This is a detailed work item specification for inspecting, servicing, and testing fire hoses and stations aboard the USNS Laramie (TAO 203) under Contract No. FY25 VR2 NXXXXXXXXXXX, Item No. 0573, Category "A" with a date of 2025-01-29.
The scope covers maintenance of 35 exterior fire stations, 68 interior fire stations, three damage control lockers, and six foam stations throughout the vessel. The equipment includes 205 1½-inch fire hoses (50 ft length), 24 2½-inch fire hoses (50 ft length), and nine 1½-inch rubber hoses (150 ft length). The contractor must perform annual inspections, maintenance, and hydrostatic testing of all fire hoses to at least 100 psi. Key requirements include operational testing of the fire main system, cleaning of fire station boxes, verification of proper equipment at each station, and testing/inspection coordination with OMT REP, ABS, and USCG. The contractor must provide temporary fire hoses during maintenance to maintain ship protection, with no more than 25% of hoses removed at any time. All work must comply with manufacturer specifications and certification requirements from USCG, ABS, and NFPA, with detailed reporting requirements in PDF format.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 4.06 RFQ AMEND 0007.pdf | ||
| 4.02 AMEND006 RFQ.pdf | ||
| CombinedDocs_6580085_6580753_6580760_6580779.pdf | ||
| Item 0573_Reference 2.1_6580462_E Fire Control Plan.pdf | ||
| Item 0558_Reference 2.4_T9589-AA-MMC-010_0_B Personnel Elevator.pdf | ||
| Item 0501_T6225-JP-MMC-010_0_0 Ballast Pump.pdf | ||
| Item 0558_Reference 2.1_ABS Guide for Lifting_appliances.pdf | ||
| AMENDMENT 0004.pdf | ||
| Item 0310_RELIANCE DWG 801625-027.pdf | ||
| 4.02 RFQ AMEND 0005.pdf | ||
| Item 0101AND0102_Ref2.1_NAVSEA DGW 623-6580092.pdf | ||
| RFQ AMEND0002.pdf | ||
| Item 0573_Ref 2.2_46 CFR Part 95 Subpart 95.10-10, Fire Hydrant and Hoses.pdf | ||
| Item0105_Reference2.1.1_6580078_C Open Rails Stanchions.pdf | ||
| RFQ Amend0003.pdf | ||
| 4.02 RFQ AMEND0001 USNS Ship VR.pdf | ||
| 4.02b J-2 Work Item Description.pdf | ||
| 4.02a J-1 Contractor_Pricing_Breakdown_USNSSHIP_VR.xlsx | XLSX spreadsheet | |
| 4.02a RFQ USNS SHIP VR.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USNS Laramie
( TAO 203 )
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
ITEM NO. 0573 CATEGORY "A" 2025-01-29
TAO187_CCSI_FIRE HOSES (1 YR) Wise, James, r
0573 - 1
1.0 ABSTRACT
The purpose of this item is to inspect, service and test the ship’s fire hoses and stations.
2.0 REFERENCES
2.1 MSC Drawing No. 555-65803596580462, Fire Control Plan
2.2 46 CFR §95.10-10, Fire Hydrants and Hoses
3.0 ITEM LOCATION/DESCRIPTION
3.1 Location/Quantity
3.1.1 Locations
a. 35 Exterior Fire Stations: Throughout the vessel; see Reference 2.1.
b. 68 Interior Fire Stations: Throughout the vessel; see Reference 2.1.
c. Three Damage Control Lockers: (01-1-1), (1-68- 1), and (1-114-3)
d. Six Foam Stations: (01-36-1), (01-39-2), (01- 49-2), (01-56-1), (01-110-1), and (01-110-2)
3.1.2 Quantity
a. 1 ½ inch fire hose, length: 50 ft – 205 from stations and spares
b. 2 ½ inch fire hose, length: 50 ft – 24 from stations and spares
c. 1 ½ inch rubber hose, length: 150 ft – Nine from hose reels and spares
3.2 Item Description: Fire Hoses
4.0 GOVERNMENT FURNISHED EQUIPMENT/MATERIAL/SERVICE: None.
5.0 NOTES
Formatted: Highlight
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 2
5.1 The contractor and all subcontractors, regardless of
tier must consult the General Technical Requirements (GTR) to determine applicability to this work item. In performance of this work item, the contractor and all subcontractors regardless of tier must comply with the requirements of all applicable GTRs including but not limited to GTRs 1 through 7, 22, 23, 24, 28, and 29.
