Oakland County Tower Modification R5.pdf
PDF 3 MB Posted
- Solicitation number
- RFP-171-180000002872-1
- Issued by
- Oakland County, Michigan
About this file
This is a technical engineering drawing package prepared by EET, LLC for tower modifications to an Oakland County communications tower located at the Pontiac Social Services site in Michigan. The drawings detail modifications required for five sections of a 285-foot self-supporting tower, including converting X-bracing assemblies to C-shape assemblies in sections T5 (230-250 ft), T6 (210-230 ft), and T9 (160-170 ft), reinforcing diagonals in section T15 (50-70 ft), and reinforcing redundant horizontals in section T17 (0-30 ft). The 16-page drawing set, dated January/June 2018, includes detailed fabrication specifications, assembly details, and parts lists for all modification components.
The modifications require various galvanized steel angles, bolts, washers, nuts, and V-clamp assemblies. Key components include 120 5" V-clamps, multiple reinforcement angles ranging from 2"x2"x1/8" to 3"x3"x1/4", and hundreds of galvanized fasteners. The drawings emphasize critical safety notices regarding structural stability during modification work, requiring temporary bracing and adherence to TIA-322 and ASSE 10.48 standards for rigging plans. All steel must meet ASTM A-36 specifications with hot-dip galvanizing per ASTM A123, and field modifications must maintain minimum edge distances and coating requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Standard Contract Terms - SHORT FORM SIGMA - 180000002872.docx | DOCX document | |
| Proposal Instructions and Vendor Questions Worksheet - 180000002872.docx | DOCX document | |
| As the Pontiac tower is today 7-5-17.pdf | ||
| Schedule B - Pricing - 180000002872.docx | DOCX document | |
| State of Michigan Oakland County Pontiac MI 3-29-2018 SAR CERTIFIED.pdf | ||
| Schedule A - Prof Services Pontiac Mods and Antennas.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
MODIFICATION SUMMARY
SECTION
FROM (ft.) TO (ft.)
MODIFICATION DESCRIPTION SHEET NUMBER
T5 230 250 CONVERT TO C-SHAPE ASSEMBLY 14-16
T6 210 230 CONVERT TO C-SHAPE ASSEMBLY 11-13
T9 160 170 CONVERT TO C-SHAPE ASSEMBLY 8-10
T15 50 70 REINFORCE DIAGONAL 6-7
T17 0 30 REINFORCE REDUNDANT HORIZONTALS 4-5
NOTES:
1. MODIFICATIONS PER EET, LLC REPORT DATED 9-29-2018 SEE SHEET 1 FOR SUMMARY
2. THIS DOCUMENT DOES NOT CONSTITUTE A CONSTRUCTION DOCUMENT. A RIGGING PLAN IN ACCORDANCE WITH ASSE 10.48
AND TIA-322 SHALL BE CREATED PRIOR TO INSTALLATION OF THE MODIFICATIONS OUTLINED IN THIS DRAWING.
3. THE MODIFICATION MEMBER LENGTHS LISTED ARE BASED UPON THEORETICAL MEMBER DATA AND/OR FIELD MEASUREMENTS
OF MEMBERS. ADDITIONAL FIELD MODIFICATION OF MEMBERS MAY BE REQUIRED TO MATCH THE ORIGINAL AS BUILT
MEMBER LENGTHS. ADDITIONAL TOWER MODIFICATIONS MAY BE REQUIRED IF THE AS BUILT CONDITIONS DIFFER FROM THE
ASSUMPTIONS USED TO CREATE THE ORIGINAL EET, LLC REPORT REFERENCED ABOVE. FIELD CUTS MAY BE REQUIRED AS
INDICATED. FIELD DRILLING OF REINFORCEMENT HOLES IS REQUIRED. SEE FABRICATION SHEETS FOR THESE LOCATIONS.
FIELD DRILL HOLES IN REINFORCEMENT ANGLES ADJACENT TO THE TOWER LEG MAY BE MOVED TO AVOID CONFLICT WITH THE
TOWER LEG DIAGONAL ATTACHMENT PLATE. A MINIMUM OF 1" OF EDGE DISTANCE IS REQUIRED. SEE SHEET 3 FOR DETAILS.
