RFC 3 RESPONSE

View the file

Other files for this federal contract opportunity

Other files attached to FIBER OPTIC PLANT MAINTENANCE, newest first.
File Type Posted
Piers_PWS_Revised.docx DOCX document
SAFETY_Program.docx DOCX document
RFC_002_RESPONSE.doc DOC document
NORFOLK_WDOL.pdf PDF
19Q0025_SOLICITATION_REV_1.docx DOCX document
19Q0025_RFC_001_RESPONSE.docx DOCX document
CDRL_A003.pdf PDF
19Q0025_SOLICITATION.docx DOCX document
CDRL_A005.pdf PDF
CDRL_A001.pdf PDF
CDRL_A004.pdf PDF
CDRL_A002.pdf PDF
Piers_NDA.docx DOCX document
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N7027219Q0025

PIER FIBER MAINTENANCE

REQUEST FOR SPECIFICATION CLARIFICATION

RFC -003

NAME OF CONTRACTOR: _____________

QUESTION:

1) Optical Time-Domain Reflectometer (OTDR) verification testing is referenced in Section 7.6.2 of the Performance Work Statement. Other than this required OTDR testing, does NCTAMSLANT require other fiber testing, such as “light meter” or “fiber end-face” testing?

2) Does NCTAMSLANT have any specific requirements for OTDR testing equipment (i.e. - manufacturer and model)? If yes, what equipment is required?

3) Does NCTAMSLANT have any specific reporting requirements or formats for the OTDR test results? If yes, what specific reports or formats are required?

4) Since we want to understand whether contractor technicians must carry OTDR equipment at all times; please answer each of these questions:

a) Is an OTDR test required for each “Emergency Call” repair?

b) Is an OTDR test required for each "Routine Call” repair?

5) Will all fiber testing and maintenance (planned, routine repair and emergency repair) be performed on ground level at a height of less than twelve (12) feet or will an aerial or bucket truck be required? Please describe the heigh requirements if more than twelve (12) feet.

6) Are there any specific tests/procedures that vendors must follow for the fiber optic maintenance and testing? If yes please list those tests/procedures.

ANSWER:

1. OTDR testing and end to end testing is the only required testing.

2. The OTDR tester must meet the industry standard requirements.

3. The test results shall be formatted in a Microsoft Office compatible file.

4. We will not dictate how to troubleshoot, but an OTDR tester could possibly be required for completion of any assigned task emergency or routine.

5. All fiber maintenance will be a height less than 12 feet. No bucket truck is required.

6. Test/procedures must meet the industry standard requirements.