This is a set of construction drawings for the Fontana Unified School District's water piping replacement project at North Tamarind Elementary School, located at 7961 Tamarind Avenue, Fontana, California 92336. The project involves comprehensive plumbing system upgrades for the Kindergarten Building C, including demolition of existing water piping infrastructure and installation of new cold water (CW) lines throughout the facility. The scope encompasses replacement of a 2-inch water valve in the yard box, capping and abandonment of existing underground water pipes, installation of new 2-inch underground water piping, and connection of new cold water lines to existing fixtures including lavatories, water closets, sinks, water fountains, and hose bibbs. The drawings also detail installation of shut-off valves, water hammer arrestors, and pressure-reducing valve stations to meet current California plumbing codes. The design was completed with a 50 percent construction document phase dated December 5, 2025, and 100 percent completion dated January 12, 2026. Bids are due no later than 2:00 p.m. on Monday, June 8, 2026, through the district's e-procurement portal, with questions accepted until 12:00 p.m. on Tuesday, May 26, 2026.
The project must comply with the 2022 California Building Code, California Electrical Code, California Mechanical Code, California Plumbing Code, California Energy Code, California Fire Code, and California Green Building Standards Code, along with applicable NFPA standards for automatic sprinkler and fire alarm systems. The contractor is responsible for identifying and properly remediating any asbestos-containing materials encountered during demolition activities in accordance with federal, state, and local regulations. The design specifications include lead-free soldered fittings, PVC piping, copper materials, Tyler no-hub couplings, and water-efficient fixtures meeting EPA WaterSense standards with maximum flow rates of 0.5 GPM for public lavatory faucets and 1.28 gallons per flush for high-efficiency toilets. All piping offsets and fixture location changes necessary to conform to structural and architectural requirements must be made by the contractor without additional cost to the owner.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T-1
TITLE SHEET
DISTRICT: 9680 CITRUS AVENUE, FONTANA, CA 92335
PROJECT DATA
SHEET INDEX
VICINITY MAP
FONTANA SCHOOL DISTRICT
WATER PIPING REPLACEMENT
N
PROJECT ADDRESS:
SCOPE OF WORK
NORTH TAMARIND ELEMENTARY SCHOOL
7961 TAMARIND AVENUE
FONTANA, CA 92336
CODES AND STANDARDS
PROJECT CONTACTS REVISIONS
DATE
SHEET NO.
SCALE
CHECKED BY
DRAWN BY
SHEET TITLE
PROJECT
CV
CK
DECEMBER 15, 2025
AS NOTED
DATE
26449 Rancho Pkwy South Lake Forest, CA 92630 Phone: (949) 215-7664 Fax: (949) 916-8670
DESIGN GROUP, INC.
www.ltddesigngroup.com
NORTH TAMARIND
ELEMENTARY SCHOOL
7961 TAMARIND AVENUE
FONTANA, CA 92336
50% CD 12-5-25
100% CD 1-12-26
2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1 TITLE 24 C.C.R.
2022 CALIFORNIA BUILDING CODE (CBC). PART 2, TITLE 24 C.C.R.
2022 CALIFORNIA ELECTRICAL CODE (CEC). PART 3, TITLE 24 C.C.R. (2020 NEC)
2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
2022 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R.
2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
AMERICAN WITH DISABILITY ACT.
PARTIAL LIST OF APPLICABLE STANDARDS.
NFPA 13
2022 EDITION.
NFPA 24
2022 EDITION.
NFPA 72
2022 EDITION.
(NOTE: SEE UL STANDARD 1971 FOR "VISUAL DEVICES")
REFERENCE CODE SECTION FOR NFPA STANDARDS - 2022 CBC (SFM) CHPT. 35
AUTOMATIC SPRINKLER SYSTEM.
PRIVATE FIRE MAINS (INCLUDED IN 2016 NFPA 13)
NATIONAL FIRE ALARM CODE (CALIFORNIA AMENDED)
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11, TITLE 24 C.C.R.