4. ALL STEEL FABRICATION AND INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE AMERICAN INSTITUTE OF STEEL
CONSTRUCTION MANUAL AND SPECIFICATIONS.
5. ALL STEEL ANGLE SHALL CONFORM TO ASTM A-36 STEEL SPECIFICATIONS - MIN. YIELD STRENGTH 36 KSI. ALL BOLTS, WASHERS AND NUTS SHALL CONFORM TO THE INDICATED ASTM SPECIFCATIONS.
6. STRUCTUAL MATERIAL SHALL NOT BE HEATED FOR STRAIGHTENING BENT OR WARPED MEMBERS.
7. THE FINISHED BOLT HOLE DIAMETERS SHALL NOT BE MORE THAN 1/16TH INCH LARGER THAN THE NOMINAL BOLT DIAMETER
UNLESS OTHERWISE NOTED.
8. ALL BOLTS SHALL BE NEW DOMESTIC UNLESS OTHERWISE NOTED.
9. ALL BOLTS SHALL BE TIGHTENED USING THE AISC TURN OF THE NUT METHOD
10. ALL STRUCTURAL STEEL SHALL BE HOT DIPPED GALVANIZED PER ASTM A123 SPECIFICATIONS AFTER FABRICATION.
11. FASTENERS AND HARDWARE SHALL BE GALVANIZED IN ACCORDANCE WITH ONE OF THE FOLLOWING:
ASTM A153, ASTM F2329, ASTM B695 CLASS 55
12. ALL FIELD INSTALLED HOLES SHALL BE DRILLED. ALL EXPOSED BARE OR DAMAGED MATERIAL SHALL BE COATED
WITH ZINGA OR SIMILAR MATERIAL. ANY DAMAGER
13. ALL INSTALLATION PROCEDURES AND SAFEGUARDS ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR/INSTALLER.
14. CONTACT THE ENGINEER IF ANY CHANGES, MODIFICATION OR ALTERATION OF THE INSTALLATION OUTLINED DUE
TO EXISTING CONDITIONS.
15. THE EXISTING STRUCTURE SHALL BE INSPECTED PRIOR TO MODIFICATION TO CONFIRM ITS CONDITION IS ACCEPTABLE
PER TIA REQUIREMENTS.
STATE OF
MICHIGAN
STATE OF
MICHIGAN
TOWER MODIFICATIONS
285' SS TOWER - PONTIAC SOCIAL SERVICES SITE
OAKLAND COUNTY
MASTER BOM
QTY.
PART NUMBER DESCRIPTION
120 10592 5" V-CLAMP
120 10599 ANGLE V-CLAMP WELDMENT
6 11005
UPPER REDUNDANT HORIZONTAL REINFORCEMENT 2" X 2" X 1/8" GALVANIZED STEEL ANGLE - SECTION T17
6 11006
LOWER REDUNDANT HORIZONTAL REINFORCEMENT 2" X 2" X 1/8" GALVANIZED STEEL ANGLE - SECTION T17
6 11008
DIAGONAL REINFORCEMENT 3" X 3" X 1/4" GALVANIZED STEEL ANGLE - SECTION T15
6 11009 T9 SECTION UPPER REINFORCEMENT ANGLE
6 11013 T6 LOWER REINFORCEMENT ANGLE
6 11016 T6 MIDDLE REINFORCEMENT ANGLE
6 11017 T6 UPPER REINFORCEMENT ANGLE
6 11018 T5 LOWER REINFORCEMENT ANGLE
6 11019 T5 MIDDLE REINFORCEMENT ANGLE
6 11020 T5 UPPER REINFORCEMENT ANGLE
3 11011
5/8" DIA. X 2" LONG A-325 GALVANIZED BOLT
3 11015
5/8" DIA. A-563 GRADE DH HEAVY HEX GALVANIZED NUT
3 11014
5/8" DIA. F436 GALVANIZED WASHER
18 11012
1/2" DIA. X 2" LONG GRADE 5 GALVANIZED BOLT
96 11004
1/2" DIA. X 4" LONG A-325 GALVANIZED BOLT - SECTION T17
144 11007A
1/2" DIA. X 6.5" LONG GRADE 5 GALVANIZED BOLT - SECTION T15
258 11002
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT
258 11003
1/2" DIA. F436 GALVANIZED WASHER
264 11034
3/8" DIA. X 1.00" LONG SAE GRADE 5 GALVANIZED BOLT
264 11032
3/8" DIA. F436 GALVANIZED WASHER
264 11033
3/8" DIA. GRADE B GALVANIZED HEX NUT
REVISION HISTORY
REV DESCRIPTION DATE
4 ADDED SHOP DIMENSION
6/12/2018
5 REPLACED 11007 WITH 11007A
6/13/2018
DETAIL BF
EDGE DETAILS NOTED IN THIS
VIEW ARE APPLICABLE
TO SECTIONS T9, T6 AND T6
DETAIL BG
TYPICAL ALL
CENTER BOLTS
DETAIL BH
TYPICAL BOTTOM DETAIL
DETAIL BJ
TYP. TOP DETAIL
SECTION BK-BK
TYPICAL ANGLE CROSS
SECTION DETAIL
BF
BG
BH
BJ
BK
BK
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
4 in AS DRAWN
6" MAX.
