steps
(Align with steps)
Manhole cover and frame
Lowes tou tfal lpip e m a x s p a c in g
H v a r
"8
6"
13" to 16"
Var.
13" to 16"
Var.
(See general note 6) (See general note 7)
NOTE: No conflict with pipe align with available shelf.
See ODOT's QPL for acceptable alternate manhole steps.
(See general note 7)
TRACER WIRE
DETAIL "A"
MANHOLE STEPS
DETAIL "B"
AND MANHOLE STEPS ORIENTATION
PRECAST FLAT SLAB TOP
OR
PRECAST CONICAL TOP
DETAIL "C"
FRONT SIDE
PLAN
PLAN
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD339
CONNECTIONS
PIPE TO STRUCTURE
R D
.d g n
REVISED NOTES07-2021
20-JAN-2023N/A
J A
N
PLAN PLAN
grout
Non-shrink
(See general note 5)
Tracer wire
(See general note 1)
Sump shown
(typ.)
grout
Non-shrink
(See general note 5)
Tracer wire (Typ.)
(See general note 1)
Sump shown
(See general note 5)
Tracer wire (Typ.)
(See general note 7)
Pipe zone (Typ.)
(See general note 7)
Pipe zone (Typ.)
(See general note 6)
Resilient connector
(See general note 5)
Tracer wire
(See general note 1)
Sump shown
(See general note 1)
Sump shown
(See general note 6)
Resilient connector (Typ.)
(See general note 5)
Tracer wire (Typ.)
(See general note 7)
Pipe zone (Typ.)
(See general note 7)
Pipe zone (Typ.)
(See general note 5)
Tracer wire (Typ.)
(See general note 6)
Resilient connector (Typ.)
CONNECTION OF FLEXIBLE PIPE TO STRUCTURECONNECTION OF RIGID PIPE TO STRUCTURE
SECTION C-CSECTION D-DSECTION A-ASECTION B-B
B
B
A A C C
D
D
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
7. Pipe zone varies, see Std. Dwg. RD300.
6. When flexible pipe is used, install resilient connectors conforming to requirements of ASTM C923.
See Std. Dwg. RD336 for tracer wire details.
5. All connecting pipes shall have a tracer wire, or approved alternate.
4. Maximum pipe diameter varies with pipe material.
3. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.
2. See appropriate standard drawings or special project details for other similar structures.
1. See Std. Dwgs. RD364, RD365, and RD366 for inlet details not shown.
04-2022 REVISED NOTES
01-2023 REVISED DETAILS AND NOTES
(typ.)
grout
Non-shrink
(typ.)
grout
Non-shrink the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD344
BASE SECTION
STANDARD MANHOLE
R D
.d g n
14-JUL-2014N/A
J U
L
(For invert channel details, see precast option at right)
PRECAST MANHOLE BASECAST IN PLACE MANHOLE BASE
SECTION B-BSECTION A-A
A A B B
(See general note 11)
Tracer wire, 12" cc max.
#3 bars, 1 - #4 Hoop (Both ways)
#4 bars, 12" cc undisturbed material
Pour concrete against
2"
Joint type as required
(See general note 11)
Tracer wire, 2 - #4 hoops bottom half of pipe
Shape channel to match
(See general note 2)
Channel
(42" if specified)
48" 8" m in
(See general note 11)
Tracer wire (Typ.)
8"
4" 3 - #4 hoops the contractor at the option of be round or octagonal, Outside of base may
Lap 10'' unless otherwise shown.
clear of nearest face of conc., All reinforcement shall be 2"
48" (42"ifspecified)
(Both ways)
#4 bars, 12" ctr. ctr.
12" ctr. ctr. max.
#3 bars, (T y p
(42" if specified)
48"
INVERT CHANNEL
min.
8" bottom half of largest pipe
Shape channel to match
(See general note 2)
Channel
(See general note 11)
Tracer wire, 6" min.
note 12
See general
"/ft. min.2 slope varies:
Concrete bench, (See general note 11)
Tracer wire, Base rock transition sections.
uniform flow lines with gradual
Construct invert channels to and/or riser(s).
May occur in manhole base section
As measured at inner manhole wall.
(See general note 11)
Tracer wire (Typ.)
m in b etw een
(T yp p ip e p en etratio n s
Pipe(s) may extend 2" max. beyond the interior manhole wall.
6. Extend pipe into manhole and grout smooth.
5. Use on 42" and 48" diameter manhole.
4. Max. pipe diameter varies with pipe material.
3. Bases may be precast or cast in place.
2. Channels shall be constructed to provide smooth slopes and radii to outlet pipe.
1. All concrete shall be commercial grade concrete.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
12. At spring line of pipe, extend channel up to crown line on 12:1 batter.
11. See Std. Dwg. RD336 for tracer wire details.
10. See Std. Dwg. RD336 for manhole steps details.
9. See Std. Dwg. RD345 for pipe to manhole connections.
8. All precast products shall conform to the requirements of ASTM C478.
plans.
