Attachment 7 Device List.xls
XLS spreadsheet 27 KB Posted
- Attached to
- Testing and Calibration of Sensors/Transmitters
- Solicitation number
- NGA-RFP-08-085
- Issued by
-
National Gallery of Art
About this file
This sensor device list shall be inserted into the solicitation documentation in Section J as Attachment 7.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A002 - Period of Performance Extension | — | |
| A001 - Device List Attachment | — | |
| RFP-08-085.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Device List
| Device Legend | ||||||
| Item | Datapoint Name | Descriptor: | Drawing Key | Device | Part Number | Range |
| 1 | ECHWSChwFlo1 | Chilled Water Flow | FV-1 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 0 - 5000 GPM |
| 2 | ECHWSChwFlo2 | Chilled Water Flow | FV-2 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 1 - 5000 GPM |
| 3 | ECHWSChwFlo3 | Chilled Water Flow | FV-3 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 2 - 5000 GPM |
| 4 | ECHWSChwRetPres | EB Chilled Water Return Pressure | PGV-2 | Veris: Gauge pressure, transducer, 0-100psi =4-20mA, | PH-X-07-S | 3 - 5000 GPM |
| 5 | ECHWSChwSupTemp | EB Chilled Water Supply Temp | TNW-1 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 4 - 5000 GPM |
| 6 | WCHWSAC23SupPress | AC 23 Supply Pressure | PGU-2 | Veris: Gauge pressure, transducer, 0-50psi =4-20mA, | PH-X-07-S | 5 - 5000 GPM |
| 7 | WCHWSBldgHeadPres | West Bldg Hd Pressure | PGU-1 | Veris: Gauge pressure, transducer, 0-250psi =4-20mA,24VDC | PH-X-08-S | 6 - 5000 GPM |
| 8 | WCHWSChwHxRetTemp | Chilled Water Return Temp | TNW-5 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 7 - 5000 GPM |
| 9 | WCHWSChwHxSupTemp | Chilled Water Supply Temp | TNW-4 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 8 - 5000 GPM |
| 10 | WCHWSCwFlo | Condenser Water Flow | FV-1 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 9 - 5000 GPM |
| 11 | WCHWSCwSupTemp | Condenser Water Supply Temp | TNW-1 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 10 - 5000 GPM |
| 12 | WCHWSPrimChwFlo | HX Primary Chilled Water Flow | FVN-1 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 11 - 5000 GPM |
| 13 | WCHWSPrimChwHxFlo | HX Primary Chilled Water Flow | FV-2 | ABB Hart ?? | ?? | 12 - 5000 GPM |
| 14 | WCHWSSecChwFlo1 | East Bldg Sec Chilled Water Flow | FV-3 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 13 - 5000 GPM |
| 15 | WCHWSSecChwFlo2 | West Bldg Sec Chilled Water Flow | FV-5 | SeaMetrics: Electromagnetic Inserstion Flow Sensor with SeaMetrics: Analog Transmitter, 4-20mA, 24VDC | EX215-B with AO55 | 14 - 5000 GPM |
| 16 | WCHWSSecChwSupTmp1 | EB Sec Chilled Water Supply Temp | TNW-6 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 15 - 5000 GPM |
| 17 | WCHWSSecChwSupTmp2 | WB Sec Chilled Water Supply Temp | TNW-7 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 16 - 5000 GPM |
| 18 | WCHWSSecSucHdPres | Secondary Suction Hd Pres | PGY-1 | Veris: Gauge pressure, transducer, 0-250psi =4-20mA,24VDC | PH-X-08-S | 17 - 5000 GPM |
| 19 | WCHWSUWHxRetTemp | HX Utility Water Return Temp | TNW-3 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 18 - 5000 GPM |
| 20 | WCHWSUWHxSupTemp | HX Utility Water Supply Temp | TNW-2 | Kele: immersion, PT1000 RTD, 0-100F, 4-20mA with | T91U-EMC-3-WS | 19 - 5000 GPM |
| 21 | WCHWSUWPmpDisPres | Utility Pump Discharge Pressure | PGY-1 | Veris: Gauge pressure, transducer, 0-250psi =4-20mA,24VDC | PH-X-08-S | 20 - 5000 GPM |
| 22 | EBChwSupPressure | EB 8th Floor Chw Pressure | ??? | Veris: Gauge pressure, transducer, 0-100psi =4-20mA,24VDC | PH-X-07-S | 21 - 5000 GPM |
| 23 | ECHWSPod3Pres | EB Pod3 Level 7 Pressure | ??? | Veris: Gauge pressure, transducer, 0-100psi =4-20mA,24VDC | PH-X-07-S | 22 - 5000 GPM |
| 24 | WCHWSUWSupplyTemp | Utility Water Supply Temperature | TNW-1 | ABB Hart Programmable Transmitter with NBS RTD -20 to 204 4-20mA | ABB TH202 with NBS 10U-86-100 | 23 - 5000 GPM |
| 25 | WCHWSUWReturnTemp | Utility Water Return Temperature | TNW-2 | ABB Hart Programmable Transmitter with NBS RTD -20 to 204 4-20mA | ABB TH202 with NBS 10U-86-101 | 24 - 5000 GPM |
| 26 | WCHWSHxChwSupplyTemp | Chiled Water Supply Temperature | TNW-4 | ABB Hart Programmable Transmitter with NBS RTD -20 to 204 4-20mA | ABB TH202 with NBS 10U-86-102 | 25 - 5000 GPM |
File details come from the government source that posted it. Updated .