4 in AS DRAWN
6" MAX.
REPLACE EXISTING
CENTER BOLT
AT INTERSECTIONS
OF TOP "X" IN SECTION T9
AND ALL INTERSECTIONS
IN SECTION T6 AND T5
REUSE EXISTING SPACER
SEE SECTION PROFILES
FOR BOLT DETAILS
FIELD FABRICATION AND
INSTALLATION DETAILS
4 in AS DRAWN
6" MAX.
REINFORCEMENT
ANGLE
4 in AS DRAWN
6" MAX.
EXISTING ANGLE
REINFORCING
ANGLE
DETAIL A
UPPER REDUNDANT HORIZONTAL
DETAIL B
LOWER REDUNDANT HORIZONTAL
DETAIL G
CLAMP ASSEMBY
SEE SHEET 3
A
B
G
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
36'-0"
32'-8 3/4"
29'-11 1/4"
MODIFICATIONS REQURIED TO BE APPLIED TO SECTION T17:
FROM 0' AGL TO 30' AGL
ADD ANGLE REINFORCEMENT TO UPPER
AND LOWER REDUNDANT HORIZONTALS
ALL THREE FACES
CLAMP ON 2" X 2" X 1/8" ANGLE TO
REDUNDANT HORIZONTALS AS SHOWN WITH
A MAXIMUM CLAMP SPACING
OF 30" CENTER TO CENTER.
M a x i m u m s p a c i n g
REDUNDANT
HORIZONTAL
2" X 2" X 1/8"
GALVANIZED ANGLE
(3) CLAMPS MIN.
REDUNDANT HORIZONTAL
2" X 2" X 1/8" GALVANIZED ANGLE
(5) CLAMPS MINIMUM
UPPER REDUNDANT HORIZONTAL PARTS LIST PER KIT
DESCRIPTIONPART NUMBER
TOTAL
REQUIRED
THIS
SECTION
QTYITEM
ANGLE V-CLAMP WELDMENT105993051
5" V-CLAMP105923052
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT1100260103
1/2" DIA. F436 GALVANIZED WASHER1100360104
1/2" DIA. X 4" LONG A-325 GALVANIZED BOLT1100460105
2" X 2" X 1/8" STEEL A-36 STEEL ANGLE1100561T17-U-A
LOWER REDUNDANT HORIZONTAL PARTS LIST PER KIT
DESCRIPTIONPART NUMBER
TOTAL
REQUIRED
THIS
SECTION
QTYITEM
ANGLE V-CLAMP WELDMENT105991831
5" V-CLAMP105921832
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT110023663
1/2" DIA. F436 GALVANIZED WASHER110033664
1/2" DIA. X 4" LONG A-325 GALVANIZED BOLT110043665
2" X 2" X 1/8" A-36 STEEL ANGLE GALVANIZED1100661T17-L-A
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
SECTION T17 FROM BASE TO 30' AGL
UPPER REDUNDANT HORIZONTAL REINFORCEMENT
(6) KITS REQUIRED TOTAL
120 in CUT TO LENGTH
Lu Lu Lu Lu
58 in
Lu
Lu
1/4 in
1/4 in
T17-U-A
SECTION T17 FROM BASE TO 30' AGL
LOWER REDUNDANT HORIZONTAL REINFORCEMENT
(6) KITS REQUIRED TOTAL
T17-L-A
Lu SHALL NOT EXCEED 30 INCHES WHEN INSTALLED
Lu SHALL NOT EXCEED 30 INCHES WHEN INSTALLED
T17-U-A
T17-L-A
DETAIL H
SECTION J-J
SEE SHEET 5 FOR DETAILS
D D
H
J
J
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
MAX. SPACING
30" CENTER TO
CENTER
MODIFICATIONS REQURIED TO BE APPLIED TO SECTION T15:
FROM 50' TO 70' AGL
ADD ANGLE REINFORCEMENT TO DIAGONAL
CLAMP ON 3" X 3" X 1/4" ANGLE TO
DIAGONAL AS SHOWN WITH
A MAXIMUM CLAMP SPACING
OF 30" CENTER TO CENTER.
