OAS 2.5 User Manual (Final) (4).pdf
PDF 2 MB Posted
- Attached to
- QPK HVAC Replacement Federal contract opportunity
- Solicitation number
- 697DCK-25-R-00183
About this file
The OAS 2.5 User's Manual is a comprehensive technical document for the Overtemp Automated System (OAS), a specialized HVAC controller designed for critical FAA facilities. The manual details the system's key features, including redundant control of two HVAC units, automatic unit switchover, adjustable set points, system status lights, audible and visual alarms, and compatibility with ERMS. The controller uses Honeywell VisionPro thermostats and is configured for cooling-only operation, with specific installer setup instructions for both primary (T1) and emergency change-over (T2) thermostats.
The manual provides detailed guidance on installation, electrical requirements, wiring connections, operational states, and troubleshooting. It includes a parts list with specific component details, such as the Honeywell VisionPro thermostat (HW-TH8321-R1001) and optional wireless remote sensors. The document also contains comprehensive appendices with thermostat configuration instructions, relay operation checks, and schematic diagrams, making it a critical reference for technicians responsible for maintaining HVAC systems in FAA equipment rooms.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI Attachment 2 - RFI Site Visit Attendance QPK HVAC Replacement FINAL.pdf | ||
| RFI Attachment 1 - FAA Tax Exempt Letter 2022.pdf | ||
| RFIs - 697DCK-25-R-00183 QPK HVAC Replacement FINAL.pdf | ||
| 697DCK-25-R-00183.pdf | ||
| Wage Determination - CO20250016 020725.pdf | ||
| M001(I) Drawing_QPK_Rev F_Final 05302024.pdf | ||
| M001(I) Drawing_QPK_Rev F_Final.pdf | ||
| SUMMARY OF WORK_Rev C_Final.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OAS
2.5 Version 2/19/2018
OAS
2.5
User’s Guide
OAS
2.5 User’s Manual
Table of Contents
General Information
Manufacturer
Definitions
Quick Reference
Installation
5.1 Physical Installation
5.2 Electrical Requirements
5.3 Connections
Operation
6.1 Introduction
6.2 User Inputs
6.3 System Status Lights
6.4
Operational States
6.5
Sequence of Operations
Troubleshooting
Parts List
Schematics
Appendixes
A Thermostat Setup
B
OAS
Functional Test
OAS
2.5 User’s Manual
Table of Contents
General Information
Manufacturer
Definitions
Quick Reference
Installation
5.1 Physical Installation
5.2 Electrical Requirements
5.3 Connections
Operation
6.1 Introduction
6.2 User Inputs
6.3 System Status Lights
6.4
Operational States
6.5
Sequence of Operations
Troubleshooting
Parts List
Schematics
Appendixes
A Thermostat Setup
B
OAS
Functional Test
OAS
2.5 User’s Manual
General Information:
This user manual is intended to accompany the
OAS
2.5
HVAC
Controller.
The
OAS
HVAC
controller is a
FAA
designed
HVAC
controller for use at critical
FAA
facilities that require reliable redundant
HVAC
control.
The
OAS
is a simple yet robust control system which captures specific operational criteria important to
NAS
equipment.
Some of these features are listed below:
1. Redundant control of
HVAC
Units
2. Primary Unit Selection
3. Adjustable Set Points
4. Automatic Unit Switch Over
5. System Status Lights
6. Audible and Visual Alarms
7. Audible Alarm Silence
8. Simplified Troubleshooting
9. Commercially Available Replacement Parts
10. Ease of Use and Reparability
11. ERMS
compatibility
Manufacturer Information:
The
OAS
2.5 was designed by
NDP
Infrastructure Engineering (Jonathan Salter, 202.744.1408) and manufactured by:
The
FAA
National Staging Area
(AJW-‐2C15P)
S.
Geospace Dr
Independence, MO
64056
Ph:
(816) 329-‐3970 http://stagingarea.faa.gov
OAS
2.5 User’s Manual
Definitions:
Dehumidify
The mechanical process of reducing the air humidity.