5.2 The contractor and all subcontractors regardless of
tier are advised to review other work items under this contract, including but not limited to Work Items 023, 567, 569, 569, 570, 571, 572, and 901 to determine their effect on the work required under this work item. Many of the definitions relating to performance of this work item are found in Work Item 001.
5.3 Per MSC-USCG MOA dated 2018, approval is granted for
the use of MILSPEC MIL-H-24606B 1.75 inch diameter fire hose with 1.50 inch brass couplings with NH thread in lieu of UL 19.
In addition, the use of wye-gate valves with 2-1/2” inlet and 1-
1/2” outlets for fire hose connections in which the closure is composed of resilient nonmetallic material is permissible provided the station can be isolated from the fire main by a cut-out valve (COV) with metal to metal seats.
6.0 QUALITY ASSURANCE REQUIREMENTS
6.1 All items shall be serviced and maintained in
accordance with OEMs specifications and certification requirements as set forth by the USCG, ABS, and National Fire
Protection Agency (NFPA).
7.0 STATEMENT OF WORK REQUIRED
7.1 Inspect, service, and test the ship’s fire hoses and
fire stations identified in Reference 2.1 and section 3.0 using
Reference 2.2 as guidance. Accomplish inspection, servicing, and testing in accordance with IMO, SOLAS, USCG and the
Manufacturer’s requirements.
7.2 Coordinate with ship’s force to tagout all required
systems and equipment. Drain and dispose of any liquid, to vessel tanks.
7.3 Provide temporary fire hoses and equipment to
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 3 adequately protect the ship from fire during the accomplishment of this item. No more than 25% of the ship’s hoses should be removed at any one time. Coordinate removals with OMT REP to ensure the vessel always has adequate coverage until the hoses are returned and reinstalled.
7.4 Conduct an annual inspection of the fire hoses and
stations using Reference 2.2 as guidance. The inspection is to verify:
7.4.1 Each fire hydrant has at least one length of
fire hose, a spanner wrench, and a hose rack or other device for stowing the hose. Spanners are suitable for use on the hose at that station.
7.4.2 Each fire station hydrant or “y” branch is
equipped with a valve so that the hose may be removed while there is pressure on the fire main.
a. Inspect all flanged connections to fire main piping and hydrants for gasket material that has been identified by APB to be "readily rendered ineffective by heat". An example of gasket material that has been accepted by ABS for us in fire main and hydrant flanged connections is reddish brown Garlock
Series 9900 or equal ABS Type Approved material per ABS Rules 4-
6-1/3.5, 4-6-2/9.5 vi), 4-7-3/1.11.1. Include a listing of connection that are unacceptable or questionable to the OMT REP.
7.4.3 Firehoses are connected to the outlets. On open
decks where no protection is afforded to the hose in heavy weather, or where the hose may be liable to damage from the handling of cargo, the hose may be temporarily removed from the hydrant and stowed in an accessible nearby location.
7.4.4 Each firehose on each hydrant has a combination
solid stream and water spray firehose nozzle approved under subpart 46 CFR §162.027.
7.4.5 Visually examine each hose for broken, damaged, or missing parts.
7.4.6 In each propulsion machinery space containing
an oil-fired boiler or internal combustion machinery, each fire hose having combination nozzle must have a low-velocity water
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 4 spray applicator that is approved under subpart §162.027. The length of the applicator must be less than 1.8 meters (6 feet).
For Tank Vessel requirements see 46 CFR Table 34.10-10(E).
7.4.7 Each low-velocity water spray applicator has
fixed brackets, hooks, or other means for stowing next to the hydrant.
7.4.8 Firehose is not being used for any other
purpose than fire extinguishing, drills, and testing.
7.4.9 Inspect the physical condition of all hoses
checking for damage, cuts, abrasions, and mildew.
7.4.10 Visually examine the hose lining at each end
for signs of delamination.
7.4.11 Fire station hydrant connections are brass, bronze, or other equivalent metal.
7.4.12 Fire hydrants, nozzles, and other fittings have
threads to accommodate the hose connections noted below.