(12) CLAMP ASSEMBLIES
PER DIAGONAL
3" X 3" X 1/4"
ANGLE CLAMPED TO
EXISTING PIPE DIAGONAL
SEE SECTION J-J
30'-6 5/8"
28'-4 1/2"
SPACING SHALL
NOT EXCEED 30"
CENTER TO CENTER
IF ANGLE IS SPLIT. CENTER THE REINFORCEMENT ON EACH
ANGLE ON THE SPAN ABOVE AND BELOW THE REDUNDANT
HORIZONTAL
REDUNDANT
HORIZONTAL
VIEW BB-BB
T15 DIAGONAL REINFORCEMENT PARTS LIST
DESCRIPTION
PART
NUMBER
TOTAL QTY.
REQUIRED
FOR T15
SECTION
QTY. PER
DIAGONAL
ITEM
ANGLE V-CLAMP WELDMENT1059972+6111
5" V-CLAMP1059272+6112
1/2" DIA. X 6.5" LONG GRADE 5 GALVANIZED BOLT11007A144+12223
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT11002144+12224
1/2" DIA. F436 GALVANIZED WASHER11003144+12225
L3" X 3" X 1/4" REINFORCEMENT ANGLE1100861T15-L-D
BB
BB
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
Lu Lu Lu Lu Lu Lu Lu Lu Lu Lu
Lu SHALL NOT EXCEED 30 INCHES WHEN INSTALLED
LAYOUT ASSUMES 25" SPACING
SOME ADJUSTMENT TO Lu MAY BE REQUIRED TO CLEAR
REDUNDANT BRACING.
IT IS ACCEPTABLE TO PROVIDE THIS COMPONENT IN TWO 130" SEGMENTS
IF THIS COMPONENT IS SPLIT INTO TWO SEGMENTS AN ADDITIONAL HARDWARE WILL BE REQUIRED
ADDITIONAL HARDWARE IS SHOWN AS " + #" IN THE BOM LISTING BELOW.
THE LENGTH OF T15-L-D MAY REQUIRE FIELD TRIMMING TO ENSURE
THE MEMBER DOES NOT HIT THE ATTACHMENT PLATES AT EACH
END OF THE REINFORCEMENT ANGLE.
T15-L-D
21'-8"
MAY BE PROVIDED AS TWO SEGMENTS
SPLIT AT THE LOCATION OF THE REDUNDANT
HORIZONTAL
3 4 5
T15-L-D
130 in 130 in
IF ANGLE IS SPLIT ADD
ONE ADDITONAL CLAMP ASSEMBLY AT
THE END OF SEGMENT HERE
6 1/2 in
1 1/2 in
L
M
N
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
150 ft AGL
170 ft AGL
160 ft AGL
MODIFICATIONS REQURIED TO BE APPLIED TO SECTION T9:
FROM 160' TO 170' AGL
CONVERT EXISTING SINGLE 3" X 3" X 1/4" ANGLE X-BRACING TO
3" X 3" X 1/4" BACK TO BACK ANGLE X-BRACING
IMPORTANT NOTICE
REMOVAL OF THE EXISTING DIAGONAL BOLTS TO ALLOW ITS
REPLACEMENT WITH PART NUMBER 11016 WHEN INSTALLING
THE BACK TO BACK ANGLES WILL LEAD TO STRUCTURAL INSTABILITY.