7. Location, elevation, diameter, slope, and number of pipe(s) varies, see project
PLANPLAN
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD345
CONNECTIONS
PIPE TO MANHOLE
R D
.d g n
REVISED DETAILS AND NOTES01-2023
20-JAN-2023N/A
J A
N
CONNECTION OF RIGID PIPE TO MANHOLE
SECTION A-A
SECTION B-B
B
B
PLAN
A A
SECTION B-B
SECTION A-A
B
A A
B
PLAN
(See general note 6)
Tracer wire slope var. (See general note 7)
Concrete invert channel, slope var. (See general note 7)
Concrete invert channel, (See general note 6)
Tracer wire (Typ.)
(See general note 14)
Pipe zone (Typ.)
(See general note 14)
Pipe zone (Typ.)
slope var. (See general note 7)
Concrete invert channel, (See general note 6)
Tracer wire (Typ.)
Grout (Typ.)
Non-shrink
"/ft. min.2 slope var.
Concrete bench, "/ft. min.2 slope var.
Concrete bench, "/ft. min.2 slope var.
Concrete bench, slope var. (See general note 7)
Concrete invert channel, slope var. (See general note 7)
Concrete invert channel, (See general note 6)
Tracer wire
"/ft. min.2 slope var.
Concrete bench, (See general note 8)
Resilient connector
"/ft. min.2 slope var.
Concrete bench, (See general note 8)
Resilient connector (Typ.)
(See general note 6)
Tracer wire (Typ.)
(See general note 8)
Resilient connector (Typ.) slope var. (See general note 7)
Concrete invert channel, (See general note 6)
Tracer wire (Typ.)
(See general note 14)
Pipe zone (Typ.)
(See general note 14)
Pipe zone (Typ.)
"/ft. min.2 slope var.
Concrete bench, Pipe zone varies, see Std. Dwg. RD300.14.
manhole adjustment rings, etc.
See Std. Dwg. RD356 for manhole covers and frames,13.
See Std. Dwg. RD344 for manhole base section.12.
See Std. Dwg. RD342 for shallow manholes.11.
See Std. Dwg. RD336 for manhole steps details.10.
not shown.
See Std. Dwgs. RD335, RD336, and RD338 for details9 .
conforming to requirements of ASTM C923.
When flexible pipe is used, install resilient connectors8.
slopes and radii to outlet pipe.
Invert channels shall be constructed to provide smooth7.
details.
approved alternate. See Std. Dwg. RD336 for tracer wire
All connecting pipes shall have a tracer wire, or6.
Maximum pipe diameter varies with pipe material.5.
pipe(s) varies, see project plans.
Location, elevation, diameter, slope, and number of4.
All concrete shall be commercial grade concrete.3.
Manhole base sections may be precast or cast-in-place.2.
ASTM C478.
All precast sections shall conform to requirements of1.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
CONNECTION OF FLEXIBLE PIPE TO MANHOLE
Grout (Typ.)
Non-shrink
Grout (Typ.)
Non-shrink the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
8. See ODOT's QPL for alternate bolt-down products.
to bicycle or pedestrian use.
subject7. Manhole grate allowed only in locations not rings.
6. See ODOT's QPL for alternate manhole adjustment adjustment.
5. See Std. Dwg. RD360 for manhole frame
4. See Std. Dwg. RD336 for manhole steps.
origin.
manufacturer's initials, heat number and point of
3. Covers and frames shall be stamped with may be submerged (no holes).
2. Watertight covers required if located where cover holes maximum.have two easement areas. Covers for sanitary manholes shall drain manhole where located in pedestrian ways or
Tamperproof covers required on sanitary or storm1.
A A
PLAN
pavement, concrete gutter or walk.
frame is to be placed in concrete, Coat outside of frame with asphalt where
NOTE:
COVER SECTION A-A
FRAME SECTION A-A
"4
6" "4 3 1"
"4
2"
"4
"4
"4
2"
"8
"4
1 2 note 4.
of 20 feet or greater. See general required for mannholes with depths
*36 inch minimum diameter cover is
"4
"4
"4
"4
COVER AND FRAME
STANDARD MANHOLE
" clearance8
"4
25" (*36") " min.2 m in
"4
"4
"4
23"
"2
" chamfer8 m a x all around to a true bearing to be machined
Cover and frame
PLAN
frame. See general note 7.
