OC_Phoenix_BAS_and_Smoke_Control_-_Bid_Drawings.pdf
PDF 20 MB Posted
- Solicitation number
- Y23-731
- Issued by
- Orange County, Orlando City, Florida
About this file
These bid documents are for the Orange County Corrections Department's Phoenix Building Replacement of the Smoke Control and Building Automation Systems project located at 2400 33rd Street, Orlando, Florida. The project involves comprehensive replacement and upgrades of existing smoke control systems, building automation systems, HVAC controls, fire/smoke dampers, and associated electrical and control infrastructure across multiple buildings (Buildings A, B, and C). The project is a 100% construction document set dated September 26, 2022, prepared by Atkins engineering firm, with an estimated project cost of $1,500,000.00 and a bid submission deadline of December 8, 2022.
The technical scope includes replacing pneumatic control systems with digital direct control (DDC) systems, upgrading fire alarm and smoke control panels, installing new motorized damper actuators, replacing electric duct heaters, integrating new building automation system controllers, and ensuring comprehensive smoke zone control and monitoring capabilities. The project requires coordination with existing systems, maintaining building safety protocols, and meeting UL 864, NFPA 72, and local code requirements. The work involves detailed modifications to HVAC equipment, control systems, electrical panels, and fire alarm infrastructure across multiple building levels, with careful attention to maintaining operational continuity and safety during the system replacement process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y23-731.pdf | ||
| OC_Phoenix_BAS_and_Smoke_Control_-_Bid_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
100% CONSTRUCTION DOCUMENTS
SEPTEMBER 26, 2022
ORANGE COUNTY MAYOR
JERRY L. DEMINGS
DISTRICT 1 COMMISSIONER
NICOLE H. WILSON
DISTRICT 2 COMMISSIONER
CHRISTINE MOORE
DISTRICT 3 COMMISSIONER
MAYRA URIBE
DISTRICT 4 COMMISSIONER
MARIBEL GOMEZ CORDERO
DISTRICT 5 COMMISSIONER
EMILY BONILLA
DISTRICT 6 COMMISSIONER
VICTORIA P. SIPLIN
Sheet Number Sheet Name Scale
Sheet Issued
G-000 COVER SHEET AND SHEET INDEX Yes
M-101 BUILDINGS B AND C FIRST LEVEL HVAC PLAN 1/8"=1'-0" Yes
No Scale
M-401 HVAC SCHEDULES
No Scale Yes
M-001 HVAC SYMBOLS LEGEND AND GENERAL NOTES YesNo Scale
M-102 1/8"=1'-0" Yes
DRAWING INDEX
BOARD OF COUNTY COMMISSIONERS
BUILDINGS B AND C SECOND LEVEL HVAC PLAN
M-103 1/8"=1'-0" YesBUILDINGS B AND C ROOF LEVEL HVAC PLAN
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st em s
DAVID L. HEIDEMAN
FL PE NO. 76792
G-001
COVER SHEET AND
SHEET INDEX
DLH
DLH
TJF
M-301 PHOENIX CHILLER PLANT CONTROLS
No Scale YesM-302
No Scale YesM-303
PHOENIX C1 THRU C6 SEQUENCE, OVERVIEW AND PARTS LIST
No Scale YesM-304
PHOENIX RTU-C7 AND C8 SEQUENCE, OVERVIEW AND PARTS LIST
No Scale YesM-305
PHOENIX AHU-1 THRU 7 SEQUENCE, OVERVIEW AND PARTS LIST
No Scale YesM-306
PHOENIX SF-1 THRU 8 SEQUENCE, OVERVIEW AND PARTS LIST
SMOKE CONTROL SYSTEM SEQUENCE, OVERVIEW AND PART LIST
No Scale Yes
Orange County Corrections Phoenix Building Replacement of the Smoke
Control and Building Automation Systems
E-001 ELECTRICAL LEGEND SYMBOL AND NOTES No Scale Yes
E-101 BUILDINGS B AND C FIRST LEVEL ELEC PLAN Yes
E-102 Yes
E-103 Yes
E-401 ENLARGED ELECTRICAL PLANS Yes
E-402 Yes
E-601 EXISTING ELECTRICAL ONE LINE DIAGRAM No Scale Yes
E-801 ELECTRICAL PANEL SCHEDULE No Scale Yes
E-701 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - DEMOLITION No Scale Yes
E-702 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - NEW No Scale Yes
E-711 ELECTRICAL SMOKE CONTROL DETAILS No Scale Yes
BUILDINGS B AND C SECOND LEVEL ELEC PLAN
BUILDINGS B AND C ROOF LEVEL ELEC PLAN
ENLARGED ELECTRICAL PLANS
1/8"=1'-0"
1/8"=1'-0"
1/8"=1'-0"
1/4"=1'-0"
1/4"=1'-0"
M-104 1/8"=1'-0" YesBUILDING A FIRST LEVEL HVAC PLAN
M-105 1/8"=1'-0" YesBUILDING A FIRST LEVEL PIPING PLAN
M-106 1/8"=1'-0" YesBUILDING A MECHANICAL MEZZANINE PLANS
E-104 YesBUILDING A FIRST LEVEL ELEC PLAN 1/8"=1'-0"
E-105 YesBUILDING A ELECTRICAL MEZZAININE PLANS 1/8"=1'-0"
M-501 SEQUENCE OF OPERATIONS No Scale Yes
MECHANICAL
ELECTRICAL
M-601 HVAC DETAILS No Scale Yes
M-502 DAMPER CONTROL SCHEMATIC DIAGRAMS No Scale Yes
No Scale YesM-307 FIREFIGHTER SMOKE CONTROL PANEL
No Scale YesM-308 MAINTENANCE SMOKE EXTRACT CONTROL PANEL
BID DOCUMENTS
NOT FOR
CONSTRUCTION
BID
GENERAL INSTALLATION NOTES
ALL COMMUNICATION CABLING SHALL BE RUN SEPARATE FROM ANY POWER WIRING.
REFER TO SPECIFICATION DIVISIONS 23 & 26 REGARDING WIRING AND CONDUIT REQUIREMENTS.
ALL CONDUIT MUST HAVE A PULL STRING INCLUDED.
LABELING, ETC... HAND WRITTEN LABELS ARE NOT ACCEPTABLE.
ALL WIRING MUST BE CLEARLY LABELED AT TERMINATION POINTS. ACCEPTABLE METHODS INCLUDE BRADY
ACTUAL CONFIGURATION OF DUCTING SYSTEMS IS TO BE DETERMINED BY OTHERS, AND CONFIGURATION
SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.
ACTUAL CONFIGURATION OF PIPING SYSTEMS IS TO BE DETERMINED BY OTHERS, ANY CONFIGURATION
SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.
ALL CONDUIT AND WIRING MUST BE INSTALLED PARALLEL TO THE BUILDING LINES.
ALL WORK SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER & MUST MEET THE APPROVAL OF
ALL WALL PENETRATIONS MUST BE SLEEVED AND SEALED PER THE SPECIFICATIONS. IF THE WALL IS A RATED WALL, F.B.O. IS AN ACRONYM FOR FURNISHED BY OTHERS.
MAXIMUM FLEXIBLE CONDUIT LENGTH NOT TO EXCEED 3 FEET.
LOCATE NEW PANELS AND ASSOCIATED COMMUNICATION CABLES 6' MIN. DISTANCE FROM ANY VFD PANEL OR HIGH POWER CONDUIT. INSTALLATION MUST CONFORM WITH ALL NATIONAL AND LOCAL CODES.
WIRING COLOR CODE:
BL = BLUE BK = BLACK BR = BROWN GR = GREEN GY = GRAY O = ORANGE
P = PURPLE R = RED Y = YELLOW WH = WHITE
OUTSIDE AIR
OUTSIDE AIR/HUMIDITY SENSOR
MAGNETIC STARTER
LOW LIMIT PRESSURE SWITCH
HIGH LIMIT PRESSURE SWITCH
MEDIA CONVERTER
LINE VOLT THERMOSTAT
PROGRAMMABLE CONTROLLER
I/O MODULE
SETPOINT CONTROLLER
HOT WATER VALVE
HUMIDIFIER
INLET GUIDE VANES
EXPANSION MODULE
OSA
0HS
MS
LLS
HLS
MC
LVT
MP581
MP503
MP501
HWV
HUM
IGV
ABB.
EX2
SYMBOLDESCRIPTION
DIFFERENTIAL PRESSURE TRANSMITTER
DIFFERENIIAL PRESSURE SWIICH
DUCT TEMPERATURE SENSOR
DOMESTIC WATER HEATER
FAN POWERED UNIT
FREEZE STAT
FLOAT SWITCH
FIRE STAT
FILTER
DAMPER END SWITCH
ELECTRIC DUCT HEATER
DUCT SMOKE DETECTOR
DPT
DPS
DTS
DWH
HE
HC
FPU
FZT
FS
FRT
FLT
ES
EDH
DSD
ABB.SYMBOLDESCRIPTION
BUILDING CONTROL UNIT
COOLING COIL
CHILLED WATER VALVE
MOTORIZED DAMPER
DUCT HUMIDITY SENSOR
DUCT CARBON DIOXIDE SENSOR
CURRENT TRANSMITTER
CURRENT SENSING SWITCH WITH RELAY
CURRENT SENSING SWITCH
CENTRAL CONTROL PANEL
AIR HANDLING UNIT
AIR FLOW RING
AIR FLOW MONITORING STATION
AVERAGING TEMPERATURE SENSOR
SYMBOL
BCU
CC
CHWV
DM
DHS
DCO
CT
CSSR
CSS
CCP
AHU
AFR
AFM
ATS
ABB.