THE REMOVAL OF THE SINGLE DIAGONAL BOLT WILL EFFECTIVELY
REMOVE THE ASSOCIATED DIAGONAL FROM THE STRUCTURE CREATING
THE INSTABILITY. ADDITIONAL TEMPORARY HORIZONTAL BRACING OR
ANOTHER SUPERVISED APPROACHED MUST BE INCORPORATED INTO
THE REPLACEMENT PROCEDURE OUTLINED IN THE RIGGING PLAN IN
ACCORDANCE WITH TIA-322.
27°
30°
DETAIL L
DETAIL M
TYPICAL SPACER DETAIL
DETAIL N
TYPICAL BRACE
TO LEG CONNECTION
SECTION T9 ASSEMBLY PARTS LIST
STATUSDESCRIPTIONPART NUMBERQTYITEM
NEWT9 SECTION UPPER REINFORCEMENT ANGLE1100961
NEW1/2" DIA. X 1-1/4" LONG GRADE 5 GALVANIZED BOLT11010602
NEW1/2" DIA. F436 GALVANIZED WASHER11003603
NEW1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT11002604
NEW5/8" DIA. X 2" LONG A-325 GALVANIZED BOLT1101135
NEW5/8" DIA. F436 GALVANIZED WASHER1101436
NEW5/8" DIA. A-563 GRADE DH HEAVY HEX GALVANIZED NUT1101537
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
IMPORTANT NOTICE
REMOVAL OF THE EXISTING DIAGONAL BOLTS WILL
LEAD TO STRUCTURAL INSTABILITY. ALL WORK
SHALL BE COMPLETED UTILIZING A RIGGING PLAN
IN ACCORDANCE WITH TIA-322 AND ASSE 10.48.
VIEWS THAT INCLUDE
THE EXISTING STRUCTURE
ARE REPRESENTATIONS
AND NOT TO SCALE
SEE PREVIOUS SHEET
FOR DETAIL LOCATIONS
1 7
5 6 7
EXISTING
DIAGONAL
5 6 7
IF THE BOLT HOLE IS OBSTRUCTED
IT MAY BE ABANDONED. IF ABANDONED
DRILL A NEW HOLE NO MORE THAN 8" FROM
THE CENTER BOLT.
13 3/4 in
AS DRAWN
3 1/2 in AS DRAWN
MAY EXTEND TO 8"
AS REQUIRED
1 3/4 in
REQUIRED
CENTER
BOLT
PART NUMBER 11009
SECTION T9 TOP REINFORCEMENT ANGLE
MATERIAL: 3" X 3" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
3 in
3 in
3/16 in
223 3/4 in
1 3/4 in
2 in
1 in
27 in
53 in
79 in
105 in
115 1/4 in
118 3/4 in
144 3/4 in
170 3/4 in
196 3/4 in
222 3/4 in
11/16 in THRU
9/16 in THRU
TYP. 10 PLACES
(2) FIELD DRILLED
(8) SHOP DRILLED
26 in
13 3/4 in
FIELD
DRILL
FIELD
DRILL
SECTION T6 PARTS LIST
DESCRIPTION
PART
NUMBER
QTYITEM
T6 UPPER REINFORCEMENT ANGLE1101761
T6 MIDDLE REINFORCEMENT ANGLE1101662
T6 LOWER REINFORCEMENT ANGLE1101363
1/2" DIA. X 2" LONG GRADE 5 GALVANIZED BOLT1101294
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT110021175
1/2" DIA. F436 GALVANIZED WASHER110031176
3/8" DIA. X 1.00" LONG SAE GRADE 5 GALVANIZED BOLT110341447
3/8" DIA. F436 GALVANIZED WASHER110321448
3/8" DIA. GRADE B GALVANIZED HEX NUT110331449
T
U
W
AA
AB
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
FACE VIEWS
TYPICAL ALL
THREE FACES
IMPORTANT NOTICE
REMOVAL OF THE EXISTING DIAGONAL BOLTS TO ALLOW
ITS REPLACEMENT WITH PART NUMBER 11016 WHEN
INSTALLING THE BACK TO BACK ANGLES WILL LEAD TO
STRUCTURAL INSTABILITY. THE REMOVAL OF THE SINGLE
DIAGONAL BOLT WILL EFFECTIVELY REMOVE THE
ASSOCIATED DIAGONAL FROM THE STRUCTURE CREATING
THE INSTABILITY. ADDITIONAL TEMPORARY HORIZONTAL
BRACING OR ANOTHER SUPERVISED APPROACHED MUST
BE INCORPORATED INTO THE REPLACEMENT PROCEDURE
OUTLINED IN THE RIGGING PLAN IN ACCORDANCE WITH TIA-322.