OAS
Overtemp Automated System
FAA
specific controller that provides control to a Unit, fully redundant
HVAC
system.
These systems are typically associated with unoccupied electrical equipment rooms.
Overtemp Condition where the room temperature becomes greater than what is considered acceptable for a normally operating
HVAC
Unit.
An Overtemp situation indicates that the selected
HVAC
Unit is not functioning properly.
Set Point
The manually inputted temperature setting for an associated thermostat.
Relay
Electronic device that when activated, allows current to pass through.
Room Temperature Actual Current Temperature of the Equipment Room as measured by the
OAS.
OAS
2.5 User’s Manual
OAS
Quick Reference:
Figure 1:
OAS
Quick Reference
Alarm:
Red Visual
Alarm Light and
Audible Alarm
System Status Lights
Indicate the presence of Control Power and a call for operation for both
HVAC
Units
Room Temperature
Control Thermostat
(T1) Provides Control to the Active
HVAC
Unit.
Setpoint input for the desired room temperature
Room Overtemp
Thermostat (T2)
Setpoint input for the overtemp switchover
Primary Unit Selector
Switch Manual control point for the selection of the desired primary Unit
Audible Alarm Silence
When the controller is in Alarm, this button silences the audible alarm tone.
Overtemp Reset
Button Resets the
Controller from an
Alarm
OAS
2.5 User’s Manual
Installation:
5.1 Physical Installation:
The
OAS
is contained within a 10”x16”x5” electrical box.
The box contains mounting holes for attaching the box to a supporting wall or stand.
The controller should be mounted at chest level in a central location where the ambient temperature is representative of the room.
Locating the unit on an uninsulated outside wall, near equipment exhaust, or in a stagnant air area may cause the system to operate inefficiently.
If space is not available for the
OAS
in a preferred location, a separate remote temperature sensor option can be added.
of these sensors are required, one for each thermostat on the
OAS.
The sensors must be setup within the thermostat settings.
Use of remote sensors should be limited to the greatest extent possible.
Buttons, thermostats and switches shall be accessible and warning light shall be generally visible within the associated room.
Allow for 3’ of clearance from the face of the control box per the latest revision of the
NEC.
5.2 Electrical Requirements:
All requirements of the most current revisions of
FAA-‐STD-‐19
and
FAA-‐C-‐1217
shall be followed.
All associated control wires run between the Controller and
HVAC
Units shall be contained within conduits.
Any outdoor conduit runs shall be rigid type with threaded connections or liquid-‐tite flexible conduit.
The
OAS
is powered by low voltage
24VAC,
supplied by the associated
HVAC
Units.
To fully isolate power from the controller, each
HVAC
must be electrically disconnected.
The
OAS
does not require a separate power circuit and the only energized power within the controller will be the
24VAC
provided from the
HVAC
Units.
Warning:
When attaching or changing wired connections within the
OAS,
ensure power is electrically isolated from
BOTH
HVAC
Units.
Failure to do so may cause sparks, damage to the
OAS,
damage to the
24VAC
Transformers in the
HVAC
units, and/or personal injury.
OAS
2.5 User’s Manual
Installation:
5.1 Physical Installation:
The
OAS
is contained within a 10”x16”x5” electrical box.
The box contains mounting holes for attaching the box to a supporting wall or stand.
The controller should be mounted at chest level in a central location where the ambient temperature is representative of the room.
Locating the unit on an uninsulated outside wall, near equipment exhaust, or in a stagnant air area may cause the system to operate inefficiently.
If space is not available for the
OAS
in a preferred location, a separate remote temperature sensor option can be added.
of these sensors are required, one for each thermostat on the
OAS.
The sensors must be setup within the thermostat settings.
Use of remote sensors should be limited to the greatest extent possible.
Buttons, thermostats and switches shall be accessible and warning light shall be generally visible within the associated room.
Allow for 3’ of clearance from the face of the control box per the latest revision of the
NEC.
5.2 Electrical Requirements:
All requirements of the most current revisions of
FAA-‐STD-‐19
and
FAA-‐C-‐1217
shall be followed.