Couplings are to:
a. Use National Standard firehose coupling threads for the 1-1⁄2 inch (38 millimeter) and 2-1⁄2 inch (64 millimeter) hose sizes (9 threads per inch for 1-1⁄2 inch hose, and 7-1⁄2 threads per inch for 2-1⁄2 inch hose); or
b. To be a uniform design, for each diameter hose, throughout the vessel to allow for interchangeability.
c. Each section of firehose is lined commercial firehose that conforms to Underwriter’s Laboratories, Inc.
Standard 19 or Federal Specification ZZ-H-451E.
d. Ensure there is a shore connection to the fire main on each side of the vessel in an accessible location.
Ensure there is an international voyage complying with ASTM F
1121. The international connection is to be capable of being used on either side of the vessel.
7.5 Conduct annual maintenance on all fire hoses and
stations in accordance with the manufacturer’s design, AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 5 installation, maintenance instructions and service bulletins.
The maintenance will include/verify:
7.5.1 Thoroughly wash out and clean the interior
surfaces of all exterior fire station boxes, removing all dirt, debris, mildew, and water prior to re-stowing fire hoses.
7.6 Conduct annual testing of the fire hoses using
Reference 2.2 as guidance and per 46 CFR §95.25-20(4). The testing is to include:
7.6.1 Upon vessel arrival and with assistance from
ship’s force conduct an operational test of the fire main system checking the pressure at the most remote and highest outlets.
Each fire pump must be capable of delivering water simultaneously from the two highest outlets at a pressure of approximately 50 psi per 46 CFR §95.10-5(c).
7.6.2 Hydrostatically test all firehoses to a test
pressure equivalent to the maximum pressure to which they may be subjected in service, but not less than 100 psi (690 kPa).
CONTRACTOR IS REQUIRED TO PROVIDE ALL EQUIPMENT TO
HYDROSTATICALLY TEST HOSES TO INLCUDE CALIBRATED GAGE.
7.6.3 The total length of any hose line in the hose
test layout to be service tested is not to exceed 300 feet per
Reference 2.2.
7.6.4 The hose test layout will be straight, without
kinks or twists.
7.6.5 The test medium is to be clean fresh water.
7.6.6 Ensure all air has been bled from the hoses
before pressure testing.
7.6.7 Test pressure will be held for a minimum of
three minutes.
7.6.8 Ensure the test gauge has been calibrated
within the last 12 months.
7.6.9 Upon successful completion, stencil the fire
hoses with date of each service test and the service test
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 6 pressure. Any new hoses will also be stenciled with the Vessel’s
Name.
7.7 Testing is to be coordinated with OMT REP and ABS and
USCG. Any firehose found to be defective and incapable of repair is to be destroyed in the presence of OMT REP. Defective hoses are to be replaced with new ship’s spares.
7.8 Care is to be used to protect the hoses and coupling
threads from damage during the accomplishment of this work item.
To prevent mechanical damage, firefighting appliances are not to be dropped or dragged.
7.9 Upon completion of all inspections, tests and repairs, return the fire hoses to the vessel and their respective station, apply a light coat of silicon-based lubricant to coupling threads, and leave fire hoses in a ready for service condition. All hoses are to be drained and thoroughly dried before being placed in storage.
7.10 Reports
7.10.1 When inspection, service and testing reveal any
deficiency a condition report is to be submitted to the OMT REP with recommended repairs and parts required. Submit one electronic copy in Portable Document Format (PDF).
7.10.2 Submit a report that includes “as released”
condition of the firehoses. Submit one electronic copy in
Portable Document Format (PDF).
7.10.3 All reports and checklists are to be completed
and signed by the person who carried out the inspection and maintenance work and countersigned by the Company’s representative.
7.11 Painting: None additional
7.12 Manufacturer’s Representative: None
7.13 Preparation of Drawings: None additional
7.14 Provide electronic copies of all revised and/or
updated technical documentation including drawings, technical
AUXILIARY MACHINERY CONTRACT NO. FY25 VR2 NXXXXXXXXXXX
0573 - 7 manuals, service bulletins, parts lists, certification and test data associated with the work performed or parts supplied to the
OMT REP.