These bid documents are for the Orange County Corrections Department's Phoenix Building Replacement of the Smoke Control and Building Automation Systems project located at 2400 33rd Street, Orlando, Florida. The project involves comprehensive replacement and upgrades of existing smoke control systems, building automation systems, HVAC controls, fire/smoke dampers, and associated electrical and control infrastructure across multiple buildings (Buildings A, B, and C). The project is a 100% construction document set dated September 26, 2022, prepared by Atkins engineering firm, with an estimated project cost of $1,500,000.00 and a bid submission deadline of December 8, 2022.

The technical scope includes replacing pneumatic control systems with digital direct control (DDC) systems, upgrading fire alarm and smoke control panels, installing new motorized damper actuators, replacing electric duct heaters, integrating new building automation system controllers, and ensuring comprehensive smoke zone control and monitoring capabilities. The project requires coordination with existing systems, maintaining building safety protocols, and meeting UL 864, NFPA 72, and local code requirements. The work involves detailed modifications to HVAC equipment, control systems, electrical panels, and fire alarm infrastructure across multiple building levels, with careful attention to maintaining operational continuity and safety during the system replacement process.

View the file

Other files

File Type Posted
Y23-731.pdf PDF
OC_Phoenix_BAS_and_Smoke_Control_-_Bid_Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

100% CONSTRUCTION DOCUMENTS

SEPTEMBER 26, 2022

ORANGE COUNTY MAYOR

JERRY L. DEMINGS

DISTRICT 1 COMMISSIONER

NICOLE H. WILSON

DISTRICT 2 COMMISSIONER

CHRISTINE MOORE

DISTRICT 3 COMMISSIONER

MAYRA URIBE

DISTRICT 4 COMMISSIONER

MARIBEL GOMEZ CORDERO

DISTRICT 5 COMMISSIONER

EMILY BONILLA

DISTRICT 6 COMMISSIONER

VICTORIA P. SIPLIN

Sheet Number Sheet Name Scale

Sheet Issued

G-000 COVER SHEET AND SHEET INDEX Yes

M-101 BUILDINGS B AND C FIRST LEVEL HVAC PLAN 1/8"=1'-0" Yes

No Scale

M-401 HVAC SCHEDULES

No Scale Yes

M-001 HVAC SYMBOLS LEGEND AND GENERAL NOTES YesNo Scale

M-102 1/8"=1'-0" Yes

DRAWING INDEX

BOARD OF COUNTY COMMISSIONERS

BUILDINGS B AND C SECOND LEVEL HVAC PLAN

M-103 1/8"=1'-0" YesBUILDINGS B AND C ROOF LEVEL HVAC PLAN

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st em s

DAVID L. HEIDEMAN

FL PE NO. 76792

G-001

COVER SHEET AND

SHEET INDEX

DLH

DLH

TJF

M-301 PHOENIX CHILLER PLANT CONTROLS

No Scale YesM-302

No Scale YesM-303

PHOENIX C1 THRU C6 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-304

PHOENIX RTU-C7 AND C8 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-305

PHOENIX AHU-1 THRU 7 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-306

PHOENIX SF-1 THRU 8 SEQUENCE, OVERVIEW AND PARTS LIST

SMOKE CONTROL SYSTEM SEQUENCE, OVERVIEW AND PART LIST

No Scale Yes

Orange County Corrections Phoenix Building Replacement of the Smoke

Control and Building Automation Systems

E-001 ELECTRICAL LEGEND SYMBOL AND NOTES No Scale Yes

E-101 BUILDINGS B AND C FIRST LEVEL ELEC PLAN Yes

E-102 Yes

E-103 Yes

E-401 ENLARGED ELECTRICAL PLANS Yes

E-402 Yes

E-601 EXISTING ELECTRICAL ONE LINE DIAGRAM No Scale Yes

E-801 ELECTRICAL PANEL SCHEDULE No Scale Yes

E-701 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - DEMOLITION No Scale Yes

E-702 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - NEW No Scale Yes

E-711 ELECTRICAL SMOKE CONTROL DETAILS No Scale Yes

BUILDINGS B AND C SECOND LEVEL ELEC PLAN

BUILDINGS B AND C ROOF LEVEL ELEC PLAN

ENLARGED ELECTRICAL PLANS

1/8"=1'-0"

1/8"=1'-0"

1/8"=1'-0"

1/4"=1'-0"

1/4"=1'-0"

M-104 1/8"=1'-0" YesBUILDING A FIRST LEVEL HVAC PLAN

M-105 1/8"=1'-0" YesBUILDING A FIRST LEVEL PIPING PLAN

M-106 1/8"=1'-0" YesBUILDING A MECHANICAL MEZZANINE PLANS

E-104 YesBUILDING A FIRST LEVEL ELEC PLAN 1/8"=1'-0"

E-105 YesBUILDING A ELECTRICAL MEZZAININE PLANS 1/8"=1'-0"

M-501 SEQUENCE OF OPERATIONS No Scale Yes

MECHANICAL

ELECTRICAL

M-601 HVAC DETAILS No Scale Yes

M-502 DAMPER CONTROL SCHEMATIC DIAGRAMS No Scale Yes

No Scale YesM-307 FIREFIGHTER SMOKE CONTROL PANEL

No Scale YesM-308 MAINTENANCE SMOKE EXTRACT CONTROL PANEL

BID DOCUMENTS

NOT FOR

CONSTRUCTION

BID

GENERAL INSTALLATION NOTES

ALL COMMUNICATION CABLING SHALL BE RUN SEPARATE FROM ANY POWER WIRING.

REFER TO SPECIFICATION DIVISIONS 23 & 26 REGARDING WIRING AND CONDUIT REQUIREMENTS.

ALL CONDUIT MUST HAVE A PULL STRING INCLUDED.

LABELING, ETC... HAND WRITTEN LABELS ARE NOT ACCEPTABLE.

ALL WIRING MUST BE CLEARLY LABELED AT TERMINATION POINTS. ACCEPTABLE METHODS INCLUDE BRADY

ACTUAL CONFIGURATION OF DUCTING SYSTEMS IS TO BE DETERMINED BY OTHERS, AND CONFIGURATION

SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.

ACTUAL CONFIGURATION OF PIPING SYSTEMS IS TO BE DETERMINED BY OTHERS, ANY CONFIGURATION

SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.

ALL CONDUIT AND WIRING MUST BE INSTALLED PARALLEL TO THE BUILDING LINES.

ALL WORK SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER & MUST MEET THE APPROVAL OF

ALL WALL PENETRATIONS MUST BE SLEEVED AND SEALED PER THE SPECIFICATIONS. IF THE WALL IS A RATED WALL, F.B.O. IS AN ACRONYM FOR FURNISHED BY OTHERS.

MAXIMUM FLEXIBLE CONDUIT LENGTH NOT TO EXCEED 3 FEET.

LOCATE NEW PANELS AND ASSOCIATED COMMUNICATION CABLES 6' MIN. DISTANCE FROM ANY VFD PANEL OR HIGH POWER CONDUIT. INSTALLATION MUST CONFORM WITH ALL NATIONAL AND LOCAL CODES.

WIRING COLOR CODE:

BL = BLUE BK = BLACK BR = BROWN GR = GREEN GY = GRAY O = ORANGE

P = PURPLE R = RED Y = YELLOW WH = WHITE

OUTSIDE AIR

OUTSIDE AIR/HUMIDITY SENSOR

MAGNETIC STARTER

LOW LIMIT PRESSURE SWITCH

HIGH LIMIT PRESSURE SWITCH

MEDIA CONVERTER

LINE VOLT THERMOSTAT

PROGRAMMABLE CONTROLLER

I/O MODULE

SETPOINT CONTROLLER

HOT WATER VALVE

HUMIDIFIER

INLET GUIDE VANES

EXPANSION MODULE

OSA

0HS

MS

LLS

HLS

MC

LVT

MP581

MP503

MP501

HWV

HUM

IGV

ABB.