For use with standard manhole
NOTE:
BB
SECTION B-B
bearing on frame around for true
Machine finish all
STANDARD MANHOLE GRATE
"4
17"
"4
"4
ADJUSTMENT RING
MANHOLE
For use with Standard Manhole Frame
SECTION C-C
PLAN
C C bearing all around
Machine to true mastic sealant
" preformed8 non-machined surfaces to be ±0.06". See general note 6 grey cast iron ASTM A48, Class 35B. Tolerance on
" and 3". Material to be2
", 2", 22
* Standard depths 1 designation heat number initials and
Manufacturer's
1" 1"
27"
23"
"4
7 "
25"
E
E
D D
Storm
PLAN
p ic k h o le
SECTION D-D
MANHOLE COVER AND FRAME
CAST IRON SUBURBAN
PLAN
SECTION E-E
AND WATERTIGHT COVER
CAST IRON TAMPERPROOF
Watertight for sanitary covers
2 holes maximum
Tamperproof, Down Detail
See Bolt
"4 or suburban pattern
Frames available in standard
BOLT DOWN DETAIL
See general note 8 so that one bolt boss is located over the manhole steps.
hexagonal head, bronze or stainless steel. Install frame
" pentagonal or2
"x12
Three required, equally spaced, NOTE:
m in m a x
26" min.
25" for details
Section A-A
See Cover 23"
"2
"4
For use on local streets only, as specified
For tamperproof and watertight covers tamperproof cover gasket, omit for
" neoprene4 cover
Manhole three required per cover stainless steel washer, " thick8
" OD x4 cover three required per
Flat rubber washer, 1"
Manhole frame maximum
Sanitary, 2 holes
RD356
AND FRAMES
MANHOLE COVERS
R D
.d g n
REVISED DETAILS AND NOTES07-2022
15-JUL-2022N/A
J U
L the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
RD364
TYPE G-1, G-2, G-2M, & G-2MA
CONCRETE INLETS
R D
.d g n
21-JUL-2015N/A
J U
L
4" drain pipe
Base drain, m in
INLET TYPE W W
G-1
G-2, G-2M, G-2MA
"8 71'-8"8
72'-8
"8 33'-3 "8
32'-3
TYPE G-1, G-2, G-2M
TYPE G-2MA
WITHOUT SUMP
DETAIL A
TABLE A
SECTION A - A
SECTION B - B
SECTION C-C
C C
PLAN
PLAN
B
B
A A
(See general note 5)
Tracer wire when directed
Shape bottom m in (T y p
6" W
W
6" b r e a k
G r a d e
Finish grade
(See general note 9) when required
" preformed filler,4
Subgrade
(See general note 5)
Tracer wire
(See general note 11)
(Typ.)
Pipe connection varies
(See general note 3)
Sump
"2
(See general note 4)
Curb (Type var.)
Aggr. backfill n o r m a l
6"
V a r ie s
W6" 6"
W
Normal pavement slope
(See general note 2)
Frame & grate see inlet G-2
For details not shown, face of concrete unless shown or noted otherwise
All reinforcement to be placed 2" clear of nearest
NOTE:
#4 bars @ 6"
#4 bars "2
(See general note 2)
Frame & grate
6'-0"
"4
2'-46"
"4
3'-4
(See general note 10)
Pay limit for conc. inlet
6"
1'-6"
6"
V a r ie s m in
Top of curb
4" drain pipe (Typ.)
Base drain, (Typ.)
Aggr. backfill
Subgrade
(See general note 5)
Tracer wire (Typ.)
(See general note 11)
(Typ.)
Pipe connection varies
(See general note 3)
Sump normal
6"
(See general note 11)
(Typ.)
Pipe connection varies flow line
Depressed gutter flow line
Normal gutter
(Typ.)
Slope 1:12 nom.
(See general note 9) when required
" preformed filler,4
Top back of curb
Top face of curb
(Typ.)
Aggr. backfill
4" drain pipe (Typ.)
Base drain, (See general note 9) when required
" preformed filler,4
Concrete inlet
(See general note 2)
Frame & grate
(See general note 5)
Tracer wire (Typ.)
Normal gutter flow line
11. See Std. Dwg. RD339 for pipe to structure connections.
10. See Std. Dwg. RD363 for gutter transition section, when curb and gutter are required.
" preformed filler (in concrete pavement or gutter only) to extend through thickness of concrete.4
9.
8. All concrete shall be commercial grade concrete.
7. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.
6. Max. pipe diameter varies with pipe material.
5. See Std. Dwg. RD336 for tracer wire details, or approved alternate.
4. For curb details, see Std. Dwgs. RD700 & RD701.
3. Provide sump only where shown on plans, and allowed by jurisdiction. See Detail A for inlet without sump.
For frame and grate details, see Std. Dwg. RD365.
Type 1 grate allowed only in locations not subject to bicycle or pedestrian use.
2. Graphics show G-1 inlet with Type 2 grate. See Table A for inlet dimensions.
crushed aggregate shall be provided. All precast inlets shall conform to requirements of ASTM C913.
"-04
1. Where precast inlets are used as an alternate to cast-in-place inlets, a 4" compacted leveling bed of sand or
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2025 - May 31, 2026
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
File details come from the government source that posted it. Updated .