BCU
C
C
VARI TRAC II
CCP
сss
CSSR
CT
Ü û
2-WAY
3-WAY
C H
W V
D M
-B
DH
S
AF
R
AF
M A
T S
D M
-A C
H W
V
RLY
RIB
SHS
RPS
PPU
SEQ
SA
RA
PWS
PCM
OTS
ZN517
SP
ZN511/521
UNITARY CONTROLLER
ZONE CONTROLLER
RELAY
RELAY IN A BOX
SPACE HUMIDITY SENSOR
ROOM PRESSURE SENSOR
PARALLEL FAN POWERED UNIT
SEQUENCER RELAY MODULE
SUPPLY AIR
RETURN AIR
DC POWER SUPPLY
PROGRAMMABLE CONTROL MODULE
OUTSIDE TEMPERATURE SENSOR
SURGE PROTECTION
TCI
UPCM
UCP
UCM
TUC
TCM
VAV
TDM
TR
TU
TKR
SPTS
TC
STS
TRANE CONTROL INTERFACE
UNIVERSAL PROGRAMMABLE CONTROL MODULE
UNIT CONTROL PANEL
UNIT CONTROL MODULE
TERMINAL UNIT CONTROL
THERMOSTAT CONTROL MODULE
VARIABLE AIR VOLUME BOX
TRAC MOTORIZED DAMPER
TRANSFORMER
TERMINAL UNIT
TRACKER 100 STAT
STRAP ON TEMPERATURE SENSOR
TIME CLOCK
SPACE TEMPERATURE SENSOR
VFD
ZDU
WTS
WFM
WFS
VARIABLE FREQUENCY DRIVE
ZONE DAMPER UNIT
WELL TEMPERATURE SENSOR
WATER FLOW METER
WATER FLOW SWITCH
DESCRIPTION SYMBOL ABB. DESCRIPTION ABB.SYMBOL DESCRIPTIONSYMBOL ABB.DESCRIPTION
HEAT EXCHANGER
HEATING COIL
ZDM
WTS
VFD
OR CARD NUMBER
TERMINAL BLOCK
DEVICE NUMBER
CONTROLLER
POINT NUMBER
POINT TYPE
MULTIPLE CONTROL DEVICE CALLOUT DESCRIPTON
TERMINAL BLOCK
OR CARD NUMBER
B0 1 1
POINT TYPE
POINT NUMBER
SINGLE CONTROL DEVICE CALLOUT DESCRIPTON
HE
RE
SE
T
FZ
T
FR
T
W
FM
RE
SE
T
ABBREVIATIONS AND SYMBOL LEGEND
ZN
ZN
ZN
PCM
PWS
RA
RIB
RLY
RPS
SA
SEQ
VAV
UPCM
UCP
TUC
TU
TRACKER
STAT X
TCM
TCI
1:00
TC
STS
SPTS
PPU
SP
SHS
TDM-X
OPS
DPT
DWH
FS
FPU
C
H
DT
S
ED
H
H W
V
M
HU
M
M оso
OSA
MS
5O3
MP
MP
MC
L HLLS
IGV
HL HLS
EX2
OHS
MP.581
H W
V
M 3-WAY
2-WAY
UCM
THE ENGINEER, ORANGE COUNTY CAPITAL FACILITIES AND ORANGE COUNTY CORRECTION FACILITIES.
THE PENETRATION SHALL BE SEALED WITH PREVIOUSLY SUBMITTED AND ACCEPTED FIRE PROOFING MATERIAL INSTALLED AS RECOMMENDED BY THE MATERIAL MANUfFACTURER.
CONTRACTOR TO PROVIDE TEMPORARY ROOFTOP AIR HANDLERS AND TEMPORARY SMOKE EXHAUST FANS FOR SMOKE ZONES UNDER CONSTRUCTION IF THOSE ZONES ARE TO REMAIN CONTINUALLY OCCUPIED. EACH TEMPORARY UNIT TO BE TIED INTO FIRE ALARM OR PROVIDE FIRE WATCH. ALL LIFE SAFETY REQUIREMENTS SHALL BE PROVIDED AS REQUIRED BY THE AHJ.
EXISTING CONTROLLERS, SENSORS, T-STATS AND WIRING TO BE REPLACED WITH NEW UL 864 CONTROLLERS, NEW SENSORS, NEW T-STATS AND NEW WIRING. SEE SPECIFICATIONS FOR REPLACEMENT OF CONTROL SYSTEMS.
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-001
HVAC SYMBOLS LEGEND
AND GENERAL NOTES
DLH
DLH
TJF
BID
NOT FOR
20x10 RETURN AIR UP 14x14 SUPPLY DUCT UP TO 2ND FLOOR
20x10 EXHAUST DUCT UP TO 2ND FLOOR SUPPLY DUCT UP TO 2ND FLOOR
14x14 SUPPLY DUCT UP TO 2ND FLOOR
EXHAUST DUCT UP TO 2ND FLOOR
20x10 EXHAUST DUCT UP TO 2ND FLOOR14x14 SUPPLY DUCT UP TO 2ND FLOOR
SUPPLY DUCT UP TO 2ND FLOOR
SUPPLY DUCT UP TO 2ND FLOOR
FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.) FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)FIRE DAMPERS (TYP.)
FIRE DAMPERS (TYP.)
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
SEE PURGE AIR DETAIL AT OUTSIDE
AIR INTAKE DETAIL 1 ON SHEET M-601
14x14 PURGE AIR UP
14x14 PURGE AIR UP
14x14 PURGE AIR UP
14x14 SUPPLY AIR DUCT UP14x14 PURGE AIR UP
14x14 PURGE AIR UP
14x14 PURGE AIR UP
UP TO EF-9
DS/CU-1
S/A FROM
SECOND
FLOOR AND
RTU-8
R/A FROM
SECOND
FLOOR AND
RTU-8
x8 8x6
8x4
10x8
24x8 x8 x1
10x8
10x8
10x8
10x8
10x8
10x8 x1 x1
28x8
10x8
10x8 x1
10x8
8x6
8x6
10x612x8
14x12 x8
10x6
10x6
10x
10x4
10x
14x10 x1
14x12
14x8 8x6
10x6 x6 x8 x6
14x
8x x6
8x6
10x6
10x6
12x6
10x6 12x8 x6
14x x88x
10x
10x
14x12
10x
10x 4 10x
8x4
10x
10x
10x
8x4
8x4
14x8
8x
10x6
10x6
10x6 x8 x1
12x88x4
8x
8x4
14x10
12x6 x8
8x x1
12x6
14x10
10x6
10x6 x8 x1
10x6
10x6
10x6
14x8 x6 x1
10x10 10x4
14x
10x
10x
10x6
14x
10x6
10x6
10x4 x6 x610 x6
14x1212x8 10x6
12x6 x8
8x x1 x1
14x10
8x4
12x8 10x6
14x12
12x6 x6 x6
10x 6 10x x8
14x12
10x10
10x6 x8
10x
8x4
10x 4 10x
10x
14x x6
10x6
8x6 10x6
14x8
8x4
14x14 PURGE AIR UP
FIRE DAMPERS (TYP.)
EXISTING FIRE ALARM CONTROL PANEL
FD
FD
FD
FD
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-101
BUILDINGS B AND C
FIRST LEVEL HVAC PLAN
DLH
DLH
TJF
BUILDINGS B AND C FIRST LEVEL HVAC PLAN
SCALE: 1/8" = 1'-0"1
REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND
INSTALL NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE
DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED
WITHIN 5'-0" OF THE DAMPER. CONNECT NEW WIRING FROM
NEW DUCT SMOKE DETECTOR BACK TO FIRE ALARM SYSTEM.
REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH
ASSOCIATED EXISTING WIRING AND REPLACE WITH NEW DDC
THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).
INSTALL NEW DDC CONTROLLER AND WIRING FOR EXISTING
AC-1/CU-1 UNIT AT BUILDING B.
ALL EXISTING DUCTWORK SHALL BE CLEANED PER
SPECIFICATION SECTION 230130.52.
INSTALL NEW 24x24 LOCKABLE ACCESS PANEL TO ACCESS
F/SD. TWO NEW CEILING ACCESS PANELS TO BE INSTALLED
ACROSS EACH WALL-MOUNTED F/SD. ONE NEW WALL
ACCESS PANEL TO BE INSTALLED AT FLOOR-MOUNTED F/SD.
REPLACE EXISTING PRIMARY FIREFIGHTER'S
SMOKE CONTROL PANEL WITH NEW UL 864
PRIMARY FIREFIGHTER'S SMOKE CONTROL
PANEL.