EX2

SYMBOLDESCRIPTION

DIFFERENTIAL PRESSURE TRANSMITTER

DIFFERENIIAL PRESSURE SWIICH

DUCT TEMPERATURE SENSOR

DOMESTIC WATER HEATER

FAN POWERED UNIT

FREEZE STAT

FLOAT SWITCH

FIRE STAT

FILTER

DAMPER END SWITCH

ELECTRIC DUCT HEATER

DUCT SMOKE DETECTOR

DPT

DPS

DTS

DWH

HE

HC

FPU

FZT

FS

FRT

FLT

ES

EDH

DSD

ABB.SYMBOLDESCRIPTION

BUILDING CONTROL UNIT

COOLING COIL

CHILLED WATER VALVE

MOTORIZED DAMPER

DUCT HUMIDITY SENSOR

DUCT CARBON DIOXIDE SENSOR

CURRENT TRANSMITTER

CURRENT SENSING SWITCH WITH RELAY

CURRENT SENSING SWITCH

CENTRAL CONTROL PANEL

AIR HANDLING UNIT

AIR FLOW RING

AIR FLOW MONITORING STATION

AVERAGING TEMPERATURE SENSOR

SYMBOL

BCU

CC

CHWV

DM

DHS

DCO

CT

CSSR

CSS

CCP

AHU

AFR

AFM

ATS

ABB.

BCU

C

C

VARI TRAC II

CCP

сss

CSSR

CT

Ü û

2-WAY

3-WAY

C H

W V

D M

-B

DH

S

AF

R

AF

M A

T S

D M

-A C

H W

V

RLY

RIB

SHS

RPS

PPU

SEQ

SA

RA

PWS

PCM

OTS

ZN517

SP

ZN511/521

UNITARY CONTROLLER

ZONE CONTROLLER

RELAY

RELAY IN A BOX

SPACE HUMIDITY SENSOR

ROOM PRESSURE SENSOR

PARALLEL FAN POWERED UNIT

SEQUENCER RELAY MODULE

SUPPLY AIR

RETURN AIR

DC POWER SUPPLY

PROGRAMMABLE CONTROL MODULE

OUTSIDE TEMPERATURE SENSOR

SURGE PROTECTION

TCI

UPCM

UCP

UCM

TUC

TCM

VAV

TDM

TR

TU

TKR

SPTS

TC

STS

TRANE CONTROL INTERFACE

UNIVERSAL PROGRAMMABLE CONTROL MODULE

UNIT CONTROL PANEL

UNIT CONTROL MODULE

TERMINAL UNIT CONTROL

THERMOSTAT CONTROL MODULE

VARIABLE AIR VOLUME BOX

TRAC MOTORIZED DAMPER

TRANSFORMER

TERMINAL UNIT

TRACKER 100 STAT

STRAP ON TEMPERATURE SENSOR

TIME CLOCK

SPACE TEMPERATURE SENSOR

VFD

ZDU

WTS

WFM

WFS

VARIABLE FREQUENCY DRIVE

ZONE DAMPER UNIT

WELL TEMPERATURE SENSOR

WATER FLOW METER

WATER FLOW SWITCH

DESCRIPTION SYMBOL ABB. DESCRIPTION ABB.SYMBOL DESCRIPTIONSYMBOL ABB.DESCRIPTION

HEAT EXCHANGER

HEATING COIL

ZDM

WTS

VFD

OR CARD NUMBER

TERMINAL BLOCK

DEVICE NUMBER

CONTROLLER

POINT NUMBER

POINT TYPE

MULTIPLE CONTROL DEVICE CALLOUT DESCRIPTON

TERMINAL BLOCK

OR CARD NUMBER

B0 1 1

POINT TYPE

POINT NUMBER

SINGLE CONTROL DEVICE CALLOUT DESCRIPTON

HE

RE

SE

T

FZ

T

FR

T

W

FM

RE

SE

T

ABBREVIATIONS AND SYMBOL LEGEND

ZN

ZN

ZN

PCM

PWS

RA

RIB

RLY

RPS

SA

SEQ

VAV

UPCM

UCP

TUC

TU

TRACKER

STAT X

TCM

TCI

1:00

TC

STS

SPTS

PPU

SP

SHS

TDM-X

OPS

DPT

DWH

FS

FPU

C

H

DT

S

ED

H

H W

V

M

HU

M

M оso

OSA

MS

5O3

MP

MP

MC

L HLLS

IGV

HL HLS

EX2

OHS

MP.581

H W

V

M 3-WAY

2-WAY

UCM

THE ENGINEER, ORANGE COUNTY CAPITAL FACILITIES AND ORANGE COUNTY CORRECTION FACILITIES.

THE PENETRATION SHALL BE SEALED WITH PREVIOUSLY SUBMITTED AND ACCEPTED FIRE PROOFING MATERIAL INSTALLED AS RECOMMENDED BY THE MATERIAL MANUfFACTURER.

CONTRACTOR TO PROVIDE TEMPORARY ROOFTOP AIR HANDLERS AND TEMPORARY SMOKE EXHAUST FANS FOR SMOKE ZONES UNDER CONSTRUCTION IF THOSE ZONES ARE TO REMAIN CONTINUALLY OCCUPIED. EACH TEMPORARY UNIT TO BE TIED INTO FIRE ALARM OR PROVIDE FIRE WATCH. ALL LIFE SAFETY REQUIREMENTS SHALL BE PROVIDED AS REQUIRED BY THE AHJ.

EXISTING CONTROLLERS, SENSORS, T-STATS AND WIRING TO BE REPLACED WITH NEW UL 864 CONTROLLERS, NEW SENSORS, NEW T-STATS AND NEW WIRING. SEE SPECIFICATIONS FOR REPLACEMENT OF CONTROL SYSTEMS.

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-001

HVAC SYMBOLS LEGEND

AND GENERAL NOTES

DLH

DLH

TJF

BID

NOT FOR

20x10 RETURN AIR UP 14x14 SUPPLY DUCT UP TO 2ND FLOOR

20x10 EXHAUST DUCT UP TO 2ND FLOOR SUPPLY DUCT UP TO 2ND FLOOR

14x14 SUPPLY DUCT UP TO 2ND FLOOR

EXHAUST DUCT UP TO 2ND FLOOR

20x10 EXHAUST DUCT UP TO 2ND FLOOR14x14 SUPPLY DUCT UP TO 2ND FLOOR

SUPPLY DUCT UP TO 2ND FLOOR

SUPPLY DUCT UP TO 2ND FLOOR

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.) FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 1 ON SHEET M-601

14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 SUPPLY AIR DUCT UP14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 PURGE AIR UP

UP TO EF-9

DS/CU-1

S/A FROM

SECOND

FLOOR AND

RTU-8

R/A FROM

SECOND

FLOOR AND

RTU-8

x8 8x6

8x4

10x8

24x8 x8 x1

10x8

10x8

10x8

10x8

10x8

10x8 x1 x1

28x8

10x8

10x8 x1

10x8

8x6

8x6

10x612x8

14x12 x8

10x6

10x6

10x

10x4

10x

14x10 x1

14x12

14x8 8x6

10x6 x6 x8 x6

14x

8x x6

8x6

10x6

10x6

12x6

10x6 12x8 x6

14x x88x

10x

10x

14x12

10x

10x 4 10x

8x4

10x

10x

10x

8x4

8x4

14x8

8x

10x6

10x6

10x6 x8 x1

12x88x4

8x

8x4

14x10

12x6 x8

8x x1

12x6

14x10

10x6

10x6 x8 x1

10x6

10x6

10x6

14x8 x6 x1

10x10 10x4

14x

10x

10x

10x6

14x

10x6

10x6

10x4 x6 x610 x6

14x1212x8 10x6

12x6 x8

8x x1 x1

14x10

8x4

12x8 10x6

14x12

12x6 x6 x6

10x 6 10x x8

14x12

10x10

10x6 x8

10x

8x4

10x 4 10x

10x

14x x6

10x6

8x6 10x6

14x8

8x4

14x14 PURGE AIR UP

FIRE DAMPERS (TYP.)

EXISTING FIRE ALARM CONTROL PANEL

FD

FD

FD

FD

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-101

BUILDINGS B AND C

FIRST LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C FIRST LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"1

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND

INSTALL NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE

DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED

WITHIN 5'-0" OF THE DAMPER. CONNECT NEW WIRING FROM

NEW DUCT SMOKE DETECTOR BACK TO FIRE ALARM SYSTEM.

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH

ASSOCIATED EXISTING WIRING AND REPLACE WITH NEW DDC

THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).

INSTALL NEW DDC CONTROLLER AND WIRING FOR EXISTING

AC-1/CU-1 UNIT AT BUILDING B.

ALL EXISTING DUCTWORK SHALL BE CLEANED PER

SPECIFICATION SECTION 230130.52.

INSTALL NEW 24x24 LOCKABLE ACCESS PANEL TO ACCESS

F/SD. TWO NEW CEILING ACCESS PANELS TO BE INSTALLED

ACROSS EACH WALL-MOUNTED F/SD. ONE NEW WALL

ACCESS PANEL TO BE INSTALLED AT FLOOR-MOUNTED F/SD.