KEYPLAN
GENERAL NOTES
AND SPECIFICATIONS
NOTE: CONTRACTOR SHALL BE RESPONSIBLE FOR
IDENTIFYING AND PROPERLY REMEDIATING ANY
ASBESTOS-CONTAINING MATERIALS ENCOUNTERED DURING
THE DEMOLITION OF EXISTING WALLS, CEILINGS AND
ASSOCIATED BUILDING COMPONENTS. ALL ASBESTOS
ABATEMENT ACTIVITIES SHALL BE PERFORMED IN
ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND
LOCAL REGULATIONS. SEE ATTACHED ENVIRONMENTAL
REPORT FOR DETAILS ON ASBESTOS CONTAINING
MATERIAL.
PLUMBING
LEGEND, DETAILS
& SCHEDULES
P-1.00
EF
S
"S" - FIXTURE TYPE
"3" - DENOTES FIXTURE NUMBER
"02" - DENOTES DETAIL CALL-OUT
"1" DENOTES EQUIPMENT NUMBER
"RTU" DENOTES ROOFTOP UNIT
"CU" DENOTES CONDENSING UNIT
"FC" DENOTES FAN-COIL
"MAU" DEMOTES MAKE-UP AIR UNIT
"EF" DENOTES EXHAUST FAN
MECHANICAL EQUIPMENT DESIGNATION
"P-3" - DENOTES DRAWING NUMBER
THESE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC, DEPICTING FUNCTION AND PLACEMENT. PROVIDE OFFSETS IN PIPING AND CHANGES IN FIXTURE LOCATIONS AS NECESSARY TO CONFORM TO STRUCTURAL AND ARCHITECTURAL REQUIREMENTS AND TO AVOID OBSTRUCTIONS. CHANGES TO ACCOMMODATE INSTALLATION OF THIS WORK WITH OTHER WORK, IN ORDER TO MEET ARCHITECTURAL
OR STRUCTURAL CONDITIONS, SHALL BE MADE WITHOUT ADDITIONAL COST TO OWNER.
SYMBOL FIXTURE
DHWW V DCW
ROUGH-IN SIZE
REMARKS
PVC PIPE & FITTINGS, 5" & GREATERBEL. FLR.
BEL. FLR.
ABV. FLR.
FITTINGS
HARRIS BRIDGIT LEAD FREE SOLDERED FITTINGS, UP TO 4"
HARRIS BRIDGIT LEAD FREE SOLDERED FITTINGS
PROVIDE TYLER 4-BAND NO-HUB COUPLINGS
PROVIDE TYLER 4-BAND NO-HUB COUPLINGS
PROVIDE TYLER 4-BAND NO-HUB COUPLINGS
PROVIDE TYLER 2-BAND NO-HUB COUPLINGS
LEAD FREESOLDERED FITTINGS
LEAD FREESOLDERED FITTINGS
PROVIDE TYLER 2-BAND NO-HUB COUPLINGS
PROVIDE TYLER 2-BAND NO-HUB COUPLINGS
LEAD FREESOLDERED FITTINGS, INSULATED
LEAD FREESOLDERED FITTINGS, INSULATED
SCH.. 40 PIPE AND MALLEABLE IRON FITTINGS
P.E. PIPE AND FITTINGS W/ ELECTRIC FUSION JOINTS
WATER
WASTE (SANITARY)
STORM DRAIN
OVERFLOW DRAIN BEL. FLR.
ABV. FLR.
BEL. FLR.
VENT (SANITARY)
INSIDEINDIRECT
OUTSIDE
BEL. FLR.
ABV. FLR.
WASTE
ABV. FLR.
INSIDE
DRAIN
INSIDE
OUTSIDE
BEL. GRADE
GAS
CONDENSATE
1 1/2"
1 1/4"
2" 260
3/4"
1/2"
SIZE
1"
PIPE
F. TANK
SYSTEM
66.5
20.6
32.1
5.7
12.1
2.1
GPM
F. VALVE
WATER HAMMER ARRESTOR)
- - 3/4" -
HB
HOSE BIBB
WHA
-1 1/2"2"4"
0.5 GPM @ 60 PSI
1.28 GALLONS/FLUSH 20.00%SINGLE FLUSHOMETER
VALVE WATER CLOSET
1.6 GALLONS/FLUSH
77.27%2.2 GPM @ 60 PSI
30.00%0.35 GPM @ 60 PSI0.5 GPM @ 60 PSI
PERCENTAGE WATER
USE REDUCTION
WATER USE DESIGN
FLOW RATE
WATER USE
BASELINE FLOW RATE
LAVATORY
FIXTURE TYPE
SINK FAUCET
RESIDENTIAL BATHROOM LAVATORY SINK FAUCETS.