REPLACE EXISTING BUILDING AUTOMATION
SYSTEM PANEL WITH NEW UL 864 BAS
CONTROL PANEL.
REPLACE EXISTING SECONDARY
FIREFIGHTER'S SMOKE CONTROL PANEL
WITH NEW UL 864 SECONDARY
FIREFIGHTER'S SMOKE CONTROL PANEL.
DEMO EXISTING PNEUMATIC AIR COMPRESSOR AND ALL
EXISTING PNEUMATIC TUBING AND WIRING. TURN OVER TO
OWNER.
REMOVE HARD CEILING BELOW EXISTING DUCTWORK IN
STAIR ROOM. PROVIDE NEW 2-HOUR RATED HORIZONTAL
ENCLOSURE AROUND EXISTING SUPPLY DUCT IN STAIR
ROOM. INSTALL NEW DRYWALL CEILING AND PAINT TO MATCH
EXISTING.
KEYED NOTES
UL 864 SMOKE CONTROL SYSTEM
UL 864 SMOKE CONTROL SYSTEM
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
BID
20x10 EXHAUST DUCT DN TO 1ST FLOOR
14x14 SUPPLY DUCT DN TO 1ST FLOOR
20x10 EXHAUST DUCT DN TO 1ST FLOOR 14x14 SUPPLY DUCT DN TO 1ST FLOOR
14x14 SUPPLY DUCT DN TO 1ST FLOOR
20x10 EXHAUST DUCT DN TO 1ST FLOOR
20x10 EXHAUST DUCT DN TO 1ST FLOOR14x14 SUPPLY DUCT DN TO 1ST FLOOR
SUPPLY DUCT DN TO 1ST FLOOR
SUPPLY DUCT DN
TO 1ST FLOOR
3 3
46x14 S/A FROM RTU-8
FROM
RTU-7
FROM
RTU-7
FROM
RTU-7
FROM
RTU-7
FROM
RTU-7
R/A FROM
RTU-8
RTU ABOVE
RTU ABOVE
RTU ABOVE
RTU ABOVE
RTU ABOVE
RTU ABOVE
RTU ABOVE
3 3
38x x8
14x14
12x8
12x6
8x4
8x
8x x8 x1
08x4 x8 x1 x1 x8 x1 x1 x1
10x6 6x4
24x6
10x8
24x6
24x6
24x6
24x6
24x14
30x14
10x8
10x8
10x6
10x6
10x6
10x10
18Ø
38x
14x14
14x10
10x8
10x
8x6
14x14
14x14
14x10
10x8
10x
8x6
8x6
8x6 x1
8x
8x 6 8x
8x610x8
38x14
14x
38x14
14x
14x
10x
10x8
8x6
14x
14x
14x
10x
10x8
8x6
8x6
8x6 x1
8x
8x
8x
8x610x8 38x
14x14 38x
14x14
14x10
10x8
10x
8x6
14x14
14x14
14x10
10x8
10x
8x6
8x6
8x6 x1
8x
8x
8x
8x6 10x8
RTU ABOVE
38x14
14x
38x14
14x
14x
10x
10x8
8x6
14x
14x
14x
10x
10x8
8x6
8x6
8x6 x1
8x
8x 68x
8x6 10x8
RTU ABOVE
RTU
C4 RTU
C3
RTU
C1
RTU
C2
RTU
C5
FD
FD
FD
FD
FD FD
FD
FD
FD
FD
FD
FD
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-102
BUILDINGS B AND C
SECOND LEVEL HVAC PLAN
DLH
DLH
TJF
BUILDINGS B AND C SECOND LEVEL HVAC PLAN
SCALE: 1/8" = 1'-0"1
REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL
NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR.
THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE
DAMPER. CONNECT NEW WIRING FROM NEW DUCT SMOKE DETECTOR
BACK TO FIRE ALARM SYSTEM.
REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED
EXISTING WIRING AND REPLACE WITH NEW DDC THERMOSTATS AND
HUMIDISTATS AND WIRING (TYPICAL).
KEYED NOTES
ALL EXISTING DUCTWORK SHALL BE CLEANED PER SPECIFICATION
SECTION 230130.52.
REMOVE EXISTING SUPPLY DUCT PENETRATING STAIR WALL AND
CAP DUCT AIRTIGHT OUTSIDE OF STAIRWELL. REMOVE F/S DAMPER
AND DUCT THROUGH WALL. PATCH WALL AS REQUIRED TO
MAINTAIN RATING.
UL 864 SMOKE CONTROL SYSTEM
UL 864 SMOKE CONTROL SYSTEM
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
BID
EXIST. SA - DN TO ZONE 4
SERVING
ZONE 4
EXIST. RA -
DN - ZONE 4
EXIST. SA -
DN - ZONE 3
EXIST. SEF-14
SERVES ZONE 4
EXIST. F/S DAMPER
EXIST. F/S DAMPER
EXIST. F/S DAMPER
EXIST. F/S DAMPER
EXIST. SA -
DN - ZONE 5
EXIST. SEF-18
SERVES - ZONE 4
EXIST. RA -
DN - ZONE 5
EXIST. F/S DAMPER
SERVING
ZONE 3
EXIST. RA -
DN - ZONE 3
EXIST. F/S DAMPER
EXIST. SEF-15
SERVES ZONE 3
EXIST. F/S DAMPER
EXIST. RA -
DN - ZONE 5
EXIST. SA -
DN - ZONE 5
EXIST. F/S DAMPER
EXIST.SEF-19
SERVING
ZONE 4
SERVING
ZONE 2
EXIST. SA -
DN - ZONE 2
EXIST. F/S DAMPER
EXIST. F/S DAMPER
EXIST. RA -
DN - ZONE 2 SERVING
ZONE 2
EXIST.SEF-16
SERVING
ZONE 1
EXIST. F/S DAMPER
EXIST. F/S DAMPER
EXIST. SA -
DN - ZONE 1
EQUIPMENT NOT INCLUDED IN UL
864 SMOKE CONTROL SYSTEM
RTU
C7
SEF
C14
RTU
C4
EF
C10
EDH
C14 532
SERVING
ZONE 5
RTU
C6
SEF
C18
EDH
C13
EDH
C11
1 4
EF
C12
SEF
C17
2 RTU
C2
EDH
C8
3 2
SEF
C15
RTU
C3
EF
C11
EDH
C10
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
SERVING
ZONE 1
SERVING
ZONE 1
EF
C13
SEF
C16
2 3 5
RTU
C1
EDH
C8
(EXISTING)
1RTU
C8
2 3 5
EDH
C15
(EXISTING)
2 3 5
SEF
C19
4 2 3 5
6 EDH
C12
(EXISTING)
SERVING
ZONE 5
RTU
C5
30x20
20x20
30x20
20x20
30x20
20x20
30x20
20x20
26x14
26x14
46x14
28x16 x1 x1
9 8
26x14
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-103
BUILDINGS B AND C
ROOF LEVEL HVAC PLAN
DLH
DLH
TJF
BUILDINGS B AND C ROOF LEVEL HVAC PLAN
SCALE: 1/8" = 1'-0"1
KEYED NOTES
REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL
NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR.
THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE
DAMPER. INSTALL DUCT ACCESS DOOR IF NONE EXISTS ON AT
LEAST ONE SIDE OF F/S DAMPER (SIDE OF ACTUATOR).
REMOVE ALL EXISTING VALVE ACTUATORS, TEMPERATURE
SENSORS, DIFFERENTIAL PRESSURE SENSORS, ELECTRIC DUCT
HEATERS. REPLACE ALL DEVICES WITH NEW DEVICES CONNECTED
TO NEW BMS SYSTEM. SEE SHEET M-303 FOR ADDITIONAL DETAILS.
REMOVE EXISTING AHU CONTROLLER AND REPLACE WITH NEW DDC
CONTROLLER AND WIRING FOR EXISTING ROOF TOP UNIT.
REPLACE CONTROL DEVICES FOR EXISTING EXHAUST FANS WITH
NEW DEVICES CONNECTED TO NEW BMS.
ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR
HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT SHALL
BE CLEANED PER SPECIFICATION SECTION 230130.52.
UL 864 SMOKE CONTROL SYSTEM
UL 864 SMOKE CONTROL SYSTEM
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR
ELECTRIC DUCT HEATER OF SAME CAPACITY.
2. CONTRACTOR SHALL REFER TO THE CONTROL DRAWINGS TO
VERIFY THE SCOPE OF WORK AND THE THE EQUIPMENT SCHEDULES
FOR THE SIZES AND CAPACITIES OF EXISTING AND/OR NEW
EQUIPMENT.
REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.7
REMOVE EXISTING DUCT SMOKE DETECTOR AND EXISTING
WIRING. REPLACE WITH NEW DUCT SMOKE DETECTOR AND
WIRING. PROVIDE STAINLESS STEEL ENCLOSURE WITH CLEAR
VIEWING WINDOW TO SMOKE DETECTOR. PROVIDE NEW
DOUBLE-WALL INSULATED DUCT ACCESS DOOR FOR
MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.