REPLACE EXISTING PRIMARY FIREFIGHTER'S

SMOKE CONTROL PANEL WITH NEW UL 864

PRIMARY FIREFIGHTER'S SMOKE CONTROL

PANEL.

REPLACE EXISTING BUILDING AUTOMATION

SYSTEM PANEL WITH NEW UL 864 BAS

CONTROL PANEL.

REPLACE EXISTING SECONDARY

FIREFIGHTER'S SMOKE CONTROL PANEL

WITH NEW UL 864 SECONDARY

FIREFIGHTER'S SMOKE CONTROL PANEL.

DEMO EXISTING PNEUMATIC AIR COMPRESSOR AND ALL

EXISTING PNEUMATIC TUBING AND WIRING. TURN OVER TO

OWNER.

REMOVE HARD CEILING BELOW EXISTING DUCTWORK IN

STAIR ROOM. PROVIDE NEW 2-HOUR RATED HORIZONTAL

ENCLOSURE AROUND EXISTING SUPPLY DUCT IN STAIR

ROOM. INSTALL NEW DRYWALL CEILING AND PAINT TO MATCH

EXISTING.

KEYED NOTES

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

BID

20x10 EXHAUST DUCT DN TO 1ST FLOOR

14x14 SUPPLY DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR 14x14 SUPPLY DUCT DN TO 1ST FLOOR

14x14 SUPPLY DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR14x14 SUPPLY DUCT DN TO 1ST FLOOR

SUPPLY DUCT DN TO 1ST FLOOR

SUPPLY DUCT DN

TO 1ST FLOOR

3 3

46x14 S/A FROM RTU-8

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

R/A FROM

RTU-8

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

3 3

38x x8

14x14

12x8

12x6

8x4

8x

8x x8 x1

08x4 x8 x1 x1 x8 x1 x1 x1

10x6 6x4

24x6

10x8

24x6

24x6

24x6

24x6

24x14

30x14

10x8

10x8

10x6

10x6

10x6

10x10

18Ø

38x

14x14

14x10

10x8

10x

8x6

14x14

14x14

14x10

10x8

10x

8x6

8x6

8x6 x1

8x

8x 6 8x

8x610x8

38x14

14x

38x14

14x

14x

10x

10x8

8x6

14x

14x

14x

10x

10x8

8x6

8x6

8x6 x1

8x

8x

8x

8x610x8 38x

14x14 38x

14x14

14x10

10x8

10x

8x6

14x14

14x14

14x10

10x8

10x

8x6

8x6

8x6 x1

8x

8x

8x

8x6 10x8

RTU ABOVE

38x14

14x

38x14

14x

14x

10x

10x8

8x6

14x

14x

14x

10x

10x8

8x6

8x6

8x6 x1

8x

8x 68x

8x6 10x8

RTU ABOVE

RTU

C4 RTU

C3

RTU

C1

RTU

C2

RTU

C5

FD

FD

FD

FD

FD FD

FD

FD

FD

FD

FD

FD

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-102

BUILDINGS B AND C

SECOND LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C SECOND LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"1

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL

NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR.

THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE

DAMPER. CONNECT NEW WIRING FROM NEW DUCT SMOKE DETECTOR

BACK TO FIRE ALARM SYSTEM.

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED

EXISTING WIRING AND REPLACE WITH NEW DDC THERMOSTATS AND

HUMIDISTATS AND WIRING (TYPICAL).

KEYED NOTES

ALL EXISTING DUCTWORK SHALL BE CLEANED PER SPECIFICATION

SECTION 230130.52.

REMOVE EXISTING SUPPLY DUCT PENETRATING STAIR WALL AND

CAP DUCT AIRTIGHT OUTSIDE OF STAIRWELL. REMOVE F/S DAMPER

AND DUCT THROUGH WALL. PATCH WALL AS REQUIRED TO

MAINTAIN RATING.

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

BID

EXIST. SA - DN TO ZONE 4

SERVING

ZONE 4

EXIST. RA -

DN - ZONE 4

EXIST. SA -

DN - ZONE 3

EXIST. SEF-14

SERVES ZONE 4

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. SA -

DN - ZONE 5

EXIST. SEF-18

SERVES - ZONE 4

EXIST. RA -

DN - ZONE 5

EXIST. F/S DAMPER

SERVING

ZONE 3

EXIST. RA -

DN - ZONE 3

EXIST. F/S DAMPER

EXIST. SEF-15

SERVES ZONE 3

EXIST. F/S DAMPER

EXIST. RA -

DN - ZONE 5

EXIST. SA -

DN - ZONE 5

EXIST. F/S DAMPER

EXIST.SEF-19

SERVING

ZONE 4

SERVING

ZONE 2

EXIST. SA -

DN - ZONE 2

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. RA -

DN - ZONE 2 SERVING

ZONE 2

EXIST.SEF-16

SERVING

ZONE 1

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. SA -

DN - ZONE 1

EQUIPMENT NOT INCLUDED IN UL

864 SMOKE CONTROL SYSTEM

RTU

C7

SEF

C14

RTU

C4

EF

C10

EDH

C14 532

SERVING

ZONE 5

RTU

C6

SEF

C18

EDH

C13

EDH

C11

1 4

EF

C12

SEF

C17

2 RTU

C2

EDH

C8

3 2

SEF

C15

RTU

C3

EF

C11

EDH

C10

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING)

SERVING

ZONE 1

SERVING

ZONE 1

EF

C13

SEF

C16

2 3 5

RTU

C1

EDH

C8

(EXISTING)

1RTU

C8

2 3 5

EDH

C15

(EXISTING)

2 3 5

SEF

C19

4 2 3 5

6 EDH

C12

(EXISTING)

SERVING

ZONE 5

RTU

C5

30x20

20x20

30x20

20x20

30x20

20x20

30x20

20x20

26x14

26x14

46x14

28x16 x1 x1

9 8

26x14

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-103

BUILDINGS B AND C

ROOF LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C ROOF LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"1

KEYED NOTES

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL

NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR.

THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE

DAMPER. INSTALL DUCT ACCESS DOOR IF NONE EXISTS ON AT

LEAST ONE SIDE OF F/S DAMPER (SIDE OF ACTUATOR).

REMOVE ALL EXISTING VALVE ACTUATORS, TEMPERATURE

SENSORS, DIFFERENTIAL PRESSURE SENSORS, ELECTRIC DUCT

HEATERS. REPLACE ALL DEVICES WITH NEW DEVICES CONNECTED

TO NEW BMS SYSTEM. SEE SHEET M-303 FOR ADDITIONAL DETAILS.

REMOVE EXISTING AHU CONTROLLER AND REPLACE WITH NEW DDC

CONTROLLER AND WIRING FOR EXISTING ROOF TOP UNIT.

REPLACE CONTROL DEVICES FOR EXISTING EXHAUST FANS WITH

NEW DEVICES CONNECTED TO NEW BMS.

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR

HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT SHALL

BE CLEANED PER SPECIFICATION SECTION 230130.52.

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR

ELECTRIC DUCT HEATER OF SAME CAPACITY.

2. CONTRACTOR SHALL REFER TO THE CONTROL DRAWINGS TO

VERIFY THE SCOPE OF WORK AND THE THE EQUIPMENT SCHEDULES

FOR THE SIZES AND CAPACITIES OF EXISTING AND/OR NEW

EQUIPMENT.

REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.7

REMOVE EXISTING DUCT SMOKE DETECTOR AND EXISTING

WIRING. REPLACE WITH NEW DUCT SMOKE DETECTOR AND

WIRING. PROVIDE STAINLESS STEEL ENCLOSURE WITH CLEAR

VIEWING WINDOW TO SMOKE DETECTOR. PROVIDE NEW

DOUBLE-WALL INSULATED DUCT ACCESS DOOR FOR

MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.

PROVIDE NEW DUCT SMOKE DETECTOR WITH NEW STAINLESS

STEEL ENCLOSURE AND CLEAR VIEWING WINDOW TO SMOKE

DETECTOR. PROVIDE NEW DOUBLE-WALL INSULATED DUCT

ACCESS DOOR FOR MAINTENANCE FOR NEW DUCT SMOKE

DETECTOR.

PROVIDE NEW VFD FOR REPLACED SMOKE EXHAUST FAN

IN NEMA 4X STAINLESS STEEL ENCLOSURE. PROVIDE NEW

UNISTRUT MOUNTING ON BRACKETS AT RTU DUNNAGE,

NEXT TO EXISTING DISCONNECTS.