All associated control wires run between the Controller and
HVAC
Units shall be contained within conduits.
Any outdoor conduit runs shall be rigid type with threaded connections or liquid-‐tite flexible conduit.
The
OAS
is powered by low voltage
24VAC,
supplied by the associated
HVAC
Units.
To fully isolate power from the controller, each
HVAC
must be electrically disconnected.
The
OAS
does not require a separate power circuit and the only energized power within the controller will be the
24VAC
provided from the
HVAC
Units.
Warning:
When attaching or changing wired connections within the
OAS,
ensure power is electrically isolated from
BOTH
HVAC
Units.
Failure to do so may cause sparks, damage to the
OAS,
damage to the
24VAC
Transformers in the
HVAC
units, and/or personal injury.
OAS
2.5 User’s Manual
5.3 Connections:
The
OAS
controller has connections identical to most modern thermostats, and therefore wiring the controller is similar.
Each installation may vary slightly, however the basic premise remains the same.
Inside the box, there are separate terminal strip areas, one for each unit.
They should appear similar to the picture below:
Figure 2:
OAS
Wiring Terminals
These connections are in accordance with industry standard, and are compatible with the vast majority of
HVAC
equipment.
The symbols are defined below for reference:
Symbol Description Standard Wire Color
R Control Power
(24VAC)
from associated
HVAC
Unit Red
Y1 Stage Cooling, control point Yellow
Y2 Stage Cooling, control point Blue
W Heat, control point White
G Fan (Supply Air Blower) Green
C Common or Neutral Brown
Wire colors and symbols may vary slightly depending on manufacturer
A single line diagram is shown on the next page for a simple packaged unit installation.
Each facility should be provided with a site specific control drawing that depicts the actual configuration.
The diagram contained in this manual shall be used for reference only.
Unit
Connections
Unit
Connections
OAS
2.5 User’s Manual
Figure 3:
Typical Control Wiring
OAS
2.5 User’s Manual
Operation:
6.1 Introduction:
The
OAS
is delivered configured, tested, and ready for the operation of a Unit, fully redundant, dual stage, cooling only, HVAC
System.
However, if a thermostat is replaced or for some other reason the thermostat needs to be reset, the required parameters are provided in “Appendix A” to assist in reprograming.
The
OAS
utilizes the Honeywell VisionPro Thermostat.
This model has a touch screen, and provides various capabilities that allow the
OAS
to be more robust and flexible while also providing a simple operational interface.
The diagram below explains the basic operation of this thermostat:
Figure 4:
Thermostat Quick Reference
Heating:
If the associated
HVAC
system includes heat, the
SYSTEM
setting on T1 (upper thermostat) only can be changed to “Auto”.
In this setting, the
OAS
will provide automatic switchover from cooling and heating as needed on the active unit.
The T2
(lower thermostat)
SYSTEM
setting must always be set to “Cool” regardless of the system configuration.
Current
Temperature
FAN
Menu Sets fan mode.
Set to
“On”
SYSTEM
Menu
Sets System
Setting.
Default is
“Cool”
Current System
Mode
Set Point
Adjusted with Up
Down Arrows
OAS
2.5 User’s Manual
6.2 User Inputs:
The
OAS
Controller has basic inputs:
Room Set Point The Desired Room Temperature To set, adjust the set point of the T1 (upper) thermostat.
This will be the temperature that the
OAS
will try to maintain the room at within a few degrees.
Recommended Set Point:
70°
Overtemp Set Point The Unit Failure Temperature To set, adjust the set point of the T2 (lower) thermostat.
This will be the temperature where the controller assumes the selected primary unit has failed, and will switch to the back-‐up unit.
Recommended Set Point:
80°
Primary Unit Selection The Unit that will operate as Primary To set, move the selector switch to the desired unit number.
Whichever unit is selected will be the operational unit unless the
OAS
is in Alarm.
To ensure similar run times on both
HVAC
Units, this selector switch should be toggled at regular intervals.
Recommended Interval:
Monthly
Care should be taken in selecting the Room and Overtemp Set Points.
Selecting a Room Temperature that is too low may result in Unit failure.
