240 120
45A Circuit for Split System A/C
100A Panel
Existing 200A Panel
Proposed Location of Cold Room
MDBC CORAL PROPAGATION PILOT STUDY
GALVESTON COLD ROOM
Proposed Location of Cold Room in The Existing Steel Framed WarehouseSCALE 1:152
2/8/2021 BEN HIGGINS
CAD
Figure 1
61'-1 1/4" '-1
99'-8"
32'-1"
'-1
'-2 o 0.4 slope of floor from outer wall to center of building
Approximately 6’-2”
Approximately 23’
8’
To Outer Wall of Steel Building
EXISTING METAL TRUSS
OF METAL WAREHOUSE
BUILDING
MDBC CORAL PROPAGATION PILOT STUDY
GALVESTON COLD ROOM
PROPOSED LOCATION OF COLD ROOMSCALE 1:4
2/8/2021 BEN HIGGINS
CAD
DRAFT
1 100A, 240V, single phase, exterior rated circuit breaker panel
2 4, 120V, 15A light switches
3 120V, 15A, 48” quad bulb, LED fixture
4 120V, 15A, 48” quad bulb, LED fixture
5 120V, 15A, 48” quad bulb, LED fixture
6 120V, 15A, 48” quad bulb, LED fixture
7 240V, 45A, Disconnect
8 36,000 BTU, 240V, 30A, split system heatpump on exterior wall of steel building
9 120V, 15A, wall outlet in splash proof cover each outlet on a separate GFIC breaker to
MDBC CORAL PROPAGATION PILOT STUDY
GALVESTON COLD ROOM
Electrical LayoutSCALE 1:45
2/8/2021 BEN HIGGINS
CAD
DRAFT
9 10 11 1312
4 5 6
AIR HANDLER
18,000 BTU
AIR HANDLER
18,000 BTU
Wall of Steel Building
100A
/4
/4
/4
/1
1 (4) AWG 240V, 100A FEED
6 (3) AWG 240V, 45A PASS THROUGH
25.3% Fill in 2” PVC conduit
2”
1”
6 (3) AWG 240V, 45A
To Split Unit Condenser
ELECTRICAL LAYOUT
1” PVC Conduit
1/2” PVC
Conduit
Two Pairs of Light Switches With Wet Location Covers
To Lights and Fans
Door
Center of Room
Pair of 120V, 15A Outlets Each on Separate GFCI Circuit Breaker
MDBC CORAL PROPAGATION PILOT STUDY
GALVESTON COLD ROOM
Electrical Layout
2/8/2021 BEN HIGGINS
CAD
DRAFT
SCALE 1:45