BID

400 400

400 400

400 400

300 100 300

3001500

335 335 375

395660

75 75

435 435 435

590 590

SF

A8

EDH

A238

SF

A7

EDH

A228

SF

A6

EDH

A21

SF

A5

EDH

A208

SF

A458

EDH

A198

SF

A358

EDH

A188

SF

A258

EDH

A178

SF

A1

EDH

A168

CU

A2

AC

A2

6EF

A1 8

AC

A1

CU

A1

UH

A1

EF

A20 6

2 8

EF

A2

EF

A3

AHU

A6

AHU

A7

AHU

A4

EF

A6

AHU

A3

AHU

A2

AHU

A1

6 8

6 8

EF

A56 8

8 9

AHU

A5

8 9

8 9

EF

A7

EF

A8 6 8

6 8

EF

A4 6 8

8 8

8 8

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x1430x1018x10

30x14 x1 x8 x1 x1 x1 x8 x1 x1 x1 x8 x1 x1 x1 x1 x1 x1 x1 x4 x1 x1 x1 x1 x1

6x x1 x1 x8 10 x8 x8

8x x1 x1 x8

8x

8x

24x6

12x10 12x10

12x10

12x10

12x10

18x10 12x8

20x14

12x6

10x8 12x8

12x10

12x8

24x8

12x10

24x14

14x10

24x8

24x12 16x12 12x10 x1 x8 x8

10x6

18x14 x8 x8 x1

10x8 6x4

12x8

12x8

12x8

12x8

10x6 10x6 x1 x8

6x4

8x6

24x424x2 x8

8x4 8x4

8x68x6 x1

0 12 x1

24x8

10 10

2 HR FIRE 1 H

R F/S

1 HR F/S2 H

R FIRE

1 H R F/S

1 HR F/S

1 1 Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-104

BUILDING A

FIRST LEVEL HVAC PLAN

DLH

DLH

TJFBUILDING A FIRST LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"1

REMOVE EXISTING PNEUMATIC FIRE/SMOKE DAMPER AND INSTALL NEW FIRE/SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE DAMPER. CONNECT NEW WIRING FROM NEW DUCT SMOKE DETECTOR BACK TO FIRE ALARM SYSTEM. INSTALL NEW 24x24 LOCKABLE ACCESS PANEL TO ACCESS F/SD. TWO NEW CEILING ACCESS PANELS TO BE INSTALLED ACROSS EACH WALL-MOUNTED F/SD. ONE NEW CEILING ACCESS PANEL TO BE INSTALLED FOR EACH DUCT RISER F/SD.

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED EXISTING WIRING AND REPLACE WITH

NEW DDC THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).

REPLACE EXISTING TRANE CONTROL PANEL WITH NEW JOHNSON CONTROLS BMS PANEL.

REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR ELECTRIC DUCT HEATER OF SAME CAPACITY.

REPLACE EXISTING SUPPLY FAN CONTROLLER WITH NEW DDC CONTROLLER.

REPLACE EXISTING EXHAUST FAN CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).

REPLACE EXISTING UNIT HEATER CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).

KEYED NOTES

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR HANDLING UNITS, EXHAUST FANS AND

OTHER EQUIPMENT SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.

REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH NEW AIR HANDLING UNIT CONTROLLER

CONNECTED TO THE NEW BAS SYSTEM.

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

REMOVE EXISTING PNEUMATIC DAMPER ACTUATORS AND PNEUMATIC TUBING. REPLACE WITH NEW ELECTRONIC DAMPER ACTUATORS, PROVIDE NEW DDC CONTROLLERS AND CONNECT TO BAS SYSTEM.

PROVIDE NEW DUCT SMOKE DETECTOR. PROVIDE NEW DOUBLE-WALL DUCT ACCESS DOOR FOR

MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.

BID

3" CHWS&R

1 1/2" CHWS&R

2 1/2" CHWS&R

1 1/2" CHWS&R

1" CHWS&R

2" CHWS&R

2 1/2" CHWS&R

1 1/2" CHWS&R1" CHWS&R

1" CHWS&R

AHU

A5

AHU

A7

AHU

A4

AHU

A6

AHU

A3

AHU

A2

AHU

A1

3" CHWS&R TO &

FROM BUILDING

3/4" HWR

2" HW

3" CW

1 1/2" HWR

2" HWS

12" FLUE UP

TO ROOF

4" FLUE

UH-1

GWH-1

CHEMICAL

SHOT FEEDER

6" CHR

6" CHWR

3" CHWS

6" CHR

CHILLED WATER

MAKE-UP[

3/4"

BACKFLOW/PRV ASSEMBLY

ASC PANEL

FOR CHILLERS

6" CHWS 6" CHWS

6" CHWS

3" CHWS

6" CHWR 2 1/2" HWS

1 1/2" HWR

X

X

X

X

X

X X X X X

X

X

X

X

X

CHILLER YARD

CH-1 CH-2

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-105

BUILDING A

FIRST LEVEL PIPING PLAN

DLH

DLH

TJFBUILDING A FIRST LEVEL PIPING PLAN

SCALE: 1/8" = 1'-0"1

ENLARGED MECH ROOM 110

SCALE: 1/4" = 1'-0"2

CHILLER YARD

SCALE: 1/8" = 1'-0"3

EXISTING CHILLERS BEING REPLACED UNDER SEPARATE CONTRACT.

KEYED NOTES

1 1

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

BID

MECHANICAL MEZZANINE

A-200

1 1/2"

26x1426x14

14x12

M

M

M

M x1 x1 x1 x1

14x12 x1

14x12

28x14

20x14

1 1/2" 1 1/2" 1 1/2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

2 1/2"

2 1/2"

2 1 /2"

2 1 /2"

AHU-5

EXISTING CONTROL

PANEL (TYPICAL)

2" 2"

AHU

A5 2 3

AHU

A7 2 3

AHU

A6 2 3

AHU

A423

2 2

AHU-7

DDC PANEL

26x16 x1 x1 x1

24x12

14x26 26x14

M

M

M

16x12 18x16 x1

2"

1 1/2"

1 1/2"

1 1/2" 1 1/2"

1 1/2"

1 1/2"

EXISTING CONTROL

PANEL (TYPICAL)

2"

MECHANICAL MEZZANINE

A-201

AHU-2

AHU

A223

AHU

A1 2 3

AHU

A3 2 3

DDC PANEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-106

BUILDING A MECHANICAL

MEZZANINE PLANS

DLH

DLH

TJF

BUILDING A MECHANICAL MEZZANINE 200 PLAN

SCALE: 1/4" = 1'-0"1 BUILDING A MECHANICAL MEZZANINE 201 PLAN

SCALE: 1/4" = 1'-0"2

NOT USED.

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR

HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT

SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.

REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH

NEW AIR HANDLING UNIT CONTROLLER CONNECTED TO THE

NEW BAS SYSTEM.

REPLACE EXISTING MOTORIZED DAMPER CONTROLLER AND

DAMPER ACTUATOR WITH NEW MODULATING ACTUATOR WITH

POSITION INDICATOR.

KEYED NOTES

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

NOT USED.5

BID

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

FLOW

SWITCH

FLOW

SWITCH

OTS-1

AI

5 3

4 6

BI

DPS-2

CHWP-2

1 4

BO

4 1

BI

4 2

BI

ALARM

STATUS

ALARM

4 3

BI

4 4

BI

STATUS

CH-2

COMPRESSOR

EVAPORATOR

WTS-1

AI

5 1

WTS-2

AI

5 2

COMPRESSOR

EVAPORATOR

CH-1

C O

N

TR

O L

PA

N

EL

C

O N

TR

O

L

PA

N

EL

B0 1 3

CHWP-1

HL DPS-1

4 5

BI

MS

S/S RIB-2

MS

S/S RIB-1

HL

UPCM

EXISTING

ENC-1

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-301

PHOENIX CHILLER

PLANT CONTROLS

DLH

DLH

TJF

THE BAS WORK INDICATED ON THIS DRAWING IS NOT

INCLUDED IN THIS PROJECT. THIS WORK IS BEING

PERFORMED AS PART OF ANOTHER PROJECT. THIS

CONTRACTOR SHALL INTERFACE WITH THE BUILDING

AUTOMATION SYSTEM FULLY INCORPORATING THE

CONTROLS INDICATED AS WELL AS VERIFYING THAT THE

CONTROLS PORTION OF TESTING AND BALANCING AND

COMMISSIONING OF THE NEW CHILLER INSTALLATION

INDICATED IS INCLUDED EITHER IN THE ORIGINAL CHILLER

CONSTRUCTION BID PACKAGE OR THIS BID PACKAGE.

NOTE:

FOR INFORMATION ONLY

BID

KEYED NOTES

REMOVE AND REPLACE EXISTING SENSOR CONNECT TO NEW BAS SYSTEM.