PROVIDE NEW DUCT SMOKE DETECTOR WITH NEW STAINLESS
STEEL ENCLOSURE AND CLEAR VIEWING WINDOW TO SMOKE
DETECTOR. PROVIDE NEW DOUBLE-WALL INSULATED DUCT
ACCESS DOOR FOR MAINTENANCE FOR NEW DUCT SMOKE
DETECTOR.
PROVIDE NEW VFD FOR REPLACED SMOKE EXHAUST FAN
IN NEMA 4X STAINLESS STEEL ENCLOSURE. PROVIDE NEW
UNISTRUT MOUNTING ON BRACKETS AT RTU DUNNAGE,
NEXT TO EXISTING DISCONNECTS.
BID
400 400
400 400
400 400
300 100 300
3001500
335 335 375
395660
75 75
435 435 435
590 590
SF
A8
EDH
A238
SF
A7
EDH
A228
SF
A6
EDH
A21
SF
A5
EDH
A208
SF
A458
EDH
A198
SF
A358
EDH
A188
SF
A258
EDH
A178
SF
A1
EDH
A168
CU
A2
AC
A2
6EF
A1 8
AC
A1
CU
A1
UH
A1
EF
A20 6
2 8
EF
A2
EF
A3
AHU
A6
AHU
A7
AHU
A4
EF
A6
AHU
A3
AHU
A2
AHU
A1
6 8
6 8
EF
A56 8
8 9
AHU
A5
8 9
8 9
EF
A7
EF
A8 6 8
6 8
EF
A4 6 8
8 8
8 8
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x1430x1018x10
30x14 x1 x8 x1 x1 x1 x8 x1 x1 x1 x8 x1 x1 x1 x1 x1 x1 x1 x4 x1 x1 x1 x1 x1
6x x1 x1 x8 10 x8 x8
8x x1 x1 x8
8x
8x
24x6
12x10 12x10
12x10
12x10
12x10
18x10 12x8
20x14
12x6
10x8 12x8
12x10
12x8
24x8
12x10
24x14
14x10
24x8
24x12 16x12 12x10 x1 x8 x8
10x6
18x14 x8 x8 x1
10x8 6x4
12x8
12x8
12x8
12x8
10x6 10x6 x1 x8
6x4
8x6
24x424x2 x8
8x4 8x4
8x68x6 x1
0 12 x1
24x8
10 10
2 HR FIRE 1 H
R F/S
1 HR F/S2 H
R FIRE
1 H R F/S
1 HR F/S
1 1 Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-104
BUILDING A
FIRST LEVEL HVAC PLAN
DLH
DLH
TJFBUILDING A FIRST LEVEL HVAC PLAN
SCALE: 1/8" = 1'-0"1
REMOVE EXISTING PNEUMATIC FIRE/SMOKE DAMPER AND INSTALL NEW FIRE/SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE DAMPER. CONNECT NEW WIRING FROM NEW DUCT SMOKE DETECTOR BACK TO FIRE ALARM SYSTEM. INSTALL NEW 24x24 LOCKABLE ACCESS PANEL TO ACCESS F/SD. TWO NEW CEILING ACCESS PANELS TO BE INSTALLED ACROSS EACH WALL-MOUNTED F/SD. ONE NEW CEILING ACCESS PANEL TO BE INSTALLED FOR EACH DUCT RISER F/SD.
REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED EXISTING WIRING AND REPLACE WITH
NEW DDC THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).
REPLACE EXISTING TRANE CONTROL PANEL WITH NEW JOHNSON CONTROLS BMS PANEL.
REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR ELECTRIC DUCT HEATER OF SAME CAPACITY.
REPLACE EXISTING SUPPLY FAN CONTROLLER WITH NEW DDC CONTROLLER.
REPLACE EXISTING EXHAUST FAN CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).
REPLACE EXISTING UNIT HEATER CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).
KEYED NOTES
ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR HANDLING UNITS, EXHAUST FANS AND
OTHER EQUIPMENT SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.
REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH NEW AIR HANDLING UNIT CONTROLLER
CONNECTED TO THE NEW BAS SYSTEM.
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
REMOVE EXISTING PNEUMATIC DAMPER ACTUATORS AND PNEUMATIC TUBING. REPLACE WITH NEW ELECTRONIC DAMPER ACTUATORS, PROVIDE NEW DDC CONTROLLERS AND CONNECT TO BAS SYSTEM.
PROVIDE NEW DUCT SMOKE DETECTOR. PROVIDE NEW DOUBLE-WALL DUCT ACCESS DOOR FOR
MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.
BID
3" CHWS&R
1 1/2" CHWS&R
2 1/2" CHWS&R
1 1/2" CHWS&R
1" CHWS&R
2" CHWS&R
2 1/2" CHWS&R
1 1/2" CHWS&R1" CHWS&R
1" CHWS&R
AHU
A5
AHU
A7
AHU
A4
AHU
A6
AHU
A3
AHU
A2
AHU
A1
3" CHWS&R TO &
FROM BUILDING
3/4" HWR
2" HW
3" CW
1 1/2" HWR
2" HWS
12" FLUE UP
TO ROOF
4" FLUE
UH-1
GWH-1
CHEMICAL
SHOT FEEDER
6" CHR
6" CHWR
3" CHWS
6" CHR
CHILLED WATER
MAKE-UP[
3/4"
BACKFLOW/PRV ASSEMBLY
ASC PANEL
FOR CHILLERS
6" CHWS 6" CHWS
6" CHWS
3" CHWS
6" CHWR 2 1/2" HWS
1 1/2" HWR
X
X
X
X
X
X X X X X
X
X
X
X
X
CHILLER YARD
CH-1 CH-2
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-105
BUILDING A
FIRST LEVEL PIPING PLAN
DLH
DLH
TJFBUILDING A FIRST LEVEL PIPING PLAN
SCALE: 1/8" = 1'-0"1
ENLARGED MECH ROOM 110
SCALE: 1/4" = 1'-0"2
CHILLER YARD
SCALE: 1/8" = 1'-0"3
EXISTING CHILLERS BEING REPLACED UNDER SEPARATE CONTRACT.
KEYED NOTES
1 1
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
BID
MECHANICAL MEZZANINE
A-200
1 1/2"
26x1426x14
14x12
M
M
M
M x1 x1 x1 x1
14x12 x1
14x12
28x14
20x14
1 1/2" 1 1/2" 1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2 1/2"
2 1/2"
2 1 /2"
2 1 /2"
AHU-5
EXISTING CONTROL
PANEL (TYPICAL)
2" 2"
AHU
A5 2 3
AHU
A7 2 3
AHU
A6 2 3
AHU
A423
2 2
AHU-7
DDC PANEL
26x16 x1 x1 x1
24x12
14x26 26x14
M
M
M
16x12 18x16 x1
2"
1 1/2"
1 1/2"
1 1/2" 1 1/2"
1 1/2"
1 1/2"
EXISTING CONTROL
PANEL (TYPICAL)
2"
MECHANICAL MEZZANINE
A-201
AHU-2
AHU
A223
AHU
A1 2 3
AHU
A3 2 3
DDC PANEL
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-106
BUILDING A MECHANICAL
MEZZANINE PLANS
DLH
DLH
TJF
BUILDING A MECHANICAL MEZZANINE 200 PLAN
SCALE: 1/4" = 1'-0"1 BUILDING A MECHANICAL MEZZANINE 201 PLAN
SCALE: 1/4" = 1'-0"2
NOT USED.
ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR
HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT
SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.
REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH
NEW AIR HANDLING UNIT CONTROLLER CONNECTED TO THE
NEW BAS SYSTEM.
REPLACE EXISTING MOTORIZED DAMPER CONTROLLER AND
DAMPER ACTUATOR WITH NEW MODULATING ACTUATOR WITH
POSITION INDICATOR.
KEYED NOTES
1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS
DRAWING IS EXISTING UNLESS NOTED OTHERWISE.
GENERAL NOTES
NOT USED.5
BID
WELL
TEMPERATURE
SENSOR
WELL
TEMPERATURE
SENSOR
WELL
TEMPERATURE
SENSOR
WELL
TEMPERATURE
SENSOR
FLOW
SWITCH
FLOW
SWITCH
OTS-1
AI
5 3
4 6
BI
DPS-2
CHWP-2
1 4
BO
4 1
BI
4 2
BI
ALARM
STATUS
ALARM
4 3
BI
4 4
BI
STATUS
CH-2
COMPRESSOR
EVAPORATOR
WTS-1
AI
5 1
WTS-2
AI
5 2
COMPRESSOR
EVAPORATOR
CH-1
C O
N
TR
O L
PA
N
EL
C
O N
TR
O
L
PA
N
EL
B0 1 3
CHWP-1
HL DPS-1
4 5
BI
MS
S/S RIB-2
MS
S/S RIB-1
HL
UPCM
EXISTING
ENC-1
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-301
PHOENIX CHILLER
PLANT CONTROLS
DLH
DLH
TJF
THE BAS WORK INDICATED ON THIS DRAWING IS NOT
INCLUDED IN THIS PROJECT. THIS WORK IS BEING
PERFORMED AS PART OF ANOTHER PROJECT. THIS
CONTRACTOR SHALL INTERFACE WITH THE BUILDING
AUTOMATION SYSTEM FULLY INCORPORATING THE
CONTROLS INDICATED AS WELL AS VERIFYING THAT THE
CONTROLS PORTION OF TESTING AND BALANCING AND
COMMISSIONING OF THE NEW CHILLER INSTALLATION
INDICATED IS INCLUDED EITHER IN THE ORIGINAL CHILLER
CONSTRUCTION BID PACKAGE OR THIS BID PACKAGE.