Additionally, selecting an Overtemp Temperature that is too close to the Room Temperature set point may cause the
OAS
to alarm during normal operation.
To prevent these issues, do no set the Room Temperature below 68°, and ensure the Overtemp Set Point is at least 6° higher than the Room Set Point.
6.3 System Status Lights:
There are status lights on the
OAS
which are intended to provide quick visual information to the user.
The lights are split up by
HVAC
Units so there are statuses shown per unit.
An illuminated power light indicates that the associated
HVAC
Unit is providing control voltage.
An illuminated Run Light indicates that the associated
HVAC
unit is active.
This light does not indicate that the unit is actually cooling, only that if cooling is called for, this is the unit that should cool.
Under normal operation, the Power lights for each unit should be illuminated, and the
Run light for the selected primary unit should be illuminated.
UNIT
UNIT
POWER
RUN
OAS
2.5 User’s Manual
6.4 Operational States:
Normal Operation:
The T1 (upper) thermostat will control the selected primary unit directly.
Only the primary unit will be allowed to run and maintain the room at the Room Set
Point.
Unit Failure:
If the primary unit fails for any reason, it will not be able to maintain the Room
Set Point.
Once the room temperature climbs above the Overtemp Set Point, the
OAS
will alarm.
During alarm, a red light will illuminate on top of the controller, the Alarm
Silence button will illuminate, and a loud alarm tone will sound from the controller.
When in alarm, the
OAS
will shutdown the selected primary unit, and T1 will begin controlling the back-‐up unit directly.
Only the back-‐up unit will be allowed to operate.
Since T1 is now controlling the back-‐up unit, the room temperature should return back to the Room Set Point.
Alarm Silence
To silence the audible alarm, press the Alarm Silence button once.
The red alarm light on the top of the controller and the light in the Alarm Silence button will remain illuminated.
Reset:
To reset the
OAS
controller from an alarm condition, press the Reset Button.
This will resume normal operation of the
OAS
controller.
If the room temperature is above the Overtemp Set Point, the Reset button will not function.
The room temperature must be below the Overtemp Set Point to reset.
Note:
The
OAS
does not monitor specific conditions in each
HVAC
unit and an alarm only indicates that the
Temperature in the room exceeded the Overtemp Set Point while the selected primary unit was active.
Upon an alarm, a technician should perform a deeper evaluation into why the selected unit was not able to maintain the Room Set Point.
OAS
2.5 User’s Manual
6.4 Operational States:
Normal Operation:
The T1 (upper) thermostat will control the selected primary unit directly.
Only the primary unit will be allowed to run and maintain the room at the Room Set
Point.
Unit Failure:
If the primary unit fails for any reason, it will not be able to maintain the Room
Set Point.
Once the room temperature climbs above the Overtemp Set Point, the
OAS
will alarm.
During alarm, a red light will illuminate on top of the controller, the Alarm
Silence button will illuminate, and a loud alarm tone will sound from the controller.
When in alarm, the
OAS
will shutdown the selected primary unit, and T1 will begin controlling the back-‐up unit directly.
Only the back-‐up unit will be allowed to operate.
Since T1 is now controlling the back-‐up unit, the room temperature should return back to the Room Set Point.
Alarm Silence
To silence the audible alarm, press the Alarm Silence button once.
The red alarm light on the top of the controller and the light in the Alarm Silence button will remain illuminated.
Reset:
To reset the
OAS
controller from an alarm condition, press the Reset Button.
This will resume normal operation of the
OAS
controller.
If the room temperature is above the Overtemp Set Point, the Reset button will not function.
The room temperature must be below the Overtemp Set Point to reset.
Note:
The
OAS
does not monitor specific conditions in each
HVAC
unit and an alarm only indicates that the
Temperature in the room exceeded the Overtemp Set Point while the selected primary unit was active.
Upon an alarm, a technician should perform a deeper evaluation into why the selected unit was not able to maintain the Room Set Point.
OAS
2.5 User’s Manual
6.5 Sequence of Operation:
OAS
2.5 User’s Manual
Troubleshooting:
Problem
Check Condition Potential Cause Corrective Action
Power light is not illuminated for a unit.