REMOVE AND REPLACE EXISTING DAMPER CONTROLLER CONNECT TO NEW BAS SYSTEM.

REMOVE EXISTING DAMPER ACTUATOR AND REPLACE WITH NEW 24v ACTUATOR WITH POSITION SENSOR.

REMOVE AND REPLACE EXISTING DAMPER WITH NEW LOW LEAKAGE F/S DAMPER. CONTRACTOR SHALL

VERIFY SIZE OF DAMPER.

REMOVE AND REPLACE EXISTING CHILLED WATER CONTROL VALVE. CONNECT TO NEW BAS SYSTEM.

REMOVE EXISTING DAMPER AND ACTUATOR. SEAL SUPPLY AIR DUCT OPENING AS SHOWN.

REMOVE AND REPLACE EXISTING EDH. CONNECT CONTROLS TO NEW BAS.

EA

NO

3 3

AO

1 5 B0

M EP-2

HL DPS-2

5 3

BI

EA/RA

5 2

AI

5 1

AI

1 6 B0

M

1 4 B0

EP-1

SD-1EDH-1

3 1

AO

4 4

BI

L HDPS-1

4 1

AI

ATS-1

C

C

LH DPT-1

4 5

AI

ATS-2

4 2

AI

ATS-3

4 3

AI

4 6

AI

LH DPT-2DM-1

1 3 B0

TYPICAL FOR 12

1EA/RTU-C1 THRU RTU-C4

4EA/RTU-C5 & RTU-C6

S/S 1 1 B0

RIB-1

MS

EA NC EA

S/S

MS

TYPICAL FOR 4

MS

S/S RIB-2

RIB-X

2 1

BO

TYPICAL FOR 4

2EA/RTU-C5&C6

TO SPACENCOA

EF#

SMOKE EF#

RTU#

C12 C11C13 C12 C11 C10

C16 C17 C15 C14 C19 C18

EXHAUST FAN INTERLOCK SCHEDULE

C1 C2 C3 C4 C5 C6

NO SA

NO NC

NOOA

CO

O

LI

NG

C O

IL

CH

W

V-

FIL

TE

R

C

C

CO

O

LI

NG

C O

IL

FIL

TE

R

NO

AO

3 2

C H

W S

C H

W R

C H

W S

C H

W R

C H

W V-

M

C M

B-

2 3 1 1 1 1

1 1 2 3

2 3

2 3

2 3

2 3

M

M

M

M

M

SUPPLY AIR FAN

SMOKE EXHAUST FAN

PS

-1A1

EA/RA GRILLE

1 EA/RTU-C1, C2, C3, C4.

RTU-C1 - EF-13

RTU-C2 - EF-12

RTU-C3 - EF-11

RTU-C4 - EF-10

REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.

INSTALL NEW STATIC PRESSURE SENSOR. EXTEND PRESSURE SENSOR BELOW

EXHAUST/RETURN AIR GRILLE IN ORDER TO SENSE THE SPACE PRESSURE.

RTU-C1 THRU RTU-C6 CONTROL DIAGRAM

SEF-C14 THRU SEF -C19 CONTROL DIAGRAM SMOKE EXHAUST MAKE-UP AIR CONTROL DIAGRAM

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-302

PHOENIX C1 THRU C6

SEQUENCE, OVERVIEW

DLH

DLH

TJF

AND PARTS LIST

BID

REPLACE EXISTING DAMPER ACTUATOR WITH NEW 120V MOTORIZED DDC ACTUATOR.

REPLACE EXISTING DEVICE WITH NEW DEVICE CONNECTED TO BMS.

REPLACE EXISTING VALVE ACTUATOR WITN NEW 24V MOTORZIED DDC ACTUATOR.

REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REUSE AVAILABLE WIRING.

REMOVE EXISTING DEVICE. REPLACE WITH 24V TRANSFORMER.

REPLACE EXISTING DEVICE WITH NEW DIGITAL FREEZESTAT, CONNECTED TO BMS.

KEYED NOTES

MM

M 2 6

M

EP-2

3 2 B0

C

C

H LDPS-1 FZT-1

R-12 3

BI 2 1

BI

SD-1HL DPS-2

2 4

BI

1DTS-2

5 AI2

AI

RIB-1

MS

3 1 B0

CP-1

M3 4 B0

3 5 B0

DTS-1

5 ZN

AI1

M

EP-1

1 24 B0

SARA

OA

FIL

TE

R

C O

O

LI

N G

C O

IL

C V-

C H

W S

C H

W R

NONO

NC

RTU-C7 AND RTU-C8 CONTROL DIAGRAM

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-303

PHOENIX RTU-C7 AND C8

SEQUENCE, OVERVIEW

DLH

DLH

TJF

AND PARTS LIST

BID

EXISTING DAMPER ACTUATOR TO REMAIN.

EXISTING DEVICE TO REMAIN.

EXISTING VALVE ACTUATOR TO REMAIN.

REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REPLACE CONTROL WIRING.

NOT USED.

EXISTING HEATER TO REMAIN.

KEYED NOTES

MM

M

2 2

M

EP-2

3 2 B0

C

C

H LDPS-1 FZT-1

R-12 3

BI 2 1

BI STAGE-2

RIBRIB

STAGE-1

RIB

STAGE-3

SD-1 EDH-1HL DPS-2

2 4

BI

3 10 B0

3 7 B0

3 8 B0

1DTS-2

5 AI2

AI

RIB-1

MS

3 1 B0

CP-1

M3 4 B0

3 5 B0

DTS-1

5 ZN

AI1

M

EP-1

1 24 B0

SARA

OA

FIL

TE

R

C O

O

LI

N G

C O

IL

C V-

NONO

NC

AHU-1 THRU AHU-7 CONTROL DIAGRAM

AHU DDC

CONTROLLER

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-304

PHOENIX AHU-1 THRU 7

SEQUENCE, OVERVIEW

DLH

DLH

TJF

AND PARTS LIST

BID

SA

DTS-2

5 AI2

AI

MS

RIB-1

5 J11 B0

EDH-1

STAGE-1

RIB

5 J9 B0

L HDPS-2

4 1

BI

DTS-1

3 ZN

AI

RA

OA

M

CP-1J1 1

AO

M

M

NO

NC

REMOVE EXISTING PNEUMATIC

ACTUATORS AND REPLACE WITH

NEW ELECTRONIC ACTUATORS,

CONNECT TO BMS

SF-1 THRU SF-8 CONTROL DIAGRAM

SD-1

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-305

PHOENIX SF-1 THRU 8

SEQUENCE, OVERVIEW

DLH

DLH

TJF

AND PARTS LIST

BID

PL-1 GPL-3 G PL-5 G PL-6 GPL-4 G PL-2 G

EF-17 ON EF-14 ONEF-16 ON EF-18 ON EF-19 ONEF-15 ON

ON

OFF

AUTO AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

(RTU-2)

S-2

(RTU-1)

S-1

(RTU-3)

S-3

ZONE 2

PRIMARY SMOKE PURGE PANEL

ZONE 4ZONE 1 ZONE 5ZONE 3

LOCATED IN CONTROL. ROOM B-105LOCATED IN COMM. ROOM C-110

EXISTING POWER 120VAC

EXISTING

FACP

FSCS

UPCM-1

120VAC

POWER

TRACER SUMMIT

BUILDING CONTROL UNIT

PHOENIX

BCU

DETAIL

COMM RISER

SEE PAGE 2 FOR

120VAC

POWER

PL-9 G PL-10 G PL-8 G PL-7 G PL-11 G PL-12 G

EF-16 ON EF-15 ONEF-17 ON EF-14 ON EF-18 ON EF-19 ON

MANS-7

(RTU-1)

S-8

(RTU-2)

S-9

(RTU-3)

S-10

(RTU-4)

MAN MAN MAN

AUTO AUTO AUTO AUTO AUTO

ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5

EXISTING POWER 120VAC

SECONDARY SMOKE PURGE PANEL

POWER

120VAC

FSCS

UPCM-8

UNIVERSAL

PROGRAMMABLE CONTROL MODULE

UNIVERSAL

PROGRAMMABLE CONTROL MODULE

REMOVE PRIMARY SMOKE PURGE

PANEL IN ITS ENTIRETY.

REMOVE SECONDARY SMOKE PURGE

PANEL IN ITS ENTIRETY.