MAXIMUM FLOW RATE - 1.5 GPM (5.7L/MIN)
ASME A 112.18.1/CSA B125.1
ASME A 112.18.1/CSA B125.1
PUBLIC METERING SELF-CLOSING FAUCETS:
MAXIMUM WATER USE - 0.25 GAL (1.0L) PER METERING CYCLE.
ASME A 112.19.19 (VITREOUS CHINA)
ANSI Z124.9-2004 OR IAPMO Z124.9 (PLASTIC)URINALS, NONWATER URINALS
WATER CLOSET (TOILETS) - TANK TYPE
U.S. EPA WATER SENSE TANK-TYPE
HIGH-EFFICIENCY TOILET
SPECIFICATION - 1.28 GAL (4.8L)
ASME A 112.19.14 AND
U.S. EPA WATER SENSE TANK-TYPE
HIGH-EFFICIENCY TOILET
SPECIFICATION - 1.28 GAL (4.8L)
WATER CLOSET (TOILETS) - FLUSHOMETER VALVE TYPE
DUAL FLUSH, MAXIMUM FLUSH VOLUME
ASME A 112.18.1/CSA B125.1PUBLIC LAVATORY FAUCET: MAXIMUM FLOW RATE -
0.5 GPM (1.9L/MIN)
ASME A 112.19.2/CSA B45.1 - 0.5 GALURINALS, MAXIMUM FLUSH VOLUME
ASME A 112.19.2/CSA B45.1 - 1.28 GAL (4.8L)WATER CLOSET (TOILETS) - FLUSHOMETER VALVE TYPE
SINGLE FLUSH, MAXIMUM FLUSH VOLUME
DESCRIPTION
COLD WATER
SANITARY VENT
S OR W
ABBR.
S OR W
W
SYMBOL
W
V
CW
V
CW
SOIL OR WASTE BELOW FLOOR OR GRADE
SOIL OR WASTE ABOVE FLOOR OR GRADE
HOT WATER
HOT WATER RETURN
FUEL GAS
CONDENSATE DRAIN
INDIRECT DRAIN LINE
HW
HWRHWR
HW
D
CD
G
D
CD
GAS COCK
DIRECTION OF FLOW
FLOOR OR GRADE
TRAP PRIMER
WALL CLEANOUT
PRESSURE REDUCING VALVE
SHUT-OFF VALVE
FLOOR CLEANOUT
TP
CWV
G.C.
P.G.
TP
CWV
P.R.V.