NOTE:
FOR INFORMATION ONLY
BID
KEYED NOTES
REMOVE AND REPLACE EXISTING SENSOR CONNECT TO NEW BAS SYSTEM.
REMOVE AND REPLACE EXISTING DAMPER CONTROLLER CONNECT TO NEW BAS SYSTEM.
REMOVE EXISTING DAMPER ACTUATOR AND REPLACE WITH NEW 24v ACTUATOR WITH POSITION SENSOR.
REMOVE AND REPLACE EXISTING DAMPER WITH NEW LOW LEAKAGE F/S DAMPER. CONTRACTOR SHALL
VERIFY SIZE OF DAMPER.
REMOVE AND REPLACE EXISTING CHILLED WATER CONTROL VALVE. CONNECT TO NEW BAS SYSTEM.
REMOVE EXISTING DAMPER AND ACTUATOR. SEAL SUPPLY AIR DUCT OPENING AS SHOWN.
REMOVE AND REPLACE EXISTING EDH. CONNECT CONTROLS TO NEW BAS.
EA
NO
3 3
AO
1 5 B0
M EP-2
HL DPS-2
5 3
BI
EA/RA
5 2
AI
5 1
AI
1 6 B0
M
1 4 B0
EP-1
SD-1EDH-1
3 1
AO
4 4
BI
L HDPS-1
4 1
AI
ATS-1
C
C
LH DPT-1
4 5
AI
ATS-2
4 2
AI
ATS-3
4 3
AI
4 6
AI
LH DPT-2DM-1
1 3 B0
TYPICAL FOR 12
1EA/RTU-C1 THRU RTU-C4
4EA/RTU-C5 & RTU-C6
S/S 1 1 B0
RIB-1
MS
EA NC EA
S/S
MS
TYPICAL FOR 4
MS
S/S RIB-2
RIB-X
2 1
BO
TYPICAL FOR 4
2EA/RTU-C5&C6
TO SPACENCOA
EF#
SMOKE EF#
RTU#
C12 C11C13 C12 C11 C10
C16 C17 C15 C14 C19 C18
EXHAUST FAN INTERLOCK SCHEDULE
C1 C2 C3 C4 C5 C6
NO SA
NO NC
NOOA
CO
O
LI
NG
C O
IL
CH
W
V-
FIL
TE
R
C
C
CO
O
LI
NG
C O
IL
FIL
TE
R
NO
AO
3 2
C H
W S
C H
W R
C H
W S
C H
W R
C H
W V-
M
C M
B-
2 3 1 1 1 1
1 1 2 3
2 3
2 3
2 3
2 3
M
M
M
M
M
SUPPLY AIR FAN
SMOKE EXHAUST FAN
PS
-1A1
EA/RA GRILLE
1 EA/RTU-C1, C2, C3, C4.
RTU-C1 - EF-13
RTU-C2 - EF-12
RTU-C3 - EF-11
RTU-C4 - EF-10
REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.
INSTALL NEW STATIC PRESSURE SENSOR. EXTEND PRESSURE SENSOR BELOW
EXHAUST/RETURN AIR GRILLE IN ORDER TO SENSE THE SPACE PRESSURE.
RTU-C1 THRU RTU-C6 CONTROL DIAGRAM
SEF-C14 THRU SEF -C19 CONTROL DIAGRAM SMOKE EXHAUST MAKE-UP AIR CONTROL DIAGRAM
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-302
PHOENIX C1 THRU C6
SEQUENCE, OVERVIEW
DLH
DLH
TJF
AND PARTS LIST
BID
REPLACE EXISTING DAMPER ACTUATOR WITH NEW 120V MOTORIZED DDC ACTUATOR.
REPLACE EXISTING DEVICE WITH NEW DEVICE CONNECTED TO BMS.
REPLACE EXISTING VALVE ACTUATOR WITN NEW 24V MOTORZIED DDC ACTUATOR.
REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REUSE AVAILABLE WIRING.
REMOVE EXISTING DEVICE. REPLACE WITH 24V TRANSFORMER.
REPLACE EXISTING DEVICE WITH NEW DIGITAL FREEZESTAT, CONNECTED TO BMS.
KEYED NOTES
MM
M 2 6
M
EP-2
3 2 B0
C
C
H LDPS-1 FZT-1
R-12 3
BI 2 1
BI
SD-1HL DPS-2
2 4
BI
1DTS-2
5 AI2
AI
RIB-1
MS
3 1 B0
CP-1
M3 4 B0
3 5 B0
DTS-1
5 ZN
AI1
M
EP-1
1 24 B0
SARA
OA
FIL
TE
R
C O
O
LI
N G
C O
IL
C V-
C H
W S
C H
W R
NONO
NC
RTU-C7 AND RTU-C8 CONTROL DIAGRAM
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-303
PHOENIX RTU-C7 AND C8
SEQUENCE, OVERVIEW
DLH
DLH
TJF
AND PARTS LIST
BID
EXISTING DAMPER ACTUATOR TO REMAIN.
EXISTING DEVICE TO REMAIN.
EXISTING VALVE ACTUATOR TO REMAIN.
REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REPLACE CONTROL WIRING.
NOT USED.
EXISTING HEATER TO REMAIN.
KEYED NOTES
MM
M
2 2
M
EP-2
3 2 B0
C
C
H LDPS-1 FZT-1
R-12 3
BI 2 1
BI STAGE-2
RIBRIB
STAGE-1
RIB
STAGE-3
SD-1 EDH-1HL DPS-2
2 4
BI
3 10 B0
3 7 B0
3 8 B0
1DTS-2
5 AI2
AI
RIB-1
MS
3 1 B0
CP-1
M3 4 B0
3 5 B0
DTS-1
5 ZN
AI1
M
EP-1
1 24 B0
SARA
OA
FIL
TE
R
C O
O
LI
N G
C O
IL
C V-
NONO
NC
AHU-1 THRU AHU-7 CONTROL DIAGRAM
AHU DDC
CONTROLLER
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-304
PHOENIX AHU-1 THRU 7
SEQUENCE, OVERVIEW
DLH
DLH
TJF
AND PARTS LIST
BID
SA
DTS-2
5 AI2
AI
MS
RIB-1
5 J11 B0
EDH-1
STAGE-1
RIB
5 J9 B0
L HDPS-2
4 1
BI
DTS-1
3 ZN
AI
RA
OA
M
CP-1J1 1
AO
M
M
NO
NC
REMOVE EXISTING PNEUMATIC
ACTUATORS AND REPLACE WITH
NEW ELECTRONIC ACTUATORS,
CONNECT TO BMS
SF-1 THRU SF-8 CONTROL DIAGRAM
SD-1
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-305
PHOENIX SF-1 THRU 8
SEQUENCE, OVERVIEW
DLH
DLH
TJF
AND PARTS LIST
BID
PL-1 GPL-3 G PL-5 G PL-6 GPL-4 G PL-2 G
EF-17 ON EF-14 ONEF-16 ON EF-18 ON EF-19 ONEF-15 ON
ON
OFF
AUTO AUTO
OFF
ON
AUTO
OFF
ON
AUTO
OFF
ON
(RTU-2)
S-2
(RTU-1)
S-1
(RTU-3)
S-3
ZONE 2
PRIMARY SMOKE PURGE PANEL
ZONE 4ZONE 1 ZONE 5ZONE 3
LOCATED IN CONTROL. ROOM B-105LOCATED IN COMM. ROOM C-110
EXISTING POWER 120VAC
EXISTING
FACP
FSCS
UPCM-1
120VAC
POWER
TRACER SUMMIT
BUILDING CONTROL UNIT
PHOENIX
BCU
DETAIL
COMM RISER
SEE PAGE 2 FOR
120VAC
POWER
PL-9 G PL-10 G PL-8 G PL-7 G PL-11 G PL-12 G
EF-16 ON EF-15 ONEF-17 ON EF-14 ON EF-18 ON EF-19 ON
MANS-7
(RTU-1)
S-8
(RTU-2)
S-9
(RTU-3)
S-10
(RTU-4)
MAN MAN MAN
AUTO AUTO AUTO AUTO AUTO
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
EXISTING POWER 120VAC
SECONDARY SMOKE PURGE PANEL
POWER
120VAC
FSCS
UPCM-8
UNIVERSAL
PROGRAMMABLE CONTROL MODULE
UNIVERSAL
PROGRAMMABLE CONTROL MODULE
REMOVE PRIMARY SMOKE PURGE
PANEL IN ITS ENTIRETY.
REMOVE SECONDARY SMOKE PURGE
PANEL IN ITS ENTIRETY.