SEQUENCE OF OPERATION - SF A1 - A8

NORMAL

OPERATION

OCCUPIED MODE

HEATING MODE

UNOCCUPIED

MODE

EMERGENCY

DURING NORMAL OPERATION EACH SUPPLY FAN SHALL BE AUTOMATICALLY CONTROLLED BY EACH INDIVIDUAL DDC SF EQUIPMENT CONTROLLER. THE INDIVIDUAL CONTROLLER AND THE DDC SYSTEM SHALL BE PROGRAMMED TO ALLOW EACH SF TO FUNCTION ACCORDING TO THE FOLLOWING SEQUENCE. EACH SF

SHALL BE PROVIDED WITH A CONTROL PANEL THAT WILL INCLUDE AT A MINIMUM:

1. H-O-A SWITCH

2. LED LIGHTS TO INDICATE THE POSITION OF THE H-O-A SWITCH

DURING OCCUPIED MODE OPERATION, THE SF SHALL RECEIVE A SIGNAL TO START FROM THE CONTROLLER OR THE BAS SYSTEM. THE NORMALLY CLOSED OA DAMPER SHALL BE OPENED AND THE RA DAMPER SHALL BE CLOSED. VERIFY THE RETURN AIR DAMPER IS CLOSED AND THE SUPPLY AIR DAMPER ARE OPEN THEN ENERGIZE THE SUPPLY AIR FAN. THE STATUS OF THE SF SUPPLY AIR FAN SHALL BE MONITORED BY A DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN. IF A FAN IS COMMANDED TO BE ENERGIZED BUT CAN NOT BE VERIFIED BY THE DIFFERENTIAL PRESSURE SWITCH, AN ALARM SHALL BE SENT TO THE BAS SYSTEM INDICATING THE FAN IS ABNORMALLY OFF. THE UNIT CONTROLS SHALL MODULATE THE OA DAMPER AND THE

RA DAMPER TO CONTROL THE RETURN AIR TEMPERATURE TO 80 DEG. F.

IF THE RETURN AIR TEMPERATURE FALLS BELOW 70 DEG. F. THE ELECTRIC HEAT SHALL BE ENGAGED TO

MAINTAIN THE RETURN AIR TEMPERATURE AT 70 DEG. F.

THE SF SUPPLY AIR FAN SHALL BE DE-ENERGIZED DURING UNOCCUPIED MODE. THE OA DAMPER SHALL BE CLOSED AND THE ELECTRIC HEAT SHALL BE DE-ENERGIZED. THE RA DAMPER SHALL BE OPENED.

UPON RECEIVING A FIRE ALARM SIGNAL FOR BUILDING A, THE UNIT SUPPLY AIR FAN SHALL BE DE-ENERGIZED, THE OA DAMPER SHALL BE CLOSED AND THE RA DAMPER CLOSED.

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-306

SMOKE CONTROL SYSTEM

SEQUENCE, OVERVIEW

DLH

DLH

TJF

AND PART LIST

BID

SMOKE ZONE 1

2. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.

3. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.

4. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE FOR FIRE DEPARTMENT OVERRIDE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.

5. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR FIRE DEPARTMENT OVERRIDE, OR FOR SYSTEM TESTING.

NOTES:

FIRE FIGHTERS SMOKE CONTROL PANEL

NOT TO SCALE

FIRE FIGHTERS SMOKE CONTROL PANEL

FOR FIRE DEPARTMENT MANUAL OVERRIDE CONTROL, AND TESTING

CONTROLS FLOW DIAGRAM

NOT TO SCALE

I/O PANEL 1

UL864

FIRE FIGHTERS

SMOKE CONTROL

PANEL

FIRE ALARM

PANEL

(BY DIV. 16)

DUCT DETECTOR

FLOW SWITCH

PULL STATION

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

BMS

FA

UL 864 FIELD

EQUIPMENT

CONTROLLER

UL 864

NETWORK

ENGINE

UL 864 FIELD

EQUIPMENT

CONTROLLER

METASYS

USER

INTERFACE

METASYS

ADS SERVER

MAINTENANCE

SMOKE CONTROL

OVERRIDE PANEL

NOTES:

1. FIRE FIGHTERS SMOKE CONTROL PANEL SHALL HAVE HIGHEST LEVEL AUTHORITY TO OVERRIDE ALL SMOKE CONTROL FUNCTIONS.

2. PROGRAMMED FIRE EVENT AND SMOKE CONTROL ACTIONS SHALL HAVE SECONDARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS.

3. MAINTENANCE SMOKE EXTRACT CONTROL PANEL SHALL HAVE TERTIARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS, WHICH SHALL

BE USED FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING DUTIES.

1. PROVIDE A UL 864 LISTED PANEL ASSEMBLY THAT PROVIDE THE FOLLOWING FUNCTIONS AND CONTROLABILITY. THIS PANEL SHALL PROVIDE OVERRIDE AUTHORITY OF ALL AUTOMATIC FIRE ALARM SMOKE CONTROL OPERATIONS FOR MANUAL USE BY THE FIRE DEPARTMENT.

PROVIDE SIGNAGE AND LOCKING KEY PER FIRE DEPARTMENT.

6. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:

H-O-A POSITION: HAND - WHITE

OFF - RED

AUTO - GREEN

ZONE STATUS: OFF - RED

ON - GREEN

FAULT - AMBER

7. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT

NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.

RTU-C1

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 2

RTU-C2

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 4

RTU-C4

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 3

RTU-C3

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 5

RTU-C5 & RTU-C6

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

PILOT LIGHT WITH LABEL, TYPICAL

MANUAL ROTARY HOA SWITCH WITH LABEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-307

FIREFIGHTER SMOKE

CONTROL PANEL

DLH

DLH

TJF

BID

1. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.

2. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.

3. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.

4. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR SMOKE PURGE, OR FOR SYSTEM TESTING.

NOTES:

MAINTENANCE SMOKE EXTRACT CONTROL PANEL

NOT TO SCALE

MAINTENANCE SMOKE EXTRACT CONTROL PANEL

FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING

5. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:

H-O-A POSITION: HAND - WHITE

OFF - RED

AUTO - GREEN

ZONE STATUS: OFF - RED

ON - GREEN

FAULT - AMBER

6. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT

NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.

SMOKE ZONE 1

RTU-C1

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 2

RTU-C2

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 4

RTU-C4

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 3

RTU-C3

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 5

RTU-C5 & RTU-C6

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

PILOT LIGHT WITH LABEL, TYPICAL

MANUAL ROTARY HOA SWITCH WITH LABEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:SEPTEMBER 26, 2022

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-308

MAINTENANCE SMOKE

EXTRACT CONTROL PANEL

DLH

DLH

TJF

BID

ROOF TOP UNIT SCHEDULE - EXISTING UNITS

G

EN

ER

AL

IN

FO

R M

AT

IO

N

MARK RTU-C1 RTU-C2 RTU-C3 RTU-C4 RTU-C5 RTU-C6 RTU-C7 RTU-C8

MANUFACTURER TRANE TRANE TRANE TRANE TRANE TRANE TRANE TRANE

SA (CFM) 4650 5000 5000 5000 2370 2370 3300 4190

OA (CFM) 1880 1880 1880 1880 730 730 400 565

RA (CFM) 2770 3120 3120 3120 1640 1640 2900 3625

TOTAL AIR (CFM) 4650 5000 5000 5000 2370 2370 3300 4190

ESP (IN. WG) 1.6 1.7 1.7 1.7 1.5 1.5 1.5 1.8

TSP (IN. WG) 4.03 4.31 4.31 4.31 3.59 3.59 4.19 4.28

RPM 1487 1542 1542 1542 1876 1876 1738 1569

MOTOR HP 7.5 7.5 7.5 7.5 3 3 5 7.5

VOLTAGE 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

O A

C O

O

LI

N G

C O

IL

EAT (DB/WB DEG. F.) 88/79 88/79 88/79 88/79 88/79 88/79 88/79 88/79

LAT (DB/WB DEG. F.) 55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 53/52.9 55/54.9

SENS (MBH) 69.5 69.5 69.5 69.5 27.0 27.0 15.7 20.9

TOTAL (MBH) 163.6 163.6 163.6 163.6 63.5 63.5 37.0 49.2

GPM 32.7 32.7 32.7 32.7 12.7 12.7 7.4 9.8

WPD (FT H20 MAX) 2.21 2.21 2.21 2.21 2.52 2.52 1.08 1.3

EWT/LWT (F) 45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55

AIR PD (IN H20 0.16 0.16 0.16 0.16 0.18 0.18 0.18 0.34

TO

TA

L

AI

R C

O O

LI

N

G C

O IL EAT (DB/WB DEG. F.) 67.1/61.3 67.1/61.6 67.1/61.3 67.1/61.3 68.8/62.2 68.8/62.2 72.6/62.1 72.3/62.0

LAT (DB/WB DEG. F.) 54.7/54.1 54.8/54.3 54.7/54.1 54.7/54.1 54.2/53.8 54.2/53.8 53.6/53.1 51.6/51.4

SENS (MBH) 63.6 67.6 63.6 63.6 38.1 38.1 69.0 95.4

TOTAL (MBH) 96.9 106.5 96.9 96.9 58.1 58.1 85.7 126.1

GPM 19.4 0.3 19.4 19.4 11.6 11.6 17.1 25.2

WPD (FT H20 MAX) 4.0 4.7 4.0 4.0 1.7 1.7 1.6 6.2

EWT/LWT (F) 45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55

AIR PD (IN H20 0.55 0.64 0.55 0.55 0.44 0.44 0.62 0.58

O A

FI

LT

ER

TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.

THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"

EFFICIENCY% 30 30 30 30 30 30 30 30

FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE

TO

TA

L

AI

R

FI

LT

ER

TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.

THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"

EFFICIENCY% 30 30 30 30 30 30 30 30

FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE

H

EA

TI

N

G

EQ

U

IP

M

EN

T MARK EDH-C8 EDH-C9 EDH-C10 EDH-C11 EDH-C12 EDH-C13 EDH-C14 EDH-C15

MAX CFM 4650 5000 5000 5000 2370 2370 3300 4190

EAT/LAT (DEG. DB) 56.6/85.6 57.6/86.2 57.6/86.2 57.6/86.2 58.6/85.0 58.6/85.0 66.0/80.0 65.5/80.4

TOTAL KW 43 46 46 46 17 17 15 20

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

STAGES SCR SCR SCR SCR SCR SCR SCR SCR

NOTES 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3

NOTES

1 PROVIDE NEW JCI BAS CONTROLLER COMPATABLE WITH UL-864 SMOKE CONTROL SYSTEM FOR RTU 1, 2, 3, 4, 5, AND 6.

2 PROVIDE NEW JCI BAS CONTROLLER FOR RTU 7 AND 8

3 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

EXHAUST FAN SCHEDULE - EXISTING EQUIPMENT

MARK EF-A1 EF-A2 EF-A3 EF-A4 EF-A5 EF-A6 EF-A7 EF-A8 EF-B9 EF-C10 EF-C11 EF-C12 EF-C13 EF-A20 EF-A21

SERVICE CAR

EXST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

VO-TECH

EXHAUST

Y0-TECH

EXHAUST

BLDG.B

RESTRMS NW POD NE POD SE POD SW POD BLDG A

MECH RM

FIRE PMP

ROOM

MANUF. CAR-MON GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK COOK COOK COOK COOK GREEN

HECK

GREEN

HECK

MODEL 10F GB120-4 GB120-4 GB-90-4 GB120-3 GB-70-4 GB-90-4 GB-90-4 BCF-106 135

ACEB

ACEB

ACEB

ACEB GB-90-4 GB-140-3

TYPE CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM) 1200 1000 1000 750 1300 150 750 750 410 1550 1750 1650 1600 1000 2100

STATIC PRESS

(IN. W.C) 4.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.75 0.9 0.9 0.9 0.9 0.125 0.125

MAX FAN RPM 1725 1180 1410 1410 1550 1290 1410 1410 1811 1425 1237 1469 1446 1410 1170

H.P. 2 0.25 0.25 0.25 0.33 0.25 0.25 0.25 0.25 0.5 0.5 0.5 0.5 0.25 0.33

VOLTS 460 120 120 120 120 120 120 120 120 120 120 120 120 120 120

PHASE 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

NOTES 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5

NOTES

1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM

2 EXHAUST FANS EF-A1 THROUGH AND INCLUDING EF-A8 SHALL BE ENERGIZED BY EXISTING WALL SWITCH 3 EXHAUST FANS EF-A1 THROUGH EF-A8, EF-B9, EF-A20 AND EF-A21 SHALL BE MONITORED FOR STATUS AND

ABNORMAL OFF ONLY. ABNORMAL OFF SHALL GENERATE AN ALARM IN THE BAS SYSTEM.

4 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

5 PROVIDED FOR SIZING INFORMATION ONLY.

SUPPLY FAN SCHEDULE - EXISTING EQUIPMENT

G

EN

ER

AL

IN

FO

R M

AT

IO

N

MARK SF-A1 SF-A2 SF-A3 SF-A4 SF-A5 SF-A6 SF-A7 SF-A8

SERVICE CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

MANUF GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

MODEL GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3

TYPE CENT CENT CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM) 3300 3300 3300 3300 3300 3300 3300 3300

STATIC PRESS

(IN. W.C) 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

MAX FAN RPM 482 482 482 482 482 482 482 482

H.P. 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

MARK EDH-A16 EDH-A17 EDH-A18 EDH-A19 EDH-A20 EDH-A21 EDH-A22 EDH-A23

AIR FLOW

RATE (CFM) 3300 3300 3300 3300 3300 3300 3300 3300

EAT/LAT

(DEG. F.) 52/86 52/86 52/86 52/86 52/86 52/86 52/86 52/86

TOTAL KW 16 16 16 16 16 16 16 16

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

STAGES SCR SCR SCR SCR SCR SCR SCR SCR

NOTES 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3

NOTES

1 CONNECT ALL SUPPLY FANS TO NEW JCI BAS SYSTEM

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

SPLIT AC UNIT SCHEDULE - EXISTING EQUIPMENT

MARK MANUF

AIR

HANDLER

MODEL

COND.

MODEL

SUPPLY FAN COOLING AIR UNIT COND.

NOTESTOTAL

CFM

OA

CFM

COND.

EAT

(DEG. F)

EVAP EAT

DB/WB

(DEG. F)

EVAP LAT

DB/WB

(DEG. F)

TOT CAP

(MBH)

SENS CAP

(MBH) STAGES MIN EER VOLTS/PH/

HZ

VOLTS/PH/

HZ

AC-A1 CU-A1 MITSUBISHI PUYA-12 PLAA-12 320 0 95 75/65 52/52 12 10.32 1 13.8 208/1/60 208/1/60

AC-A2 CU-A2

NOTES

1 CONNECT ALL EQUIPMENT TO NEW JCI BAS SYSTEM

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

AHU SCHEDULE - EXISTING UNITS

GENERAL INFORMATION COOLING COIL HEATING EQUIPMENT

NOTESMARK MANUF.

FAN CFM ESP

(IN WG)

TSP

(IN WG)

MOTOR

HP

MOTOR

BHP

VOLTS/

PH/HZ

FAN

OUTLET

EAT

(DB/WB)

LAT

(DB/WB)

COOLING

CAPACITY

CHILLED

WATER

FLOW

RATE PRESSURE DROP CW

VALVE MARK CFM

EAT/LAT TOTAL

VOLTS PHASE STAGES

TOTAL SENS

(MBH)

TOT

(MBH)

EWT/LWT

(F.) (GPM) FLUID

(FT) AIR (IN) TYPE (DEG. F) KW

AHU-A1 TRANE 1550 750 1.5 1.84 1 0.77 460/3/60 14x14 85/71.8 56.6 98.8 45/55 19.7 3.9 0.3 2-WAY EDH-A1 1550 52/85.0 15 460 3 SCR 1,2,3 AHU-A2 TRANE 1500 750 1.5 1.82 1 0.74 460/3/60 14x14 86.1/72.3 52/51.84 56.7 98.6 45/55 19.7 3.9 0.3 2-WAY EDH-A2 1500 52/86.1 15 460 3 SCR 1,2,3 AHU-A3 TRANE 2330 1350 1.75 2.51 2 1.62 460/3/60 14x14 86.1/73.2 52/51.9 87.37 160.05 45/55 31.9 8.9 0.6 2-WAY EDH-A3 2330 52/86.1 26 460 3 SCR 1,2,3 AHU-A4 TRANE 2700 600 1.5 2.46 2.5 1.99 460/3/60 14x14 80.2/67 52/51.9 83.92 122.98 45/55 24.5 5.6 0.8 2-WAY EDH-A4 2700 52/80.2 17 460 3 SCR 1,2,3 AHU-A5 TRANE 1550 1000 2.1 2.5 1.5 0.96 460/3/60 14x14 86.9/72.8 52/51.9 60.7 103.4 45/55 24.1 2.6 0.4 2-WAY EDH-A5 1550 52/86.9 19 460 3 SCR 1,2,3 AHU-A6 TRANE 1720 800 1.5 1.82 1 0.74 460/3/60 14x14 86.3/73.2 52/51.9 57.1 104.1 45/55 20.7 4.3 0.3 2-WAY EDH-A6 1720 52/86.3 17 460 3 SCR 1,2,3 AHU-A7 TRANE 3700 1000 1.75 2.22 2 1.78 460/3/60 18x18 81.7/68.5 52/51.9 95.10 147.9 45/55 29.5 3.8 0.4 2-WAY EDH-A7 3700 52/81.7 26 460 3 SCR 1,2,3