210` AGL
230` AGL
MODIFICATIONS REQURIED TO BE APPLIED TO SECTION T6:
FROM 210' TO 230' AGL
CONVERT EXISTING SINGLE 2" X 2" X 3/16" ANGLE X-BRACING TO
2" X 2" X 3/16" BACK TO BACK ANGLE X-BRACING
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
UPPER
MIDDLE
LOWER
EXISTING
DIAGONAL
26°
DETAIL T
CENTER CONNECTION
TYPICAL ALL 9 LOCATIONS
DETAIL U TYPICAL
DETAIL W TYPICAL
DETAIL AA
TYPICAL
DETAIL AB
TYPICAL
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
EXISTING
DIAGONAL
EXISTING
DIAGONAL
REINFORCEMENT
DIAGONAL
7 8 9
7 8 9
7 8 9
7 8 9
7 8 9
2 7/16 in TYP.
PART NUMBER 11017
T6 UPPER REINFORCEMENT ANGLE
MATERIAL: 2" X 2" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
PART NUMBER 11016
T6 MIDDLE REINFORCEMENT ANGLE
MATERIAL: 2" X 2" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
PART NUMBER 11013
T6 LOWER REINFORCEMENT ANGLE
MATERIAL: 2" X 2" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
DETAIL BC
TYPICAL ALL
CENTER BOLTS
DETAIL BD
TYP. ALL
OTHER BOLTS
BC
BD
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
2 in
2 in
3/16 in
152 5/8 in
146 3/4 in
139 7/8 in
2 in
2 in
3/16 in
2 in
2 in
3/16 in
1 1/4 in
1 in
26 in 26 in
26 in
26 in
(1) in
1 7/16 in
1 1/4 in
1 in
26 in
26 in
26 in 26 in
(1) in
7/16 in THRU
TYP. 8 PLACES
(2) FIELD DRILLED
(6) SHOP DRILLED
FIELD DRILL
FIELD DRILL
FIELD DRILL
FIELD DRILL
FIELD DRILL
FIELD DRILL
1 in
26 in 26 in
26 in
26 in
1 in
7/16 in THRU
TYP. 8 PLACES
(2) FIELD DRILLED
(6) SHOP DRILLED
1 7/16 in9/16 in THRU
1 3/16 in
7/16 in THRU
CENTER
BOLT
CENTER
BOLT
CENTER
BOLT
9/16 in
7/16 in THRU
TYP. 8 PLACES
(2) FIELD DRILLED
(6) SHOP DRILLED
12 in
12 7/8 in
9 in
12 in
10 5/8 in
6 1/8 in
12 in
12 in
9 1/4 in
10 3/8 in
15 in
(9/16) in
(13/16) in
PARTS LIST
DESCRIPTIONPART NUMBERQTYITEM
T5 LOWER REINFORCEMENT ANGLE1101861
T5 MIDDLE REINFORCEMENT ANGLE1101962
T5 UPPER REINFORCEMENT ANGLE1102063
1/2" DIA. X 2" LONG GRADE 5 GALVANIZED BOLT1101294
1/2" DIA. F436 GALVANIZED WASHER110031175
1/2" DIA. A563 GRADE DH HEAVY HEX GALVANIZED NUT110021176
3/8" DIA. X 1.00" LONG SAE GRADE 5 GALVANIZED BOLT110341207
3/8" DIA. F436 GALVANIZED WASHER110321208
3/8" DIA. GRADE B GALVANIZED HEX NUT110331209
AG
AH
AJ
AK
AL
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
IMPORTANT NOTICE
REMOVAL OF THE EXISTING DIAGONAL BOLTS TO ALLOW
ITS REPLACEMENT WITH PART NUMBER 11016 WHEN
INSTALLING THE BACK TO BACK ANGLES WILL LEAD TO
STRUCTURAL INSTABILITY. THE REMOVAL OF THE SINGLE
DIAGONAL BOLT WILL EFFECTIVELY REMOVE THE
ASSOCIATED DIAGONAL FROM THE STRUCTURE CREATING
THE INSTABILITY. ADDITIONAL TEMPORARY HORIZONTAL
BRACING OR ANOTHER SUPERVISED APPROACHED MUST
BE INCORPORATED INTO THE REPLACEMENT PROCEDURE
OUTLINED IN THE RIGGING PLAN IN ACCORDANCE WITH TIA-322.