SOV
FCO
WCO
COMBINE WASTE AND VENT BELOW
PRESSURE GAUGE W/PETE COCK
UNDERGROUND PIPE
GRADE
HANDICAP
GR
HC
TYPICAL
WITH
VENT THROUGH ROOFVTR
W/
TYP
SHUT-OFF VALVE IN YARD BOXSOV/YB
G
RISE
UNION
SLOPE IN DIRECTION OF FLOW
WATER HAMMER ARRESTOR
ABOVE
ABOVE FINISHED FLOOR
POINT OF DISCONTINUATION
POINT OF CONNECTION
WHA
POD
RPBP
ABV
AFF
POC
BELOW
BEHIND
CAST IRON
CUBIC FEET PER HOUR
CONNECTION
CEILING
CLEANOUT TO GRADE
CLEAN-OUT IN YARD BOX
CONTINUATION
BEH
BEL
CFH
CI
CONN
CLG
CONT
COTG
COYB
AP ACCESS PANEL
REDUCED PRESSURE BACKFLOW
COLD WATER
EXISTING
DETAIL
DEMOLITION FIXTURES
FLOOR
FROM
FIRE SPRINKLER HEAD
FINISHED FLOOR ELEVATION
FIRE DEPT. CONNECTION
CW
DTL
EX
FLR
FFE
FR
FSH
FDC
DOWN
GWGW GREASE WASTE ABOVE FLOOR OR GRADE
GWGW GREASE WASTE BELOW FLOOR OR GRADE
SANITARY GREASE VENTGVGV
GPM FLOW
5. BACKFLOW PREVENTER
X 100
11. AVERAGE PRESSURE DROP, PSI/100 Ft.
10. DEVELOPED LENGTH 120% OF ITEM 9
9. ACTUAL LENGTH OF SYSTEM, Ft.
8. PRESSURE AVAILABLE FOR FRICTION, PSI
7. WATER PRESSURE (MIN.), PSI
ITEM 10
ITEM 8
6. TOTAL LOSSES, PSI
4. PRESSURE REGULATING STATION, PSI
3. RESIDUAL PRESSURE REQUIRED, PSI
2. STATIC LOSS, PSI
1. METER LOSS, PSI
PRV SET @
MATERIAL: COPPER
SUB- METER SIZE:
STREET PRESSURE:
(23'X0.43)
PSI
PSI
3" FOR 80
3.27
14.11
60.89
9.89
COLD WATER
T.D.L. TOTAL DEVELOP LENGTH
PREVENTER
P-3
PPP SS750316
REVISIONS
DATE
SHEET NO.
SCALE
CHECKED BY
DRAWN BY
SHEET TITLE
PROJECT
CV
CK
DECEMBER 15, 2025
AS NOTED
DATE
26449 Rancho Pkwy South Lake Forest, CA 92630 Phone: (949) 215-7664 Fax: (949) 916-8670
DESIGN GROUP, INC.
www.ltddesigngroup.com
NORTH TAMARIND
ELEMENTARY SCHOOL
7961 TAMARIND AVENUE
FONTANA, CA 92336
50% CD 12-5-25
100% CD 1-12-26
3/4" DCW
FROM ABV.
OR BEL.
W/ VACUUM
BREAKER
STAINLESS STEEL BOX
& LOCKING DOOR
10-3/8"
INTEGRAL
STOP
OUTLET 8-5/8"
EXTERIOR WALL
SHUT-OFF
VALVE
ACORN NO. 8104-SSLF W/ VACUUM BREAKER
& REMOVABLE LOOSE KEY HANDLE.
MAIN
ACCESS BOX
QUARTER TURN BALL VALVE
FINISHED GRADE
PRE-CAST CONCRETE
OFFSET AS REQUIRED
TO MEET DIMENSION
SHOWN IN ACCESS BOX
CAST IRON ACCESS COVER
WITH THE NAME OF THE
SERVICE CAST IN COVER
UNION
QUIRED.
EARTH.
COLD WATER OR GAS TO
BLDG. SLEEVE FOOTING
OR GRADE BEAM AS RE-
SUPPORT VALVE BOX WITH
(4) 2" X 2" REDWOOD STAKES
DRIVEN TO UNDISTURBED
WITH 1/4" MAX. SLOT
WIDTH
SELECT MATERIAL FREE OF
ORGANIC MATTER AND STONES 12"
OR LARGER, 90% COMPACTED
AGGREGATE BASE
90% COMPACTED
ASPHALT CEMENT
OR RESTORED SURFACES
SOFT BEDDING OF SAND
OR STONE/ORGANIC FREE
EARTH, 90% COMPACTED
NOTE:
1. TRENCHING SHALL RUN ADJACENT TO EXISTING STRUCTURES AND NOT PASS THROUGH EXISTING FOOTING PAD.
2. TRENCH SHALL BE BROUGHT TO 120 PERCENT OPTIMUM MOISTURE CONTENT AND COMPACTED TO A MINIMUM
RELATIVE COMPACTION OF 90% IN ACCORDANCE WITH ASTM D1557.
12"
WATER HAMMER ARRESTOR
QUARTER TURN BALL VALVE
FINISH FLOOR
ACCESS PANEL
CEILING
P-2.0
PLUMBING FLOOR
PLANS
REVISIONS
DATE
SHEET NO.