(If power light is not illuminated for the backup unit, make the backup unit the primary and perform these steps.
If the power light illuminates in only one mode, perform the
System Test in App B)
• 24VAC
present at the R terminal for the associated
Unit?
• 24VAC
is present at R terminal
• Lose Connection
Check
Connections within the
OAS
to ensure there are no loose wires or short circuits
• Tighten and/or secure loose connections as needed.
• Bad Relay
Perform System
Test in Appendix B to ensure all
Relays are operational
• Replace Defective
Relay (see parts list)
• Bad
LED
Check
LED
operation by applying
24VAC
across contacts.
• Replace
LED
bulb
(see parts list)
• 24VAC
is not present at R terminal
• Unit is electrically isolated.
• Check breakers and disconnects for the associated Unit.
• Check Associated
Unit Control
Power
24VAC
output
Measured between terminals R and C terminals in the
Unit.
• Check control transformer for a fuse or built in circuit breaker.
If no
CB
or fuse are present, and transformer is not outputting
24VAC,
Replacement of the transformer may be required.
Run light is not illuminated for the selected unit.
• Is
OAS
is in Alarm?
OAS
is in Alarm.
• When in Alarm, the “Run Light” should be illuminated for the back-‐up Unit and not the selected Unit.
• Reset
OAS
and troubleshoot the selected unit.
• Is the
FAN
setting on T1 set to “On”?
• FAN
Setting set to
“Auto”.
• The Run light is tied directly to the call for indoor fan.
In “Auto” setting, the Run light will only illuminate during a call for cooling.
• It is recommended that the fan be run continuously on the active Unit.
Change
T1
FAN
Setting to
“On”.
FAN
Setting set to
“On”
• Bad
LED
Check
LED
operation by applying
24VAC
across contacts.
• Replace
LED
bulb
(see parts list)
OAS
2.5 User’s Manual
Problem Check Condition Potential Cause Corrective Action
Sporadic clicking sounds while opening the
OAS
Panel
N/A
• Relays are engaging/disengaging randomly as
OAS
door is moving.
• Short or loose connection in
Wiring Bundle between panel door and relay board
• Inspect for loose connections and repair as needed.
• Request
Replacement
Controller from
Staging Area.
OAS
is in Alarm and will not reset
Is Room
Temperature above
Overtemp Setpoint
(T2)?
• Room Temperature is above Overtemp
Setpoint.
• OAS
Alarm cannot be reset when the conditions would immediately put it back into Alarm.
• Alternate Units, ventilate, and/or add temporary cooling to bring down the room temperature.
• Room Temperature is below Overtemp
Setpoint.
• T2 may be in a time delay function
• Allow some time for T2 to reset (5 minutes max) and retry.
Upper thermostat
(T1) isn’t functioning.
Is the Power Light illuminated for the selected unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the selected unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
Lower thermostat
(T2) isn’t functioning.
Is the Power Light illuminated for the back-‐up unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the backup unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
OAS
2.5 User’s Manual
Problem Check Condition Potential Cause Corrective Action
Sporadic clicking sounds while opening the
OAS
Panel
N/A
• Relays are engaging/disengaging randomly as
OAS
door is moving.
• Short or loose connection in
Wiring Bundle between panel door and relay board
• Inspect for loose connections and repair as needed.
• Request
Replacement
Controller from
Staging Area.
OAS
is in Alarm and will not reset
Is Room
Temperature above
Overtemp Setpoint
(T2)?
• Room Temperature is above Overtemp
Setpoint.
• OAS
Alarm cannot be reset when the conditions would immediately put it back into Alarm.
• Alternate Units, ventilate, and/or add temporary cooling to bring down the room temperature.
• Room Temperature is below Overtemp
Setpoint.
• T2 may be in a time delay function
• Allow some time for T2 to reset (5 minutes max) and retry.
Upper thermostat
(T1) isn’t functioning.
Is the Power Light illuminated for the selected unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the selected unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
Lower thermostat
(T2) isn’t functioning.
