| Attachment E - RFQ Question Submittal Form | ||||||
| Question No. | RFP Attachment No. | REFERENCE | QUESTION | GOVERNMENT RESPONSE | ||
| Page | Section | Para. | ||||
| 1 | 2 (SOW) | 9 | 3 | f | Does the absorber on all of the rooms need to be removable or only on Volume 4? | This requirement should apply to all three anechoic volumes. The referenced paragraph has been moved to Section 2 to indicate that it applies to all three anechoic volumes. |
| 2 | 2 (SOW) | 9 | 3 | b | Is 100 dB at 40 GHz required or will 80 dB or 90 dB at 40 GHz be acceptable? Also, is 100 dB at 40 GHz required for all four chambers? | As stated in the section for each chamber (Volume 4, Section 3; Volumes 1 and 2, Section 4; Volume 3, Section 5), the minimum shielding requirement is 100 dB across the minimum range of 100 MHz to 40 GHz. There is no change to the SOW. |