FACE VIEWS
TYPICAL ALL
THREE FACES
230` AGL
250` AGL
MODIFICATIONS REQURIED TO BE APPLIED TO SECTION T5:
FROM 230' TO 250' AGL
CONVERT EXISTING SINGLE 1-3/4" X 1-3/4" X 3/16" ANGLE X-BRACING TO
1-3/4" X 1-3/4" X 3/16" BACK TO BACK ANGLE X-BRACING
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
EXISTING
DIAGONAL
32°
DETAIL AG
DETAIL AH
TYPICAL
DETAIL AJ
TYPICAL
DETAIL AK
TYPICAL
DETAIL AL
TYPICAL
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
4 5 6
EXISTING
DIAGONAL
REINFORCEMENT
ANGLE
EXISTING ANGLE
7 8 9
7 8 9
7 8 9
2 3/16 in TYP.
PART NUMBER 11020
T5 UPPER REINFORCEMENT ANGLE
MATERIAL: 1-3/4" X 1-3/4" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
PART NUMBER 11019
T5 MIDDLE REINFORCEMENT ANGLE
MATERIAL: 1-3/4" X 1-3/4" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
PART NUMBER 11018
T5 LOWER REINFORCEMENT ANGLE
MATERIAL: 1-3/4" X 1-3/4" X 3/16" A-36 STEEL ANGLE
(6) REQUIRED TOTAL
FINISH: HOT DIPPED GALVANIZED
DETAIL BE
BE
A A
B B
EET, LLC
Granger, IN USA
1-574-277-0670
PROPRIETARY
This drawing is the proprietary property of EET, LLC and may not be used, adapted, reproduced, copied, or disclosed without the prior written consent of EET, LLC.
PAGE
DRAWN BY: DATE:
APPROVED BY: DATE:
JRE
1/2/2018
JRE
6/13/2018
DRAWING NO.
B
OAKLAND COUNTY TOWER
MODIFICATIONS
SIZE:
Oakland County
Tower
Modification R5
REVISION:
SCALE:
N.T.S.
Owner: Prepared For:
Engineering by:
119 7/8 in
126 3/8 in
119 7/8 in
1 3/4 in
1 3/4 in
3/16 in
N.T.S
N.T.S
N.T.S
1 3/4 in
1 3/4 in
3/16 in
1 3/4 in
1 3/4 in
3/16 in
1 in
26 in
26 in
9 1/4 in
4 5/8 in
26 in
26 in
1 1/8 in
1 5/16 in
FIELD
DRILL
FIELD
DRILL
FIELD
DRILL
FIELD
DRILL
FIELD
DRILL
FIELD
DRILL
1 in
26 in 26 in
12 3/8 in
8 in
26 in 26 in
20 3/8 in
1 5/16 in
1 1/8 in
1 in
1 5/16 in
1 in
26 in 26 in
9 1/4 in
4 5/8 in
26 in 26 in
1 in
13 7/8 in
1 1/8 in
CENTER
BOLT
CENTER
BOLT
CENTER
BOLT
CENTER
BOLT
TYP.
1 5/16 in
ALL OTHER BOLTS
1 1/8 in
9/16 in
THRU
7/16 in
THRU TYP.
7/16 in THRU
TYP. 6 PLACES
(2) FIELD DRILLED
(4) SHOP DRILLED
7/16 in THRU
TYP. 7 PLACES
(2) FIELD DRILLED
(5) SHOP DRILLED
7/16 in THRU
TYP. 6 PLACES
(2) FIELD DRILLED
(4) SHOP DRILLED
9 in
3 3/8 in
File details come from the government source that posted it. Updated .