SEQUENCE OF OPERATION - SF A1 - A8
NORMAL
OPERATION
OCCUPIED MODE
HEATING MODE
UNOCCUPIED
MODE
EMERGENCY
DURING NORMAL OPERATION EACH SUPPLY FAN SHALL BE AUTOMATICALLY CONTROLLED BY EACH INDIVIDUAL DDC SF EQUIPMENT CONTROLLER. THE INDIVIDUAL CONTROLLER AND THE DDC SYSTEM SHALL BE PROGRAMMED TO ALLOW EACH SF TO FUNCTION ACCORDING TO THE FOLLOWING SEQUENCE. EACH SF
SHALL BE PROVIDED WITH A CONTROL PANEL THAT WILL INCLUDE AT A MINIMUM:
1. H-O-A SWITCH
2. LED LIGHTS TO INDICATE THE POSITION OF THE H-O-A SWITCH
DURING OCCUPIED MODE OPERATION, THE SF SHALL RECEIVE A SIGNAL TO START FROM THE CONTROLLER OR THE BAS SYSTEM. THE NORMALLY CLOSED OA DAMPER SHALL BE OPENED AND THE RA DAMPER SHALL BE CLOSED. VERIFY THE RETURN AIR DAMPER IS CLOSED AND THE SUPPLY AIR DAMPER ARE OPEN THEN ENERGIZE THE SUPPLY AIR FAN. THE STATUS OF THE SF SUPPLY AIR FAN SHALL BE MONITORED BY A DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN. IF A FAN IS COMMANDED TO BE ENERGIZED BUT CAN NOT BE VERIFIED BY THE DIFFERENTIAL PRESSURE SWITCH, AN ALARM SHALL BE SENT TO THE BAS SYSTEM INDICATING THE FAN IS ABNORMALLY OFF. THE UNIT CONTROLS SHALL MODULATE THE OA DAMPER AND THE
RA DAMPER TO CONTROL THE RETURN AIR TEMPERATURE TO 80 DEG. F.
IF THE RETURN AIR TEMPERATURE FALLS BELOW 70 DEG. F. THE ELECTRIC HEAT SHALL BE ENGAGED TO
MAINTAIN THE RETURN AIR TEMPERATURE AT 70 DEG. F.
THE SF SUPPLY AIR FAN SHALL BE DE-ENERGIZED DURING UNOCCUPIED MODE. THE OA DAMPER SHALL BE CLOSED AND THE ELECTRIC HEAT SHALL BE DE-ENERGIZED. THE RA DAMPER SHALL BE OPENED.
UPON RECEIVING A FIRE ALARM SIGNAL FOR BUILDING A, THE UNIT SUPPLY AIR FAN SHALL BE DE-ENERGIZED, THE OA DAMPER SHALL BE CLOSED AND THE RA DAMPER CLOSED.
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-306
SMOKE CONTROL SYSTEM
SEQUENCE, OVERVIEW
DLH
DLH
TJF
AND PART LIST
BID
SMOKE ZONE 1
2. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.
3. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.
4. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE FOR FIRE DEPARTMENT OVERRIDE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.
5. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR FIRE DEPARTMENT OVERRIDE, OR FOR SYSTEM TESTING.
NOTES:
FIRE FIGHTERS SMOKE CONTROL PANEL
NOT TO SCALE
FIRE FIGHTERS SMOKE CONTROL PANEL
FOR FIRE DEPARTMENT MANUAL OVERRIDE CONTROL, AND TESTING
CONTROLS FLOW DIAGRAM
NOT TO SCALE
I/O PANEL 1
UL864
FIRE FIGHTERS
SMOKE CONTROL
PANEL
FIRE ALARM
PANEL
(BY DIV. 16)
DUCT DETECTOR
FLOW SWITCH
PULL STATION
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
BMS
FA
UL 864 FIELD
EQUIPMENT
CONTROLLER
UL 864
NETWORK
ENGINE
UL 864 FIELD
EQUIPMENT
CONTROLLER
METASYS
USER
INTERFACE
METASYS
ADS SERVER
MAINTENANCE
SMOKE CONTROL
OVERRIDE PANEL
NOTES:
1. FIRE FIGHTERS SMOKE CONTROL PANEL SHALL HAVE HIGHEST LEVEL AUTHORITY TO OVERRIDE ALL SMOKE CONTROL FUNCTIONS.
2. PROGRAMMED FIRE EVENT AND SMOKE CONTROL ACTIONS SHALL HAVE SECONDARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS.
3. MAINTENANCE SMOKE EXTRACT CONTROL PANEL SHALL HAVE TERTIARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS, WHICH SHALL
BE USED FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING DUTIES.
1. PROVIDE A UL 864 LISTED PANEL ASSEMBLY THAT PROVIDE THE FOLLOWING FUNCTIONS AND CONTROLABILITY. THIS PANEL SHALL PROVIDE OVERRIDE AUTHORITY OF ALL AUTOMATIC FIRE ALARM SMOKE CONTROL OPERATIONS FOR MANUAL USE BY THE FIRE DEPARTMENT.
PROVIDE SIGNAGE AND LOCKING KEY PER FIRE DEPARTMENT.
6. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:
H-O-A POSITION: HAND - WHITE
OFF - RED
AUTO - GREEN
ZONE STATUS: OFF - RED
ON - GREEN
FAULT - AMBER
7. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT
NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.
RTU-C1
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 2
RTU-C2
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 4
RTU-C4
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 3
RTU-C3
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 5
RTU-C5 & RTU-C6
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
PILOT LIGHT WITH LABEL, TYPICAL
MANUAL ROTARY HOA SWITCH WITH LABEL
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-307
FIREFIGHTER SMOKE
CONTROL PANEL
DLH
DLH
TJF
BID
1. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.
2. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.
3. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.
4. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR SMOKE PURGE, OR FOR SYSTEM TESTING.
NOTES:
MAINTENANCE SMOKE EXTRACT CONTROL PANEL
NOT TO SCALE
MAINTENANCE SMOKE EXTRACT CONTROL PANEL
FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING
5. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:
H-O-A POSITION: HAND - WHITE
OFF - RED
AUTO - GREEN
ZONE STATUS: OFF - RED
ON - GREEN
FAULT - AMBER
6. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT
NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.
SMOKE ZONE 1
RTU-C1
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 2
RTU-C2
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 4
RTU-C4
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 3
RTU-C3
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
SMOKE ZONE 5
RTU-C5 & RTU-C6
HAND
OFF
AUTO
OFF
ZONE STATUS
ON FAULT
PILOT LIGHT WITH LABEL, TYPICAL
MANUAL ROTARY HOA SWITCH WITH LABEL
Sheet Number:Designed By:
JOB No.100071175
Phase:
Checked By:
Date Issued:SEPTEMBER 26, 2022
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O ra ng e
Co un ty C or re ct io ns
3r d St re et
, O rla nd o, F L
100% CD
Ph oe ni x
Bu ild in g
Re pl ac em en t o f t he
S m ok e
Co nt ro l a nd B ui ld in g
Au to m at io n
Sy st
M-308
MAINTENANCE SMOKE
EXTRACT CONTROL PANEL
DLH
DLH
TJF
BID
ROOF TOP UNIT SCHEDULE - EXISTING UNITS
G
EN
ER
AL
IN
FO
R M
AT
IO
N
MARK RTU-C1 RTU-C2 RTU-C3 RTU-C4 RTU-C5 RTU-C6 RTU-C7 RTU-C8
MANUFACTURER TRANE TRANE TRANE TRANE TRANE TRANE TRANE TRANE
SA (CFM) 4650 5000 5000 5000 2370 2370 3300 4190
OA (CFM) 1880 1880 1880 1880 730 730 400 565
RA (CFM) 2770 3120 3120 3120 1640 1640 2900 3625
TOTAL AIR (CFM) 4650 5000 5000 5000 2370 2370 3300 4190
ESP (IN. WG) 1.6 1.7 1.7 1.7 1.5 1.5 1.5 1.8
TSP (IN. WG) 4.03 4.31 4.31 4.31 3.59 3.59 4.19 4.28
RPM 1487 1542 1542 1542 1876 1876 1738 1569
MOTOR HP 7.5 7.5 7.5 7.5 3 3 5 7.5
VOLTAGE 460 460 460 460 460 460 460 460
PHASE 3 3 3 3 3 3 3 3
O A
C O
O
LI
N G
C O
IL
EAT (DB/WB DEG. F.) 88/79 88/79 88/79 88/79 88/79 88/79 88/79 88/79
LAT (DB/WB DEG. F.) 55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 53/52.9 55/54.9
SENS (MBH) 69.5 69.5 69.5 69.5 27.0 27.0 15.7 20.9
TOTAL (MBH) 163.6 163.6 163.6 163.6 63.5 63.5 37.0 49.2
GPM 32.7 32.7 32.7 32.7 12.7 12.7 7.4 9.8
WPD (FT H20 MAX) 2.21 2.21 2.21 2.21 2.52 2.52 1.08 1.3
EWT/LWT (F) 45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55
AIR PD (IN H20 0.16 0.16 0.16 0.16 0.18 0.18 0.18 0.34
TO
TA
L
AI
R C
O O
LI
N
G C
O IL EAT (DB/WB DEG. F.) 67.1/61.3 67.1/61.6 67.1/61.3 67.1/61.3 68.8/62.2 68.8/62.2 72.6/62.1 72.3/62.0
LAT (DB/WB DEG. F.) 54.7/54.1 54.8/54.3 54.7/54.1 54.7/54.1 54.2/53.8 54.2/53.8 53.6/53.1 51.6/51.4
SENS (MBH) 63.6 67.6 63.6 63.6 38.1 38.1 69.0 95.4
TOTAL (MBH) 96.9 106.5 96.9 96.9 58.1 58.1 85.7 126.1
GPM 19.4 0.3 19.4 19.4 11.6 11.6 17.1 25.2
WPD (FT H20 MAX) 4.0 4.7 4.0 4.0 1.7 1.7 1.6 6.2
EWT/LWT (F) 45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55
AIR PD (IN H20 0.55 0.64 0.55 0.55 0.44 0.44 0.62 0.58
O A
FI
LT
ER
TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.
THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"
EFFICIENCY% 30 30 30 30 30 30 30 30
FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE
TO
TA
L
AI
R
FI
LT
ER
TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.
THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"
EFFICIENCY% 30 30 30 30 30 30 30 30
FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE
H
EA
TI
N
G
EQ
U
IP
M
EN
T MARK EDH-C8 EDH-C9 EDH-C10 EDH-C11 EDH-C12 EDH-C13 EDH-C14 EDH-C15
MAX CFM 4650 5000 5000 5000 2370 2370 3300 4190
EAT/LAT (DEG. DB) 56.6/85.6 57.6/86.2 57.6/86.2 57.6/86.2 58.6/85.0 58.6/85.0 66.0/80.0 65.5/80.4
TOTAL KW 43 46 46 46 17 17 15 20
VOLTS 460 460 460 460 460 460 460 460
PHASE 3 3 3 3 3 3 3 3
STAGES SCR SCR SCR SCR SCR SCR SCR SCR
NOTES 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3
NOTES
1 PROVIDE NEW JCI BAS CONTROLLER COMPATABLE WITH UL-864 SMOKE CONTROL SYSTEM FOR RTU 1, 2, 3, 4, 5, AND 6.
2 PROVIDE NEW JCI BAS CONTROLLER FOR RTU 7 AND 8
3 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.
EXHAUST FAN SCHEDULE - EXISTING EQUIPMENT
MARK EF-A1 EF-A2 EF-A3 EF-A4 EF-A5 EF-A6 EF-A7 EF-A8 EF-B9 EF-C10 EF-C11 EF-C12 EF-C13 EF-A20 EF-A21
SERVICE CAR
EXST
Y0-TECH
EXHAUST
Y0-TECH
EXHAUST
Y0-TECH
EXHAUST
Y0-TECH
EXHAUST
Y0-TECH
EXHAUST
VO-TECH
EXHAUST
Y0-TECH
EXHAUST
BLDG.B
RESTRMS NW POD NE POD SE POD SW POD BLDG A
MECH RM
FIRE PMP
ROOM
MANUF. CAR-MON GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK COOK COOK COOK COOK GREEN
HECK
GREEN
HECK
MODEL 10F GB120-4 GB120-4 GB-90-4 GB120-3 GB-70-4 GB-90-4 GB-90-4 BCF-106 135
ACEB
ACEB
ACEB
ACEB GB-90-4 GB-140-3
TYPE CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT
AIR FLOW
RATE (CFM) 1200 1000 1000 750 1300 150 750 750 410 1550 1750 1650 1600 1000 2100
STATIC PRESS
(IN. W.C) 4.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.75 0.9 0.9 0.9 0.9 0.125 0.125
MAX FAN RPM 1725 1180 1410 1410 1550 1290 1410 1410 1811 1425 1237 1469 1446 1410 1170
H.P. 2 0.25 0.25 0.25 0.33 0.25 0.25 0.25 0.25 0.5 0.5 0.5 0.5 0.25 0.33
VOLTS 460 120 120 120 120 120 120 120 120 120 120 120 120 120 120
PHASE 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NOTES 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5
NOTES
1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM
2 EXHAUST FANS EF-A1 THROUGH AND INCLUDING EF-A8 SHALL BE ENERGIZED BY EXISTING WALL SWITCH 3 EXHAUST FANS EF-A1 THROUGH EF-A8, EF-B9, EF-A20 AND EF-A21 SHALL BE MONITORED FOR STATUS AND
ABNORMAL OFF ONLY. ABNORMAL OFF SHALL GENERATE AN ALARM IN THE BAS SYSTEM.
4 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.
5 PROVIDED FOR SIZING INFORMATION ONLY.
SUPPLY FAN SCHEDULE - EXISTING EQUIPMENT
G
EN
ER
AL
IN
FO
R M
AT
IO
N
MARK SF-A1 SF-A2 SF-A3 SF-A4 SF-A5 SF-A6 SF-A7 SF-A8
SERVICE CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
CLIMATE
CHANGER
MANUF GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
GREEN
HECK
MODEL GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3
TYPE CENT CENT CENT CENT CENT CENT CENT CENT
AIR FLOW
RATE (CFM) 3300 3300 3300 3300 3300 3300 3300 3300
STATIC PRESS
(IN. W.C) 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
MAX FAN RPM 482 482 482 482 482 482 482 482
H.P. 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
VOLTS 460 460 460 460 460 460 460 460
PHASE 3 3 3 3 3 3 3 3
MARK EDH-A16 EDH-A17 EDH-A18 EDH-A19 EDH-A20 EDH-A21 EDH-A22 EDH-A23
AIR FLOW
RATE (CFM) 3300 3300 3300 3300 3300 3300 3300 3300
EAT/LAT
(DEG. F.) 52/86 52/86 52/86 52/86 52/86 52/86 52/86 52/86
TOTAL KW 16 16 16 16 16 16 16 16
VOLTS 460 460 460 460 460 460 460 460
PHASE 3 3 3 3 3 3 3 3
STAGES SCR SCR SCR SCR SCR SCR SCR SCR
NOTES 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3
NOTES
1 CONNECT ALL SUPPLY FANS TO NEW JCI BAS SYSTEM
2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.
3 PROVIDED FOR SIZING INFORMATION ONLY.
SPLIT AC UNIT SCHEDULE - EXISTING EQUIPMENT
MARK MANUF
AIR
HANDLER
MODEL
COND.
MODEL
SUPPLY FAN COOLING AIR UNIT COND.
NOTESTOTAL
CFM
OA
CFM
COND.
EAT
(DEG. F)
EVAP EAT
DB/WB
(DEG. F)
EVAP LAT
DB/WB
(DEG. F)
TOT CAP
(MBH)
SENS CAP
(MBH) STAGES MIN EER VOLTS/PH/
HZ
VOLTS/PH/
HZ
AC-A1 CU-A1 MITSUBISHI PUYA-12 PLAA-12 320 0 95 75/65 52/52 12 10.32 1 13.8 208/1/60 208/1/60
AC-A2 CU-A2
NOTES
1 CONNECT ALL EQUIPMENT TO NEW JCI BAS SYSTEM
2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.
3 PROVIDED FOR SIZING INFORMATION ONLY.
AHU SCHEDULE - EXISTING UNITS
GENERAL INFORMATION COOLING COIL HEATING EQUIPMENT
NOTESMARK MANUF.
FAN CFM ESP
(IN WG)
TSP
(IN WG)
MOTOR
HP
MOTOR
BHP
VOLTS/
PH/HZ
FAN
OUTLET
EAT
(DB/WB)
LAT
(DB/WB)
COOLING
CAPACITY
CHILLED
WATER
FLOW
RATE PRESSURE DROP CW
VALVE MARK CFM
EAT/LAT TOTAL
VOLTS PHASE STAGES
TOTAL SENS
(MBH)
TOT
(MBH)
EWT/LWT
(F.) (GPM) FLUID
(FT) AIR (IN) TYPE (DEG. F) KW
AHU-A1 TRANE 1550 750 1.5 1.84 1 0.77 460/3/60 14x14 85/71.8 56.6 98.8 45/55 19.7 3.9 0.3 2-WAY EDH-A1 1550 52/85.0 15 460 3 SCR 1,2,3 AHU-A2 TRANE 1500 750 1.5 1.82 1 0.74 460/3/60 14x14 86.1/72.3 52/51.84 56.7 98.6 45/55 19.7 3.9 0.3 2-WAY EDH-A2 1500 52/86.1 15 460 3 SCR 1,2,3 AHU-A3 TRANE 2330 1350 1.75 2.51 2 1.62 460/3/60 14x14 86.1/73.2 52/51.9 87.37 160.05 45/55 31.9 8.9 0.6 2-WAY EDH-A3 2330 52/86.1 26 460 3 SCR 1,2,3 AHU-A4 TRANE 2700 600 1.5 2.46 2.5 1.99 460/3/60 14x14 80.2/67 52/51.9 83.92 122.98 45/55 24.5 5.6 0.8 2-WAY EDH-A4 2700 52/80.2 17 460 3 SCR 1,2,3 AHU-A5 TRANE 1550 1000 2.1 2.5 1.5 0.96 460/3/60 14x14 86.9/72.8 52/51.9 60.7 103.4 45/55 24.1 2.6 0.4 2-WAY EDH-A5 1550 52/86.9 19 460 3 SCR 1,2,3 AHU-A6 TRANE 1720 800 1.5 1.82 1 0.74 460/3/60 14x14 86.3/73.2 52/51.9 57.1 104.1 45/55 20.7 4.3 0.3 2-WAY EDH-A6 1720 52/86.3 17 460 3 SCR 1,2,3 AHU-A7 TRANE 3700 1000 1.75 2.22 2 1.78 460/3/60 18x18 81.7/68.5 52/51.9 95.10 147.9 45/55 29.5 3.8 0.4 2-WAY EDH-A7 3700 52/81.7 26 460 3 SCR 1,2,3
NOTES
1 PROVIDE NEW JCI BAS CONTROLLER FOR FOR ALL AHU'S
2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.