SCALE
CHECKED BY
DRAWN BY
SHEET TITLE
PROJECT
CV
CK
DECEMBER 15, 2025
AS NOTED
DATE
26449 Rancho Pkwy South Lake Forest, CA 92630 Phone: (949) 215-7664 Fax: (949) 916-8670
DESIGN GROUP, INC.
www.ltddesigngroup.com
NORTH TAMARIND
ELEMENTARY SCHOOL
7961 TAMARIND AVENUE
FONTANA, CA 92336
50% CD 12-5-25
100% CD 1-12-26
DEMOLITION KEYNOTES:
RECONSTRUCTION KEYNOTES:
DEMO EXISTING 2" WATER VALVE IN YARD BOX AND REPLACE WITH NEW. TEST
WATER PRESSURE AND REPORT TO OWNER.
CAP EXISTING UNDERGROUND 2" WATER PIPE AND ABANDON IN PLACE.
PROVIDE NEW 2" UNDERGROUND WATER PIPE.
CONTRACTOR SHALL VERIFY EXISTING CONDITIONS BEFORE COMMENCING WORK.
CONTRACTOR SHALL VERIFY EXISTING CONDITIONS BEFORE COMMENCING WORK.
3 EXISTING GAS SHUT OFF VALVE TO REMAIN.
4 CAP EXISTING INCOMING WATER PIPING ABOVE CEILING. PATCH WALL AND CEILING
TO MATCH EXISTING.
5 DEMO ALL EXISTING WATER PIPING ABOVE CEILING AND PATCH TO MATCH EXISTING.
EXISTING SANITARY TO REMAIN.6
CAP EXISTING 1 12" UNDERGROUND WATER PIPE.7
PROVIDE NEW 2" CW ABOVE CEILING AND PATCH CEILING TO MATCH EXISTING.
CONNECT NEW 3/4" CW TO EXISTING LAVATORY. PROVIDE NEW SHUT OFF VALVE.
CONNECT NEW 1 1/2" CW TO EXISTING WATER CLOSET. REUSE EXISTING FLUSH VALVE.
CONNECT NEW 3/4" CW TO EXISTING SINK. PROVIDE NEW SHUT OFF VALVE. PATCH
WALL AND CEILING TO MATCH.
8 EXISTING 2" UNDERGROUND GAS PIPE TO REMAIN.
9 ABANDON EXISTING 2" UNDERGROUND WATER PIPE IN PLACE.
1/8" = 1'-0"
1PLUMBING DEMOLITION FLOOR PLAN - KINDERGARTEN BUILDING C
PLUMBING RECONSTRUCTION FLOOR PLAN - KINDERGARTEN BUILDING C
1/8" = 1'-0"
1 2
CONNECT NEW 3/4" CW TO EXISTING WATER FOUNTAIN. PROVIDE NEW SHUT OFF VALVE.
PROVIDE NEW 1 1/2" SHUT OFF VALVE AND WATER HAMMER ARRESTOR INSIDE WALL
MOUNTED ACCESS PANEL FOR SERVING EACH RESTROOM. LOCATE AT 48" AFF.
PROVIDE NEW 3/4" CW TO NEW HOSE BIBB. PATCH WALL TO MATCH.
9 PROVIDE NEW 2" CW IN YARDBOX IN PLANTER AREA.
10 RUN NEW 2" CW OUTSIDE THE EXISTING WALL AND PENETRATE ABOVE CEILING.
10 2 2
11 PROVIDE NEW 3/4" CW DOWN TO HOSE BIBB, PATCH WALL TO MATCH EXISTING.
12 RECONNECT NEW 3/4" CW TO EXISTING HOSE BIBB IN GRASS AREA.
13 PROVIDE NEW 3/4" CW ABOVE EXISTING CEILING AND PATCH CEILING TO MATCH EXISTING.
14 PROVIDE NEW 3/4" UNDERGROUND CW.
| T-1 - Title Sheet |
| T-1 |
| P-1.0 Plumbing Legend, Details and Schedules |
| P-1.00 |
| P-2.0 Plumbing Floor Plans |
| P-2.0 |