Is the Power Light illuminated for the back-‐up unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the backup unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
OAS
2.5 User’s Manual
Parts List:
QTY
Description Make/Model Part No
EA
Thermostat Honeywell VisionPro
HW-‐TH8321-‐R1001
AS
Selector Switch Eaton Switch
EA
10250T3011
Contact
EA
10250T1
EA
Indicator Lights Grainger 24M067
AS
Push Button (Alarm Silence)
ABB
Button
EA
MP1-‐31R
Contact
EA
MCBH-‐01
LED
EA
MLBL-‐01R
AS
Push Button (Reset)
ABB
Button
MP1-‐30R
Contact
MCBH-‐01
EA
Relay
IDEC
RH-‐4B-‐UL
AC24V
Optional Parts:
QTY
Description Make/Model Part No
EA
Wireless Remote Sensors Honeywell C7189R
OAS
2.5 User’s Manual
Schematics:
OAS
2.5 User’s Manual
OAS
2.5 User’s Manual
Appendix A
Appendix A
T1 (Top):
Installer Setup:
Application Commercial Thermostat Name Thermostat Zoned No Equipment Module No Connect Redlink No Installer Setup
NEXT
Thermostat Type Non-‐ Programmable Temperature Scale Fahrenheit Outdoor Air Sensor No Heating System None (Cool Only) Cooling Stages A-‐L/A Terminal None Control Options Basic Cool/Compressor
CPH
Stg Cool/Compressor
CPH
Stg Compressor Off time Off Extended Fan Run Time in Cool Off Min Cool Setpoint Keypad Lockout Unlocked Wired Sensor on S Terminal No Filter Type:
Media Number of Filters Air Filter Reminder Off Humidifier Type None Humidifier Pad Reminder Off Dehumidifier None Defumidifier Filter Reminder Off Ventilation Type None Ventilation Filter Reminder Off Number of
UV
Devices None Custom Reminder
NEXT
Backlighting On Demand Clock Format 12hr Daylight Savings Time Off Indoor Temp Offset Indoor Humidity Offset Alert Light Indicator On Dealer Name
NEXT
Dealer Phone
NEXT
Dealer Email
NEXT
Dealer Website
NEXT
Dealter Message
NEXT
DONE
Exit Installer Setup
YES
T2 (Bottom):
Installer Setup:
Application Commercial Thermostat Name Thermostat Zoned No Equipment Module No Connect Redlink No Installer Setup
NEXT
Thermostat Type Non-‐ Programmable Temperature Scale Fahrenheit Outdoor Air Sensor No Heating System None (Cool Only) Cooling Stages A/L/A Terminal Off Control Options Basic Cool/Compressor
CPH
Stg Compressor Off time Off Extended Fan Run Time in Cool Off Min Cool Setpoint Keypad Lockout Unlocked Wired Sensor on S Terminal No Filter Type:
Media Number of Filters Air Filter Reminder Off Humidifier Type None Humidifier Pad Reminder Off Dehumidifier None Defumidifier Filter Reminder Off Ventilation Type None Ventilation Filter Reminder Off Number of
UV
Devices None Custom Reminder
NEXT
Backlighting On Demand Clock Format 12hr Daylight Savings Time Off Indoor Temp Offset Indoor Humidity Offset Alert Light Indicator On Dealer Name
NEXT
Dealer Phone
NEXT
Dealer Email
NEXT
Dealer Website
NEXT
Dealter Message
NEXT
DONE
Exit Installer Setup
YES
Main Screen Settings:
SYSTEM:
COOL
FAN:
ON
OAS
2.5 User’s Manual
B
Appendix B
Relay Operation Check:
Note:
This test confirms the proper operation of the
OAS
controller.
This test is best performed using isolated
24VAC
power sources as shown below.
Test can be performed using control power from the
HVAC
Units, but this test will cause non-‐continuous operation of the units, so care must be taken to ensure the equipment space remains at a desirable temperature.
During Test, note any inconsistencies from the expected checks and utilize this information for troubleshooting faulty components or other issues.
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B