3 PROVIDED FOR SIZING INFORMATION ONLY.
EXHAUST FAN SCHEDULE - NEW EQUIPMENT
MARK SEF-C14 SEF-C15 SEF-C16 SEF-C17 SEF-C18 SEF-C19
SERVICE NW POD
SMOKE
NE POD
SMOKE
SE POD
SMOKE
SW POD
SMOKE CNE CSW
MANUF. COOK COOK COOK COOK COOK COOK
MODEL 300
ACRUB
ACRUB
ACRUB
ACRUB
ACRUB
ACRUB
TYPE CENT CENT CENT CENT CENT CENT
AIR FLOW
RATE (CFM) 5800 5800 5800 5800 2000 2000
STATIC PRESS
(IN. W.C) 0.75 0.75 0.75 0.75 0.5 0.5
MAX FAN RPM 539 539 539 539 683 683
H.P. 1.5 1.5 1.5 1.5 0.33 0.33
VOLTS 460 460 460 460 460 460
PHASE 3 3 3 3 1 1
NOTES 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5
NOTES
1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM
2 INSTALL VFD FOR EACH EXHAUST FAN.
3 EACH FAN SHALL BE RATED FOR SMOKE CONTROL SERVICE.
4 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND
ADDITIONAL SCOPE OF WORK.
5 PROVIDED FOR SIZING INFORMATION ONLY.
CENTRAL COOLING PLANT SEQUENCE OF OPERATION
INPUTS
CHILLED WATER PLANT GENERAL
A. THE CHILLER PLANT SERVING THE PHOENIX BLDG CONSISTS OF TWO (2) AIR-COOLED SCROLL CHILLERS, CH-1 AND CH-2, PIPED IN PRIMARY-FLOW CONFIGURATION AND DESIGN TO PRODUCE CHILLED WATER AT 45°F (ADJ.). CHILLED WATER IS DISTRIBUTED TO THE BUILDING BY CONSTANT VOLUME PUMPS, CHP-1 & CHP-2, ONE PUMP PER
CHILLER. PUMPS OPERATE WITH ASSOCIATED CHILLER.
SEQUENCE OF OPERATION
A. THE CHILLERS UNIT CONTROLLER SHALL CONTROL THE OPERATION OF THE CHILLER PLANT BASED ON TIME OF DAY SCHEDULING, TIME CLOCK, OR FROM MANUAL
COMMAND FROM THE OPERATOR.
B. ON A START COMMAND FROM THE CONTROLLER, THE CHILLED WATER SYSTEM SHALL ENABLED THE LEAD CHILLER'S CHILLED WATER PUMP AND AFTER FLOW IS PROVEN AT THE CHILLED WATER BARRELS (VIA DIFFERENTIAL PRESSURE SWITCH) THE CHILLER SHALL BE ENABLED TO OPERATE.
C. THE CHILLER MICROPROCESSOR-BASED CONTROL PANEL SHALL THEN MODULATE THE COMPRESSORS TO MAINTAIN 45°F (ADJ) LEAVING CHILLED WATER SUPPLY TEMPERATURE.
D. CHILLERS, CH-1 AND CH-2, AND ASSOCIATED PUMPS, CHP-1 AND CHP-2, SHALL BE ROTATED FROM DUTY TO STAND-BY ON A WEEKLY BASIS. WHEN CHILLER OPERATION IS DISCONTINUED, THE CHILLER PUMP SHALL CONTINUE TO OPERATE FOR A PERIOD OF ONE MINUTE (ADJ.) TO REMOVE RESIDUAL REFRIGERANT CAPACITY.
E. IF THE OUTSIDE AIR TEMPERATURE DROPS BELOW 34°F (ADJ), THE CHILLED WATER PUMPS, CHP-1 AND CHP-2, SHALL ALTERNATE OPERATION FOR 30 MINUTES AT A TIME. THE PUMPS SHALL CONTINUE TO ALTERNATE OPERATION UNTIL THE OUTSIDE AIR TERMATURE REACHES 36°F (ADJ) AT WHICH TIME THE PUMPS SHALL SHUT OFF.
ALARMS
A) IF EITHER CHW PUMP FAILS TO START AFTER BEING CALLED TO OPERATE, THE CONTROLLER SHALL DISPLAY AN ALARM AND THE CONTROLLER SHALL ENABLE THE STAND-BY
CHILLER AND CHW PUMP.
B) IF CHWS TEMPERATURE RISES ABOVE PREDETERMINED SETPOINT, CONTROLLER SHALL DISPLAY AN ALARM.
C) THE CONTROLLER SHALL DISPLAY AN ALARM IF DIFFERENTIAL PRESSURE RISES ABOVE OR FALLS BELOW PREDETERMINED SETPOINTS (ADJ).
RETURNING CHILLED WATER TEMP.
LEAVING CHILLED WATER TEMP.
CHILLER (CH-1)
CHILLER (CH-2)
DIFFERENTIAL PRESSURE TRANSMITTER
CHP-1
CHP-2
OUTDOOR AIR TEMPERATURE
FLOW SWITCH (CH-1)
FLOW SWITCH (CH-2)
NOTES:
AT A MINIMUM, PROVIDE THE ABOVE POINTS OF CONTROL AND/OR MONITORING AT THE CHILLER UNIT CONTROLLER (SIMILAR TO CH530 CONTROL PANEL).1 PROVIDE ALL REQUIRED HARDWIRED INTERLOCKS BETWEEN CHILLER AND ASSOCIATED PUMPS, FLOW SWITCHES AND/OR DIFFERENTIAL PRESSURE SWITCHES TO MAINTAIN CHILLER WARRANTY. CONTRACTOR SHALL COORDINATE REQUIREMENTS WITH CHILLER MANUFACTURER .
ANALOG
SYSTEM,
DESCRIPTION
APPARATUS,
OR AREA
CHILLER PLANT POINT SCHEDULE
OUTPUTS
ALARMS
BINARY BINARY ANALOG
NOTES
AI
CH-2, EWT
T
H
DPS CH-2, LWT
AI T
CHP-2
CH-2
BO
BI START/STOP
STATUS
H
NO
AI
CH-1, EWT
T CHP-1
BO
BI START/STOP
STATUS
DPS CH-1, LWT
TAI
EXP-1
CH-1
BO
BI START/STOP
STATUS
CHWS&R
TO UNIT A
CHILLER YARD CHWS&R
TO UNIT C
MECHANICAL ROOM
CHWS
CHWR
AS-1
MAKE-UP
WATER
L
FLOW SWITCH (BY
CHILLER MFG.) NC BO
BI START/STOP
STATUS
L
PRIMARY FLOW CHILLED WATER PLANT DIAGRAM
NO SCALE M-401
H L
H L
RHTE
MP
ER
AT
UR
E
(°F
PR
ES
SU
RE
(P
SI
FL
OW
(G
PM
UN
IT
RU
N
LO
AD
A
MP
S
ST
AT
US
O N/
OF
F
FL
OW
S
TA
TU
S
(O
PE
N)
AI
R
FL
OW
ST
AT
US
O
PE
N
/ C
LO
SE
D
OP
EN
/ C
LO
SE
CH
W P
UM
P
RE
QU
ES
T
EN
AB
LE
/ D
IS
AB
LE
ST
AR
T /
S
TO
P
CH
W
P
UM
P
RE
QU
ES
T
VA
LV
E
PO
SI
TIO
N
SE
T P
OI
NT
A
DJ
US
TM
EN
T
MO
DU
LA
TIO
N
HI
A
NA
LO
G
BT
UH
LO
W
A
NA
LO
G
AL
AR
M
HI
B
IN
AR
Y
LO
W B
IN
AR
Y
SE
NS
OR
FA
IL
GENERAL NOTE:
CONTROL SCOPE FOR CHILLER PLANT INVOLVES CONNECTING
EXISTING CHILLERS AND CHILLED WATER PUMPS TO THE NEW
BAS SYSTEM AND PROGRAMMING THE SEQUENCE OF OPERATION.
ALL CONTROL DEVICES SHOWN ON THE CHILLED WATER PLANT
DIAGRAM ARE EXISTING-TO-REMAIN AND SHALL BE FIELD VERIFIED
B…