NOTES

1 PROVIDE NEW JCI BAS CONTROLLER FOR FOR ALL AHU'S

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

EXHAUST FAN SCHEDULE - NEW EQUIPMENT

MARK SEF-C14 SEF-C15 SEF-C16 SEF-C17 SEF-C18 SEF-C19

SERVICE NW POD

SMOKE

NE POD

SMOKE

SE POD

SMOKE

SW POD

SMOKE CNE CSW

MANUF. COOK COOK COOK COOK COOK COOK

MODEL 300

ACRUB

ACRUB

ACRUB

ACRUB

ACRUB

ACRUB

TYPE CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM) 5800 5800 5800 5800 2000 2000

STATIC PRESS

(IN. W.C) 0.75 0.75 0.75 0.75 0.5 0.5

MAX FAN RPM 539 539 539 539 683 683

H.P. 1.5 1.5 1.5 1.5 0.33 0.33

VOLTS 460 460 460 460 460 460

PHASE 3 3 3 3 1 1

NOTES 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5

NOTES

1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM

2 INSTALL VFD FOR EACH EXHAUST FAN.

3 EACH FAN SHALL BE RATED FOR SMOKE CONTROL SERVICE.

4 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND

ADDITIONAL SCOPE OF WORK.

5 PROVIDED FOR SIZING INFORMATION ONLY.

CENTRAL COOLING PLANT SEQUENCE OF OPERATION

INPUTS

CHILLED WATER PLANT GENERAL

A. THE CHILLER PLANT SERVING THE PHOENIX BLDG CONSISTS OF TWO (2) AIR-COOLED SCROLL CHILLERS, CH-1 AND CH-2, PIPED IN PRIMARY-FLOW CONFIGURATION AND DESIGN TO PRODUCE CHILLED WATER AT 45°F (ADJ.). CHILLED WATER IS DISTRIBUTED TO THE BUILDING BY CONSTANT VOLUME PUMPS, CHP-1 & CHP-2, ONE PUMP PER

CHILLER. PUMPS OPERATE WITH ASSOCIATED CHILLER.

SEQUENCE OF OPERATION

A. THE CHILLERS UNIT CONTROLLER SHALL CONTROL THE OPERATION OF THE CHILLER PLANT BASED ON TIME OF DAY SCHEDULING, TIME CLOCK, OR FROM MANUAL

COMMAND FROM THE OPERATOR.

B. ON A START COMMAND FROM THE CONTROLLER, THE CHILLED WATER SYSTEM SHALL ENABLED THE LEAD CHILLER'S CHILLED WATER PUMP AND AFTER FLOW IS PROVEN AT THE CHILLED WATER BARRELS (VIA DIFFERENTIAL PRESSURE SWITCH) THE CHILLER SHALL BE ENABLED TO OPERATE.

C. THE CHILLER MICROPROCESSOR-BASED CONTROL PANEL SHALL THEN MODULATE THE COMPRESSORS TO MAINTAIN 45°F (ADJ) LEAVING CHILLED WATER SUPPLY TEMPERATURE.

D. CHILLERS, CH-1 AND CH-2, AND ASSOCIATED PUMPS, CHP-1 AND CHP-2, SHALL BE ROTATED FROM DUTY TO STAND-BY ON A WEEKLY BASIS. WHEN CHILLER OPERATION IS DISCONTINUED, THE CHILLER PUMP SHALL CONTINUE TO OPERATE FOR A PERIOD OF ONE MINUTE (ADJ.) TO REMOVE RESIDUAL REFRIGERANT CAPACITY.

E. IF THE OUTSIDE AIR TEMPERATURE DROPS BELOW 34°F (ADJ), THE CHILLED WATER PUMPS, CHP-1 AND CHP-2, SHALL ALTERNATE OPERATION FOR 30 MINUTES AT A TIME. THE PUMPS SHALL CONTINUE TO ALTERNATE OPERATION UNTIL THE OUTSIDE AIR TERMATURE REACHES 36°F (ADJ) AT WHICH TIME THE PUMPS SHALL SHUT OFF.

ALARMS

A) IF EITHER CHW PUMP FAILS TO START AFTER BEING CALLED TO OPERATE, THE CONTROLLER SHALL DISPLAY AN ALARM AND THE CONTROLLER SHALL ENABLE THE STAND-BY

CHILLER AND CHW PUMP.

B) IF CHWS TEMPERATURE RISES ABOVE PREDETERMINED SETPOINT, CONTROLLER SHALL DISPLAY AN ALARM.

C) THE CONTROLLER SHALL DISPLAY AN ALARM IF DIFFERENTIAL PRESSURE RISES ABOVE OR FALLS BELOW PREDETERMINED SETPOINTS (ADJ).

RETURNING CHILLED WATER TEMP.

LEAVING CHILLED WATER TEMP.

CHILLER (CH-1)

CHILLER (CH-2)

DIFFERENTIAL PRESSURE TRANSMITTER

CHP-1

CHP-2

OUTDOOR AIR TEMPERATURE

FLOW SWITCH (CH-1)

FLOW SWITCH (CH-2)

NOTES:

AT A MINIMUM, PROVIDE THE ABOVE POINTS OF CONTROL AND/OR MONITORING AT THE CHILLER UNIT CONTROLLER (SIMILAR TO CH530 CONTROL PANEL).1 PROVIDE ALL REQUIRED HARDWIRED INTERLOCKS BETWEEN CHILLER AND ASSOCIATED PUMPS, FLOW SWITCHES AND/OR DIFFERENTIAL PRESSURE SWITCHES TO MAINTAIN CHILLER WARRANTY. CONTRACTOR SHALL COORDINATE REQUIREMENTS WITH CHILLER MANUFACTURER .

ANALOG

SYSTEM,

DESCRIPTION

APPARATUS,

OR AREA

CHILLER PLANT POINT SCHEDULE

OUTPUTS

ALARMS

BINARY BINARY ANALOG

NOTES

AI

CH-2, EWT

T

H

DPS CH-2, LWT

AI T

CHP-2

CH-2

BO

BI START/STOP

STATUS

H

NO

AI

CH-1, EWT

T CHP-1

BO

BI START/STOP

STATUS

DPS CH-1, LWT

TAI

EXP-1

CH-1

BO

BI START/STOP

STATUS

CHWS&R

TO UNIT A

CHILLER YARD CHWS&R

TO UNIT C

MECHANICAL ROOM

CHWS

CHWR

AS-1

MAKE-UP

WATER

L

FLOW SWITCH (BY

CHILLER MFG.) NC BO

BI START/STOP

STATUS

L

PRIMARY FLOW CHILLED WATER PLANT DIAGRAM

NO SCALE M-401

H L

H L

RHTE

MP

ER

AT

UR

E

(°F

PR

ES

SU

RE

(P

SI

FL

OW

(G

PM

UN

IT

RU

N

LO

AD

A

MP

S

ST

AT

US

O N/

OF

F

FL

OW

S

TA

TU

S

(O

PE

N)

AI

R

FL

OW

ST

AT

US

O

PE

N

/ C

LO

SE

D

OP

EN

/ C

LO

SE

CH

W P

UM

P

RE

QU

ES

T

EN

AB

LE

/ D

IS

AB

LE

ST

AR

T /

S

TO

P

CH

W

P

UM

P

RE

QU

ES

T

VA

LV

E

PO

SI

TIO

N

SE

T P

OI

NT

A

DJ

US

TM

EN

T

MO

DU

LA

TIO

N

HI

A

NA

LO

G

BT

UH

LO

W

A

NA

LO

G

AL

AR

M

HI

B

IN

AR

Y

LO

W B

IN

AR

Y

SE

NS

OR

FA

IL

GENERAL NOTE:

CONTROL SCOPE FOR CHILLER PLANT INVOLVES CONNECTING

EXISTING CHILLERS AND CHILLED WATER PUMPS TO THE NEW

BAS SYSTEM AND PROGRAMMING THE SEQUENCE OF OPERATION.

ALL CONTROL DEVICES SHOWN ON THE CHILLED WATER PLANT

DIAGRAM ARE EXISTING-TO-REMAIN AND SHALL BE FIELD VERIFIED

B…